Cable Size Calculation

Ampere calculation for single anchor winch:

P = √3 x V x I x cosΦ x η

630 = √3 x 0.69 x I x 0.85 x 0.962 (Values are taken from motor nameplate, refer page no.2)

I = 644.67 A

From Cable Datasheet:

Current carrying capacity of 1 run of 3C x 95 sq.mm = 259A (Refer page no. 4)

Current carrying capacity of 4 runs of 3C x 95 sq.mm = 4 x 259A = 1036 A

De-rating factor

(A) Assuming double banking of cables = 0.8


(B) Due to variation in ambient temperature (50 0C) = 0.95

Total de-rating factor = 0.8 X 0.95 = 0.76

Diversified cable rating = 0.76 x 1036 = 787.36 A

Conclusion:

From the above calculation, it is evident that 4 Runs of 3C x 95 sq.mm will be sufficient to cater the
ampere requirement of the single anchor winch.
VFD cables TEOF
Offshore Cables

TEOF VFD F-RFOU


or F-RFOU+MUD
0,6/1 kV

Construction > Conductor


flexible tinned copper conductor multi bunched according to IEC 60228 cl.5
easier to install e more resistant to vibration
> Insulation
R
HF-HEPR (high modulus) according to IEC 60092-351
HF-HEPR insulation with low dielectric constant to reduce reflected wave peak
voltage magnitude. This allows for longer output cables distances and minimize
the effect of high frequency noise induced into plant ground system
thickness according to IEC 60092-353
> Bedding / inner covering
F
halogen free compound
indicative thickness according to IEC 60092-353
(inner covering)
> Braid armour
O
Cu/PETP tape and copper braid made of tinned copper wires
according to IEC 60092-353
overall tinned copper braid and foil shield (PET+copper)
provides 100% coverage containing VFD EMI emission
> Outer sheath
U
halogen free thermosetting compound
SHF2 according to IEC 60092-359
or
U+MUD
halogen free, mud resistant thermosetting compound
SHF MUD according to NEK III ed. 2004
thickness according to IEC 60092-353
> Marking
e. g. : “PRYSMIAN(*) - TEOF - F RFOU 0,6/1 kV (VFD) nc x sect./braid sect.
MUD RESISTANT 'metric year”
Applicable NEK 606 III ed. Design guidelines
IEC 60092-350 Design guidelines
standards IEC 60092-351
IEC 60092-352
Insulating material
Choice and installation of electric cables
IEC-60092-353 Design guidelines
IEC 60092-359 Sheathing materials
IEC 60332-1-2 Flame retardance
IEC-60332-3-22 Fire retardance
IEC-60754-1 Halogen free properties
IEC-61034-2 Smoke emission properties

on request

CSA 22.2 n.38-95 cold bend/impact test at low temperature


Additional marking "-40 °C" when requested

(*) factory code

low
r

IEC 60332-1-2 VERY GOOD VERY GOOD LOW EMISSION -20 °C GOOD r = 6D
IEC 60332-3-22
22 EXCELLENT
(MUD RES)
technergy
INTEGRATED CABLING SOLUTIONS
TM

> Low Voltage cable - Armoured

> Fire retardant - Low smoke - Halogen free

TEOF VFD F-RFOU 0,6/1 kV

N° of cores x csa / csa Conductor Insulation Diameter Overall Net weight Minimum D.C. Current Fault Reactance at
braid diameter thickness over diameter approx. bending resistance carrying current
approx. nominal bedding approx. radius at 20 °C capacities at 250 °C 50 Hz 60 Hz
approx. max. 45 °C free air
(n x mm2) (mm2) (mm) (mm) (mm) (mm) (kg/km) (mm) (Ohm/km) (A) (kA) (Ohm/km) (Ohm/km)

3x50 /25 9,1 1,4 28,5 34,7 2700 209 0,393 167 7,15 0,077 0,092
3x70 /35 10,8 1,4 32,6 39,6 3650 238 0,277 214 10,01 0,074 0,089
3x95 /50 12,1 1,6 36,3 43,9 4650 264 0,210 259 13,59 0,074 0,089
3x120 /60 14,3 1,6 41,0 49,1 5900 295 0,164 301 17,16 0,072 0,087
3x150 /70 16,1 1,8 46,1 54,5 7300 327 0,132 347 21,45 0,072 0,087

All data refer to cables with cl. 5 conductors