You are on page 1of 12
Air System Sizing Summary for AC/DC ROOM. Project Nane: SKIKDA Prepared by: bect snn7me. 05:33 PM Alt System information ‘system Name ACIDIC ROOM. Equipment Class PKG ROOF Number of Zanes 4 System Type SZCAV Floor area 164.5 Sizing Zone and Space Si Zore CFM Peak zone sensible load Caleulation Months Jan to Dec ‘Spece CFM ‘Coincident space loads Sizing Deta Calculated Central Cooling Coil Sizing Data Total colload 28 Tons Load occurs at Ju 1500 Sensible cal load 2.6 Tans OADB/WE 91.0 / 740 *F Coil CFMat Jul 1500 1432 CFM Entering DB WB 16.0 162.2 °F Max possible CFM 1432 CFM Leaving DB /WB 55.3 540 °F Design supply temp, 53.0 °F Coll ADP 53.0 °F ‘Ten 5a.4 Bypass factor 9.100 BTU 205.6 Resuting RH 46% Woter flow @ 10.0 rise = gm Zone T-stat Check of 1 OK ‘Supply Fan Sizing Data ‘Actual max CFM at Jul 1300, 1432 CFM Fan mater BHP 0.08 BHP Standard CFM 1398 CFM Fan mater KW 0.06 KW ‘Actual max CFM 8.87 CFM Fan static 0.20 in. wa, Outdoor Ventilation Air Data Design airflow CFM 36 CFM CFiiperson 18.00 CFMiperson CFM 9.22 CFM Carrier Hourly Analysis Program v4.04 Paget Zone Sizing Summary for AC/DC ROOM. Project Nane: SKIKDA snn7me. Prepared by: bect 05:33 PM ‘Sizing Calculation information Zone and Space Sizing Method! Zore CFM Peak zone sensible load Caleulation Months Jan to Dec ‘Spece CFM ‘Coincident space loads Sizing Deta Calculated Zone Sizing Data Maximum] Design Time] Maximum’ Cooling air of| Heating sensible Flow Peak Load fone Namo: ameu)| ce Load] «MBH one t 308 1822 1432 “ua 1300 46 Zone Terminal Sizing Data No Zone Terminal Sizing Data required fortis system ‘Space Loads and Airflows Cooling] Time Air] Heating Izone Name Sensible of] Flow Load Space lame mutt| et Load| _icem»| cae mone 4 ‘ACIDE ROOM i aoe] wl ta00 Te a6 Carrier Hourly Analysis Program v4.04 Page? Air System Design Load Summary for AC/DC ROOM Project Nane: SKIKDA snn7me. Prepared by: bect 05:33 PM DESIGN COLNE DESIGN HEATING. [COOLIIG DATA AT Jul 1500 IHEATING DATA AT DES HTS [COOLING OADB /WB 91.0 F (74.0 IEATING OA DB | WB -6.0°F 7.2 F ‘Sensible Latent Sensible| Latent -OUELOADS Detais| _etunn| _eTunn Detais| __ceTuhn| _eTunn) (Solar Loads 19 316] : 19 - : fal Transmission 10 fF 370) “10 2261 fof Transmission 181 fF 2s 1611 “ural (class Transmission 19 158] 194 a5 [Skylcht Transmission off o of o jar Transmission. oe o co o oor Transmission 61 fF 24 71 0 arttions "128 fF 70s "23 o Icetina off o of o loverhead Lightina s2aw “110s = o o [Task Lighting cow! o o o lecic Equant ToDoWI as o o eons 2 530) 310 o o o itr tion : 0 o o o 0 iscelaneous : 0 o : o 0 [Safety Factor 7103 10%. 2a a 1 o o b> Total Zone Loads. : 30674] 1001 z 92 o ‘one Conclionina 30460) ‘004 107 o enum Wall Loe O& o . a o enum Root Load 0% o o o enum Lighting Loc 0% o o o tun Fan Load aaaacrw o =| 453 cr 0 [vention Load 35 CFM 353 2 35 CFM 75 a [Supply Fan Lose 1432 CFM. 212] =| 432 cr 712] [Space Fan Col Fans. : o = : o uct Hest Gain / Loss & o : 1 o b> Tatal Svatem Load : BID 102 : 36 0 Icentral Cootin Co - 31255) 1933. zi o o b> Tatal Conditior 31255] 1943 0 0 key: Positive vallues are elg loads Positive values are htg loads Heqative values are hta loads. Heaative values are clq loads Carrier Hourly Analysis Program v4.04 