You are on page 1of 2

Simple Tests To Assure Proper DC Motor Performance

polarity, brushholder spacing, setting shorted. However, variations in the


neutral and two-way run testing. All magnetic circuit can lead to unequal
of these tests can usually be per- drop test voltages even though the
formed with the motor assembled, coils are sound.
although in some cases the end If a coil tests shorted by the AC
bracket on the commutator end may drop test method, it should be
need to be removed to access the field removed from the pole piece, if
lead connections. possible, and comparison tested to
another removed coil that has tested
Drop Testing Fields (Shunt,
Series, Interpoles) satisfactory and is also separate from
Shorted shunt fields can cause the its pole piece. The reason for this is
motor to operate erratically, vary in that iron differences, such as a split in
speed, or may cause armature current the frame or even a terminal box
and/or speed to increase. Shorted opening, can affect the AC drop test.
By Tom Bishop, P.E. Some other examples that illustrate
series fields may cause the motor
EASA Technical Support Specialist iron differences are:
speed to vary more than normal; and
shorted interpoles often cause • Coils placed flat on a concrete floor
Editor’s Note: Following is the first may be affected by the proximity of
of a two-part article that describes sparking (sometimes severe) at the
brushes. The most common test to reinforcing rod in the floor.
several simple tests to perform that can • Coils placed on a steel frame table
help make sure a DC motor operates detect shorted fields is the drop test.
The drop test can be performed may be affected by the proximity
properly. To learn more on this subject, of the steel framework.
EASA’s “Fundamentals of DC using AC or DC voltage. For an AC
drop test, the tolerance is that the coils • Field coils placed side-by-side for
Operation and Repair Tips” seminar testing may indicate a difference in
includes dozens of other tests and tips. be balanced within 10% of the
average. For the DC drop test, the the coils at each end, since they do
This seminar will be offered next not have the same amount of iron
March 18-19 in Denver. Watch tolerance is reduced to +/- 5% of the
average. The drawback to the DC drop on both sides.
upcoming issues of CURRENTS for • Sometimes, a shorted coil will
more details. test is that it relies on Ohms Law to
detect shorted turns. With a tolerance cause a lower test value for the
*** of +/- 5%, a coil with 1000 turns could coils immediately adjacent to it.
There are many tests that can be have a short between two turns less AC voltage drop testing of
performed on a DC motor to verify than 50 turns apart, and still be within interpoles, series or compensating
the integrity of windings, correct coil tolerance (50/1000 = 0.05, or 5%). windings can be done using an AC
polarities and proper running perfor- The AC drop test is more suitable welder if the service center test panel
mance. What we will address in this than the DC drop test in probing for can not supply the low voltage
article are a select few simple tests shorted coil turns. Shorted turns in a necessary to limit the current to below
that can help assure a motor operates coil act like a closed secondary on a rated amperes. Typically, the voltage
properly when the customer applies it. transformer. The voltage drop needed is less than 120 volts. The
Our intent is not to oversimplify and variation with shorted coils is often voltage drop test with lower voltage
suggest that performing these tests quite dramatic, typically much greater uses the same acceptance criteria as
alone is all that is required for an than the acceptance judgment value. higher voltage; however, the lower
effective repair. Rather, the intent is to That makes the AC test the preferred coil voltage values must be measured
highlight some tests that give a drop test method. Typically 120 (or more precisely.
maximum return for the time invested 240) volts AC is applied to the shunt Because many of these high
in testing. field circuit and the voltage drop current coils have relatively few turns,
The tests we will cover are drop across each coil is measured. A a coil-to-coil resistance comparison
testing fields, checking interpole variation from average of greater than may also reveal shorted turns. The
polarity, checking compound field 10% is an indicator that a coil is Continued On Page 2

