You are on page 1of 5

Manandes SCCI calle 10 #1004 y Av.

10 Manta- Ecuador
Formación Técnica Div. Tele/fax 624078 – 626652 email: manandes@ecua.net.ec

AC CURRENT
TRANSFORME
RS

General:
To reduce danger to personnel, and to reduce the heat generated by high AC current,
toroidal AC Current Transformers (also called transducers) are inexpensive, common
solutions. Generally speaking, these devices, also known as "donuts", reduce the line
current from its rating to 5 amps AC. Thus the receiving instrument never sees anything
more than a maximum of 5 amps (amperage is the killer; voltage is of lesser danger).
When using CT's, one must make sure the load or burden that is connected to the
secondary is not above the limits of the CT. The load limit is specified by its VA ratings
(usually running from 2 to 10 VA). The larger the VA, the more resistance can be tolerated
by the CT. When in doubt, utilize a CT and a CT transmitter that converts AC amperage
into a 4-20 mA DC signal for long lead lengths (and specify compatible receiving
instruments scaled, however, in AC amps).
To calculate load:
1. Resistance of wire (typically, the CT comes with 24" of 16 AWG wire; 16 AWG
has a resistance of .0041 ohms per foot: 50 feet out and 50 feet back would 100 x .
0041 = .41 ohms
2. Resistance of Analog or Digital Indicator/Recorder/Datalogger, typically .1 ohm
3. VA=I2R (for example, 5 amps2 x 100 feet of 16 AWG= .41 + .1 for a meter= 10.5
VA
Therefore it is obvious that any distances over a few feet from the CT should mandate a
transmitter.
Installation:
The donut transformer can be ordered with mounting feet or flat bottom configuration for
surface mounting, or simply hung through the primary conductor with one or more primary
turns (see Ratio Modification below).
Care must be taken to ensure the secondary leads are connected at all times when current
is passing through the primary conductor.
Multipoint Switches:
In 3 phase systems, the amp meter (0-5 ACA receiving instrument) can be switched
externally from phase to phase to monitor the various currents. CAUTION: NEVER
BREAK THE SECONDARY CIRCUIT OF A CURRENT TRANSFORMER AS HUMAN LIFE
AS WELL AS CONNECTED EQUIPMENT CAN BE ENDANGERED BY INDUCED HIGH
396680325.doc Página 1 de 5
Manandes SCCI calle 10 #1004 y Av. 10 Manta- Ecuador
Formación Técnica Div. Tele/fax 624078 – 626652 email: manandes@ecua.net.ec

VOLTAGES. All Current Transformer Secondaries must be short-circuited when not in use,
and the S ampere terminal of the meter-receiver connection must connect to a secondary
"BEFORE" the short is removed from that secondary. Switches must "MAKE BEFORE
BREAK", and must keep all unused secondaries shorted. (Voltage switching is just the
opposite--all voltage switches must "break before make" and all unused potential
transformer secondaries should be kept open)
Common Characteristics of CT's
1. Frequency affects a C/T only because the lines of flux generated by the primary
current begin to appear as DC as the frequency gets very low; a C/T needs the AC
CYCLE changes to induce the secondary current. With anyone's toroidal C/T, you
will experience a drop in accuracy as the frequency goes down from 60 Hz. One
can manufacture a C/T with an exotic metal core that is not quite as affected as the
silicon grain oriented steel most commonly used, but the improvement would be
questionable and at high cost.
2. Below 60 Hz, the accuracy will be affected by the drop in frequency and voltage:
with Instrument Transformers CT's having the maximum acknowledged accuracy of
0.3% ANSI Rating, you will experience a drop in accuracy at 9 Hz to 5%; at 6 Hz it
might be 7.5% of full scale. A Split Core unit might have double the inaccuracy, or
more (for example, a 1% Split Core being used at 9 Hz will experience an accuracy
rating of 33% - {.3%/5% is as 1%/X or X = 5/.3 = 16.7 x 2}. Remember, it is difficult
to come up with test equipment with enough power to test full scale at unusual
frequencies. The lesson here is to take the most accurate C/T you can if you are
running in lower frequencies than 60 Hz.
3. Exercising the C/T beyond its current rating for short periods is not usually a
problem; each CIT has a Thermal Rating Factor (if not published, then you must
assume it is 1.0). This is a "continuous thermal current rating factor". The
Instrument Transformer model 5A (page 5, Section 2) has a factor of 1.33 at 300C.
This means this particular C/T can be operated at 133% of its primary rated current
CONTINUOUSLY without overheating (a 200:5 can thus be operated at 200 x 1.33
or 266 primary amps continuously). Other CIT's have thermal rating factors of 1.5
and 2.0 etc. On a momentary basis, any CIT will usually operate at 64 times its
primary current rating for 1 second; 150 times its current rating for 1 cycle.
4. Above 60 Hz, a CIT becomes conversely more accurate up to about 4000 Hz.
Above this, you must examine the wave shape carefully because it causes the core
to saturate. 400 Hz is the published limit with some manufacturers; there is usually
no problem with accuracy or heat or saturation at this frequency.
5. 4-20 mA DC Transmitters
a. For all such transmitters, an independent, stable prime power is a requisite
for published operational accuracy and characteristics.
b. The internal transmitter of the device usually will not operate below 85
volts (43 Hz)
c. Frequency response with a constant 120V 60 Hz Prime Power starts to fall
off at 20 Hz; by 9 Hz it will be off by 5% Full Scale. At 6 Hz it will be off by
7.5% etc.
6. P/T's and Frequency: the ratio of voltage to frequency is important to a P/T (but
not to a C/T). It must remain constant, or the P/T will overheat. Lesson: do not
power a P/T from a variable frequency drive unless this ratio can be made constant.

