REMEHA QUINTA PRO RANGE - SUGGESTED SCHEMATICS WITH CONTROL AND POWER WIRING DETAILS

QUINTA PRO RANGE


Suggested Schematics with Control
and Power Wiring Details

SUPER CONDENSING HIGH EFFICIENCY FULLY MODULATING PREMIX BURNER ULTRA LOW NOx RECYCLABLE
107% NCV ≥ 82/71°C 108.9% NCV ∆T 50/30°C BOILER CONTROL CLEAN COMBUSTION BREEAM EXCELLENT MATERIALS

High efficiency wall hung condensing boiler


with ultra low NOx emissions
PANTONE 287 EC PANTONE 2985 EC PANTONE PANTONE 200 EC PANTONE 376 EC PANTONE
Process Black EC Process Cyan EC
QUINTA PRO RANGE OUTPUTS
QP30: 8.0 - 31.4 kW
QP45: 8.0 - 43.0 kW
QP65: 12.0 - 65.0 kW
QP90: 14.1 - 89.5 kW
PANTONE 287 EC QP115: 16.6 - 114.0 kW
PANTONE 2985 EC PANTONE
Process Cyan EC
Schematics with Control Page

Control Options for the Quinta Pro Series of Boilers p3

External controls by others


Simple Quinta Pro boiler domestic installation - p4-5
Typical ‘S’ plan, heating and hot water
Single Quinta Pro boiler, heating only p6-7
Single Quinta Pro boiler, heating only with low loss header p8-9
Single Quinta Pro boiler, heating and priority hot water using a low loss header p10-13
and pump or valve kit

Remeha supplied controls


Single Quinta Pro boiler, heating only using the iSense controller p14-16
(room/weather compensation)
Single Quinta Pro boiler, heating and Priority DHW using the iSense controller p17-19
(room or outside compensation)
Multiple Quinta Pro boilers HTG only using a low loss header with the Celcia MC4 p20-21
and iSense (room or outside compensation)
Multiple Quinta Pro boilers HTG and Priority DHW using a low loss header with p22-24
the Celcia MC4 and iSense (room or outside compensation)
Multiple boilers, heating and hot water using a low loss header with the p25-30
iSense Pro controller (optimising/weather compensated control for dual
heating zone and hot water from all or single boilers)
Connecting multiple boilers with external control interlocks and alarm p31
and run signals
Quinta Pro nominal flow rates and boiler resistances p31

Note: We supply the Grundfoss 25/80 (Part No. S101621) as standard for the full Quinta Pro
range. This will alter due to changes in EU regulations. The Quinta Pro 30 will operate on speed
1, the 45 and 65 will operate on speed 2, and the 90 and 115 will operate on speed 3. They are
intended to act as a shunt pump. In the layouts illustrated, they are designed to operate on a
20ºC Delta TΔ. If using a pump without a low loss header, please take into account both the
boiler and system resistance and also when being used in conjunction with a calorifier and low
loss header. Contact our sales or technical departments for further assistance.

The hydraulic and control layouts illustrated in this brochure are for guidance only and must be
used in conjunction with the Quinta Pro and iSense Pro installation and service manuals. They
do not constitute a full system design. Remeha Commercial accept no liability for any loss or
damage rising from any errors or omissions that may be inadvertently contained in this booklet.

When connecting a control cable to the OT terminals on the main control PCB, disconnect and
remove the factory fitted lead connected to the IF- 01 PCB.

Some earths and neutrals are omitted for clarity.

All systems, mechanical and electrical, must be installed to the current regulations by a suitably
qualified engineer.

2
Control Options for the Quinta Pro 30 / 45 / 65 / 90 and 115 series
The Remeha range of Quinta Pro boilers are supplied as standard with an “Open Therm”
control interface which enables direct weather compensation using Remeha single and
multi boiler controls. The customer can choose to use external control options supplied
by others without affecting boiler performance.

Supplied by others
On/off control:
• Boiler requires a permanent 230v supply and is enabled using a volt free switch/relay.
The boiler will modulate its output to maintain the flow temperature setpoint,
normally 80ºC, but can be adjusted on the boiler between 20ºC and 90ºC
0-10 volt control:
• Boiler requires a permanent 230v supply and is enabled and modulated using a 0-10
volt signal from a Building Management System or quality panel mounted optimiser/
compensator. The control can be flow temperature or percentage output based
• Temperature based example: if 56ºC flow is required from the boiler, the control will need to
supply 5.6v. The output will be modulated to maintain a flow temperature of 56ºC
• Percentage based example: if the control logic requires that a boiler should be running
at 33%, the control will need to supply 3.3v to the boiler. The boiler will run at 33% output
with a variable flow temperature
• Applications - domestic/commercial and industrial installations, with a variety of heat
emitters, DHW via calorifiers or plate heat exchangers, and installations where a variety
of different temperature zones are required at the same time

Supplied by Remeha Commercial as optional extras


iSense Controller - Single/multi boiler weather compensating controller
• A simple to operate room/boiler mounted thermostat/timer which can be used with a
combination of outside/room and flow temperature sensors to vary the boiler output
(flow temp) to suit weather conditions. The iSense can be installed in a reference room
and can also be mounted in a boiler when used in weather compensated mode.
It has a 7 day timer with multiple on/off and night setback periods, holiday function,
frost protection and manual override
Celcia MC4
• Multiple boiler weather compensating controller with step control (up to 4 boilers)
to be used in conjunction with the iSense controller
• The iSense can be mounted in a reference room, in the plant room or on the boiler
• The MC4 is mounted adjacent to the boiler group
iSense Pro - Multiple boiler weather compensating controller with sequence control (up to 8 boilers)
• Optimiser compensator which can provide 2 timed heating zones and uses a combination
of outside, flow and room temperature to vary the boiler output (flow temp) to suit weather
conditions. Can also provide time control to DHW circuit. The iSense Pro controller is mounted
in a wall box when used with the Quinta Pro and is complete with timer, night setback, frost
protection and pump cycling protection. The iSense Pro controller will sequence and rotate
the lead boiler on multiple installations. This controller also has the ability to accept remote
extension timers, supplied as an optional extra, which will allow the heating system to run
on daytime compensation outside the normal timed settings without need for access or
interference to the boiler or controller. Ideal for school lettings/night classes etc.

Note: We do not advise using a combination of external and built-in controls as in most cases
there can be no interface between them; it is likely they will ‘conflict’ with each other
and neither will work properly. The exception to this is when using the iSense Pro kit KT1154
in conjunction with a Remote BMS controller (see page 31).

