Professional Documents
Culture Documents
This specjfication provides standard tolerances for concrete con- PREFACE TO SPECIFICATION CHECKLIST
struction. This document is intended to be used as the reference doc- P l . Standard Specification 117 is intended to be used
ument for establishing tolerancesfor concrete construction by speci-
fication writers and ACI committees writing Standards,
in its entirety by reference in the Project Specification.
Individual sections, articles, or paragraphs should not
be copied into the Project Specifications since taking
them out of context may change their meaning.
Keywords: bending (reinforcing steels); building codes; concrete construction;
concrete piles; concretes; floors; formwork (construction); masonry; mass con- P2. Building codes establish minimum requirements
crete; piers; precast concrete; prestressed concrete; reinforcing steels; specifi- necessary to protect the public. Some of the require-
cations; splicing; standards; tolerances (mechanics). ments in this Standard Specification may be more
stringent than the minimum in order to insure the level
of quality and performance that theOwner expects the
FOREWORD structure to provide. Adjustments to the needs of a
Fl. This foreword is included for explanatory pur- particular project should be made by the Architect/En-
poses only; it is not a part of Standard Specification gineer by reviewing each of the items in the Specifica-
117. tion Checklist and then including the Architect/Engi-
F2. Standard Specification 117 is a Reference Stan- neer’s decision on each item as a mandatory require-
dard which the ArchitectIEngineer may cite in the ment in the Project Specifications.
Project Specifications for any construction project, to- P3. These mandatory requirements should designate
gether with supplementary requirements for the spe- the specific qualities, procedures, materials, and per-
cific project. formance criteria for which alternatives are permitted
This standard is not intended to apply to special or for which provisions were not made in the Standard
structures not cited in the standard such as nuclear re- Specification. Exceptionsto the StandardSpecification
actors and containmentvessels, bins and silos, and pre- should be made in the Project Specifications, if re-
stressed circular structures. It is also not intended to quired.
apply to the specialized construction procedure of P4. A statement such as the following will serve to
shotcrete. make Standard Specification AC1 117 an official part
F3. Standard Specification117 addresses each of the of the Project Specifications:
Three-Part Section Format of the Construction Speci- Tolerances for Concrete Construction and Mate-
fications Institute, organized by structural elements, rials shall conform toall requirementsof AC1 117,
structural components and .types of structures; the Standard Specifications for Tolerances for Con-
numbering system reflects this organization. The lan- crete Construction and Materials, published by the
guage is imperative and terse to preclude an alterna- American Concrete Institute, Detroit, Michigan,
tive. except as modified by the requirements of these
F4. A Specification Checklistis included as a preface Contract Documents.
to, but not forming a part of, Standard Specification
117. The purpose of this Specification Checklist is to Adopted as a Standard of the American Concrete Institute in November 1989
assist the ArchitecUEngineer in properlychoosing and in accordance with the Institute’s standardization procedures.
Copyright O 1990, American Concrete Institute. AU rights reserved, includ-
specifying the necessary mandatory and optional re- ing the making of copla unless pemussion is obtained from thecopyrlght pro-
prietors.
quirements for the Project Specification. *Chairman during initial development of this document.
COPYRIGHT 2002; ACI International (American Concrete Institute) Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
01:39:20 MDT Questions or comments about this message: please call the Document
117-1
Policy Management Group at 1-800-451-1584.
A C 1 117 90 U Obb2949 0034370 4 U
117.2 AC1 STANDARD
P5. The Specification Checklist that follows is ad- Checklist consists of two columns; the first identifies
dressed to each item of the Standard Specification the sections, parts, -and articles of the Standard Speci-
where the ArchitecVEngineer must or may make a fication and the second column contains notes to the
choice of alternatives; may add provisions if not indi- ArchitecUEngineer to indicate the type of action re-
cated; or may take exceptions. The Specification quired by the Architect/Engineer.
TOLERANCES 117.3
Section 3 - Cast-in-place
concrete for foundations
3.4.1.2 Footings Plus tolerance for the vertical dimensions is not specified because no limit is im-
posed. Specifier must designate plus tolerance if desired.
Section 4 - Cast-in-place
concrete for buildings
4.5.5 Floor finish The procedures for specifying and measuring floor finish tolerances set forth herein
are not appropriate for narrow aisle warehouse floors with defined traffic lanes de-
signed for useby specialized wheeled equipment. Consult specific equipment man-
ufacturers for their recommendations.
Section 5 - Precast
concrete The tolerances for precast concrete are intended to apply to all types of precast
concrete construction cast onsite(including tilt-up) and offsite except as set forth
below. Variationsto these tolerances may be advisable after consideration of panel
size and construction techniques required.
ToIerances set forth herein are not intended to apply to plant production of pa-
tented or copyrighted structural systems and/or elements. Designers, specifiers and
contractors should contact the Licensorsof such systems and/or products for ap-
plicable tolerances.
