DIVISION 2 – SITEWORK
Section 02200 – EARTHWORK (Filling & Grading)
0.1 Coarse grained fill materials inside buildings & 0.1 Stone fragments, sand & gravel mix, fine sand, silt or clayey sand
under parking areas, driveways & walkways & gravel, passing a 75mm. sieve. The fraction passing a
0.075mm (No. 200) sieve shall have a liquid limit not to exceed
35% & plasticity index not exceeding 12%
0.2 Fine grained fill materials outside the limits of 0.2 Silt, clay, silt clay or clayey silt, passing a 0.075mm (No. 200)
the buildings, for landscape purposes sieve and shall have a liquid limit not less than 40% & a plasticity
index not less than 11%
0.3 Granular fill materials to form a capillary water 0.3 Clean, crushed, non-porous rock; crushed or uncrushed gravel,
barrier uniformly graded & of a size which will pass a (25mm) 1-inch
mesh screen & be retained on a No. 4 mesh screen
0.4 Excavated material approved for use as backfill 0.4 Free of stones larger than 50mm in longest dimension, roots &
organic materials
0.5 Soil treatment 0.5 Provide water-based chemical for termite control or soil
poisoning (DURSBAN or LENTREK or approved equal)
0.2 Concrete coarse aggregate 0.2 Aggregates shall be well-graded, clean, hard particles of gravel
or crushed rock conforming to the Standard Specification for
Concrete Aggregates (ASTM Designation C-33: latest revision)
0.3 Concrete fine aggregate 0.3 Sand shall be coarse sand free from injurious materials such as
shells, earth or organic materials. Sand from salt water is not
allowed
0.4 Water 0.4 Water shall be clean & free from injurious amount of oils, acids,
alkali, organic materials or other deleterious substances
0.6 Controlled strength of concrete 0.6 Concrete shall develop a minimum of 28-day cylinder strength
of 20.7 MPa (3000 psi)
DIVISION 3 – CONCRETE
Refer to detailed Construction Specifications, Dwg. No. S-1.
Section 03100 – CONCRETE FORMWORK
0.1 Formwork 0.1 Plywood formworks must be free from warp & gross deformities,
sufficiently braced with solid lumber & applied w/ form release
agent at its casting surface before each casting. For unexposed
beams & columns, use 12mm (1/2”) thk plywood. For exposed
concrete, use 19mmx100mm (3/4” x 4”) T&G. Verify w/ FLI
Engineers
0.2 Gravel 0.2 Well-graded, clean, hard particle of gravel or crushed rock. Use
38mm (1 ½”) maximum for slabs and 19mm (3/4”) for columns,
beams & retaining walls
0.3 Sand 0.3 Clean, washed sand, strong, durable & free from organic
materials
0.4 Water 0.4 Fit for drinking & free from injurious amount of oils, acids, alkali,
organic materials or other deleterious substances
0.5 For footings, beams, columns, suspended 0.5 Concrete compressive strength (fc’) = 20.7 MPa (3000 psi)
slabs, gutter, walls, canopy, retaining walls,
girders, Carport slab
0.6 For Laundry, Patio & interior slab on grade, 0.6 Concrete compressive strength (fc’) = 17.2 MPa (2500 psi)
counter, planters
0.7 Lean concrete 0.7 Concrete compressive strength (fc’) = 10.0 MPa (1500 psi)
0.8 Plastering of toilet walls & exterior walls 0.8 Add one pack of SAHARA for every bag of cement in concrete
mixture
DIVISION 4 – MASONRY
Refer to detailed Construction Specifications, Dwg. No. S-1.