3
Simple Quinta Pro boiler domestic installation
Typical ‘S’ plan, heating and hot water
(Time and temperature control by others)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected
to the factory fitted fly lead

Boiler Control Settings


(see 5.7.2 in technical documentation)
• Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the control being used
• Use the zone valve end switches to provide the volt free switch pair on OT on the main
control PCB to enable the boiler
• Boiler output will vary between 18% part load set point and 100% full load set point
to achieve the boiler flow set point (code P1)

System Components
(not supplied)
• Simple two channel time clock providing 230v switched supplies to control
heating and domestic hot water
• System pump
• Cylinder thermostat
• Room thermostat
• HTG and DHW zone valves c/w a single end switch (closes on valve fully open)
• Wiring centre

Note:
1. Maintain polarity on all connections
2. Some Neutral and Earth connections have been omitted for clarity
3. The schematic is for guidance only and does not constitute a design
4. Heating and hot water can be operated independently or simultaneously
with this layout provided the control selected will allow it

4
Quinta Pro single boiler heating and dome
stic hot water, usinga
simple ‘S’ Pla
n
Quinta
Single Pro single
Quinta Proboiler heating
boiler, andand
heating domestic hot wa
domestic ter,
hot usinga
water,
simple
using a‘S’simple
Pla
n ‘S’ Plan

QP 001S

QP 001S
QP 001S

O
Shunt

Shunt

QP 001SA QP 001SA

5
QP 001SA
Single Quinta Pro boiler, heating only
(Time and temperature control by others)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead

Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed

Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)

Boiler Control Settings


(see 5.7.2 in technical documentation)
• Connect the external controls (volt free) to the OT terminals on the main control PCB (on/off).
Boiler will modulate to the set point set in P1 or the 0 -10v terminals on the IF-01.
Control option based on temperature or output can be adjusted on the jumper on the IF-01.
(See installation manual for full details)
• Boiler will recognise the type of control being used
• Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
• Pump: connect the heating pump to terminals shown on the PCB SCU - S02 max 400Va
(1.5 amp). Alternatively, pump can be connected to the fly lead supplied with the boiler
to plug X81; this a max duty of 200w (0.8 amp)

6
Quinta Pro single boiler heating only
Single Pro
Quinta Quinta Proboiler
single boiler,heating
heatingonly
only

QP 002
QP 002
QP 002

QP 002A
QP 002A
QP 002A

7
Single Quinta Pro boiler, heating only with low loss header
(Time and temperature control by others)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected
to the factory fitted fly lead

Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed

Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)

Boiler Control Settings


(see 5.7.2 in technical documentation)
• Boiler will recognise the type of control being used
• Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
• Connect the external controls (volt free) to the OT terminals on the main control PCB
(on/off). Boiler will modulate to the set point set in P1 or the 0 -10v terminals on the IF- 01.
Control option based on temperature or output can be adjusted on the jumper on the IF- 01.
(See installation manual for full details)
• Pumps: connect pump PM1 to the heating pump terminals shown on the PCB SCU - S02
max 400Va (1.5 amp). Connect the shunt pump SH1 to the pump fly lead supplied with the
boiler to plug X81

8
Quinta Pro single boiler heating only with loss heading
Single Quinta Pro boiler, heating only with low loss header
Quinta Pro single boiler heating only with loss heading

QP 003

QP 003
QP 003

QP 003A
QP 003A
QP 003A

9
Single Quinta Pro boiler, heating with priority hot water
using a low loss header and pump or valve kit
(Time and temperature control by others)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected
to the factory fitted fly lead

Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed

Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)

Boiler Control Settings


(see 5.7.2 in technical documentation)
• Boiler will recognise the type of control being used
• Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
• Connect the external controls (volt free) to the OT terminals on the main control PCB
(on/off). Boiler will modulate to the set point set in P1
• Pumps: connect pump PM1 to the heating pump terminals shown on the PCB SCU - S02 max
400Va (1.5 amp). Connect the shunt pump SH1 to the fly lead supplied with the boiler to plug
X81 max 200w (0.8 amp). On pump installations, connect the shunt pump to the terminals
shown; a contactor or relay will be required if loading exceeds 1.5 amps
• 3-way valve: on the 3-way valve option, connect the valve to the terminals shown on the PCB
SCU – S02

Important:
When using the Remeha supplied low loss header and pump kit and the DHW diverting valve or
primary pump kit, the calorifier must be sited within 3M of the boiler. In both cases, the DHW
cylinder must be a high recovery unit capable of accepting the full or adjusted DHW output of the
boiler being used (reference parameter P18).

10
Single Quinta
Quinta
Quinta Pro Pro boiler,
Pro single
single boilerheating
boiler heatingwith
heating withpriority
with priorityhot
priority hotwater
hot waterusing
water usingaa
using alow
low
low
loss header.
loss 3-way valve DHW priority Quinta Pro 30/45/65 only
loss header. Three way valve DHW priority Quinta Pro 30/45/65 only
header. Three way valve DHW priority Quinta Pro 30/45/65 only

QP 004
QP
QP 004
004

Single Quintasingle
Quinta Pro boiler, heating with priority hot water using aa
Quinta Pro
Pro single boiler
boiler heating
heating with
with priority
priority hot
hot water
water using
using a
low loss
low header pump option. DHW priority can be used on all
low loss header pump option DHW priority can be used on
loss header pump option DHW priority can be used on all
all
Quinta Pro
Quinta Prorange
range
Quinta Pro range

QP 004A
QP
QP 004A
004A

11
Single Quinta Pro boiler, heating with priority hot water using a
low loss header (3-way valve option)

Note: Control PCB s are shown diagrammatically


Earths are omitted for clarity

Time/temp control
HTG (volt free) Thermostat Safety Limiter
Time control DHW 3 way valve
2 Port
(volt free) spring
Factory fitted return Cylinder Note: Control PCB s are shown diagrammatically
supply lead to valve Thermostat Earths are omitted for clarity
be connected 230v fused 2 C 1 2 C 1
to a 230v fused Time/temp control supply for
HTG (volt free) Thermostat Safety Limiter
spur for boiler 2 port valve
Time control DHW 3 way valve
permanent supply 2(connected
Port to
(volt free) spring 230v Fused
Factory fitted boiler supply)
return Cylinder HWS time Supply
valve Boiler
supply lead to Thermostat control (connected to
Tdhw boiler supply)
be connected 230v fused
Wiring detail of controls when using a Live 2 C 1 2 C 1
to a 230v fused

Orange
Grey

Brown
Blue
Remeha Commercial Calorifier,supply for
a volt free
Neutral
spur for boiler HWS time control and a 2 Port 2 spring
portreturn
valve
valve. If using a different type of calorifier, please Boiler Signal out (volt free)
permanent supply (connected to
follow manufacturer’s instructions regarding 2 Port Spring Return
boiler supply) 230v
Boiler Fused
Signal in (volt free) Motorised Valve
control and wiring details HWS time Supply
Boiler
control (connected to
Tdhw boiler supply)
Wiring detail of controls when using a Live

Orange
Grey

Brown
Blue
Remeha Commercial Calorifier, a volt free
Neutral
HWS time control and a 2 Port spring return
valve. If using a different type of calorifier, please Boiler Signal out (volt free)
follow manufacturer’s instructions regarding 2 Port Spring Return
control and wiring details Boiler Signal in (volt free) Motorised Valve

QP 004B

Single Quinta Pro boiler, heating with priority hot water using a
low loss header (Pump option)

Note: Control PCBs are shown diagrammatically


Earths are omitted for clarity

Contactor or relay required if both pumps


Time/temp control PM1 and SH1 loading exceeds 1.5 amps
HTG (volt free)
Time control DHW 2 Port
Factory fitted (volt free) spring Pump Pump Shunt pump Thermostat Safety Limiter
PM1 PM2 SH1 Note: Control PCBs are shown diagrammatically
return Cylinder
supply lead to valve Earths are omitted for clarity
Thermostat
be connected
to a 230v fused Contactor or relay required if both pumps
Time/temp control 230v fused Wiring detail of controls when using aPM1 Remehaand SH1 loading exceeds 1.5 amps
spur for boiler
HTG (volt free) supply for Commercial Calorifier with a 2 Port spring return
permanent supply Time control DHW valve. If using a different type of calorifier, please 2 C 1 2 C 1
22 port valve
Port
Factory fitted (volt free) spring Pump Pump Shunt
follow manufacturer’s pumpregarding
instructions
Thermostat Safety Limiter
(connected toCylinder
return control and wiring details
PM1 PM2 SH1
supply lead to boiler supply)Thermostat
valve
be connected 230v Fused
to a 230v fused HWS time Supply
Boiler Wiring detail of controls when using a Remeha
spur for boiler 230v fused control (connected to
Tdhw
Commercial Calorifier with a 2boiler
Port spring
supply)return
permanent supply supply for 2 C 1 2 C 1
valve. If using a different type of calorifier, pleaseLive
Orange
Grey