5.1.4 Camber For members with a span-to-depth ratio equal to or exceeding 30, the stated cam-
ber tolerance may require special production measures and result in cost premi-
ums. Where feasible, a greater tolerance magnitude should be utilized where the
span-to-depth ratio is equal to or greater than 30.
5.3 Planer Industrial precast products may not conform to the planar tolerances. Manufac-
elements turers should be consulted for appropriate tolerances for their products.
6.4 - Cross-sectional dimensions 1.2.3 Tolerances are not cumulative. The most re-
6.5 - Relative alignment strictive tolerance controls.
1.2.4 Plus (+) tolerance increases the amount or di-
Section 7 -
Cast-in-place,vertically slipfarmed mension to which it applies, or raises a level alignment.
structures, p. 117.11 Minus (- ) tolerance decreases the amount or dimen-
7.1 - Vertical alignment
7.2 - Lateral alignment sion to which it applies, or lowers a level alignment. A
7.3 - Cross-sectional dimensions nonsignedtolerancemeans or +
Whereonlyone-.
7.4 - Relative alignment signed tolerance is specified (+ or - ), there is no limit
in the otherdirection.
Section 8 -
Mass concrete structures other than
buildings, p. 117.1 1
8.1 - Vertical alignment
8.2 - Lateral alignment
1.3 - Definitions
Arris - The line, edge, or hip in which two straight
8.3 - Level alignment
8.4 -
Relative alignment or curved surfaces of a body, forming an exterior an-
gle, meet; a sharp ridge, as between adjoining channels
Section 9 - Canal lining, p. 117-11
9.1 - Lateral alignment
of a Doric column.
Bowing - The displacement of the surface of a
9.2 - Level alignment planar element from a plane passing through any three
9.3 - Cross-sectiohal dimensions corners of the element.
Clear distance - In reinforced concrete, the least
Section 10 - Monolithic siphons and culverts, p. distance between the surface of the reinforcement and
117-11 the referenced surface, Le., the form, adjacent rein-
10.1 - Lateral alignment
10.2 - Level alignment forcement, embedment, concrete, or other surface.
10.3 - Cross-sectional dimensions Concealed surface -“Surface not subject to visual
observation during normal useof the element.
Section 11 - Cast-in-placebridges, p. 117.12
11.1 - Vertical alignment
Contract documents - The project contract, the
project drawings, and theproject specifications.
11.2 - Lateral alignment Cover - In reinforced concrete, the least distance
-
11.3 Level alignment between the surface of the reinforcement and the outer
11.4 - Cross-sectional dimensions
11.S - Relative alignment surface of the concrete.
Flatness - The degree to which a surface approxi-
Section 12 - Pavement and sidewalks, p. 117-12 mates a plane.
Lateral alignment - The location relative to a spec-
12.1 - Lateral alignment
12.2 - Level alignment ified horizontal line or point in ahorizontal plane.
Level alignment - The location relative to a speci-
Section 13 - Chimneys and cooling towers, p. fied horizontal plane. When applied t o roadways,
117-12 bridge decks, slabs, ramps, or other nominally hori-
13.1 - Vertical alignment zontal surfaces established by elevations, level align-
13.2 - Diameter ment is defined as the vertical location of the surface
13.3 - Wall thickness
relative to the Specified profile grade and specified cross
Section 14 - Cast-in-place nonreinforced pipe, slope.
Levelness - The degree to which a line or surface
p. 117.12
14.1 - Wall thickness parallels horizontal.
14.2 - Pipe diameter Precast linear element - Beam, column, or similar
14.3 - Offsets unit.
14.4 - Indentations Precast planar element - Wall panel, floor panel, or
similar unit.
Project Specifications - The building specifications
SECTION 1 -
GENERAL REQUIREMENTS which employ AC1117 by reference, and which serve as
1.1 - Scope the instrument for making the mandatory and optional
1.1.1 This specification designates standard toler- selections available under these and for specifying items
ances for concrete construction. not covered herein,
1.1.2 The indicated tolerances govern unless other- Relative alignment - The distance between two or
wise specified, more elements in any plane, or the distance between
adjacent elements, or the distance between an element
1.2- Requirements and a defined point orplane.
1.2.1 Concrete construction shall meet the specified SpiraZ - As used in circular stave silo construction,
tolerances. is defined as the distortion that results when the staves
1.2.2 Tolerances shall not extend the structure be- are Document
misaligned so that their edges are inclined while
COPYRIGHT 2002; ACI International (American Concrete Institute) provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
yond legal boundaries. their outer
01:39:20 facesor comments
MDT Questions are vertical, Theplease
about this message: resulting assembly
call the Document
Policy Management Group at 1-800-451-1584.
TOLERANCES 117.5
appears twisted with the vertical jointsbecoming long- 2. The range of variation permitted in maintaining
pitch spirals. a specified dimension.
