A Study on The Black Start Capability of

VSC-HVDC Using Soft-starting Mode


Mingxia Zhou1, Sheng Li1, Jianhua Zhang1, Zongqi Liu1, Yinhui Li1
1 Key Laboratory of Power System Protection and Dynamic Security Monitoring and Control
(North China Electric Power University)㧘Ministry of Education, Beijing, 102206, China

Abstract-A good Black-Start scheme is important and necessary [3], soft energization method is adopted in this paper in order to
to resume power supply fast and efficiently after black out, and avoid high transient inrush current and high transient voltage
how to choose black-start power is the first thing to consider in the completely while energizing major power system equipments. A
scheme. In this paper, the advantages of VSC-HVDC as black start contrast is also made between two methods (in [3] and this
power are analyzed. The ability of VSC-HVDC to soft energize paper) of soft start-up long no-load line using VSC-HVDC.
major power system equipment is proved through simulation by
software PSCAD/EMTDC. Simulation waveforms during soft
II. OPERATION MECHANISM AND BASE CONTROL
STRATEGY OF VSC-HVDC
energization are illustrated. These plots have described the good
voltage and frequency characteristics of VSC-HVDC. Assume a two-level, six-pulse voltage source converter
Furthermore, the transition from black start control to normal (VSC) shown in Fig. 1 is• considered. The fundamental vector of
power flow control is discussed. Simulation results indicate that by the AC bus voltage is U •S , and the fundamental• vector of the
using soft energization, VSC-HVDC is an ideal black start power. VSC side AC voltage is U C , which lags behind U S an angle of
, and the converter reactance is X .
Keywords: black start, HVDC, soft energizing, VSC-HVDC

I. INTRODUCTION
With the scale expansion of modern power system, power
system faults are becoming more and more complex, a fault in a
subsystem possibly gives rise to a fault of the whole network,
even a serious blackout, thus brings great influence on social
economy and people’s living and a lot loss. So, it is of great Fig. 1 Voltage source converter
importance to study on black start .
As for traditional black start, there are a lot of problems to be If the harmonics is ignored, then
considered in the restoration of power system after black out, U SUC
such as: generator's self-excitation; continuing fundamental P= sin δ (1)
X
frequency over voltage, switching surge and resonant over
voltage while switching on a long no-load line; ferromagnetic U S (U S − U C cos δ )
Q= (2)
resonance while charging transformer; the stability of voltage X
and frequency and so on. M (3)
UC = Ud
Black Start function of VSC-HVDC has already been tested in 2
American Eagle Pass project [1], there is very simple Where P and Q are the active and reactive power absorbed by
introduction of black start in [1], and its emphasis point is VSC respectively. From (1) and (2), it can be concluded that P
Back-to-Back Tie. Ref. [2] has done field test on the whole and Q can be controlled independently by  and UC. When pulse
process of black start using VSC-HVDC as black start source, width modulation (PWM) is adopted,  is the phase angle of the
the results recorded demonstrate the excellent frequency and fundamental component of modulation wave, and UC is
voltage control performance. Ref. [3] has studied on “soft proportional to the modulation index M of PWM˄shown in (3).
start-up” long no-load line with VSC-HVDC, but it is limited to So it is possible to control P and Q independently by  and M.
soft starting-up long no-load line, soft starting-up other major Fig. 2 is the phasor diagram of VSC under steady-state
power system equipments is not mentioned. Based on [2] and operation and fundamental frequency condition [4]. From Fig.2,
VSC can operate in any quadrant of P-Q planar graph by
controlling M and ¥. For example, in the first quadrant, -90嘙<
This work was supported in part by National Hi-Tech Research
Development Program ୄ2008AA05Z216୅.
¥<0嘙, it can be drawn from (1) and (2) that P<0 and Q<0, other
quadrants are the same sense. Thanks to the ability of VSC to

嘋,((( 910 ,3(0&


operate in four quadrants, VSC can adjust the power (either then VSC1 will be blocked, after relay equipments for AC line
active or reactive) in a wide range from absorption to generation detect the fault, the AC breaker (B1, refer to Fig. 4) will be
up to rated power of HVDC. Based on this, VSC can operate as opened, at this time the control strategy of VSC1 will change to
STATCOM that compensate reactive power of AC bus AC voltage control (refer to Fig. 5).
dynamically, and stabilize AC bus voltage [5], [6].