0.2 Mortar sand 0.2 Clean, washed sand, strong, durable & free from organic
materials. Conform to ASTM C 35-67
0.3 Water 0.3 Fit for drinking & free from injurious amount of oils, acids, alkali,
organic materials or other deleterious substances
0.4 Controlled strength of mortar 0.4 A)Mortar & grout compressive strength (fc’)= 13.8 MPa (2000 psi)
for non-load bearing CHB
B)Mortar & grout compressive strength (fc’)= 17.2 MPa (2500 psi)
for load bearing CHB
0.5 Adhesive mortar requirements 0.5 Use ABC Adhesive Mortar for laying vitrified ceramic tiles w/
ABC Dispersion Compound additive (or approved equal)
0.6 Grout requirements for kitchen, laundry & 0.6 Use ABC Grout pre-mixed dry wall filler for wall tile joints either
toilet tile works glazed or semi-glazed tiles(or approved equal)
0.2 Roof Deck parapet & as indicated in the plans 0.2 100mm. thk. ordinary hollow blocks (350 psi), steam cured
0.3 Reinforcing bar 0.3 Masonry reinforcing yield strength (fy) = 230 MPa (33,000 psi).
Structural Grade bars, conforming to ASTM Specification
A615/ PNS 49 of size shown on plans. Use standard sizes.
0.4 Tie wire requirements 0.4 Gauge 16 Galvanized Iron (G.I.) tie wires
DIVISION 5 – METALS
Refer to detailed Construction Specifications, Dwg. No. S-1.
0.2 Standard solid section requirements 0.2 Mild steel angles, flat bars, square bars, channels, U- & other
sections. For canopy eaves, framing, C- purlins, grille works,
miscellaneous fabricated mounting brackets, straps, dowels,
frames & connectors as indicated in the plans. Upgrade to next
higher/ bigger size & thickness if specified sizes & thickness
are unavailable
0.3 Bolt accessory requirements 0.3 Low carbon steel with type, shape, size, threading, correspon-
ding nut & accessories as required
0.7 Balusters 0.7 20 x 20 x 1.5 mm thk tubular steel bar & 20 x 20mm square bar,
twisted, painted “Antique” finish
0.10 Gutter 0.10 610 x .40mm thk (Ga 24) Spanish type gutter, prepainted G.I.
by PHILMETAL
0.2 Decorative handrail at façade 0.2 100 x 50 x 1.5mm thk tubular steel
0.3 Decorative steel bracket 0.3 100 x 50 x 1.5mm thk tubular steel
0.2 Plywood & plyboard 0.2 STA. INES VENEER AND PLYWOOD CO., or approved equal
0.3 Hardware & fasteners 0.3 Use metal nails, screws, bolts, plates, straps, misc. fasteners or
anchorage concealed or countersunk whenever called for, w/
size, shape & type to ensure a rigid connection for framing joints
0.2 Interior stair riser moulding 0.2 From 25 x 25mm. kiln dried Tanguile quarter-C moulding
0.3 Kitchen base cabinet framing & base plate 0.3 From 50 x 50mm & 50 x 75/100mm kiln dried Tanguile
0.4 Kitchen base cabinet & Master’s Bedroom 0.4 19mm (3/4”) thk class A Tanguile plyboard. For miscellaneous
closet components of cabinets& closets housing which are concealed
or to be painted, for free-span shelves, dividers, counters,
cabinet & closet doors. Provide solid wood edging
0.5 Interior stair riser cover 0.5 6mm thk ordinary plywood
0.6 Canopy eaves 0.6 4.5mm thk fiber cement board “Hardi flex” by JAMES HARDIE
0.7 Master Bedroom partition adjacent to stair 0.7 4.5mm thk fiber cement board wall boards by JAMES HARDIE
on metal studs
0.8 T & B ceiling at Grnd Flr 0.8 4.5mm thk fiber cement board wall boards by JAMES HARDIE
on metal furring
0.9 For wood assembly requirements 0.9 WELDWOOD or approved equal, water-resistant wood glue &
SELLY LIQUID NAILS or approved equal water- resistant
wood sealer