Specified surface, plane, or line - A surface, plane, 3. A permitted variation from location or align-
or line specified by the contract documents; specified ment.
planes and lines may slope and specified surfaces may Vertical alignment - The location relative to speci-
have curvature. fied vertical plane ora specified vertical line or from a
Tolerance - line or plane referenceto a vertical lineor plane. When
l . The permitted variation from given
a dimension applied to battered walls, abutments or other nearly
or quantity. vertical surfaces, vertical alignment is defined as the
"Ic 4
STRAIGHT
2'
2B 2
IS~METRICVIEW
STANDEE
(ISOMETRIC VIEW)
SAW-CUT ENDS
FOR END BEARING
SPLICES
$r$
Maximum deviation from "square" to
the end 12 in. of the bar (Bar Size
IV2 deg.fcfsholl
#8-#II) be:spllce
compressien
4 d e g . f ~tension splice
for butt splices1
COPYRIGHT 2002; ACI International (American Concrete Institute) Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
01:39:20 MDT Questions or comments about this message: please call the Document
Fig. 2.1(a) - Standard fabricatitîg tolerances for bar sizes #3 through #Il
Policy Management Group at 1-800-451-1584.
A C 1 337 90 Obb2747 0034374 L M
o o o
B
LAPrK
o o o o @
OZ
SPIRAL
o @
NOTES: TOLERANCE SYMBOLS:
Entireshearingandbendingtolerancesarecustomarilyab- 1. Bar Sizes #3, #4, #5:
sorbed in the extension past thelast bend in a bentbar. = plus or minus % in. when gross bar length < 12 ft
All tolerances single plane and as shown. Tolerances for Types = plus or minus 1 in. when gross bar length P 12 ft
S1 through S6,S11, and TI through T9 apply only the Bar Sizes 2. Plus or minus 1 in.
#3 through # 8 . 3. Plus O, minusin.
*Dimensions on this line are to be within tolerance shown, but 4. Plus or minus % in.
are not to differ from opposite parallel dimension more than in. 5. Plus or minus 1/2 in. for diameter S 30 in.
Angular deviation-Maximum plus or minus 2% deg or plus or Plus or minus 1 in. for diameter > 30 in.
minus % in. perft, but not less than * h in., on all90-deg hookiand 6 . Plus or minus 1.5 percent of o dimension L plus or minus 2 in.
bends. minimum. If application of positive tolerance to Type 9 results
in a chord length equal to or greater thanthe arc or bar length,
the bar may be shipped straight.
c * 4
TYPICAL
ANGULAR
o -F.
c9 7 o DEVIATION
ALL 90.
HOOKS AND
7 7
t y + BENDSSHOWN
ON THIS PAGE
0-
NOTES:
o(10) 4 "--.M TOLERAhCE SYMBOLS:
Maximum deviation from "square" to the end
12 in. of the bar (BurSim #14,#18)
shall be:
1% degfor
splice
compression
Fig. 2.1(b) - Standard fabricating tolerances for bar sizes #14 and #18
-
2.2 Reinforcement placement 2.2.3 Concrete cover measured perpendicular to con-
2.2.1 Tolerances shall not permit a reduction in cover crete surface in direction of tolerance
except as set forth in Section 2.2.2 hereof. When member size is 12 in. or less ...... - % in.
2.2.2 Clear distance to side forms and resulting con- When member size is over 12 in. ......... - % in.
crete surfaces and clear distance to formed and result- Reduction in cover shall not exceed one-third
ing concrete soffits in direction of tolerance specified concrete cover.
When member size is 4 in. or less ........ + % in. Reduction in coverto formed soffitsshall not
........ - % in. exceed ....................................................... Vi in.
When member size is over 4 in. but not over 12 2.2.4 Distance between reinforcement:
...................................................
in. % in. One-quarter specified distance not to exceed
When member size is over 12 in. but not over 2 ......................................................... 1 in.
....................................................
ft Concrete Institute)
COPYRIGHT 2002; ACI International (American % in. Providing that distance between
Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
reinforcement
When member size is over 2 ft. ................
01:39:20 MDT Questions or comments about this message: please call the Document
1 Policy
in. Management Group at shall not be less than the greater of the bar di-
1-800-451-1584.
117-8 AC1 STANDARD
ameter or 1 in. for unbundled bars. 2.2.8 Embedded length of bars and length of bar
For bundled bars, the distance between bun- laps:
dles shall not be less than the greater of 1 in. or
1.4 times the individual bar diameter for 2 bar
#3 through #11 bar sizes ......................
- 1 in,
#14 and #18 bar sizes (embedment only) - 2 in.
bundles, 1.7 times the individual bar diameter 2.2.9 Bearing plate forprestressng tendons, devia-
for 3 bar bundles and 2times the individual bar tion from specified plane.. .......................... 1 degree
diameter for 4 barbundles.