Brown
Blue

2 port valve follow manufacturer’s instructions regarding Neutral


(connected to control and wiring detailsBoiler Signal out (volt free)
boiler supply) 2 Port Spring Return

HWS time
230v
Boiler Fused
Signal
Supply
in (volt free) Motorised Valve QP 004C
Boiler
control (connected to
Tdhw boiler supply)
Live
Orange
Grey

Brown
Blue

12
Neutral QP 004C
Boiler Signal out (volt free)
2 Port Spring Return
Boiler Signal in (volt free) Motorised Valve
Wiring detail of controls when using a Remeha
Commercial Calorifier. If using a different type
of calorifier, please follow manufacturer’s
instructions regarding control and wiring details.

QP004D
QP 004D
QP004D

Wiring detail of controls when using a Remeha


Commercial Calorifier with a 2 Port spring
return valve and an iSense or Open Therm
controller. If using a different type of calorifier,
please follow manufacturer’s instructions
regarding control and wiring details.
Set Boiler parameter P37 to 0.
2 C 1 2 C 1
Note: Calorifier Thermostat temperature should
be set 5oC higher than the iSense control hot 2 C 1 2 C 1
water setting.

Boiler 230v Fused Supply

Boiler R L 230v Fused Supply

RL
Live
Neutral
Live
Boiler Signal out (volt free)
Neutral

Boiler Signal out (volt free)


Boiler Signal in (volt free)

Boiler Signal in (volt free)


QP004E
QP004E
QP 004E

13
Single Quinta Pro boiler, heating only using the iSense controller
(room or weather or room/weather compensated)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead

Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed

Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)

Boiler Control Settings


(see 5.7.2 in technical documentation)
• Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the type of control setting used

Fitting the Control


• For room compensation, fit the control in a normally occupied reference room within the
building being heated
• For room/weather compensation, an outside sensor can be fitted. If requiring weather
compensation only, the iSense can be fitted into the boiler control panel. In this case an
outside sensor must be fitted and connected to ‘Tout’ in the boiler on the main control PCB
• Connect the 2 wire control to the OT terminals on the main PCB. Please refer to the
instructions supplied with the iSense controller package
• Set up the controller to suit the design requirements and occupancy times for HTG in
accordance with the instruction documents supplied with the controller

Note: The iSense controller can provide both room or weather compensation or room and
weather compensation.
Room compensation = iSense fitted in a reference room, no outside sensor
Weather compensation = iSense fitted in a boiler or plant room, outside sensor required
Room/weather compensation = iSense fitted in a reference room, outside sensor required

14
Quinta Pro single boiler heating only room compensation using the
Single
QuintaQuinta Pro boiler,
Pro single heating only
boiler heating only,room
roomcompensation
compensationusing
usingthe
the
iSense controller
iSense
iSensecontroller
controller
Normal position for the iSense controller
Normal position
mounted for the
in reference iSense
room controller
within the building
mounted
(room in reference room within the building
compensation)
(room compensation)

Suggested height in room


Suggested height in room
100m Max
100m Max

1.6M
1.6M
230v Supply
230v Supply

Pump PM1
Pump PM1

Condensate
Condensate
Gas
Gas
Flow
Flow

Return
Return
QP 005
QP005
QP 005

Single Quinta Pro boiler, heating only, weather compensation using


Quinta Pro single boiler heating only weather compensation using
the iSense
Quinta controller
Procontroller
single boiler heating only weather compensation using
the iSense
the iSense controller
Normal position for the iSense controller
mounted
Normal in reference
position room
for the within
iSense the building
controller
mounted in reference room within the building
Suggested height in room
Suggested height in room

100m Max iSense can be fitted in the boiler if


used for weather
iSense compensation
can be fitted only
in the boiler if
1.6M

100m Max
used for weather compensation only
1.6M

100m Max
100m Max
230v Supply
Outside sensor 230v Supply
onOutside
North sensor
facing wall Pump PM1
on North
facing wall Pump PM1

Condensate
Condensate
Gas
Flow
Gas
Flow
Return
Return

QP
QP 005A
005A
QP 005A

15
Single Quinta Pro boiler heating only using the iSense controller

Single
Single Quinta
Quinta Pro
Pro boiler
boiler,heating
heatingonly
onlyusing
usingthe
theiSense
iSensecontroller
controller

Note: Control PCBs are shown diagrammatically


Earths are omitted for clarity

OT

Factory fitted iSense controller


supply lead to Pump PM1
be connected Note: Control PCBs are shown diagrammatically
to a 230v fused Earths are omitted for clarity
spur for boiler
permanent supply OT

Factory fitted iSense controller QP 005B


supply lead to Pump PM1
be connected
to a 230v fused
spur for boiler
permanent supply

QP 005B
QP 005B

Single Quinta Pro boiler heating only using the iSense controller
Single Quinta Pro
(room/weather or boiler,
weather heating only using the iSense controller
compensation)
(room/weather or weather compensation)
Single Quinta Pro boiler heating only using the iSense controller
(room/weather or weather compensation)

Note: Control PCBs are shown diagrammatically


Earths are omitted for clarity
OT
Outside Sensor
Factory fitted iSense controller
supply lead to Pump PM1
be connected Note: Control PCBs are shown diagrammatically
to a 230v fused Earths are omitted for clarity
spur for boiler
permanent supply OT
Outside Sensor
Factory fitted iSense controller
supply lead to Pump PM1
be connected QP 005C
to a 230v fused
spur for boiler
permanent supply

QP 005C

16
Single Quinta Pro boiler, heating with hot water priority, heating
room or weather compensated with the iSense controller
(Optimising/Weather compensated heating with timed hot water)
Power Supply
• Boiler requires a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead

Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed

Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)

Boiler Control Settings


(see 5.7.2 in technical documentation)
• Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the type of control setting used
• Fit the control in a normally occupied reference room within the building being heated.
Refer to the instructions supplied with the control package
• Set up the controller to suit the design requirements and occupancy times for heating and
hot water in accordance with the instruction documents supplied with the controller
• Install the outside sensor on a North facing wall in a sheltered position and connect to
terminals ‘Tout’ on the main PCB of the boiler

DHW Control
Diverting valve option:
Connect valve to the terminals shown, connect shunt pump PM1 to the terminals shown.
Connect valve ports AB, A and B as shown (AB = boiler, A = hot water, B = heating)
Primary Pump option:
Connect pump PM1 to the terminals shown
Connect shunt pump to the terminals shown

Note: This option will only operate with a calorifier sensor. This is to allow the iSense to control
the hot water times.