UC

US


UC
Fig. 4 Experimental Circuit of soft energization

Fig. 2 Phasor diagram of VSC under steady-state operation and fundamental


frequency condition In Fig. 5, VpuR is the magnitude of VSC1 side AC voltage
(p.u), Vref is the set value of VSC1 side AC voltage, and mr is
In a VSC based HVDC system, there are three basic control the modulation ratio of PWM.
modes for the VSC. a) Constant DC voltage control; b) Constant
DC current or active power control; c) Constant AC voltage
control. In mode a) and b), the reactive power sent to the AC
system by the VSC is also controlled [7]. In this paper, there will
be transition of control modes mentioned above for a VSC, this
is because the control modes during normal power flow is Fig. 5 AC voltage controller diagram
different from that in black start. Details about the transition of
control modes will be discussed in the following. IV. BLACK START EXPERIMENT
III. CONTROL STRATEGY OF VSC-HVDC DURING DIFFERENT In [2], the restoration sequence is firstly controlling VSC1
OPERATION CONDITIONS side AC voltage to rated voltage, then closing breaker B1 (refer
to Fig. 4)to switch on the no load line, and then switching on the
Fig.3 shows the experimental circuit of black start in a system
transformer T1 and T3 in turn. When T3 is energized, the
with VSC-HVDC, it is obtained by making some changes of the
auxiliary equipment of G1 can be switched on. After G1 reached
four machine two regional systems in [8]. Some main
the synchronous, it can be synchronized connected to the island
parameters of the circuit are: the working frequency is 60 HZ,
grid at a proper time. In this process of black start, inrush current
the rated voltage value of bus 5,6,7,9,10,11,12 is 230kV, the line
and transient over voltage would happen by just simple
length between bus 5 and 6 id 180 km, bus 6 and 7 is 10 km, bus
operation of switching on the breakers, and possibly cause
6 and 12 is 200km. Other parameters are given with reference to
failure of restoration.
[8]. In Fig. 3, the system on the left side of VSC1 is Area1; the
The method of soft starting-up the long no load line is adopted
system on the right side of VSC2 is Area 2. The tie-line between
in [3]. The method in [3] is switching B1 at a moment during the
two areas is VSC-HVDC, and its main parameters can be seen in
ascending process of VSC1 side AC voltage.
Table . The black out happens in Area1, VSC-HVDC,
In this paper, the restoration sequence is: firstly, the circuit
functioned as “firewall”, prevents Area2 against outages
breaker B1 and B2 are closed, and then control VpuR increase
expanding and propagating [9].
gradually from 0 to 1. The process is named soft energizing.
Steps afterwards are the same as mentioned above in [2]. Details
about simulation experiment are as follows.
A. Soft energizing the long no load line and transformer
Fig.6 shows the simulation of soft energizing the long no load
line and transformer. Plot 1 shows the frequency of system in
Area1. Plot 2 shows that VpuR (Vac represents) ascends from 0
to 1 along the appointed curve (Vacref represents), VpuR
Fig. 3 Experimental Circuit of black start study in a system with VSC–HVDC reaches its rated value at 1s. Plot 3 shows the DC voltage (rated
56kV) of VSC2. Plot 4 and 5 show the active and reactive power
During normal operation, VSC1 in Fig.3 adopts active and absorbed by VSC1. Plot 6 shows the voltage of the long no load
reactive power control; VSC2 adopts DC voltage control and line, where Vlinebegin is the voltage of phase A at the start of
reactive power control. When there is a black out in Area1, the the line, and Vlineend is the voltage of phase B at the end of the
control and protection of VSC1 will identify the fault quickly, line. Plot 7 and 8 are Phase A currents of T1 and T3. Plot 9, 10,

911
and 11 are obtained by zooming plot 6, 7, and 8.