2.2.5 Spacing of nonprestressed reinforcement, de-
viation from specified location 2.3 -Placement of embedded items
In slabs and walls other than stirrups and ties 2.3.1 Clearance to reinforcement the greater of the
..........................................................
3 in. bar diameter or ............................................. 1 in.
Stirrups .....
depth of beam in inched12 X 1 in. 2.3.2 Vertical alignment, lateral alignment, and level
Ties alignment.. ...................................................
1 in.
.......
least width of column in inched12 X 1 in.
However, total number of bars shall not be less
than that specified. 2.4 -
Concrete batching
2.2.6 Placement of prestressing reinforcement or See Table 2.4.
prestressing steel ducts
2.2.6.1 Lateral placement 2.5 -Concrete properties
Member depth (or thickness) 24 in. or less 2.5.1 Slump, where specified as “maximum ” or “‘not
.......................................................
?h.in. to exceed, ” f o r all values.............................. + O in.
Member depth (or thickness)over 24 in. ....1 in. Specified slump 3 in. or less .............. - 1% in.
2.2.6.2 Verticalplacement Specified slump more than 3 in. ......... - 2% in.
Member depth (or thickness) 8 in. or less Slump, when specified as a single value
.......................................................
?4 in. Specified slump 4 in. or less .................... 1 in.
Member depth (or thickness) over 8 in. but not Specified slump more than 4 in.. ........... 1% in.
over 24 in ..........................................
% in. Where range is specified there is no tolerance.
Member depth (or thickness) more than 24 2.5.2 Air content, where no range is specified and
in ....................................................
% in. specified air content by volume is 4 percent or
2.2.1 Longitudinal location of bends and ends of greater................................................ 1% percent
bars: Where range is specified, thereis no tolerance.
At discontinuous ends of members ...........1 in.
At other locations ................................ .2 in.
SECTION 3 -
FOUNDATIONS
3.1 - Vertical alignment
3. l.1 Drilled piers
Table 2.4 3.1.1.1 Category A - For unreinforced shafts ex-
Material Tolerance tending through materials offering no or
Cementitious materials minimal lateral restraint (i.e., water, nor-
30% of scale capacity or greater 1% of cumulative weight
Less than 30% of scale capacity +
- 0% to 4% of the required mally consolidated organic soils, and soils
cumulative weight that might liquefy during an earthquake)
Water
Added water or ice 1% of the total water content
- 12.5 percent of shaft diameter.
which includes added water, 3.1.1.2 Category B - For unreinforced shafts ex-
ice, and water on aggregates
’ Total water content 3% of total water content
tending through materials offering lateral
restraint (soils other than those indicated
Aggregates
a) Cumulative batching in Category A) - not more than 1.5 per-
Over 30% of scale capacity 1% of the required cumulative cent of the shaft length.
weight
30% of scale capacity or less 0.3% of scale capacity or 3% 3.1.1.3 Category C - For reinforced concrete
of the required cumulative shafts - not more than2.0 percent of the
weight, whichever is less
b) Individual material batching 2% of the required weight shaft length.
Admixtures 3% of the reauired amount
-
8.1 Vertical alignment 10.3 - Cross-sectional dimensions
8.1.1 Surfaces 10.3.1 Cross sectionat any point
.................................
Visible surfaces 1Yi in. Increase thickness: greater of 0.05 times thick-
Concealed surfaces.. .......................... .2?4 in. ness, or .........................................
+ % in.
8.1.2 Side walls f o r radial gates and similar water- Decrease thickness: greater of 0.25 times thick-
tight joints .................................................
COPYRIGHT 2002; ACI International (American Concrete Institute)
X 6 Document
01:39:20 ness, about
in. MDT Questions or comments ........................................
provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
or this message: please call the Document
Policy Management Group at 1-800-451-1584.
- % in.
A C 1 337 90 m 0662949 0034380 7 m
117.12 AC1 STANDARD
SECTION 11 -
CAST4N-PLACE BRIDGES highspots shallnot exceed .............................. '/S in.
11.1 -Vertical alignment 12.2.2 Mainline pavements in transverse direction,
11.1.1 Exposed surfaces ............................. % in. the gap below a 10 f t unleveled straightedge restingon
11.1.2 Concealed surfaces.......................... 1?h in. highspots shall not exceed.. ............................ ?4in.
12.2.3 Ramps, sidewalks, and intersections, in any
11.2 - Lateral alignment direction, the gap below a 10 f t unleveled straightedge
Centerline alignment ............................ . 1 in. resting on highspots shall not exceed., .............. % in.
'i
COPYRIGHT 2002; ACI International (American Concrete Institute) Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
01:39:20 MDT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
,
- ~~~ ~ ~ ~~ ~~ ~ ~~ ~ ~~
THE FOLLOWING DISCUSSIONS, WHICH WERE PUBUSHED IN THE NOVEMBER-DECEMBER 1989 AC1 Materials
Journal (PP. 619-628),ARE NOT PART OF THE REPORTAC!117-81,BUTAREPROVIDEDASADDITIONAL
INFORMATION TO THE READER.
