You are on page 1of 1

1.

DRAIN DOWN VALVES INSTALLED AT ALL LOW POINTS


WITHIN THE WATER SYSTEM.

2. AIR VENTS INSTALLED AT ALL HIGH POINTS WITHIN THE


WATER SYSTEM.

DRV
LEGEND
SHOWER
IV - ISOLATING VALVE
THERMOSTATIC TP - TEST POINT
IV SCV MIXING VALVE (TMV)
RISER R24 RISER R30 RISER R40 NRV - NON RETURN VALVE
LEVEL8-PLANTROOM LEVEL8-PLANTROOM SET AT A MAXIMUM LSV - LOCK SHIELD VALVE
TMV TEMPERATURE OF 43°
22Ø IND BCWS FC - FLEXABLE CONNECTION
22Ø IND HWS F 15Ø HRW 15Ø HRW
IV SCV CS - COMMISSIONING SET
15Ø IND HWS R 22Ø BCWS 22Ø BCWS
22Ø HCW 15Ø HWS R 15Ø HWS R
22Ø BCWS 22Ø BCWS
WHB ALL ISOLATION STR - STRAINER
15Ø HWS R 15Ø HWS R
28Ø BCWS 22Ø HWS F 22Ø HWS F VALVES TO BE OF DC - DRAIN COCK
22Ø HWS F 22Ø HWS F

HWS-R
HWS-F
15Ø HWS R THE LEVER AAV - AUTOMATIC AIR VENT

BCWS
28Ø HWS F
OPERATED TYPE. DRV - DOUBLE REGULATING VALVE
SV - SAFETY VALVE
IV IV NC - NORMALLY CLOSED
NO - NORMALLY OPEN
MCW - MAINS COLD WATER
THERMOSTATIC MIXING VALVE PCIV - PRESSURE INDEPENDENT CONTROL VALVE
INSTALLED ON DISABLED WHB ONLY DCV - DOUBLE CHECK VALVE
INLINE WITH ICL TPS AND SET AT A PS - PRESSURE SWITCH
MAXIMUM TEMPERATURE OF 45°
P PRESSURE GAUGE
DETAIL A
TYPICAL DOMESTIC WATER CONNECTIONS TO WHB AND T TEMPERATURE GAUGE
SINK SINK SHR WHB WHB WHB WHB
SHOWER
WHB
VALVE
22Ø HCW
WC WHB WHB SHR WC
COMMISIONING SET

PRESSURE REDUCING VALVES ON COLD CONTROL VALVE

15Ø HWS R
22Ø HWS F
22Ø BCWS
WATER MAIN BRANCH LINE.
OUTLET PRESSURE SET AT 2 BAR. PHASE 3 BCWS/HCW SERVICE
WC WC WC URINAL URINAL URINAL URINAL
PHASE 3HWS SERVICE
703 KITCHENETTE 701 CLEANER'S STORE 702A SHOWER 702 MALE WC 753 DISABLED WC 754 WC/SHOWER PRESSURE REDUCING VALVES ON HOT
772 MECHATRONICS LAB EXISTING SERVICE
LEVEL 7 LEVEL 7 WATER MAIN BRANCH LINE.
15Ø HCW OUTLET PRESSURE SET AT 2 BAR. TYPICAL OUTLET
22Ø HCW
28Ø BCWS
15Ø HCW 15Ø HCW
15Ø HWS R ALL ISOLATION VALVES ARE OF THE
22Ø BCWS 22Ø BCWS
28Ø HWS F
15Ø HWS R 15Ø HWS R
LEVER OPERATED TYPE.

IND HWS-R
IND HWS-F
IND BCWS
28Ø IND BCWS 22Ø HWS F 22Ø HWS F
L TO R: 28Ø IND HWS F LAB
15Ø BCWS 15Ø IND HWS R SINK
15Ø HWS F OUTLETS
15Ø BCWS L TO R: 15Ø HWS R
28Ø BCWS 22Ø HCW
15Ø HWS F DRV SCV
15Ø HWS R
15Ø HWS R 28Ø HWS F

IV IV IV

22Ø HCW
DETAIL B
SINK SHR WHB WHB WHB WHB TYPICAL INDUSTRIAL WATER CONNECTION TO
SINK UNITS AND LAB EQUIPMENT
WC WHB SINK WC WHB WHB SHR WC