17
Quinta Quinta
Single Pro single
Pro boiler
boiler,heating
heatingand
andhot
hotwater
waterpriority.
priority.Heating
Heatingroom
or outside
room weather
or outside compensated
weather with the
compensated withiSense controller.
the iSense controller.
Three way valve hot water priority Quinta Pro 30/45/65
3-way valve hot water priority Quinta Pro 30/45/65 only only

Normal position
Normal position for
for the
the iSense
iSense controller
controller
mounted in
mounted in reference
reference room
room within
within the
the building
building
(room compensation)
(room compensation)

room
inroom
heightin
100m Max
100m Max

Suggestedheight
1.6M
1.6M
Suggested
100m Max
Max 230v
230v
100m Supply
Supply

Pump PM1
Pump PM1

DHW Sensor
DHW Sensor
Condensate
Condensate

Gas
Gas
AB
AB
Flow
Flow
A
A B
B
DHW Diverting valve
DHW Diverting valve

22 Port
Port spring
spring return
return valve
valve Bypass valve
Bypass valve Return
Return

QP 006
QP 006
QP 006

Quinta Quinta
Single Pro single
Pro boiler
boiler,heating
heatingand
andhot
hotwater
waterpriority.
priority.Heating
Heatingroom
or outside
room weather
or outside compensation
weather with the
compensation iSense
with controller.
the iSense controller.
Pump option hot water priority can be used on all Quinta
Pump option hot water priority can be used on all Quinta Pro Pro range
range

Normal position
Normal position for
for the
the iSense
iSense controller
controller
mounted in
mounted in reference
reference room
room within
within the
the building
building
(room compensation)
(room compensation)
100m Max
Max
room

100m
inroom

iSense can
iSense can be
be fitted
fitted into
into boiler
boiler
heightin

control panel
panel for
for outside
outside
Suggestedheight

control
1.6M
1.6M

230v
weather compensation
weather compensation only only
230v
100m Max
100m Max Supply
Supply
Suggested

Outside sensor
Outside sensor on
on
North facing
North facing wall
wall
Pump PM1
Pump PM1

Pump PM2
Pump PM2
Sensor
DHW Sensor
DHW
Condensate
Condensate

Gas
Gas
Flow
Flow

22 Port
Port spring
spring Bypass valve
Bypass valve Return
Return
return valve
return valve

QP
QP 006A
006A

18
Single Quinta Pro boiler, heating and priority hot water
using the iSense controller (3 Port valve option)

OT

Factory fitted iSense controller Outside


supply lead to Sensor 3 way valve
Note: Control PCBs are shown diagrammatically Pump PM1
be connected
Earths are omitted for clarity
to a 230v fused Calorifier
spur for boiler Sensor
permanent supply Boiler parameter P37 must be set to 0
2 Port
spring
return
See drawing QP004E valve

230v fused
supply for
2 port valve

QP 006B

Single Quinta Pro boiler, heating and priority hot water


using the iSense controller (Pump option)

Note: Control PCBs are shown diagrammatically


Earths are omitted for clarity
OT

Factory fitted Outside Pump PM1 Pump PM2


iSense controller
supply lead to Sensor
be connected
to a 230v fused Calorifier
spur for boiler Sensor
permanent supply Boiler parameter P37 must be set to 0
2 Port
spring
return
See drawing QP004E valve

230v 3amp fuses


supply for
2 port valve

QP 006C

19
Multiple Quinta Pro boilers, heating only, outside weather or room
compensation with the Celcia MC4 and iSense controller with a low
loss header (Optimising/weather compensated)
Power Supply
• Boilers require a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead

Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed

Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)

Fitting the Controls


• Fit the iSense controller in a normally occupied reference room within the building being
heated if room and weather compensation is required. If weather only is required,
the iSense can be fitted in a boiler control panel. Install the MC4 controller adjacent
to the boiler plant and connect as shown
• Install the outside sensor on a North facing wall, and connect to the MC4
(for weather compensation only)

Boiler Control Settings


(see 5.7.2 in technical documentation)
• Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the type of control setting used
• Set up the controller to suit the design requirements and occupancy times for HTG in
accordance with the instruction documents supplied with the controller

Note: Installation can be designed without the use of a low loss header. Omit the header and
shunt pumps. A heating pump must be capable of overcoming the combined resistance of the
boiler, system and pipe work.
A reverse return with a common loop and single primary pump would be suitable.

20
Multiple Quinta Pro boilers, HTG only using a low loss header,
outside weather/room compensation with the Celcia MC4
and iSense controller
Normal position for the iSense
Normal position
controller forin
mounted the iSense
reference
controller
room withinmounted in reference
the building
room within the building

room
room
100m Max
100m Max

in in
iSense can be mounted

height
iSense
boilercan
for be mounted

1.6M
in weather

height
Celcia

1.6M
MC4
Celcia in boiler for weather
compensation only
MC4
compensation only

Suggested
100m Max

Suggested
230v 230v
100m Max Supply
230v Supply
230v
Outside sensor Supply Supply
Outside
on Northsensor Shunt Pump Shunt Pump
on North
facing wall Shunt Pump Shunt Pump
facing wall

Condensate Pump PM1


Condensate Pump PM1
Gas
Gas
Flow
ers rs

Flow
boiloile

Htg Flow sensor


ourur b

Htg Flow sensor


to tfo fo

Return
Return
TwTowo

QP 007

Multiple Quinta Pro boilers, heating only using a low loss header,
outside weather or room compensation with the Celcia MC4
and iSense controller
iSense mounted in reference room
(or boilermounted
iSense for weather compensation
in reference room only)
(or boiler for weather compensation only)

OT - Bus DIGI
OT - Bus DIGI Outside sensor on
North
Outsidefacing wall
sensor on
North facing wall
100max
100max
Boiler No. 1 Note: Control PCBs are shown diagrammatically
Boiler No. 1 Note: Control
Earths PCBsfor
are omitted are shown diagrammatically
clarity
Earths are omitted for clarity
Factory fitted supply
lead to be
Factory connected
fitted supply Shunt pump
to lead
a 230v fused
to be spur for
connected Shunt pump
boiler permanent
to a 230v supply
fused spur for

MC4
boiler permanent supply
Shunt pump Shunt pump Shunt pump
Shunt pump Shunt pump Shunt pump
System Pump PM1 Switch spur 230v
(MaxPump
System 1amp)PM1 Rated atspur
Switch 3amps
230v
(Max 1amp) Rated at 3amps
OT OT OT
OT OT OT
X81 X81 X81 L N E E 17 18 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14
X81 X81 X81 L N E E 17 18 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Boiler No. 4 Boiler No. 3 Boiler No. 2


Boiler No. 4 Boiler No. 3 Boiler No. 2

Flow Sensor
Mount on flow pipework to
Flow Sensor
register
Mount ona common flow to
flow pipework
temperature
register a common flow
temperature

QP 007A
QP 007A
QP 007A

21
Multiple Quinta Pro boilers, heating and hot water priority,
outside weather or room compensation with the Celcia
MC4 and iSense controller with a low loss header
(Optimising/Weather compensated)
Power Supply
• Boilers require a permanent 230v single phase supply fused at 6.3 amps
connected to the factory fitted fly lead

Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed

Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)

Fitting the Controls


• Fit the iSense controller in a normally occupied reference room within the building being
heated if room and weather compensation is required. If weather only is required, the iSense
can be fitted in a boiler control panel. Install the MC4 controller adjacent to the boiler plant
and connect as shown.
• Install the outside sensor on a North facing wall in a sheltered position and connect to the MC4