117-01
COPYRIGHT 2002; ACI International (American Concrete Institute) Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
01:39:20 MDT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
117-D2 MANUAL OF CONCRETE PRACTICE
committee’s general belief that these tolerances are As the chairman gf AC1 Committee 533, Precast
treated by the strength reduction factor and other Panels, I want to express the opinion of the committee
conservatisms within the design codes. with respect to the AC1 Committee 117 document.
The tolerances proposed in AC1 117, however, are Committee 533 recently had a draft of its guide doc-
much more extensive and liberal than those currently ument reviewed by ACI’s Technical Activities Committee
contained in the design codes. AC1 Committee 349is (TAC). There weremanycriticisms about the format
concerned that the adoption of these tolerances with no and content of our document, and we are considering
consideration by the designer of the potential strength- those comments to improve our guide. One of the con-
reducing effect of the tolerances could result in signifi- sistent comments received was that the AC1 533 guide
cantly reduction in the strength of the structures. This did not reference or follow AC1 117 tolerance specifi-
is especially true if the additive effective of tolerances cations.
on location, size, alignment, etc., are considered simul- The committee specifically took the position that
taneously. AC1 11 7 tolerances would not be referenced because
If AC1 117’s tolerances are accepted, should the en- they were deemed unrepresentative of current practices
gineer consider them all simultaneously in the design within the precast/prestressed concrete industry. The
of the structure? Are the strength reduction factors and tolerances givenin the newAC1117 standard are an
other conservatisms in the design codes sufficient to improvement over those listed in the 1981 standard.
offset the strength-reducing effect ofAC1117’s toler- However, the PC1 Committee on Tolerances prepared
ances? If adequate design margin does exist for the tol- an excellent, realistic document that is more consistent
erances, does the engineer only need to consider the with the precast-prestressed industry’s practice.’ AI-
amount of deviation above the tolerance in assessing though the new AC1 117 standard has a format similar
the as-built condition of structures? to that of the PC1 committee report, Committee 117
Because of these considerations, AC1 Committee 349 has lumped too many precast concrete products, re-
cannot agree at this time with the tolerances in the pro- gardless of their end use, into one set of tolerances.
posed AC1 117-89. We as a committee believe that the ACI 117 ap-
proach is too restrictive and that product tolerances for
precast/prestressed concrete need to be broadened into
industrialized and architectural products. Generally,the
By JAMES M. HENRY AC1 117 tolerances are consistent only with the PC1
Member American Concrete Institute. Project Manager, Stolte Inc.. Oakland, tolerances for architectural panels.
CaliJ
Although TAC will most likely continue to admon-
The following comments apply to Section 4 - Cast- ish AC1 533 for not referencing AC1117 tolerances,
in-Place Concrete for Buildings, and Section 7 - Cast- AC1 533 firmly believes that the PC1 document on tol-
in-Place,VerticallySlipformedStructures.Morespe- erances is a better, more representative compilation on
cifically, the concern is about vertical alignment. tolerances for precast-prestressed concrete.
The tolerances stated in the referenced sections for
vertical alignment are not compatible with American REFERENCE
Institute for Steel Construction (AISC) tolerances for l . PC1 committee on Tolerances. “Tolerances for Precast and
Prestressed Concrete,” Journul. Prestressed Concrete Institute, V. 30,
vertical aligment. The potential for conflict between No. 1, Ja?.-Feb. 1985, pp. 26-112.
concrete contractors and structural steel contractors
would be very high if these toleranceswere specified for
the concrete work on a composite steel/concrete high- By JOHN E. SADLER
rise building. Member American Concrere Institute. Chairman ACI Committee 313,
Consulting Engineer. Columbus, Ohio
My personal experience includes 28 composite build-
ingsin the past 10 years.Recentexamplesarethe AC1 Committee 313, Concrete Bins and Silos, has re-
AT & T Building in Kansas City and the IBM Building viewed the proposed “Standard Specifications for Tol-
in Atlanta. These buildings contain major structural erances for Concrete Construction and Materials (AC1
concrete core elements. 117)” and finds it to be generally satisfactory for Com-
The development of steel-grid stablized slipform mittee 313’s purposes.
systems in the mid-1970s made construction of con- At the Atlanta Convention, Committee 313 reviewed
crete cores and exterior shearwalls to AISC tolerances tolerance items in AC1 117 and in AC1 3 13 and ap-
easily feasible. With fixed/tied forms it is merely a proved the removal of all tolerances from the AC1 313
matter of accurate alignment and adequate bracing. A document if AC1117will include the special require-
warning comment in the specification checklist orin a ments of silos in the document. Those special require-
footnote to the standard is suggested. ments (as follows) are tabulated in Section 13 in a
Except for the point just made, the specification is a format similar to that chosen by AC1 117 for the pro-
fine piece of work. posed standard.