0.2 Waterproofing of concrete canopy at Laundry, 0.2 3 coats elastomeric type waterproofing paint submit sample
Patio & false balcony at facade for approval
0.3 T & B at 2nd. Flr. 0.3 4 coats cementitious type waterproofing (MORTASEAL
or approved equal)
0.2 For adhesive requirements 0.2 SELLY LIQUID NAILS Solvent-based Synthetic Rubber Contact
Type Adhesive (or approved equal)
0.3 For Door/Window frames against walls, bet. 0.3 SELLY NO MORE GAP Acrylic Latex Gap Sealant Rubber
countertop & splashboard, corners, walls Contact Type Adhesive (or approved equal)
& ceiling
0.4 For non-porous surfaces such as glass, 0.4 SELLY BATHROOM & KITCHEN SEALANT Acid Cure Silicon
ceramics & porcelain (or approved equal)
0.2 D2 (Dining) 0.2 40mm. thk. KD Tanguile French door, stained “Xyladecor” finish
0.3 D3 (Kitchen), D6 (Balcony), D4 (T&B) 0.3 40mm. thk. hollow core flushed door w/ 6mm. thk. marine
plywood both face. Stained “Xyladecor” finish for D3 & D6,
enamel paint finish for D4
0.4 D5 (Bedrooms) 0.4 40mm. thk. hollow core flushed door w/ 6mm. thk. ordinary
plywood both face, enamel paint finish
0.2 D2 (Dining) 0.2 4 pcs. (per door) - 3 ½” x 3 ½” non-removable pin butt hinge
by HAFELE
0.3 D3 (Kitchen) & D6 (Balcony) 0.3 3 pcs. - 3 ½” x 3 ½” non-removable pin butt hinge by YALE
0.4 D4 (T&B) & D5 (Bedrooms) 0.4 3 pcs. - 3 ½” x 3 ½” loose-pin heavy-duty butt hinges by YALE
LOCKSETS
0.5 D1 (Living) 0.5 Alta Handleset, satin chrome finish, H507-AT, by SURE-LOC
0.6 D2 (Dining) 0.6 Heavy-duty knobset AR-302 with escutcheon trim, satin chrome
finish, by SURE-LOC
0.7 D3 (Kitchen), D5 (Bedrooms), D6 (Balcony) 0.7 Arapaho Entrance lockset, satin chrome finish, AR307-AT
by SURE-LOC
0.8 D4 (T&B) 0.8 Arapaho Cylindrical privacy lockset, satin chrome finish, AR302
by SURE-LOC
MISCELLANEOUS
0.9 For all cabinets & closets hinges 0.9 Concealed hinges No. 316.30.500 (HAFELE)
0.10 For all cabinet & closet door pull 0.10 10mm dia. wire pull, chrome finish
0.11 For exterior and T&B doors 0.11 Provide 25 x 25mm & 32mm wide anti slip brass nosing
DIVISION 9 – FINISHES
Section 09200 – PLASTERING
Note: Plain cement plaster scratch & finish coats, both consist of one (1) part Portland Cement & two (2) parts clean,
washed sand measured by volume.
INTERIOR WALL
0.1 All interior wall surfaces (including upper part 0.1 Plain cement plaster, painted finish. Verify color w/ Architect
of T & B walls)
EXTERIOR WALL
0.2 All exterior walls indicated in the drawings 0.2 A) Non firewall- Plain cement plaster, textured painted finish.
Spray fine texture using fine sand, perlite & stickwell adhesive.
Verify color w/ Architect
0.2 Hallway & Bedrooms at 2nd Flr 0.2 100 x 900 x 1.3mm. thk. vinyl floor planks (APO or approved
equal)
0.3 T & B at Grnd Flr& 2nd.Flr 0.3 200 x 200mm. vitrified floor tiles (EUROTILES, MARIWASA,
LEPANTO or approved equal)
INTERIOR WALL
0.4 T & B at Grnd & 2nd Floors, Laundry Sink, 0.4 200 x 200mm. ceramic wall tiles (EUROTILES, MARIWASA,
Kitchen counter & splash wall LEPANTO or approved equal)
0.2 T&B at Grnd Flr 0.2 4.5mm. thk. fiber cement board by JAMES HARDIE on metal
furring, painted textured “spraytex” finish
0.2 Carport 0.2 Plain cement finish with 10 x 10mm. groove lines & 20mm dia
exposed aggregates accent & borders w/ Amersil repellant
CONCRETE/ MASONRYSURFACES
0.1 Exterior wall field surfaces 0.1 A) Non firewall- Plain cement plaster, textured painted finish.
Spray fine texture using fine sand, perlite & stickwell adhesive.