Boiler Control Settings


(see 5.7.2 in technical documentation)
• Set boiler code P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the type of control setting used
• Set up the controller to suit the design requirements and occupancy times for HTG in
accordance with the instruction documents supplied with the controller

Domestic Hot Water


• When using the Remeha supplied low loss header and pump kit and the hot water diverting
valve or primary pump kit, the calorifier must be sited within 3m of the boiler. In both cases,
the hot water calorifier must be a high recovery unit capable of accepting the full or adjusted
hot water output of the boiler being used (reference parameter P18)
• Set up the controller to suit the design requirements for the hot water times and temperature

22
Multiple
Quinta ProQuinta Proboiler
multiple boilers, heating
heating andandhot hot
wa water
ter priority
priority usingusing
alow a
low header
loss loss header, outside
outside,weatherweather
orroomor room compensation
compensation with thewith
lciathe
Ce
Celcia
MC4 MC4
and andcontroller
iSense iSense controller
.
(Hot water produce by single boiler
(Hot water produce by single boiler onlyonly
- 3 -port
3 port valve)
valve)
Quinta Pro 30/45/65 only
Normal position for the iSense
controller mounted in reference
room within the building

Suggested height in room


100m Max

1.6M
Celcia
Celcia
MC4
MC4

100m Max 230v


230v 230v
230v
Supply
Supply Supply
Supply
Outside sensor
Outside sensor
on North
on North Shunt Pump
Shunt Pump
Shunt Pump
Shunt Pump
facing wall
facing wall

Condensate
Pump PM1
Pump PM1
DHW
DHW
Sensor
Sensor
Gas
AB
AB
Flow
ilers

AA B
B Htg Flow
Flow sensor
sensor
Htg
r bo

Bypass
Bypass
fou

valve
valve
to

Calorifier
Calorifier 22 Port
Port spring
spring return
return valve
valve Return
Two

QP
QP 008
008

Multiple
Quinta ProQuinta Proboiler
multiple boilers, heating
heating andand hot hot
wa water
ter priority
priority usingusing
alow a
low header
loss loss header, outside
outside,weatherweather
orroomor room compensation
compensation with thewith
Celciathe
Celcia
MC4 MC4
and andcontroller
iSense iSense controller
.
waterproduce
(Hot water producebybysing
single boiler
le boiler onlyonly - pump
- pump option)
option)
All of the Quinta range
Normal position for the iSense
controller mounted in reference
room within the building
Suggested height in room

100m Max
1.6M

Celcia
Celcia
MC4
MC4

100m Max 230v


230v 230v
230v
Supply
Supply Supply
Supply
Outside sensor
Outside sensor
on North
on North Shunt Pump
Shunt Pump Shunt Pump
Shunt Pump
facing wall
facing wall

DHW Pump
DHW Pump

Condensate
Pump PM1
Pump PM1
DHW
DHW
Sensor
Sensor
Gas
Flow
s
iler

Htg Flow
Htg Flow sensor
sensor
r bo

Bypass
Bypass
valve
valve
fou

22 Port
Port spring
spring Return
to

Calorifier
Calorifier return valve
return valve
Two

QP 008A
QP 008A

23
Quinta Pro multiple boilers heating and priority hot water using a
Quinta Pro
Multiple multipleboilers,
boilers heating and
andpriority
priorityhot
hotwater
water usingaa
low loss, Quinta
outsidePro
weather orheating
room compensation with the using
Celcia
low loss
low loss,header,
outsideoutside
weather or room
weather orcompensation
room with the
compensation Celcia
with the
MC4 and iSense controller.
MC4
Celcia and iSense
MC4produced controller.
and iSense
(Hot water bycontroller
single boiler only - 3 Port valve)
(Hot water produced
(Hot water produced by bysingle
singleboiler
boileronly
only--33Port
Portvalve)
valve)
iSense mounted in reference room
(or boiler control panel)
iSense mounted in reference room
(or boiler control panel)

OT - Bus DIGI
Outside sensor on
OT - Bus DIGI
North facing wall
Outside sensor on
North facing wall
100m max
Note: Control PCBs are shown diagrammatically 100m max
Earths are omitted for clarity
Note: Control PCBs are shown diagrammatically
Earths are omitted for clarity
2 Port spring
Factory fitted return valve
supply lead to 2 Port spring Shunt pump
Factory fitted return valve Calorifier
be connected Thermostat
supply lead to Calorifier See drawing QP004E Shunt pump
to a 230v fused
be connected 230v fused supplyThermostat
spur for boiler See drawing QP004E
to a 230v fused for 2 port valve
permanent supply 230v fused supply
spur for boiler

MC4
for 2 port valve
permanent supply
Shunt pump Shunt pump Shunt pump

MC4
Boiler Shunt pump Shunt pump Shunt pump
Parameter
Boiler P37 System Pump PM1 Switch spur 230v
must be set to 0 (Max 1amp) Rated at 3amps
Parameter P37 On/off On/off On/off
System Pump PM1 Switch spur 230v
must be set to 0 On/off
OT On/off
OT On/off
OT (Max 1amp) Rated at 3amps

OT OT OT
X81 X81 X81 L N E E 17 18 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14

X81 X81 X81 L N E E 17 18 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Boiler No. 4 Boiler No. 3 Boiler No. 2


Boiler No. 4 Boiler No. 3 Boiler No. 2

Flow Sensor
Mount on flow pipework to
Flow Sensor
register a common flow
Mount on flow pipework to
temperature
register a common flow
temperature
QP 008B
QPQP 008B
008B

Quinta
MultiplePro multiple
Quinta boilers heating
Pro boilers, heating and
and priority hot water using
using aa
Quinta Pro multiple boilers heating and priority hot water using a
low
low loss, outside outside
loss header, weatherweather
or roomorcompensation with thewith
room compensation Celcia
the
low loss, outside weather or room compensation with the Celcia
MC4
Celciaand iSense
MC4 controller.
and iSense controller
MC4 and iSense controller.
(Hot
(Hot water produced by single boiler only
only -- pump
pump option)
option)
(Hot water produced by single boiler only - pump option)
iSense mounted in reference room
(or boiler control panel)
iSense mounted in reference room
(or boiler control panel)

OT - Bus DIGI
Outside sensor on
OT - Bus DIGI
North facing wall
Outside sensor on
North facing wall
100m max
Note: Control PCBs are shown diagrammatically 100m max
Earths are omitted for clarity
Note: Control PCBs are shown diagrammatically
Earths are omitted for clarity
2 Port spring
Factory fitted return valve Shunt DHW
pump pump
supply lead to 2 Port spring
Calorifier Shunt DHW
Factory fitted return valve
be connected Thermostat pump pump
supply lead to Calorifier See drawing QP004E
to a 230v fused
be connected 230v fused Thermostat
supply
spur for boiler See drawing QP004E
to a 230v fused for 2 port valve
permanent supply 230v fused supply
spur for boiler

MC4
for 2 port valve
permanent supply
Shunt pump Shunt pump Shunt pump

MC4
Boiler Shunt pump Shunt pump Shunt pump
Parameter P37 System Pump PM1 Switch spur 230v
Boiler (Max 1amp) Rated at 3amps
must be set to
Parameter P37 0 On/off On/off On/off
System Pump PM1 Switch spur 230v
On/off
OT On/off
OT On/off
OT (Max 1amp) Rated at 3amps
must be set to 0
OT OT OT
X81 X81 X81 L N E E 17 18 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14