WC WC WC URINAL URINAL URINAL URINAL ALL ISOLATION VALVES TO BE OF THE


LEVER OPERATED TYPE.
603 KITCHENETTE 601 DISABLED WC 602A SHOWER 602 MALE WC 655 CLEANER'S STORE 653 FEMALE DISABLED WC 654 WC/SHOWER
LEVEL 6 22Ø IND BCWS
LEVEL 6 HARVESTED CWDS
22Ø IND HWS F
15Ø IND HWS R 15Ø HCW PRV (SET AT 2 BAR)
15Ø HCW 22Ø BCWS 15Ø HWS R
22Ø HCW 15Ø HCW 22Ø HWS F
IV
15Ø BCWS 28Ø BCWS 22Ø BCWS 22Ø BCWS STR
15Ø HWS R 15Ø HWS R EXISTING DOM. HWS R EXISTING DOM. HWS R
15Ø HWS F 28Ø HWS F EXISTING DOM. HWS F EXISTING DOM. HWS F CONTINUES TO SERVE WC / URINAL
22Ø BCWS EXISTING IND. HWS R 15Ø HWS R EXISTING IND. HWS R EXISTING IND. HWS R NORTH BLOCK OUTLETS
(INSTALLED AT PHASE 2)
15Ø HWS R EXISTING IND. HWS F 22Ø HWS F EXISTING IND. HWS F EXISTING IND. HWS F DETAIL C
22Ø HWS F
TYPICAL HARVESTED WATER CONNECTIONS TO
WC's AND URINALS

15Ø HCW
T-B
SHR WHB WHB WHB WHB SINK BCWS
HWS-F
SINK WHB WC WHB WC WHB WHB SHR WC WHB WC SINK SINK HWS-R
521 FABRICATION W/SHOP PRV
FUME CUPBOARD T TO B:
22Ø BCWS IV
15Ø HWS F
15Ø HWS R
DC

PRV TBV
FILL WC WC WC URINAL URINAL URINAL URINAL DC
POINT
(TANK) FLIGHT ARENA 501 DISABLED WC 502A SHOWER 502 MALE WC 503 KITCHENETTE 551 FEMALE DISABLED WC 552 WC/SHOWER 573 STAFF WC 573 STAFF WC IV
LEVEL 5 LEVEL 5 DC
15Ø HCW 15Ø HCW 22Ø HCW DETAIL D
15Ø BCWS 22Ø HCW
TYPICAL RISER BRANCH DETAIL
22Ø BCWS 22Ø BCWS
15Ø HCW
15Ø HWS R 15Ø HWS R
22Ø BCWS
22Ø HWS F 22Ø HWS F
15Ø HWS R
22Ø BCWS
22Ø HWS F
15Ø HWS R
22Ø HWS F

413 OPEN PLAN


OFFICE

WHB WHB WHB WHB WHB

SINK
SINK SINK WC WHB WHB SHR WC

WC WC URINAL URINAL WC WC WC
DATA CENTRE 451 CLEANERS' 401 CLEANER'S
COFFEE MACHINE EXTERNAL PLANT STORE STORE 402 DISABLED WC 404 MALE WC 403 FEMALE WC 452 WC/SHOWER

LEVEL 4 LEVEL 4
15Ø MCWS
RISER R23
15Ø HCW 22Ø HCW
22Ø BCWS
15Ø HWS R
22Ø HWS F 15Ø HCW 15Ø HCW
22Ø BCWS 22Ø BCWS 22Ø BCWS
54Ø IND HWS F 15Ø HWS R 15Ø HWS R 15Ø HWS R
35Ø IND HWS R 22Ø HWS F 22Ø HWS F 22Ø HWS F
22Ø HWS R
35Ø HWS F

WHB WHB WHB


SINK WATER
DRINKING SINK BOILER
WC WHB WC WHB WC WHB WHB SHR WC
POINT WATER
COOLER

WC WC WC
RD AS INSTALLED 11/05/2017
3C02 CORRIDOR 350 OPEN PLAN OFFICE 301 DISABLED WC 302 DISABLED WC 303 FEMALE WC 351 FEMALE DISABLED WC 352 WC/SHOWER 357 KITCHENETTE
LEVEL 3 LEVEL 3 Revision Description Date
22Ø HCW 22Ø HCW
22Ø BCWS 22Ø BCWS
22Ø BCWS
15Ø HWS R 15Ø HWS R 15Ø HCW 15Ø HCW
15Ø HWS R
22Ø HWS F 22Ø HWS F 22Ø BCWS 22Ø BCWS
15Ø HWS F
15Ø HWS R 15Ø HWS R
22Ø IBCWS
22Ø HWS F 22Ø HWS F
15Ø IHWS R
22Ø IND HWS F
22Ø IHWS F
15Ø IND HWS R

LAB
SINK WHB WHB WHB WHB WHB WHB WHB WHB SINK WHB WHB WHB WHB WC
OUTLET
Project
22Ø BCWS
AMP - PHASE 3 MENG1101C

Title
MECHANICAL AND ENGINEERING BUILDING
WC WC WC WC WC WC URINAL URINAL URINAL URINAL URINAL URINAL WC WC WC DOMESTIC WATER SERVICES SCHEMATIC
204B AERONAUTICS WIND TUNNEL 2 204C WIND TUNNEL CONTROL LOBBY 251 FEMALE WC SHEET 2 OF 2
253 CLEANERS STORE 201 MALE WC 252 DISABLED WC
LEVEL 2 LEVEL 2
RISER R24 RISER R30 RISER R40 Drawn by Checked File

AH TDJ SCHP53RD02
Drawing Number Revision Scale
NTS@A0
MENG/SCH/P53/RD02 RD Date
14.06.2016