COPYRIGHT 2002; ACI International (American Concrete Institute) Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
01:39:20 MDT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
~- ~ ~
TOLERANCES 117-D3
proposed addition to ACII I 7 to cover ACI 313 ances in the AC1 530 document which were submitted
requirements to Committee 117 last November represent the com-
SECTION 13-CONCRETE SILOS AND STACKING mittee's balloted. approved values complying with the
TUBES FOR STORING GRANULAR MATERIALS standards for both ASCE and ACI.
13.1"Slipformed or jumpformed structures Our committee was unanimous in the opinion that
13.1.1-Translation and rotation from a fiedpoint AC1 could not unilaterally alter the decision of the
at the baseof the structure combined committee. We strongly urge you accept the
For heights 100 ft or less ........................... 3 in. AC1 530 standards as part of your document.
For heights greater than 100 ft, Xo0 times the height
but not morethan .................................... 4 in.
13.1.2-Lateral alignment of walls By R. W. SNOOK
Each 10 ft of diameter or distance between Membcr American Concrete Insfifure. Chairman A C I Committee 307,
Presidenf. Chimney Consultanfs. h e . . Allison Park. Pa.
walls ................................................... '/i in.
But not more than ................................... 3 in. The proposed specification neither addresses nor ex-
13.1.3-Cros-sectional dimensions empts chimneys or other large hollow concrete struc-
+ 1 in.
Walls ................................................. tures (i.e., silos, building cores, hyperbolic cooling
................................................ H in. towers, etc.). As a consequence, chimneys would most
13.1.3-Openings and embedded plates or anchors likely be subject to theprovisions of Section 8 Mass -
Vertical locationof centerline ..................... 3 in. Concrete Structures Other Than Buildings. I believe
Horizontal location of centerline .................1 in. this section does not consider the unique construction
techniques employed with tall, tapered thin-walled
structures.
13.2-Precast circular stave silo erection tolerances As Chairman of AC1 Committee 307, I suggest that
13.2.1-Translation rotation or bulging from a f i e d chimneys be exempt from the provisions of AC1 117
point at the baseof the structure since construction tolerances for chimneys are ad-
For heights 100 ft orless ........................... 3 in. dressed in Section 3.8 of the new AC1 307 standard,
For heights greater than 100 ft, Xo0 times the height which was adopted in November 1988.
but not morethan .................................... 4 in. Alternatively, I suggest that AC1 117 be revised to
13.2.2-Lateral alignment or spiral' of vertical stave include a Section 13 - Chimneys, as follows. in which
joints the construction tolerancesnow included in Section 3.8
Each 10 ft height ........................................ 1 in. of 307 would be restated.
13.3.3"Relative alignment or bulging
In a 10 ft height, not more than ..................1 in.
13.2.4-Lateral alignment of walls CONSTRUCTION TOLERANCES
For each 10 ft of diameter ......................... 1 in. Section 13-Chimneys
But not more than ................................... 3 in. 13.1 The chimney shell shall be constructed within the
13.2.5"Hoop count and spacing tolerance limits set forth herein.
Number of hoops in a specified wall height .......O 13.1.1 Vertical alignment of centerpoint - The cen-
Spacing of hoops ..................................... 1 in. terpoint of the shell shall not vary from its vertical axis
by more than0.001 of the height of the shell at the time
of measurement, or 1 in., whichever is greater. Lo-
By W. THOMAS SCOTT cally, the centerpoint of the shell shall not be changed
The Ceco Corporafion. Sanfa Ana, CaliJ by more than 1 in. per 10 ft.
13.1.2 Diameter - The measured outside shell di-
The text does not indicate that the straightedge is to ameter at any section shall not vary from the specified
be 10 ft long as referenced in the discussion. Is this an diameter by more than 1 in. plus 0.01 of the specified
oversight or are you leaving the length of the straight- or theoretical diameter.
edge open to interpretation of the specifier? Varying 13.1.3 Wall thickness - The measured wall thick-
the length of the straightedge could produce very dif- ness shall not vary from the specified wall thickness by
ferent results. more than - % inch, + Vi in. for walls 10 in. thick or
less, or by more than - Vi in. + 1 in. for walls greater
By JOHN M. SHEEHAN than 10 in. thick. A single wall thickness measurement
Member American Concrefe Insfifure, Senior Vice Presidenf. Damon G.
is defined as the average of at least four measurements
Douglas Co., Cranford. N.J. taken over a 60-deg arc.