X81 X81 X81 L N E E 17 18 19 1 2 3 4 5 6 7 8 9 10 11 12 13 14

Boiler No. 4 Boiler No. 3 Boiler No. 2


Boiler No. 4 Boiler No. 3 Boiler No. 2

Flow Sensor
Mount on flow pipework to
Flow Sensor
register a common flow
Mount on flow pipework to
temperature
register a common flow
temperature
QP
QP008C
008C
QP 008C

24
iSense Pro Multiple Boiler Controller
The iSense Pro kits listed below show the basic kits for two boilers. Any additional boilers
(up to 8 boilers) will require an extra Open Therm (OT) interface (AD287) and a Bus Cable
(1 x AD124 -1.5m). Systems with two circuits will require two extra flow sensors (AD199).
All installations and fitting instructions are supplied with the iSense Pro kits or available
via our website www.remeha.co.uk

Basic Two Boiler Kit: Quinta Pro Option AD244


Kit No. KT1089
1 x AD283: iSense Pro complete with wall box Part No. 100018256
1 x AD244: Room Sensor Basic (no control) Part No. 100012044
1 x AD287: Open Therm Interface (not required in first boiler) Part No. 100018921
1 x AD134: Bus Cable 12m (iSense controller to second boiler) Part No. 88017851
1 x AD199: Flow Sensor Part No. 88017017
1 x AF60: Outside Sensor Part No. 95362450
1 x KVT60: DHW Sensor Part No. 95362448

Basic Two Boiler Kit: Quinta Pro Option AD278


Kit No. KT1090
1 x AD283: iSense Pro complete with wall box Part No. 100018256
1 x AD278: Room Sensor Control (temperature control) Part No. 100017732
1 x AD287: Open Therm Interface (not required in first boiler) Part No. 100018921
1 x AD134: Bus Cable 12m (iSense controller to second boiler) Part No. 88017851
1 x AD199: Flow Sensor Part No. 88017017
1 x AF60: Outside Sensor Part No. 95362450
1 x KVT60: DHW Sensor Part No. 95362448

Basic Two Boiler Kit: Quinta Pro Option AD258


Kit No. KT1091
1 x AD283: iSense Pro complete with wall box Part No. 100018256
1 x AD258: Digital Room Sensor Control (remote control) Part No. 100013478
1 x AD287: Open Therm Interface (not required in first boiler) Part No. 100018921
1 x AD134: Bus Cable 12m (iSense controller to second boiler) Part No. 88017851
1 x AD199: Flow Sensor Part No. 88017017
1 x AF60: Outside Sensor Part No. 95362450
1 x KVT60: DHW Sensor Part No. 95362448

Basic Two boiler Kit: Quinta Pro Option 0 -10v


Kit No. KT1154
1 x AD283: iSense complete with wall box Part No. 100018256
1 x AD199: Flow Sensor Part No. 88017017
1 x AD287: Open Therm Interface (not require for first boiler) Part No. 100018921
1 x Bus Cable 12m (iSense to second boiler) Part No. 88017836

25
iSense Pro Controller Kit Options
The options illustrated show the four types of controls available. The difference
with the first three kits depends on which type of internal sensor/control is used.

KT1089: the basic internal sensor, no adjustment is available

KT1090: the inside sensor can be used to adjust the room temperature

KT1091: includes a digital remote control which not only acts as a sensor but changes can
be made to the main controller which includes set point temperatures and it can also override
the time settings on both heating and hot water

KT1154: can be used as a boiler sequencer. Will require a 0 - 10v input from a remote
BMS controller

KT1152: required when using more than two boilers (one kit per added boiler up to eight boilers)
e.g. six boilers will require four KT1152

Fitting and user instructions are supplied complete with the iSense Pro kits. The controller is
suitable for 2 - 8 boilers and will time control two zones (optimising and compensating) and
also control temperature and time hot water (note hws control is via a sensor not a thermostat).

Note: The OT cable between the iSense controller and the first boiler is not supplied.
Cable should be 2 core .7mm² (screened when running with higher voltage cables)

iSense Pro Component Details


iSense Pro controller complete with wall box AD283 - Part No. 100018256
Room Sensor Basic AD244 - Part No. 100012044
Room Sensor Temperature Control AD278 - Part No. 100017732
Digtal Remote Room Control AD - Part No. 100013478
Open Therm Interface AD287 - Part No. 100018921
Strap on Temperature Sensor AD199 - Part No. 88017017
Outside Sensor AF60 - Part No. 95362450
DHW Sensor KVT60 - Part No. 95362448
Bus Cable AD134 - 12 metre cable - Part No 88017851
Bus Cable AD124 - 1.5 metre cable - Part No.88017836

The following accessories are not yet available for the iSense Pro.
Please contact our sales or technical departments for further information.

Digital Wireless Remote Control AD256 - Part No.100013475


Wireless Outside Sensor AD251 - Part No.100013306
Wireless Receiver AD252 - Part No.100013307
(must be used if AD256 and AD251 is used)

Note: The above kits and controls will also be suitable for the floor standing Gas 110
Boilers with the exception of the Quinta Pro Open Therm interface (AD287). This will
be replaced by the Open Therm interface AD286 Part No.100018920. This interface
fits external to the boiler.

26
Multiple boilers, heating and hot water using a low loss header with
the iSense Pro controller (Optimising/weather compensated control
for dual heating zone and hot water from all or single boilers)
Power Supply
• Boilers require a permanent 230v single phase supply fused at 6.3 amps connected to the
factory fitted fly lead.

Boiler Interlocks
(for pressure switches etc.)
• Safety Interlock - remove the existing link and fit volt free switch pair to BL on the main
control PCB. If the circuit is open the boiler will go to a shut down mode displaying code
9 and will restart when the circuit is closed

Indication Controls
(to report actual function)
• Common Alarm - volt free relay on SCU-X01 (see boiler manual for full details)
• Boiler Run - volt free relay on SCU-X01 (see boiler manual for full details)

Boiler Control Settings


(see 5.7.2 in technical documentation)
• Set boiler codes P1 to the required flow temp i.e. 80 = 80ºC (system design requirements)
• Boiler will recognise the type of control setting used

Fitting the controls


• Use the following hydraulic and wiring diagrams to best match the building requirements
• Fit the iSense Pro in the supplied wall mounted box adjacent to the boiler plant
• Connect all chosen auxiliary controls i.e. pumps, 3 way valves, outside sensor, flow sensors
etc. as indicated

Control Logic
• Set up the iSense Pro controller in conjunction with the iSense Pro installation and service
manual and to suit the installation and building heat loss response time. It will provide timed
weather compensated heating with an optimum start facility (uses inside and outside
sensors to delay the on time as dictated by weather conditions)
• Heating (all boilers available): during the timed on periods the heating will be daytime
weather compensated (in accordance with the heating curve programmed). The controller
will directly control each boiler, modulating their output and calling as many as are required
­to achieve the desired comfort conditions dictated by the compensation parameters
• Hot water: two hydraulic options are available as shown in the diagrams. When using
the single boiler option, the hot water controls, i.e. the pump and sensor, are taken to
the boiler controls. A separate volt free time control will have to be used (not supplied
by Remeha Commercial)
• The following diagrams QP009 to QP009E show systems with two zones.
If only using a single zone, use zone B controls and omit zone C controls

Kit KT1154 will enable the iSense Pro controller to operate as a boiler sequencer. This will
require a 0 - 10v input from an external source i.e. BMS controller. The iSense Pro will control
the boilers to achieve the setpoint temperature supplied from the BMS control i.e. 5v will equal
50ºC. How the iSense Pro will sequence the boilers (lead/lag etc) will depend on how the user
control parameters are set within the iSense Pro controller.

