FINAL DESIGN

DESIGN CRITERIA REPORT – FIRE PROTECTION 2017/03/02

077-04-GHEACO-B06-P-RPT-00000B
AL ADAN HOSPITAL

Title:

DESIGN CRITERIA REPORT – FIRE PROTECTION

Document No: Version:


077-04-GHEACO-B06-P-RPT-00000B 00

Purpose of Issue: Date:


For Approval 2017/03/02

Prepared by: JRU

Verified by: RCN

Approved: MDW
Al Adan Hospital
42-2014/2013

TABLE OF CONTENTS

1. PURPOSE..................................................................................................................................................... 1

2. TABLES AND FIGURES.................................................................................................................................. 2

DESIGN CRITERIA REPORT – FIRE PROTECTION TABLE OF CONTENTS Page i


077-04-GHEACO-B06-P-RPT-00000B
Al Adan Hospital
42-2014/2013

1. PURPOSE

The purpose of this document is to establish a set of design criteria related to the Fire Protection system to be
started soon on the ECP Building Final Design phase, for review and approval by SHBC before the start of the work
if applicable.

If necessary, this document will be successively updated if it is found that there are elements or equipment items
for which criteria have not been defined.

DESIGN CRITERIA REPORT – FIRE PROTECTION Page 1


077-04-GHEACO-B06-P-RPT-00000B
Al Adan Hospital
42-2014/2013

2. TABLES AND FIGURES

EMERGENCY CAR PARK


Fire Fighting Design Criteria

SYSTEM DESIGN CRITERIA

1.- FIRE EXTINGUISHERS Maximum distance to be travelled: 35 m


Maximum height from ground : 1,5 m
Inside Fire Hose Cabinet:
- 1 Unit 6 Kg Dry Powder Extinguisher
- 1 Unit 9 lts Water Extinguisher
Inside IT room, Electrical Room
- 1 Unit 6 Kg Dry Powder Extinguisher
Outside Transformer Room
- 1 Unit 25 Kg Dry Powder Extinguisher Trolley Type
2.- FIRE HOSE CABINETS
2.1.- FHC-1 FIRE HOSE CABINETS WITH LANDING
VALVE Maximum coverage: 36 m (30 m hose + 6 m jet)
Inside Fire Hose Cabinet:
- 25 mm hose reel (30 m)
- 65 mm seat valve (Landing Valve)
- 1 Canvas hose 30 m x 40 mm
- 1 Unit 6 Kg Dry Powder Extinguisher
- 1 Unit 9 lts Water Extinguisher
Placed near stairways
Minimum Pressure 4,5 Bar
Maximum pressure 6,9 bar (otherwise provide PRV)
Will be fed from the nearest standpipe, even if the
standpipe belongs to a different smoke sector

DESIGN CRITERIA REPORT – FIRE PROTECTION Page 2


077-04-GHEACO-B06-P-RPT-00000B
Al Adan Hospital
42-2014/2013

2.2.- FHC-2 FIRE HOSE CABINETS WITHOUT LANDING


VALVE Maximum coverage: 36 m (30 m hose + 6 m jet)
Inside Fire Hose Cabinet:
- 25 mm hose reel (30 m)
- 1 Unit 6 Kg Dry Powder Extinguisher
- 1 Unit 9 lts Water Extinguisher
For completing the coverage of FHC-1
Minimum Pressure 4,5 Bar
Maximum pressure 6,9 bar (otherwise provide PRV)
Will be fed from the nearest standpipe, even if the
standpipe belongs to a different smoke sector
3.- STANDPIPE For feeding Spinklers, Hose Reels and Landing Valves
Risers through shafts next to the stairways
DN 150 if feeding Spks., FHC´s and LV
DN 100 if feeding FHC´s and LV
Placed near stairways
Hydraulic calculations with two LV units flowing (2 x
250 gpm)
Time in service: 60 minutes
4.- INSTALATION CONTROL VALVE (ICV) - 1 Unit at the inlet of the building
DN acording the main loop in the basement.
5.- FIRE HYDRANTS DN 150
An isolating valve each
Hydraulic calulation with two outlets flowing (2x250
gpm)
Time in service: 60 minutes
Minimum Pressure 4,5 Bar
Maximum pressure 6,9 bar (otherwise provide PRV)
Maximum distance between two units 75 - 100 m
6.- FIRE BRIGADE BREECHING INLET DN 150
4 threaded front inlets DN 65 mm
Conected to main loop through check valve DN 150

DESIGN CRITERIA REPORT – FIRE PROTECTION Page 3


077-04-GHEACO-B06-P-RPT-00000B
Al Adan Hospital
42-2014/2013

7.- SPRINKLERS - WET COLUMN A - ORDINARY HAZARD


Type of risk (as NFPA and tender document) Hydraulically calculated
A.- Basement & Parking Areas: Ordinary Hazard Operation área: 139 m²
Flow: 6,1 lpm/m²
Time in service: 60 minutes
Residual pressure in the last sprinkler: 0.50 bar
Protection Area : 12,,1 m²
Maximum Distance between sprinklers: 4,6 m
Minimum Distance between sprinklers: 1,8 m
Maximum Distance from Walls: 2,3 m
(One-half of the allowable maximum dist. between
sprinklers)
Minimum Distance from Walls: 108 mm
Ducts wider than 80 cm with sprinkler at the
underside
Dropped ceilings higher than 80 cm with additional
sprinkler
8.- QUICK RESPONSE SPRINKLERS For sectorizating
Maximum Distance between sprinklers: 1,8 m
Maximun numbers of sprinklers per branch: 8
Branch Diameter: 50 mm
9.- LOW EXPANSION FOAM SYSTEM
A - DIESEL GENERATOR ROOM (OPEN SPRINKLERS) Foam type: Synthetic AFFF.
Mixture: 3%.
Design density: 6,5 lpm/m².
Time in service: 10 min.
Repositioning time of foam: 24 h.
10.- CLEAN AGENT FM-200 SYSTEM High Tension and Low Tension room
TO DEVELOP BY SPECIALIZED CONTRACTOR

DESIGN CRITERIA REPORT – FIRE PROTECTION Page 4


077-04-GHEACO-B06-P-RPT-00000B