Fig. 7 A comparison between two methods of soft start-up

B. switching on the auxiliary equipment of G1


Station transformer with power rating of approximately
100MVA was energized at 2s, and a load of 56MW and 14MVar
was switched simultaneously, the load represents auxiliary
equipment for G1, or called plant electric consumption.
Fig. 8 shows the recorded signals during this process. It can be
seen that the active power and reactive power absorbed by
VSC1 changed with the load switching, plot 4 and 5 show that
VSC1 provided the active and reactive power of the load. The
frequency was maintained at 60HZ from plot 1. A small
transient was initiated on the DC voltage, but it was maintained
at 56kV later, refer to plot 3. The AC voltage magnitude
experienced a small dip, but it was controlled to the reference
value quickly after the transient. Plot 7 and 8 show the currents
in T1 and 3, the inrush currents were not large however, and
disappeared soon.

Fig. 6 Soft energizing long no load line and transformer

It should be noticed that since VSC1 acted as a black start


source, there would be no problems about Generator's
Self-excitation. B1 and B2 were closed at the beginning, and
thanks to the ability of VSC1 to regulate VpuR ascend from 0 to
1 along the appointed curve, there were not any kinds of
over-voltage or inrush currents when energizing long no load
line and transformer. The AC current in plot 10 during the
steady state was not zero, this was due to high frequency filter.
The filter was connected in between B1 and VSC1 and it is not
included in Fig. 4.
Fig. 7 is a comparison between two methods of soft start-up.
Plot 1 is the method mentioned in [3], here, the long no load line
is switched at 0.6s when VpuR reaches 0.5. It can be seen that
there is switching surge on phase B at the end of the line. Plot 2
is the method in this paper, we can see that during the whole
process of energizing long no load line, there is not over voltage
or surge at all. So, soft start-up method presented in this paper is
a better one.
Fig. 8 Switching on the auxiliary equipment of G1

912
C. Switching G1 into grid mode. The process of transition from black start control to
G1 with power rating of 900MVA had been started up with normal power flow control can be seen in Fig. 11, it happened at
the help of auxiliary power supplied by VSC1 as described 3.08s. Here, reference time axis is different from that in steps
above. At 3.8s, when the condition of unit synchronous above, this is because we took snapshot during simulation in
switching was satisfied, generator 1 was connected to the island PSCAD. It is obvious that the transition is satisfactory. The
grid. Plot 4 in Fig. 9 shows that stable system performance was step-test of active power at 5s (seen in plot 2) shows the control
obtained. The frequency of the AC voltage was also kept stable mode has changed to power flow control which has superior
close to 60HZ, refer to plot 1. control effect.

Fig. 11 Transition from black start control to normal power flow control

Fig. 9 Synchronizing in G1 rated 900MVA


Definition of signals in Fig. 5-Fig. 8 is in Table Ċ.

D. Restoring part of load in Area 1


V. CONCLUSION
80MW and 5Mvar load, part of the original Load 7, was In this paper, the black start policy including the control mode
switched at 5s. The frequency of AC voltage was excellent as adjusting of VSC-HVDC and proper sequence of restoration is
before. The process of switching G2 and restoring the rest load analyzed. The voltage and frequency control ability of
is similar to C and D. VSC-HVDC ensure the process of restoration of the black
system to be smoothly without inrush current and transient over
voltage. By contrast, a better soft start-up method is presented.
Using this method, the ability of VSC-HVDC to softly energize
major power system equipment is proved through simulation by
PSCAD/EMTDC. Simulation results indicate that VSC-HVDC
is an ideal black start power source.
VI. APPENDIX
TABBLE I
THE PARAMETER OF VSC-HVDC LINE