Pages Air System Sizing Summary for CONTROL ROOM Project Nane: SKIKDA Prepared by: bect snn7me. 05:38 PM Alt System information ‘system Name CONTROL ROOM Equipment Class PKG ROOF Number of Zanes 4 System Type SZCAV Floor area 316 Sizing Zone and Space Si Zore CFM Peak zone sensible load Caleulation Months Jan to Dec ‘Spece CFM ‘Coincident space loads Sizing Deta Calculated Central Cooling Coil Sizing Data Total colload 5.0 Tans Load occurs at Ju 1300 Sensible cal load 56 Tans OADB/WE BBB 73.4 °F Coil CFMat Jul 1300 3097 CFM Entering DB WB T6A 62.3 °F Max possible CFM 3097 CFM Leaving DB /WB 55.4 544 °F Design supply temp, 53.0 °F Coll ADP B34 'F ‘Ten S34 Bypass factor 9.100 BTU 190.3 Resuting RH 46% Woter flow @ 10.0 rise —= apm Zone T-stat Check of 1 OK ‘Supply Fan Sizing Data ‘Actual max CFM at Jul 1300, 3097 CFM Fan mater BHP 0.18 BHP Standard CFM 3022 CFM Fan mater KW 9.3 KW ‘Actual max CFM 8.22 CFM? Fan static 0.20 in. wa, Outdoor Ventilation Air Data Design airflow CFM 84 CFM CFiiperson 21.00 CFMiperson CFM 0.22 CFM? Carrier Hourly Analysis Program v4.04 Paget Zone Sizing Summary for CONTROL ROOM Project Nane: SKIKDA snn7me. Prepared by: bect 05:38 PM ‘Sizing Calculation information Zone and Space Sizing Method! Zore CFM Peak zone sensible load Caleulation Months Jan to Dec ‘Spece CFM ‘Coincident space loads Sizing Deta Calculated Zone Sizing Data Maximum] Design Time] Maximum’ Cooling air of| Heating sensible Flow Peak Load fone Namo: ameuy| ce Load] «MBH one t 66.6 3057 3097 “ua 1300 107, Zone Terminal Sizing Data No Zone Terminal Sizing Data required fortis system ‘Space Loads and Airflows Cooling] Time Air] Heating Izone Name Sensible of] Flow Load Space lame mutt| et Load| _icem»| cae fone 4 ‘CONTROL ROOM i ees] a ta00 a7 Oz Carrier Hourly Analysis Program v4.04 Page? Air System Design Load Summary for CONTROL ROOM Project Nane: SKIKDA snn7me. Prepared by: bect 05:38 PM DESIGN COLNE DESIGN HEATING. [COOLIIG DATA AT Jul 1300 IHEATING DATA AT DES HTS [COOLING OADB /WB 88.8 F (73.4-F IEATING OA DB | WB -6.0°F 7.2 F ‘Sensible Latent Sensible| Latent -OUELOADS Detais| _etunn| Tun Details] __ceTuhn| _eTunn) (Solar Loads a2 ot : 4240 : : fal Transmission 258 fF 10) 259 S20 fof Transmission 377 fF 3357 S77 fe 3452 (class Transmission a2 303) 42 ‘1890 [Skylcht Transmission ore o oe 0 jar Transmission. oe o ra o oor Transmission SET fF 2 S77 0 arttions 301 fF 2H 301 o Icetina off o co o loverhead Lightina 758 W 2518 = o o [Task Lighting ow! o o o lecic Equant 5000 W1 Siti o o eons 4 1181 EEE} o o o itr tion : o o o o 0 iscelaneous : 0 o : o 0 [Safety Factor 7103 10%. ana a2 1 o o b> Total Zone Loads. : 56541 Zot z 10563 o ‘one Conclionina 5868) 2001 2825 o enum Wall Loe O& o . a 0 enum Root Load 0% o o o enum Lighting Loc 0% o o o tun Fan Load oar cru 0 =| sos7 cr o [vention Load 4 CFM. “sal 28S. 4 cru a1 a [Supply Fan Lose 3087 CEM. 459 =| aoa? cr 159] [Space Fan Col Fans. : o = : o uct Hest Gain / Loss & o 1 o b> Tatal Svatem Load : ars, 56. = 143 0 Icentral Cootin Co - 87486) 4136. zi o o b> Tatal Conditior 67486) 4196. 