396680325.doc Página 2 de 5
Manandes SCCI calle 10 #1004 y Av. 10 Manta- Ecuador
Formación Técnica Div. Tele/fax 624078 – 626652 email: manandes@ecua.net.ec

AC CURRENT TRANSFORMERS
HOW TO OBTAIN SPECIAL RATIOS FROM STANDARD
RATINGS
Window type current tranformers are rated on the basis of a single primary turn. However, other ratios are
obtainable by the use of multiple turns. Most window type current tranformers can have its nominal ratio
adjusted to a non-standard ratio by the use of primary and secondary turns.

396680325.doc Página 3 de 5
Manandes SCCI calle 10 #1004 y Av. 10 Manta- Ecuador
Formación Técnica Div. Tele/fax 624078 – 626652 email: manandes@ecua.net.ec

Primary Turn Ratio Secondary Turn


Modification Ratio Modification
Formula: Ka = Kn x Nn / Na Formula : Ip/Is = Ns/Np
Where: Where:
Ka = Actual Transformer Ratio Ip = Primary Current
Kn = Nameplate Tranformer Ratio Is = Secondary Current
Na = Actual Number of Primary Turns Np = Number of Primary Turns
Nn = Nameplate Number of Primary Turns Ns = Number of Secondary Turns
The ratio of the current transformer can be Example: A 300:5 Current Tranformer.
modified by adding more primary turns to the 300 p / 5s = 60s / 1p
tranformer. By adding primary turns, the current
required to maintain five amps on the secondary (In practicality one turn is dropped form
is reduced. the secondary as a ratio correction
Example: A 100:5 current tranformer designed factor.)
for one primary turn. The ratio of the current tranformer can be
modified by altering the number of
secondary turns by forward or
backwinding the secondary lead through
the window of the current tranformer.
By adding secondary turns, the same
primary current will result in a decrease in
secondary output. By subtracting
secondary turns, the same primary
current will result in greater secondary
output.
Again using the 300:5 example adding
1. Primary Turn five secondary turns will require 325 amps
NAMEPLATE RATIO -- on the primary to maintain the 5 amp
100:5 secondary output or:
ACTUAL RATIO -- 325 p / 5s = 65s / 1p
100:5 Deducting 5 secondary turns will only
2. Primary Turns require 275 amps on the primary to
NAMEPLATE RATIO -- maintain the 5 amp secondary output or:
100:5 275p / 5s = 55s / 1p
ACTUAL RATIO -- 50:5 The above ratio modifications are
3. Primary Turns achieved in the following manner:
NAMEPLATE RATIO --
100:5
ACTUAL RATIO -- 25:5

TECHNICAL DATA
CURRENT TRANSFORMERS RATIO MODIFICATION
Relatively large changes in ratio may be achieved through the use of primary turns. For example:

396680325.doc Página 4 de 5
Manandes SCCI calle 10 #1004 y Av. 10 Manta- Ecuador
Formación Técnica Div. Tele/fax 624078 – 626652 email: manandes@ecua.net.ec

CT RATIO NUMBER OF PRIMARY TURNS MODIFIED RATIO


100:5A 2 50:5A
200:5A 2 100:5A
300:5A 2 150:5A
100:5A 3 33.3:5A
200:5A 3 66.6:5A
300:5A 3 100:5A
100:5A 4 25:5A
200:5A 4 50:5A
300:5A 4 75:5A
A primary turn is the number of times the primary conductor passes through the CT's
window. The main advantage of this ratio modification is you maintain the accuracy and
burden capabilities of the higher ratio. The higher the primary rating the better the
accuracy and burden rating.
You can make smaller ratio modification adjustments by using additive or subtractive secondary turns. For
example, if you have a CT with a ratio of 100:5A. By adding one additive secondary turn the ratio
modification is 105:5A, by adding on subtractive secondary turn the ratio modification is 95:5A. Subtractive
secondary turns are achieved by placing the "X1" lead through the window from the H1 side and out the H2
side. Additive secondary turns are achieved by placing the "X1" lead through the window from the H2 and out
the H1 side. So, when there is only one primary turn each secondary turn modifies the primary rating by 5
amperes. If there is more than one primary turn each secondary turn value is changed (i.e. 5A divided by 2
primary turns = 2.5A). The following table illustrates the effects of different combinations of primary and
secondary turns:
CT RATIO 100:5A
PRIMARY TURNS SECONDARY TURNS RATIO ADJUSTMENT
1 -0- 100:5A
1 1+ 105:5A
1 1- 95:5A
2 -0- 50:5A
2 1+ 52.5:5A
2 2- 45.0:5A
3 -0- 33.3:5A
3 1+ 34.97:5A
3 1- 31.63:5A

396680325.doc Página 5 de 5

You might also like