Treated w/ masonry neutralizer (BOYSEN B-44). 2 top coat w/
semi-gloss latex paint (BOYSEN Permacoat No.715)
0.2 All interior wall surfaces (including upper part 0.2 Treated with masonry neutralizer (BOYSEN B-44), First coat w/
of T & B walls) flat latex paint (BOYSEN Permacoat No.701), apply masonry
putty (BOYSEN No.7311), 2 top coat w/ semi-gloss latex paint
(BOYSEN Permacoat No.715)
0.3 Cement mouldings, wall bands, window 0.3 Treated with masonry neutralizer (BOYSEN B-44), First coat w/
casings, trims flat latex paint (BOYSEN Permacoat No.701), apply masonry
putty (BOYSEN No.7311), 2 top coat w/ gloss latex paint
(BOYSEN Permacoat No.715)
0.4 Exterior & interior concrete ceiling surfaces 0.4 Treated with masonry neutralizer (BOYSEN B-44), First coat w/
flat latex paint (BOYSEN Permacoat No.701), apply masonry
putty (BOYSEN No.7311), top coat w/ fine textured “spraytex”
paint finish (BOYSEN Permatex No.3101)
METAL SURFACES
0.6 Steel grilles, handrail, balusters, decorative 0.6 First coat with epoxy primer (BOYSEN Epoxy Red Lead
bracket, decorative lattice, jambs, exterior & Primer No.2270 or BOYSEN Zinc Chromate Primer
interior stair metal parts, canopy fascia No.2260), 2 top coat with enamel paint (BOYSEN Quick-dry
Enamel No.600)
WOOD SURFACES
0.7 Interior stair wood tread, plywood riser, 0.7 Surface preparation (BOYSEN Wood Paste Filler No.60),
mouldings, cabinets, closets w/ lacquer finish first coat (BOYSEN Lacquer Sanding Sealer No.1254 &
(where applicable) BOYSEN Oil Stain Series No.2700), top coat (BOYSEN
Clear Dead Flat Lacquer No.1253)
0.8 Cabinets & shelves w/ automotive lacquer finish 0.8 First coat w/ primer (BOYSEN Primer Lacquer Surfacer No. 305),
(where applicable) 2nd coat w/ putty (BOYSEN Lacquer Spot Putty No.306), 3rd
coat (BOYSEN Primer Lacquer Surfacer No.305), topcoat w/
automotive lacquer (BOYSEN Automotive Lacquer No.1300).
Note: Apply putty as needed for plain enamel finishes using
BOYSEN Plasolux Glazing Putty No.311. Primer/putty are white
0.9 Exterior doors/ wood w/ “Xyladecor” finish 0.9 A) Do not use knotting, primers or undercoats- apply “Xyladecor”
(where applicable) (BOYSEN) directly to bare wood. Apply min. 2 coats
B) Apply by brush, spray or by dipping in an open trough or tank
of “Xyladecor” to achieve the total covering rate (or loading).