13.2 Openingsandembedments - Tolerances on the
Committee 530 regrets that it cannot accept the pro- size and location of openings and embedments in the
posed tolerances for masonry construction. The toler- shell cannot be uniformly established due to the vary-
ing degrees of accuracy required depending on the na-
*Spiral means the distortion that resultsif the staves are ti!tedslightly.IO that ture of their use. Appropriate tolerances for opening
eventhoughtheirouterfacesare vertical. theIr edgcs,are,lnclined. Thecom-
bined effect of such misplacement is to eau? vertical Joint llnes to 5 long-pitch
and embedment sizes and locations shall be established
spirals rather than straight lines. The resultmg assembly appearstwisted. for each chimney.
COPYRIGHT 2002; ACI International (American Concrete Institute) Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
01:39:20 MDT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
1 17-04 MANUAL OF CONCRETE PRACTICE
COPYRIGHT 2002; ACI International (American Concrete Institute) Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
01:39:20 MDT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
TOLERANCES 117-05
cifier to include specialized tolerances. In response to of standard manufactured products. Committee 117
the comments from Mr. Duffy and other AC1 commit- will undertake as new business, with the help of Com-
tees, the following clarifying paragraph has been added mittee 533 and PCI, the distinguishment of architec-
defining the applicable scope of the Specification: “The tural and industrial precast elements. In the interim, the
tolerances in this Specification do not apply to special following clarification has been added to the optional
Structures or procedures not citedin the document, specification checklist: “5.3 - Planar Elements: In-
such as nuclear reactor vessels and containment, circu- dustrial precast products may not conform to the
lar prestressed concrete tank structures, and shot- planar tolerances. Manufacturers should be consulted
Crete.” for appropriate tolerances for their products.”
With respect to Mr. Dobrowolski’s concerns, Com- In accordance with Mr. Sheehan’s comments, the
mittee 117will undertake as new business the concept specified tolerances for masonry have been modified to
of including a separate section pertaining to architec- avoid any conflict with Committee 530. The”finish on
tural surfaces and looks forward to working with the surface of the concrete footingsto receive masonry
Committee 303 in this undertaking. In the interim, the has not been modified. Construction practice forform-
Optional Specification. Checklist emourages specifiers ing continuous concrete footings below masonry in-
desiring specialized concrete construction to use spe- volveseitherplacingthe concrete against excavated
cialized tolerances. As indicated in Commentary Sec- earth or side forms. When placed against earth, flag
tion 4, Specification Paragraph 4.5 determines the nails set at intervals along the length of the footing are
smoothness of surfaces. The slope rate tolerance of )/S commonly used for grade control. When placed against
in. in 10 ft for formed surfaces is more rigorous than a forms, the top of the form or a chalk line snapped on
plywood deflection criteria of 1/400. the form faceis used for grade control. The strikeoff is
The tolerances for slipform structures were estab- generally performed in conjunction with vibration and
lished from measurements taken between 1978 and1982 minor finish is performed by laborers using wood dar-
on slipformed high-rise concrete buildings. The ele- bies or short two-by-fours on edge. This striking and
ment slipforms were office buildings’ central cores and finishing operation occurs in, around, and through
multiple shearwalls for condominiums. The committee reinforcing dowels. These methods are economical.The
welcomes any data Mr. Henry could furnish regarding physical impediment of dowels makes the achievement
tolerances achieved on his referenced projects, so that of an accurate and high-quality finish on thetop of the
it might undertake as new business the review of slip- footing impractical. Several years ago, Committee 117
form tolerancesagainst current technologyandany measured a limited number of footingsthat satisfactor-
need for more rigorous tolerances due to a particular ily received masonry to determine the acceptability of
building structural system. It is noted that the AISC levelalignmentof +I” fi in.Thisis in agreement
frame tolerances are 1500, with maximum limits es- withAC1530.Localized slopechanges or flatness of
tablished depending on the number of stories. The the footing top was not measured using a leveled 10-ft
specified translation and rotation tolerances for verti- straightedge. Extensive measurements of slabs per-
cally slipformed building elements are more rigorous formed for other purposes revealed that care and mul-
than AISC’s general envelope tolerance, but maximum tipje finishing operations are necessary if a slope varia-
allowable deviations exceed some of AISC’s require- tion of Vi in. in10 ft from levelis to be maintained.
ments. Applying this requirement to footin’gs, as suggested by
The tolerances for precast panels are covered by Committee 530, seems unrealistic and unnecessary.