VSC-HVDC Parameters Value Unit

Voltage Source(L-L,RMS) 230 kV

Transformer Capacity 300 MVA

Transformer Wiring Group Y/


Fig. 10 Restoration of some load VSC1/VSC2
Transformer Rated Voltage 230/20 kV

E. Transition from black start control to normal power flow control Transformer Positive Sequence
0.1 pu
As shown in previous steps, the VSC-HVDC provides Leakage Reactance
excellent voltage and frequency control. Once all the
DC capacitor 5000 F
generations in the grid are restored and loads are connected, the
VSC HVDC can be switched to normal power control mode by DC Circuit DC resistance 2.98 
the operator. No transient should be noticed at mode switching, Length of DC Line 220 km
as the on-line measured active and reactive power will be used
PWM Carrier Wave Frequency 1980 HZ
as initial active and reactive power settings in the power control

913
TABBLE Ċ
DEFINITION OF SIGNAL IN FIG. 6 –FIG. 11
Signal name Definition Unit
f Frequency of system in Area 1 Hz
Normalized value of the AC side voltage
Vacref pu
reference of VSC1
Normalized value of the AC side voltage
Vac pu
of VSC 1
dcVoltagelnv DC voltage of VSC 2 side kV
Pvscshiji Active power absorbed by VSC 1 MW
Qvsc1shiji Reactive power absorbed by VSC 1 Mvar
Voltages of phases A at the start of the line
Vlinebegin kV
near Bus 5
Voltages of phases B at the end of the line
Vlineend kV
near Bus 5
Itranformer1 Phase A current of transformer T1 kA
Itranformer3 Phase A current of transformer T3 kA

ACKNOWLEDGMENT
This work was supported in part by National Hi-Tech
Research Development Program. We authors give our deepest
gratitude to the program.

REFERENCES
[1] T Larsson, A Petersson, A Edris, D Kidd, R Haley, F Aboytes. “Eagle Pass
Back-to-Back Tie: A Dual Purpose Application of Voltage Source
Converter technology,” IEEE Power Engineering Society Transmission
and Distribution Conference, pp. 1686-1691, 2001.
[2] Ying Jing-Hafner, Hugo Duchen, Michael Karlsson, Leif Ronstrom, Bernt
Abrahamsson. “HVDC with Voltage Source Converter—A Powerful
Standby Black Start Facility,” IEEE T&D Conference, Chicago, April
2008
[3] Guangkai Li, Chengyong Zhao, Xingran Zhang, Gengyin Li. “Research on
“Soft Start-up” of VSC-HVDC in Power System Restoration after
Blackouts,” 2007 Second IEEE Conference on Industrial Electronics and
Applications, pp.1939-1944, November 2008
[4] ZHENG Chao, ZHOU Xiao-xin, LI Ruo-mei. “Dynamic Modeling and
Transient Simulation for Voltage Source Converter Based HVDC,” Power
System Technology, Vol. 29, No.16, pp.1-5, August 2005 (Chinese).
[5] Xu Zheng, "Dynamic behavior analysis of AC/DC electric power system",
Beijing: Mechanic industry press, 2004 (Chinese).
[6] Zhao Chengyong, Li Jinfeng, and Li Guangkai, "VSC-HVDC control
strategy based on respective adjustment of active and reactive power,"
Automation of Electric Power System, vol. 29, No. 9, pp. 20-24, May. 2005
(Chinese).
[7] Zhang Guibin, Xu Zheng, and Wang Guangzhu, "Steady-state model and
its nonlinear control of VSC-HVDC system," Proceedings of CSEE, vol.
22, No. 1, pp. 17-22, 2002.
[8] Kundur P. Power System Stability and Control. New York: MCGraw -H
ill, 1994
[9] Michael P. Bahrman and Brian K. Johnson. “The ABCs of HVDC
Transmisson Technologies,” IEEE Power & Energy magazine, pp.32-44,
March/April 2007