0.10 Plywood ceiling/ partition, wood doors w/ 0.10 First coat w/ primer (BOYSEN White Interior Primer & Sealer
flatwall enamel finish (where applicable) No.300, BOYSEN Flatwall Enamel No.800, BOYSEN White
Glazing Putty No.311), 2 top coats w/ enamel paint (BOYSEN
Flatwall Enamel No.800)
0.2 Kitchen 0.2 TEKA & HCG fixtures (or approved equal)
1)Sink 1) Single bowl stainless steel American Series, Model
25.22.1B, single tap hole by TEKA
2) Faucet 2) “Amazona” KF3511 single hole faucet, metal handle w/
goose neck tubular spout. Polished chrome finish &
complete fittings by HCG (or approved equal)
0.3 Water supply lines/ fittings 0.3 Unplasticized Polyvinyl Chloride(uPVC) in-house water pipes &
fittings, blue color, (NELTEX, ATLANTA, EMERALD, LUCKY or
approved equal )
0.4 Sewer, drainage & vent lines 0.4 Unplasticized Polyvinyl Chloride (uPVC) sanitary pipes & fittings
(NELTEX, ATLANTA, EMERALD, LUCKY or approved
equivalent), Series 600
0.5 Water meter 0.5 6-digit register, multi-jet copper alloy, (by AQUA JET)
0.6 Gate valves 0.6 Chrome finish, 125 Psi (by KITZ)
0.7 Floor drains 0.7 100 x 100mm. stainless steel floor drain JFD 101 (by JAMAN)
0.8 Hose bibb 0.8 Metal alloy, heavy duty chrome finish (PRICE PFEISTER,
VALLEY II or approved equal)
0.9 Septic tank 0.9 2 pcs- 1,000-Liters capacity, plastic purifying septic tank
(KOTEC or approved equal)
0.10 Catch basin, area drain, junction box 0.10 100mm. thk. concrete hollow blocks, plastered finish on interior
side of perimeter only, provide 50mm. thick pre-cast concrete
cover as shown in plans (C.I. grating cover where applicable)
DIVISION 16 – ELECTRICAL
Section 16050 – ELECTRICAL MATERIALS
0.1 Conduits & Fittings 0.1 Rigid steel conduit (RSC), Sched. 40; by MC GILL, PUSAN,
NICH or approved equal for Main Feeder Line & other exposed
lines.
Unplasticized Polyvinyl Chloride (uPVC) Sched 40 for load side
lines & other underground, embedded on walls or slabs
concealed ceilings, by NELTEX (Powerguard), ATLANTA
(Permaline- Thick Wall), EMERALD (V2000 Series), CROWN or
approved equivalent
0.2 Panelboard 0.2 Din Rail Type Enclosure, plastic base box, clear plastic cover &
plastic board cover w/ easy press-open, plastic tag slip for easy
identification, complete w/ terminal/ shell blocks, removable din
rail plate, multiple knock-out holes for easy wiring.
0.3 Circuit Breakers 0.3 Din Rail Type Circuit Breakers by CHINT, DELIXI or approved
equal, common internal trip, 240V AC, 60Hz, Thermal- Magnetic
Type.
0.4 Conductors
A) Power Line (Wires & Cables) A) 600V insulation level, THW (main line) & TW (load side)
copper wires, solid for sizes 1.6mm dia – 2.6mm dia &
stranded for 8.0sq mm & above, UNICON, ORION, SYCWIN
or approved equivalent
C) Telephone Line C) RG #6U coaxial cable, 60% Braid, TIMES FIBER, ALCATEL,
BELDEN or approved equivalent
B) Weatherproof Outlet B) 16A, 250V AC, 3-wire grounding type, duplex convenience
outlet, Classic White, Wide Series complete w/ mounting strap
& weatherproof plate cover (self-closing type) by ROYU,
AKARI or approved equivalent
C) Device Plate Cover C) Classic White, Wide Series Model plate cover complete w/
mounting strap by ROYU, AKARI or approved equivalent
D) Wall Telephone/ Cable TV Outlet D) 9mm dia hole blank insert w/ Classic White, Wide Series plate
cover complete w/ mounting strap by ROYU, AKARI or
approved equivalent
E) Wall Switch E) 16A, 300V AC, 2-pole, quick-connect type, Classic White,
Wide Series complete w/ mounting strap by ROYU, AKARI or
approved equivalent
F) Wall ACU Outlet E) 16A, 250V AC, 3-wire grounding tandem type, Classic White,
Wide Series complete w/ mounting strap by ROYU, AKARI
or approved equivalent
G) Wall Range Outlet G) 16A, 250V AC, 3-wire grounding multi-purpose type, Classic
White,Wide Series complete w/ mounting strap by ROYU,
AKARI or approved equivalent
J) Light Outlet J) 100mm (4”) dia, keyless porcelain receptacle, 100W, 240V
K) Grounding System K) Soft drawn copper wire 8.0sq mm, min- 14.0sq mm max (as
per specified on plan) on a 16mm dia x 3000mm long Hot
dipped galvanized ground rod.