0 0 key: Positive vallues are elg loads Positive values are htg loads Heqative values are hta loads. Heaative values are clq loads Carrier Hourly Analysis Program v4.04 Pages Air System Sizing Summary for ESC ROOM Project Nane: SKIKDA Prepared by: bect snn7me. 05:33 PM Alt System information ‘system Name ESC ROOM Equipment Class PKG ROOF System Type SZCAV Number of Zanes 4 Floor area 2608 ft Sizing Zone and Space Si Zore CFM Sum of space airflow rates Calculation Months Jan to Dec ‘Spece CFM Individual peak space loads Sizing Deta Calculated Central Cooling Coil Sizing Data Total colload AA Tons Load occurs at Ju 1400 Sensible cal load 3.8 Tons OADB/WE 90.4 73.9 °F Coil CFMat Jul 1400 2453 CFM Entering DB WB 16.2 162.8 °F Max possible CFM 2453 CFM Leaving DB /WB 56.4 54.8 °F Design supply temp, 53.0 °F Coll ADP 53.8 °F ‘Ten 55.6 Bypass factor 0.100 BTU 1331 Resuting RH 48% Woter flow @ 10.0 rise —= apm Zone T-stat Check of 1 OK ‘Supply Fan Sizing Data ‘Actual max CFM 2453 CFM Fan mater BHP 9.413 BHP Standard CFM 2101 CFM Fan mater KW 0.09 KW ‘Actual max CFM 8.00 CFM Fan static 0.20 in. wa, Outdoor Ventilation Air Data Design airflow CFM 50 CFM CFiiperson 15.00 CFMiperson CFM 0.22 CFM? Carrier Hourly Analysis Program v4.04 Paget Zone Sizing Summary for ESC ROOM Project Nane: SKIKDA snn7me. Prepared by: bect 05:33 PM ‘Sizing Calculation information Zone and Space Sizing Method! Zore CFM Sum of space airflow rates Calculation Months Jan to Dec ‘Spece CFM Individual peak space loads Sizing Deta Calculated Zone Sizing Data Maximum] Design Time] Maximum’ Cooling air of| Heating sensible Flow Peak Load fone Namo: ameu)| CEM Load] «MBH one t 44 23 2153 “ua 1300 78 Zone Terminal Sizing Data No Zone Terminal Sizing Data required fortis system ‘Space Loads and Airflows Cooling] Time Air] Heating Izone Name Sensible of] Flow Load Space lame mutt| et Load| _icem»| cae mone 4 ESC ROOM i asa] 4300 2S a Carrier Hourly Analysis Program v4.04 Page? Air System Design Load Summary for ESC ROOM. Project Nane: SKIKDA snn7me. Prepared by: bect 05:33 PM DESIGN COOLNG DESIGN HEATING. [COOLIIG DATA AT Jul 1400 IHEATING DATA AT DES HTS [COOLING OADB /WB 90.4 F (73.9 F IEATING OA DB | WB -6.0°F 7.2 F ‘Sensible Latent Sensible| Latent -OUELOADS Detais| _etunn| _eTunn Details] __ceTuhn| _ieTunn) (Solar Loads ue exo] : ea : : fal Transmission "84 fF 613 184 a7 fof Transmission 268 fF 2334 263 2466 (class Transmission af 255) Ed “00 [Skylcht Transmission off o on o jar Transmission. oe o co o oor Transmission 268 fF 13 263 0 arttions 215 fF 215) 215 o Icetina off o of o loverhead Lightina sao 1822] = o o [Task Lighting ow! o o o lecic Equant 10000 w aai20 o o eons 4 1181 EEE} o o o itr tion : o o o o 0 iscelaneous : 0 o : o 0 [Safety Factor 7103 10%. ans a2 1 o o b> Total Zone Loads. : 5351 Zot z a3 o ‘one Conclionina 44593 2001 1882 o enum Wall Loe O& o . a o enum Root Load 0% o o o enum Lighting Loc 0% o o o tun Fan Load misacru o =| ares cm o [vention Load 60 CFM 322 ars 0 CFM 2200 a [Supply Fan Lose 2153. CFM. 319) =| iss crm 319] [Space Fan Col Fans. : o = : o uct Hest Gain / Loss & o 1 o b> Tatal Svatem Load : a5 sao = 29] 0 Icentral Cootin Co - 45775) 3485) zi o o b> Tatal Conditior 45775 3495 0 0 key: Positive vallues are elg Toads Positive values are htg loads Heqative values are hta loads. Heaative values are clq loads Carrier Hourly Analysis Program v4.04 Pages Air