Test And Drain Valve

A61
FEMALE x FEMALE CERTIFICATIONS

Standard equipment:
Female NPT inlet and outlet, forged
brass body, brass finish ball
b with teflon seats. LISTED 36Y7

FM approved at 300 psi *


a UL listed •

c
a/b (Orifice - K factor) c (plug) PORT A B C D H

1”(3/8”-2.8)* 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”

C 1”(7/16”- 4.2)* 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”

1” (1/2”-5.6)• * 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”


H
B
1”(17/32”- 8)• * 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”
D
PORT

1-1/4” (3/8”-2.8)* 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”

1-1/4” (7/16”-4.2)* 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”


A 1-1/4” (1/2”-5.6)• * 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”

1”-1/4”(17/32”- 8)• * 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”

SPECIFY THREAD 1-1/4” (5/8”-11.2)* 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”

1-1/4” (3/4”-14)* 1/4” 1-1/16” 5-1/32” 2-43/64” 5-11/32” 4-27/64” 1-57/64”

A61
GROOVE X GROOVE CERTIFICATIONS

Standard equipment:
GROOVE inlet and outlet, forged
b brass body, brass finish ball with
teflon seats.
FM approved at 300 psi
a

a/b (Orifice - K factor) c (plug) PORT A B C D H

1-1/4” (3/8” - 2.8) 1/4” 1-1/16” 6-13/32” 2-43/64” 5-11/32” 4-27/64” 1-1/4”groove
C 1-1/4” (7/16” - 4.2) 1/4” 1-1/16” 6-13/32” 2-43/64” 5-11/32” 4-27/64” 1-1/4”groove

H 1-1/4” (1/2” - 5.6) 1/4” 1-1/16” 6-13/32” 2-43/64” 5-11/32” 4-27/64” 1-1/4”groove
B
D 1-1/4” (17/32” - 8) 1/4” 1-1/16” 6-13/32” 2-43/64” 5-11/32” 4-27/64” 1-1/4”groove
PORT

1-1/4” (5/8” - 11.2) 1/4” 1-1/16” 6-13/32” 2-43/64” 5-11/32” 4-27/64” 1-1/4”groove

1-1/4” (3/4” - 14) 1/4” 1-1/16” 6-13/32” 2-43/64” 5-11/32” 4-27/64” 1-1/4”groove
A

SPECIFY THREAD

42
(Technical communication n° A-
039)

A61 Test and Drain


valve
Standard equipment

Female NPT inlet and outlet, forged brass body,


chrome plated ball with teflon seats.

Products

Test and drain valve


Female x Female

1" (orifice 1/2")


1 1/4"(orifice 1/2")
1" (orifice 17/32")
1 1/4" (orifice 17/32")

Thread

A61Y005 1" NPT (orifice 1/2")


A61Y006 1 1/4" NPT (orifice 1/2")
A61Y015 1" NPT (orifice 17/32")
A61Y016 1 1/4" (orifice 17/32")
Dimensions

PORT A B C
2 5
1" (orifice 1/2) 1 7/64" 5 1/32"
45/64" 11/32"
2 5
1" (orifice 17/32") 1 7/64" 5 1/32"
45/64" 11/32"
2 5
1 1/4" (orifice 1/2") 1 7/64" 5 1/32"
45/64" 11/32"
1 1/4" (orifice 2
1 7/64" 5 1/32" 511/32"
17/32") 45/64"

Inspection and test of the wet pipe sprinkler


system
System Test Connections
The initial test required on a wet pipe automatic
sprinkler system is the hydrostatic test at not Wet Systems
less that 200 psi for two hours, or 50 psi in
excess of the static pressure, when the A test connection not less than 1 in. (25 mm) in
maximum static pressure exceeds 150 psi. diameter, terminating a smooth bore corrosion
During the hydrostatic test there should be no resistant orifice, given a flow equivalent to one
visible leakage from the sprinkler system sprinkler of a type having the smallest orifice
piping. installed on the particular system, shall be
provided to test each waterflow alarm device for
The underground mains leading to the sprinkler each system. The test connection valve shall be
system should always be thoroughly flushed readily accessible. The discharge shall be to the
before the mains are connected to the system. outside, to a drain connection capable of
A weekly inspection of all water control valves accepting full flow under system pressure or to
and alarm control valves is recommended to be another location where water damage will not
certain they remain open. (Giacomini A200 result.
valves have green indicator to see their open or
closed position from 50 ft distance)
Drainage