Planar elements in Specification Section 5.3. The toler- Unrealistic tolerances are either ignored because they
ance is. intended to be of general application and nor- are unneeded or bécome the basis for an unnecessary
mal usage for both manufactured and job-cast planar discute between contracting parties. It is suggested that
elements. The problem outlined by Mr. Meinhardt Committee 117 and 530 measure the slope of the vari-
arises in determining whether an itemis industrial or ation in the surface of footings that are satisfactorily
architectural, or an industrial product used for an ar- receiving masonry and are constructed with current
chitecturalpurpose. In theOptional Specification techniques to determine if there is a need for a slope
Checklist, specifiers are encouraged to use specialized tolerancewithin the + / - Y2 in. elevation tolerance
tolerances when necessary. For guidance in applicable envelope. If it is required, the data collected should re-
tolerances, the commentary to the specification refers veal the appropriate magnitude.
the specifier to “Tolerances for Precast and Prc- Mr. Campbell appropriately calls Committee 117’s
stressed Concrete” published in the January-February attention to the Committee 358 report regarding con-
1985 PC1 Journal, pp. 26-1 12, and the Optional Speci- crete-guidewayconstruction.Anerectiontolerance of
fication Checklist refers the specifier to the licensor of X 6 in. andsurfaceirregularitytolerance of Ya in. has
patented or copyrighted structural systems for toler- been added to the specification for guideway and sup-
ances. port steering surfaces.
Committee 117’s specification was forwarded to PC1 Mr. Sadler indicates Committee 313has determined
for review, and no changes were requested by the PC1 that concrete bins and silos are specialized structures
reviewers. Specified tolerances closely coordinate with with toleranceneedsdifferentfromslipformedbuild-
applicable PC1 recommended tolerances for the array ing elements. However, Committee 3 13 has in process
COPYRIGHT 2002; ACI International (American Concrete Institute) Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
01:39:20 MDT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.
117-D6 MANUAL OF C O N C R M PRACTICE
a complete revision of their standard, and changes are early revision of the specification.
proposed in tolerances. So, we have added bins and Committee 543 felt that there was a conflict between
silos to the exceptions in the Foreword and Optional the location tolerance of the internal void and the toi-
Specification Checklist, and will consider this as new erance for wall thickness for prefabricated concrete Pil-
business at the appropriate time. ing. There is not a conflict because the exterior size O f
Similarly, Mr. Snook points out the specialized needs the pile can vary. Committee 117 will undertake in co-
of structures addressed by Committee 307. Accord- ordination with Committee 543 their suggestion for a
ingly, a separate section has been added to the specifi- minor revision to the wall thickness tolerance as new
cation incorporating their tolerances. Their section on business.
“Openings and Embedments” is not a tolerance. The The TAC Specification Committee commented on
specification preference and checklist cover the need for the inappropriateness of referencing AC1 3 18 and other
the specifier to designate specialized and unique toler- codes in a specification. Accordingly, these references
ances. To avoid confusion, Committee 307’s comments have been deleted from the section on Project Docu-
regarding openings and embedments have been in- ment references inthe Commentary.
cluded in the commentary.
Mr. Ytterberg is a member of Committee 117 and has
participated in discussions of tolerancing floor finishes
over several years. His objections to the use of the
ASTM E 1155 method of measuring floor finishes have
not been persuasive. Articles regardingthe evolution of
the F-number system and extensive data from field
measurements havebeen published (“Floor Toler-
ances,” ConcreteInternational, V. 10, No. 6, June
1988, pp. 51-57; “Measuring the Quality of Floor Fin-
ishes,” Concrete International, V. 11, No. 6, June
1989,pp.41-49). Committee 117 purposefully left the
traditional 10-ft straightedge tolerancing method in the
specification to provide the specifier an option as to
method and to ease any transition to statistical sam-
pling techniques. It is noted that a number of Fortune
500 companies and specifying entities have incorpo-
rated ASTM E 1155 over the past several years. Mr.
Ytterberg’s company has been instrumental in the de-
velopment of equipment to measure floor finishes and
is currently working within ASTM to develop sup-
porting test methods. Committee 117is committed to
undertake as urgent new business the slab-finish toler-
ance system advocated by Mr. Ytterberg and any addi-
tional techniques resulting from the rapidly evolving
technology in this area.
In addition to discussion received by the editor,
Committee 117received directly from other AC1 tech-
nical committees various comments regarding coordi-
nation.
Committee 346 pointed out that cast-in-place con-
crete pipe requires special tolerances. Accordingly, the
tolerances appearing in Chapter 5 ofAC1346-81have
been incorporated in a new section in Committee 117’s
specification for cast-in-place nonreinforced pipe.
Committee 423, Prestressed Concrete, forwarded its
current tolerances for the location of prestressing rein;
forcement or prestressing steel ducts. Their recom-
mended tolerances have been included in the Specifica-
tion. In addition, information to the specifier has been
added in the Commentary regarding how these toler-
ances may affect the designation of cover.
Committee 355 hasforwarded as “work in Pro-
gress” tolerances for anchorages installed i n previously
castconcrete. Committee 117 will undertake as new
business these applicable tolerances for inclusion in an
COPYRIGHT 2002; ACI International (American Concrete Institute) Document provided by IHS Licensee=Bechtel Corp/9999056100, User=, 07/25/2002
01:39:20 MDT Questions or comments about this message: please call the Document
Policy Management Group at 1-800-451-1584.