8QEDODQFHSURWHFWLRQIRU 72&&

FDSDFLWRU EDQNV
1MRK 580 140-BEN
Page 1
Revision: -
Issued: November 2002
Data subject to change without notice

)HDWXUHV • Protects capacitor banks by supervising • Both current stages definite time delayed
the unbalance current for selective functioning
• Low set current stage for alarm • Measuring principle insensitive to harmon-
ics
• Higher set trip stage disconnects the bat-
tery before healthy units are damaged

$SSOLFDWLRQ Capacitor banks are made up of individual normally balanced parts of the capacitor
units which are series and parallel connected. bank. Under normal conditions, no current
Each unit is made up of several series and flows in the interconnection. A low set cur-
parallel connected elements. If one element is rent stage gives alarm when elements are
short-circuited or disconnected by internal damaged and current flows in the intercon-
fuses, the load on the remaining elements nection. The trip stage is set to disconnect the
increases.The unbalance protection is con- bank before healthy elements become over-
nected to a current transformer which mea- loaded and damaged.
sures the current flowing between two

)XQFWLRQDOLW\ The current measuring element continuously the set time delay tLow. If the current
measures the unbalance current and compares becomes higher than the set operate value
it to the set operate value for the two current IHigh during a time exceeding the set time
stages. A filter ensures immunity to distur- delay tHigh, the output relay for the high cur-
bances and harmonic currents.The output rent stage operates.
relay for the low current (alarm) stage oper-
ates if the current becomes higher than the set The input signal BLOCK blocks both the low
operate value ILow during a time exceeding set and the high set functions.

)XQFWLRQEORFN
TOCC-
72&&
BLOCK TRLS
TRHS

xx00000635.vsd
8QEDODQFHSURWHFWLRQIRUFDSDFLWRU EDQNV 72&&
1MRK 580 140-BEN
Page 2

,QSXWDQGRXWSXW 7DEOH ,QSXWVLJQDOVIRUWKH72&& 72&& IXQFWLRQEORFN


VLJQDOV 6LJQDO 'HVFULSWLRQ
BLOCK Blocks the unbalance protection function

Path in local HMI: ServiceReport/Functions/CapUnbalance/FuncOutputs

7DEOH 2XWSXWVLJQDOVIRUWKH72&& 72&& IXQFWLRQEORFN


6LJQDO 'HVFULSWLRQ
TRLS Alarm from the low set current stage
TRHS Trip from the high set current stage

7HFKQLFDOGDWD
7DEOH 72&&8QEDODQFHSURWHFWLRQ
)XQFWLRQ 6HWWLQJUDQJH $FFXUDF\
+] +]
Operate current of low set (2-100) % of I5b in steps of +/- 3.0 % of Ir +/- 5 % of Ir
stage I>Low 1%
Time delay tLow of current (0.000-60.000) s in steps of +/- 0.5 % +/- 10 ms +/- 0.5 % +/- 10 ms
stage I>Low 1ms
Operate current of high set (2-200) % of I5b in steps of +/- 3.0 % of Ir at I ≤ Ir +/- 5 % of Ir at I ≤ Ir
stage I>High 1%
+/- 3.0 % of I at I > Ir +/- 5 % of I at > Ir
Time delay tHigh of current (0.000-60.000) s in steps of +/- 0.5 % +/- 10 ms +/- 0.5 % +/- 10 ms
stage I>High 1ms

0DQXIDFWXUHU
$%%$XWRPDWLRQ7HFKQRORJ\3URGXFWV$%
Control & Force Measurement
Substation Automation
SE-721 59 Västerås
Sweden
Tel: +46 (0) 21 34 20 00
Fax: +46 (0) 21 14 69 18