27
Quinta Pro multiple boiler HTG only using a low loss header outside,
Quinta Pro
Multiple multiple
Quinta
weather/room Pro boiler HTG
boilers,
compensationHTG onlyiSense
only
with usingaPro
using alow
low lossheader,
loss header outside,
controller.
weather/room
outside compensation
weather/room with iSense
compensation Pro controller.
with iSense Pro controller
Normal position for the iSense Pro
remote controllers or room sensors mounted
Normal position for the iSense Pro
in reference room within the building
remote controllers or room sensors mounted
in reference room within the building
100m Max
iSense Pro
Outside sensor in wall 100m Max
Zone B Optional Zone C

room in room

Suggested
iSense
mounted Pro
on North
Outside sensor inbox
wall
facing wall Zone B Optional Zone C

Suggested
height inheight
on North mounted

1.6M 1.6M

1.6M 1.6M
230v

height inheight
100m Max 230v
box
facing wall

Suggested
Supply Supply
100m Max 230v 230v

room in room
Suggested
Supply Supply
Pump SH1 Pump SH2

Pump SH1 Pump SH2 Htg Flow sensor

Condensate Htg Flow sensor

Condensate Pump B Pump C


Gas
rs rs

Flow 3 Port valve B 3 Port valve C


Pump B Pump C
oile oile

Gas
3 Port valve B 3 Port valve C
ix b ix b

Flow
to s to s
Two Two

Return

Return

QP 009
QP 009
QP 009

Multiple Quinta Pro boilers, heating and HTG and DHW using
a Quinta Pro
low loss multiple
header, boiler
outside HTG and DHWcompensation
weather/room using a low loss
withheader,
Quinta Pro
outside multiple boiler
weather/room HTG and DHW using
compensation a low
Proloss header,
iSense Pro controller (DHW via multiplewith iSense
boilers) controller.
outside
(DHW viaweather/room compensation with iSense Pro controller.
multiple boilers)
(DHW via multiple boilers)
Normal position for the iSense Pro
remote controllers or room sensors mounted
Normal position for the iSense Pro
in reference room within the building
remote controllers or room sensors mounted
in reference room within the building
iSense 100m Max
Pro
room in room

Suggested

Zone B 100m Max Zone C


Outside sensor in wall
iSense
on North mounted
Pro
height inheight

Suggested
1.6M

1.6M

inbox
wall
height inheight

Outside
facing sensor
wall Zone B Zone C
Suggested

on North mounted
100m Max 230v 230v
1.6M

1.6M

box
room in room

facing wall Supply Supply


Suggested

100m Max 230v 230v


Supply Pump SH2 Supply Htg Flow sensor Htg Flow sensor
Pump SH1
Pump
Htg B sensor
Flow Pump
Htg FlowC sensor
Pump SH1 Pump SH2
DHW sensor
Pump B Pump C
3 Port valve 3 Port valve
Condensate DHW sensor

Gas 3 Port
Pump DHW1valve 3 Port valve
Condensate
rs rs

Flow
oile ile

Gas Pump DHW1


ix b ix bo

Flow
to s to s
Two Two

Return Bypass valve 2 Port spring return valve

Return Bypass valve 2 Port spring return valve

QP 009A
QP 009A
QP 009A

6 28
6
Multiple Quinta Pro boilers, HTG only using a low loss header,
outside weather/room compensated with iSense Pro
(to be used in conjuction with QP009)

0 - 10v C C B AUV
S Syst
CDI CDI CDR
C B C B BF AF - + O T E N L C S N E N L C S N E N L E N L N L

Switch Fused
Supply
Room Room Flow Flow Flow HWS O/Side Htg Pump 3 Port Htg Htg
HWS Secondary Pump
Sensor Sensor Sensor Sensor Sensor Sensor Sensor C Valve C Pump B Valve B
(if required)

Bus Cable Note: When using single zone, control


Interface AD287 fitted into (B) flow sensor is connected to S Syst.
each boiler (not required
for No.1 boiler)
Bus Cable

Some earths omitted for clarity


s
iler
8 bo

Diagram shows both heating


On/off
2 to

On/off On/off circuits connected (B-C). Delete


controls /pumps/3 port valves of
OT zone C if only one circuit is required

Shunt pump SH1 Shunt pump SH2 Shunt pump SH3


Boiler No.1 Boiler No.2 Boiler No.3 QP 009B

Multiple Quinta Pro boilers, heating and HTG and DHW using a low
loss header, outside weather/room compensation with the iSense
Pro controller (DHW via multiple boilers)
(to be used in conjuction with QP009A)

0 - 10v C C B AUV
S Syst
CDI CDI CDR
C B C B BF AF - + O T E N L C S N E N L C S N E N L E N L N L

Switch Fused
Supply
Room Room Flow Flow Flow HWS O/Side Htg Pump 3 Port Htg Htg
HWS Secondary Pump
Sensor Sensor Sensor Sensor Sensor Sensor Sensor C Valve C Pump B Valve B
(If required)

Bus Cable Note: When using single zone control Thermostat Safety
Interface AD287 fitted into (B) flow sensor is connected to S Syst. Limiter
each boiler (not required
for No.1 boiler)
Bus Cable 2 C 1 2 C 1
HWS Primary Pump
Some earths omitted for clarity
s
iler
8 bo

On/off
2 to

On/off On/off
Orange
Blue
Grey
Brown

Wiring detail of controls when using a Remeha


OT Diagram shows both heating Commercial Calorifier with a 2 port spring return
circuits connected (B-C). Delete valve. If using a different type of calorifier, please 2 Port Spring Return
controls /pumps/3 port valves of follow manufacturer’s instructions regarding Motorised Valve
zone C if only one circuit is required control and wiring details
Shunt pump SH1 Shunt pump SH2 Shunt pump SH3
Boiler No.1 Boiler No.2 Boiler No.3

QP 009C

29
Multiple Quinta Pro boilers, HTG and DHW using a low loss header,
Quinta
outside Pro multiple boiler
weather/room HTG and with
compensation DHWthe
using a low
iSense loss
Pro header,
controller
outside
(DHW fromweather/room
single boiler) compensation with the iSense Pro controller.
(DHW from single boiler)
Normal position for the iSense Pro
remote controllers or room sensors mounted
in reference room within the building

iSense
100m Max
DHW Pro
Outside sensor

Suggested height in room


Time

Suggested height in room


on North Control
in wall Zone 1 Optional Zone 2
mounted
facing wall box

1.6M

1.6M
100m Max 230v
Supply
Pump Pump
Pump SH1 SH2 SH3

Htg Flow sensor


DHW
Thermostat Htg Flow sensor
Condensate
Pump B Pump C
Gas
Bypass
valve Flow 3 Port valve B 3 Port valve C
Boiler flow
s
iler