System Sizing Summary for TELECOM ROOM Project Nane: SKIKDA Prepared by: bect snn7me. 05:38 PM Alt System information ‘system Name TELECOM ROOM Equipment Class PKG ROOF Number of Zanes 4 System Type SZCAV Floor area 164.5 Sizing Zone and Space Si Zore CFM Peak zone sensible load Caleulation Months Jan to Dec ‘Spece CFM ‘Coincident space loads Sizing Deta Calculated Central Cooling Coil Sizing Data Total colload 23 Tens Load occurs at Ju 1400 Sensible cal load 2A Tons OADB/WE 90.4 73.9 °F Coil CFMat Jul 1400 1463 CFM Entering DB WB 16.3 162.6 °F Max possible CFM 1463 CFM Leaving DB /WB 55.7 544 °F Design supply temp, 53.0 °F Coll ADP B34 F ‘Ten 13 Bypass factor 9.100 BTU 168.3 Resuting RH AT % Woter flow @ 10.0 rise —= apm Zone T-stat Check of 1 OK ‘Supply Fan Sizing Data ‘Actual max CFM at Jul 1400, 1463 CFM Fan mater BHP 0.07 BHP Standard CFM 1435 CFM Fan mater KW 0.05 KN ‘Actual max CFM 7.20 CFM Fan static 0.20 in. wa, Outdoor Ventilation Air Data Design airflow CFM 36 CFM CFiiperson 18.00 CFMiperson CFM 9.22 CFM Carrier Hourly Analysis Program v4.04 Paget Zone Sizing Summary for TELECOM ROOM Project Nane: SKIKDA snn7me. Prepared by: bect 05:38 PM ‘Sizing Calculation information Zone and Space Sizing Method! Zore CFM Peak zone sensible load Caleulation Months Jan to Dec ‘Spece CFM ‘Coincident space loads Sizing Deta Calculated Zone Sizing Data Maximum] Design Time] Maximum’ Cooling air of| Heating sensible Flow Peak Load fone Namo: ameu)| ce Load] «MBH one t 250 163. “163 “a 1400 0 Zone Terminal Sizing Data No Zone Terminal Sizing Data required fortis system ‘Space Loads and Airflows Cooling] Time Air] Heating Izone Name Sensible of] Flow Load Space lame mutt| et Load| _icem»| cae fone 4 ‘TELECOM ROOM i eo] wa ta00 Tes a0 Carrier Hourly Analysis Program v4.04 Page? Air System Design Load Summary for TELECOM ROOM Project Nane: SKIKDA snn7me. Prepared by: bect 05:38 PM DESIGN COOLNG DESIGN HEATING. [COOLIIG DATA AT Jul 1400 IHEATING DATA AT DES HTS [COOLING OADB /WB 90.4 F (73.9 F IEATING OA DB | WB -6.0°F 7.2 F ‘Sensible Latent Sensible| Latent -OUELOADS Detais| _etunn| Tun Detais| __ceTuhn| _eTunn) (Solar Loads 19 317] : 194 : : fal Transmission 325 fF 933 325 562 fof Transmission 181 fF 113921 1611 “ural (class Transmission 19 451 194 a5 [Skylcht Transmission off o of o jar Transmission. oe o co o oor Transmission 61 fF 23 71 0 arttions "128 fF 70s} "23 o Icetina off o of o loverhead Lightina s2aw “110s = o o [Task Lighting cow! o o o lecic Equant So00W| 7060) o o eons 2 530) 310 o o o itr tion : 0 o o o 0 iscelaneous : o o : o 0 [Safety Factor 7103 10%. 2s a 1 o o b> Total Zone Loads. : 25005 1001 z 013 o ‘one Conclionina 24597 ‘004 194 o enum Wall Loe O& o . a o enum Root Load 0% o o o enum Lighting Loc 0% o o o tun Fan Load aaeacrw 0 =| aes cr o [vention Load 35 CFM Ea a6 35 CFM 76 a [Supply Fan Lose 1163 CEM. 172 =| 7183 cr 72 [Space Fan Col Fans. : o = : o uct Hest Gain / Loss & 0 1 0 b> Tatal Svatem Load Pane] 1916 : o 0 Icentral Cootin Co - 25264 4912. zi o o b> Tatal Conditior 25264] 1912. 0 0 key: Positive values are elg loads Positive values are htg loads Heqative values are hta loads. Heaative values are clq loads Carrier Hourly Analysis Program v4.04 Pages

You might also like