You are on page 1of 2

VRLA BATTERIES MSK 150

maintenance-free
rechargeable sealed lead acid battery
2V-150AH

Outer dimensions(mm)
mm(inch)

20

106± 3 (4.17± 0.12 )


8

(M8 Bolt)
170 ± 3 (6.69± 0.12 )

338 ±3 (13.31± 0.12 )


333 ±3 (13.11 ± 0.12 )
The LONG sealed lead-acid rechargeable battery is non-spillable and maintenance free. A valve regulated lead-
2V , 150Ah
acid battery is a starved electrolyte AGM type battery and has a safety valve which prevents excessive build up
of gas pressure inside the battery. Valve-regulated lead acid batteries rely upon internal gas recombination to
minimize electrolyte loss over the life of the battery, thereby eliminating the need for re-watering. A lead-acid
battery has lead positive plates, lead oxide negative plates, and an electrolyte which is a solution of sulfuric acid
and distilled water. The plates and the plate separator material between them are arranged in plate packs in duce r

Pro

ed
at
c er i f i c
MH16982 t

plate compartments. VRLA batteries are particularly suited for remote back-up power applications because they KUNG LONG BATTER IES

do not require the same type of periodic maintenance required by flooded cells. These differing maintenance
requirements provide cost savings.

Battery Construction

Component Positive plate Negative plate Container Cover Safety valve Terminal Separator Electrolyte

Raw material Lead dioxide Lead UL94VO UL94VO Rubber Copper Fiberglass Sulfuric acid

General Features Application


Absorbent Glass Mat(AGM) technology for efficient gas • Alarm System
recombination of up to 99% and freedom from • Medical Equipment
electrolyte maintenance or water adding. • Cable Television
• Control Equipment
Not restricted for air transport-complies with
• UPS
IATA/ICAO Special Provision A67.
• Communication Equipment
UL-recognized component. • Toys
Can be mounted in any orientation. • Emergency power System
Computer designed lead , calcium tin alloy grid for • Security System
high power density.
Long service life , float or cyclic applications.
Maintenance-free operation.
Low self discharge.

Specifications

0
Nominal Voltage 2V Capacity 30 C 105%
0
Number of cell 1 affected by 25 C 100%
0 0
Capacity (10 hr 25 C) 150Ah Temperature(20hr) 0C 85%
0
Design Life 15 Years -15 C 75%
Length 170 ± 3mm 1 month Remaining capacity: 94%
Self-Discharge
Width 106 ± 3mm 0
at 25 C 3 month Remaining capacity: 90%
Dimensions
Height 333 ± 3mm 6 month Remaining capacity: 85%
0 0 0 0
Total Height 338 ± 3mm Normal operating temperature 25 C ± 3 C (77 F ± 5 F)
0 0 0
Approx Weight 13.55Kg(29.81Lbs) Operating temperature range -15 C~50 C(5~122 F)
0 0 0
10 hr(15A,1.8V) 150Ah Storage temperature -20 C~60 C(-4~140 F)
Capacity Float charging voltage(20 C)
0 2.21 to 2.25V
5 hr(26.2A,1.8V) 127.5Ah 0
0 0
25 C(77 F) Coefficient 3.3mV/ C/cell
0 2.33 to 2.36V
1 hr(95A, 1.8V) 90Ah Cyclic charging voltage(25 C) 0
Coefficient 5mV/ C/cell
Internal Resistance (Full charged
0 0.75 mΩ Maximum charging current 45A
Battery at 25 C)
Terminal material Copper Maximum Discharge current 750A(5sec)
VRLA BATTERIES MSK 150
maintenance-free
rechargeable sealed lead acid battery
2V-150AH

Constant Voltage Charging Characteristic Life Characteristics Of Standby Use


d (0.25CA,20 O C )

nt
e
e

ge
m
rg

re
120

ta
lu
ha

ur

ol
Vo

C
C

V
( %) (xCA) (V)
140
100
120 0.25

Capacity(%)
2.50 CHAR GE D V OL UM E 80
100
0.20
2.33 CHAR GE VOLTA GE
80 60
Test ing condition s floating v oltag e: 2.21 to 2.25V/ Cell
0.15 O O
2.17 ambient t empera ture: 20 C(68 F )
60 40
0.10
2.00
40
20
0.05
20 1.83 CHAR ING CURR ENT

0 0
0 2 4 6 8 10 12 14 16 18 20
0 2 4 6 8 10
Cha rging Tim e (h ours) Life (year)

Capacity Retention Characteristic


Relationship Between C harging Voltage and (%)
Temperat ure 100
(V)
(12V) (8V) ( 6V) (4V) ( 2V) 0℃(32℉)

Remaining Capacity
75
15.6 10.4 7.8 5.2 2.6 10℃(50 ℉)

15.0 10.0 7.5 5.0 2.5 50 20℃(68 ℉)


C YC LE USE
40℃(104℉) 30℃(86 ℉)
14.4 9.6 7.2 4.8 2.4

13.8 9.2 6.9 4.6 2.3 25


STAND B Y US E
13.2 8.8 6.6 4.4 2.2
0
3 6 9 12 15 18
-10 0 10 20 30 40 50 60
O Storage Time (months)
Am bien t Te mp eratur e( C)

Effect of Temperature on Capacity 20℃(68℉)


120

0.05CA
100 0.1CA
Capacity %

0.25CA
80 0.6CA

1CA
60 2CA

40

20

0
-20 -10 0 10 20 30 40 50 ℃
-4 14 32 50 68 86 104 122 ℉
Temperature

Trickle (or float) Service Life Cycle Service Life


20
(1) Discharge : 0.17CA for 3hr
(2) Charge : 0.1CA for 9hr
120 (3) End of life discharge voltage : 1.65 Vpc
15
(4) Temperature : 20
Life (years)

100
C a pa city %

6 80

60
Discharge Depth 100% Discharge Depth 50%
Discharge Depth 30%
40
1.5

20

20 30 40 50 (℃) 0
68 86 10 4 12 2 (℉) 0 200 400 600 800 1000 1200 1400 1600 1800 2000

Ambi ent Temperature Number of Cycles (times)

O o
Constant Current Discharge Characteristics(Amperes,25 C) Constant Power Discharge Characteristics(Watts,25 C)
F.V/Time
20min 30min 1h 2h 3h 5h 8h 10h 20min 30min 1h 2h 3h 5h 8h 10h

1.80V 165 109 77.0 47.7 36.0 24.4 17.4 15.3 261 209 151 95.6 71.9 49.3 36.0 29.8

1.67V 183 144 90.6 53.6 39.9 27.3 18.8 16.2 324 271 177 105 78.6 54.0 38.0 32.4

1.6V 191 149 94.5 56.5 41.9 28.2 19.5 16.3 332 299 178 107 80.2 54.5 38.4 32.9

Revision 1.2

廣隆光電科技股份有限公司 Kung Long Batteries Industrial Co., Ltd.


南投市自立三路 6 號 NO.6 TZU-LI 3 ROAD NANTOU CITY TAIWAN TEL:+886-49-2254777~8 FAX:+886-49-2253607
Contents in this data sheet are subject to change for improvement without prior notice to users. For clarifications and updated information, please contact us.