EASA CURRENTS ■ May 2004 1


Simple Tests To Assure Proper DC Motor Performance
Continued From Page 1

resistance to be measured is very low, If the brushholder leads are output voltage. Figure 1 illustrates the
typically requiring a digital low accidentally swapped, the polarity of interpole polarity test circuit.
resistance ohmmeter (DLRO) capable the armature relative to the interpoles
Compound (Series-to-Shunt)
of reading into the milli- or micro-ohm will be reversed. Depending on the Field Polarity
range. A variation in excess of 5% design, the brushes may not arc until The series and shunt field coil
from average for any one coil is an the motor is loaded. The arcing tends polarities should almost always be the
indicator of either a short or a high- to be proportional to the load, and same as each other; that is, cumulative
resistance connection. A coil resistance arcing at full load can be severe compound. Because of their instability,
that is too low indicates a short, and if enough to cause a flashover. This is there are almost no real-world applica-
too high, a poor connection (e.g., a one of the most common repair tions for differential compound motors.
“cold solder joint”). problems experienced unless the Differential compounding is the
A variation of the AC drop test is technician follows the procedure to condition where the series field coil
the impedance test. AC voltage is confirm interpole polarity. polarity opposes that of the associated
applied to a single coil, and the exact Low voltage AC, typically 30-60 shunt field coils.
voltage and current recorded. The volts, can be applied to the armature In almost all cases, if a differentially
exact same voltage is applied to each and interpole circuit to verify correct connected motor is operated with load,
of the other coils, and the currents are interpole polarity. The voltage is sparking at the brushes will occur due
compared. Impedance is the ratio of applied on two brushholders of to increased armature current. Output
voltage to current, and by keeping the opposite polarity, and the output power or torque is a function of field
voltage constant, any change in voltage is measured on the A1 and A2 strength multiplied by armature current.
current directly reflects a change in leads in the terminal box. The output The formula that relates this is:
impedance. Being an AC drop test, voltage will be less than the input Torque = k F I; where k is a constant,
the tolerance for acceptable imped- voltage if the interpole polarity is F is field flux (strength) and I is
ance variation is 10%. As with the AC correct. The principle at work here is armature current. The armature
drop test, the proximity of other iron that the interpole opposition of current must increase to compensate
will affect the results. Table 1 armature flux is like a “buck” for the weakened field with a differ-
summarizes the tolerance values for autotransformer; correct polarity ential connection.
both AC and DC drop tests. results in lower combined armature To verify series-to-shunt field
and interpole circuit output voltage. polarity, connect an analog DC
Table 1: Tolerance values for The typical output voltage of correct voltmeter (no more than 3 volts scale)
AC and DC drop tests. polarity interpoles is about 1/2 to 2/3 to the series field leads, with the
of the input voltage. If the output positive meter lead on S1. Using a 12-
Drop Test Tolerance voltage is higher than the input, 24 volt DC supply, flash (briefly
reverse the interpole leads. If the contact and immediately disconnect)
AC +/- 10% of the average
voltage drop voltages are the same, either the the shunt field, applying positive
DC +/- 5% of the average
interpoles are disconnected, or an voltage to the F1 lead, and observe
voltage drop equal number of them are opposing the deflection on the voltmeter.
If 120 volts is applied to 4 coils, the
each other. Therefore, check for If the meter indication is upscale
average voltage drop should be 30 volts. incorrect polarity. Motors with (positive), the fields are cumulative
Deviation should be within the stated compensating (pole-face) windings
tolerance from that average. compound, which is almost always
will typically develop a very low the correct relationship.
Interpole Polarity If the meter deflects downscale
Interpole polarity should be such (negative) the fields are differentially
that the interpoles oppose the magnetic compounded and probably incorrect.
A.C. Input ARM A.C. Output
flux of the armature. If the interpole In Part II next month, we will
Interpoles
polarity is incorrect, severe sparking at learn about these DC motor tests:
the brushes typically results. In some brushholder spacing, setting
cases, reversed interpole polarity can neutral and two-way run testing.
lead to flashover. Figure 1: Interpole polarity test.

2 EASA CURRENTS ■ www.easa.com

You might also like