DHW Sensor
bo

Secondary
six

Pump 2 Port spring return valve Return


Calorifier
to
Two

QP 009D
QP 009D
Multiple Quinta Pro boilers, heating and priority hot water
using a low loss header, outside weather or room compensation
Quinta
with Pro multiple
the iSense boilers heating and priority hot water using a
controller
low
(Hot loss,produced
water outside weather orboiler
by single room only
compensation with the Celcia
- pump option)
MC4 and the iSense controller.
(Hot water produced by single boiler only - pump option)
0 - 10v C C B AUV
S Syst
CDI CDI CDR C B C B AUX 0 - 10v BUS
C B C B BF AF - + O T E N L C S N E N L C S NS Syst. E N L ECDINCDR
L N L
CDI
N N N L N L N L N L AF BF B C B C OVBA
Neutral
Close
Open
Neutral
Close
Open

Switch Fused Supply


Room Room Flow Flow Flow O/Side Htg Pump 3 Port Htg Htg HWS Secondary Pump
Sensor Sensor Sensor Sensor Sensor Sensor C HWS Secondary
Valve C Pump B Valve B (If required)
Pump X
Bus Cable
(If required) 1 2 3
Interface AD287 fitted into
3 Port 3 Port
each boiler (not required
Htg Htg O/S Common Flow
Flow PCBs Roomdiagrammatically
Room
Boiler No. 1 in cascade Note: Control are shown
Valve
for C boiler)
No.1 Valve B Pump C Pump B Sensor Flow Sensor Sensor B Sensor C Sensor B Sensor C
Bus Cable Main control PCB PCB-SCU - S02 PCB - SCU - X01 PCB - IF 01
PUMP
OT BL R L Tout Tdhw X81
s
iler

Pump hws/3wv Egv Status Status Status OTm 0-10v 0-10v


s
iler

X81 X81 X81


8 bo

OT OT E N L E N C D E N L NC C NO NC C NO NC C NO
6 bo
2 to

On/off On/off
2 to

On/off On/off On/off

OT OT OT
BR BL GN/YW

Factory fitted supply lead


Shunt pump SH2 Shunt pump SH3 to be connected to a 230v
Boiler No.2 Boiler No.3 Shunt pump Shunt pump Shuntfor
fused spur pump
boiler
Boiler
Time No 1 in cascade
control Boiler No. 2 Boiler No. 3 Boilersupply
permanent No. 4
Shunt pump Pump
DHW 2 port spring
Time Control SH1 PM2
DHW (voltNote:
free)Controlreturn
PCB’s valve
are Calorifier Diagram shows both heating circuits connectedSome earths
Factoryshows
fitted both heating circuits
(volt free) Shunt Pump shown diagrammatically
Diagram connected (B-C). Delete
2 Port pump SH1 PM2 Thermostat Valve and thermostat (B-C)wiring when using a Remeha Remtank
delete controls /pumps/3 port valvesomitted
of
supply /pumps/3
controls lead to port valves of zonespring
C if only one circuit
Calorifieris required. 230v fused supply for calorifier, see separate details on page 13. For other types of
be connected
return zone C if only one circuit is required
calorifiers please follow manufacturer’s instructions for clarity
Note: When using single zone control (B) flow sensor
valve is connected to S Syst.
Thermostat 2 port valve (from boiler supply)
to a 230v fused Valve and thermostat wiring when using
230v fused supply
spur for boiler
for 2 port valve our Remtank calorifier see separate Earths omitted for clarity
permanent supply (from boiler supply) detail on page 13. For other type calorifiers
please follow manufacturers instructions. QP 009E
QP 009E
30
28
Quinta Pro multiple boilers, HTG only using a 0-10v input from a
remote BMS control

0 - 10v C C B AUV
S Syst
CDI CDI CDR
C B C B BF AF - + O T E N L C S N E N L C S N E N L E N L N L

Flow Sensor AD199

Flow Sensor

Bus Cable Interface AD287 fitted into Switch Fused Supply


each boiler (not required External BMS
for No.1 boiler) Controller
(not supplied)
Bus Cable

s
iler
8 bo
OT OT 2 to
On/off On/off On/off

OT
Some earths omitted for clarity
QP 009F
Shunt pump SH1 Shunt pump SH2 Shunt pump SH3
Boiler No.1 Boiler No.2 Boiler No.3

Connecting multiple boilers with external control interlocks and


Connecting multiple boilers with external control interlocks and
alarm and run signals.
alarm and run signals

Boiler No. 1 Boiler No. 2 Boiler No. 3

On/off On/off On/off

External
interlock

Connect boilers in parallel. Ensure polarity is maintained on each boiler

Boiler No. 1 Boiler No. 2 Boiler No. 3

X3 X4 X3 X4 X3 X4

Status Status Status Status Status Status

Nc C No Nc C No Nc C No Nc C No Nc C No Nc C No

Supply voltage (max 230v 1amp)

Supply voltage (max 230v 1amp)


Run Signal
N Connect boilers in parallel. Ensure polarity is maintained on each boiler
Diagram shows run signal connected to X3 on SCU - X01
N X3 potentiometer will be set to 2.
Alarm signal is connected to X4 the X4 potentiometer will be set to 0.
There are various options. Please refer to the Quinta Pro installation booklet.
Alarm Signal
QP 010

Quinta Pro Nominal flow rates and boiler resistances


QP 010
Quinta Pro 30 output Quinta Pro 45 output Quinta Pro 65 output Quinta Pro 90 output Quinta Pro 115 output
29.3kW @ 80/60ºC 40kW @ 80/60ºC 61kW @ 80/60ºC 84.2kW @ 80/60ºC 107kW @ 80/60ºC

Nom flow Boiler Nom flow Boiler Nom flow Boiler Nom flow Boiler Nom flow Boiler
System ∆t l/s resistance l/s resistance l/s resistance l/s resistance l/s resistance
mbar mbar mbar mbar mbar
20 0.35 70.00 0.48 90.00 0.73 130 1.00 140 1.28 250
19 0.37 77.56 0.50 99.72 0.77 144 1.06 155 1.35 277
18 0.39 86.42 0.53 111.1 0.81 160 1.12 173 1.42 309
17 0.41 96.89 0.56 124.5 0.86 180 1.18 194 1.51 346
16 0.44 109.38 0.60 140.6 0.91 203 1.26 219 1.60 391
15 0.47 124.44 0.64 160.0 0.97 231 1.34 249 1.71 444
14 0.50 142.86 0.68 183.6 1.04 265 1.44 286 1.83 510
13 0.54 165.68 0.74 213.0 1.12 308 1.55 331 1.97 592
12 0.58 194.44 0.80 250.0 1.22 361 1.68 389 2.13 694
11 0.64 231.40 0.87 297.5 1.33 430 1.83 463 2.33 826
10 0.70 280.00 0.96 360.0 1.46 520 2.01 560 2.56 1000

31
Designed and produced by Sans Frontiere Marketing Communications – 01273 487 800 – www.sansfrontiere.co.uk
Remeha Commercial
Head Office
Remeha House
Molly Millars Lane
Wokingham
Berkshire RG41 2QP
T: 0118 978 3434
F: 0118 978 6977
E: boilers@remeha.co.uk

www.remeha.co.uk

The data published in this technical sales leaflet is based on the latest information (at date of publication)
and may be subject to revisions. It should be read in conjunction with our full technical brochure
(available on request). We reserve the right to continuous development in both design and manufacture,
therefore any changes to the technology employed may not be retrospective, nor may we be obliged
to adjust earlier supplies accordingly.
Issue 2 date: Nov 2012
TreadLightly
ON THE PLANET

Remeha is committed to carbon offsetting