All sprinkler pipes and fittings shall be so


installed that the system may be drained

Giacomini Test and Drain valve merges in one


valve the above two functions of testing and
draining the system.
Connections to the branch line (a and b) 1" and
1 1/4"
Orifice 1/2" or 5/8" size
The valves will be available for two orifices: ½ Stem seals: two "O" rings with stem inserted
inch and 5/8" from inside of the valve.
Special patented construction allows the ball to
be supported at the flow inlet side by a special In multistory buildings where waterflow alarm
plastic housing. devices are provided at each floor or where
By rotation of the lever handle the valve can be more than one alarm device is provided in one
set at: sprinkler system, a test type pipe shall be
· OFF position provided for
· Test position
· Drain position

The intent of this section is to require It permits both an electrically operated alarm
inspector's test connection located in a manner and a water motor alarm supplied from an alarm
which will provide for the testing of all water valve to be tested through a single test pipe.
flow alarm devices.

Pressure
VEHZ.EX4430 - Drain Fittings, Special Type http://database.ul.com/cgi-bin/XYV/template/LISEXT/1FRAME/showpag...

VEHZ.EX4430
Drain Fittings, Special Type

Page Bottom

Drain Fittings, Special Type

See General Information for Drain Fittings, Special Type

GIACOMINI SPA EX4430


VIA PER ALZO 39
28017 S MAURIZIO D'OPAGLIO, NOVARA ITALY

Model A61 Test and Drain fitting, 1 in. and 1-1/4 in. NPT size simulating a 2.8, 4.2, 5.6, 8.0, 11.2 and 14.0 K-factor, for installation in threaded steel
pipe where pressures do not exceed 300 psig.

Model A61 Test and Drain fitting, 2 in. NPT size simulating a 4.2, 5.6, 8.0, 11.2, 14.0, 16.8, 22.4 and 25.2 K-factors, for installation in threaded or
grooved steel pipe where pressures do not exceed 300 psig.

This fitting is intended for installation on sprinkler systems in accordance with the Standard for Installation of Sprinkler Systems, NFPA 13.

Last Updated on 2009-09-28

Questions? Print this page Notice of Disclaimer Page Top

Copyright © 2010 Underwriters Laboratories Inc.®

The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's Follow-Up Service. Only those products bearing the UL Mark should be considered to be Listed and covered under UL's Follow-Up
Service. Always look for the Mark on the product.

UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Designs and/or Listings (files) must be presented in their entirety and in a non-misleading manner, without any manipulation of the data
(or drawings). 2. The statement "Reprinted from the Online Certifications Directory with permission from Underwriters Laboratories Inc." must
appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in the following format: "Copyright ©
2010 Underwriters Laboratories Inc.®"

1 de 1 19/07/2010 02:37 p.m.


Sprinkler System Alarm Testers
Each separate sprinkler system must be equipped with a separate waterflow alarm. In a high rise building, the system for each floor
must be separately alarmed. Where pressure reducing valves are used, a dual alarm and drain piping arrangement is required. The
alarm testers listed below combine test and drain valves, a waterflow sight glass, and a calibrated flow orifice in a single assembly to
simplify the piping required for such arrangements.

Model A61

Rated working
Nominal
Model Designation Size, inches NPS pressure, Remarks
K-factor(s)
psi (kPa)
A61 1 2.8, 4.2, 5.6, 8.0 300 (2070) a

2.8, 4.2, 5.6, 8.0, 11.2,


A61 1 1⁄4 300 (2070) a, b
14.0

4.2, 5.6, 8.0, 11.2,


A61 2 14.0, 16.8, 22.4, and 300 (2070) a, b
25.2

Remarks:
a. Devices supplied with female NPT threaded end connections.
b. Devices supplied with grooved end connections.

Company Name: Giacomini SpA


Company Address: Strada Per Alzo 39, 28017 S Maurizio d'Opaglio, Italy
Company Website: http://www.giacomini.com
Listing Country: Italy
Certification Type: FM Approved

© 2007-2010 FM Approvals. All rights reserved. 1 of 1