ADVANCED METERING
INFRASTRUCTURE CODE
(AMI)
Advanced Metering Infrastructure Code CS-CSI-P1/C4

CONTENT

A. Multi meter case for MSB connection / Multi meter case for LV panel 4
B. Service Cabinet / Electric room connection / Single meter case for MSB / Single meter case 5
for LV panel connection

ADVANCED METERING INFRASTRUCTURE CODE (AMI)

Page 03 of 08
Issue : 0 16-10-2016 Unclassified
Advanced Metering Infrastructure Code CS-CSI-P1/C4

Advanced Metering Infrastructure Code (AMI)

Amendment to the Regulations for the Installation of Electrical wiring to accommodate the
Advanced Metering Infrastructure (AMI) components “Additional Field Requirements for
AMI”

In addition to Kahramaa Installations regulations, the below shall be considered for Advanced Metering
Infrastructure system (AMI); additional Drawing named “Advanced Metering Infrastructure Layout” shall
become a part of the Building Permit document submission for Kahramaa approval.

A. Multi meter case for MSB connection / Multi meter case for LV panel

1) In each / typical floors, provide Two embedded 32 mm PVC conduit (2 nos. x 32 mm) between each
group Electricity meters of (max 12 meters) and the corresponding group of Water meters (Between both
groups) with pulling rope and the following embedded junction boxes (provide access panels on false
ceiling, if required).

a. In electricity metering room near to the Main Distribution Board, install 2 Nos. 150mm x 150mm x
100mm size end junction box to connect with the 2 No.s 32 mm PVC conduits.

b. In water metering room near corresponding Water meter cabinet, install 2 Nos. 150mm x150mm
x 100mm size end junction box to connect with the 2 No.s 32 mm PVC conduits .
ADVANCED METERING INFRASTRUCTURE CODE (AMI)

c. Install 32 mm conduit to connect the above 2 Nos. end Junction Boxes at water metering room
(in item b above) to corresponding water meters cabinets Up to 3 cabinets maximum, each of
the 2 nos. end junction boxes should be connected to each water meter cabinet (when cabinet
does not exist stop at group of meters with 150x150x100 mm end Junction box) and all conduits
should have a pulling rope (every cabinet suppose to have 4 meters only).

d. For every conduit; Install pulling junction boxes in every 10-15mtr distance / corner portions.

2) Provide 1 x 32 mm embedded heavy-duty PVC conduit with 5c. 2.5mm2 cables (R, Y, B, N & E) for
‘interconnecting power supply’ between the main water meter chamber and nearest ground floor electrical
room / LV room and Provide another 1 x 32 mm embedded heavy-duty PVC conduit between the main
water meter chamber and The MDF with pulling rope with the following embedded junction boxes:

(Proper waterproofing is required for the conduits in main water meter chamber and building retaining
wall)

a. Install IP65, 150mm x 150mm x 100mm size end junction box near to the Main Distribution Board
/ LV panel in ground floor electrical room with a 32 mm PVC conduit connecting with pulling rope
at Main LV panel and Install IP65, 150mm x 150mm x 100mm size end junction box near to the
‘MDF’.

b. In main water meter chamber, install 2 nos. IP65, 100mm x 100mm x 50mm size end junction box
on high level and ensure the connection to the 2 nos. 32 mm heavy duty conduits mentioned in
point 2 above.

c. Install pulling chamber / junction box in every 20-25mtr distance / corner portions.

3) In main LV room a 500mm (Height) x 500mm (Width) provision required on the wall with 100mm x
100mm x 50mm size surface mount type junction box for each data concentrator (AMI Device);. Following
additional requirements are to be incorporated.

a. Install embedded conduit with 5c. 2.5mm2 cables (R, Y, B, N & E) from the LV panel-metering
compartment to the data concentrator junction box on the wall. Each data concentrator requires
a 3ph+N supply from the respective main LV panels, each LV panel will have a Data Concentrator.

b. Distance between the data concentrator junction boxes shall be minimum 300mm, if two or more
main LV panels are in the main LV room.

Page 04 of 08
Issue : 0 16-10-2016 Unclassified
Advanced Metering Infrastructure Code CS-CSI-P1/C4

4) Provide embedded 38mm PVC conduit for between the MDF panel and main LV rooms with pulling
rope and the following embedded junction boxes (provide access panels on false ceiling, if required).

a. Install 150mm x 150mm x 100mm size end junction box 30 cm from MDF.

b. Install 150mm x 150mm x 100mm size end junction box in main LV room, near to data concentrator.

c. In case of more than one concentrator in main LV room (More than one Main LV panel), install
100mm x 100mm x 50mm size Junction box near to each data concentrator and install and
connect 25 mm conduit between these 100mm x 100mm x 50mm size Junction boxes and the
100mm x 100mm x 50mm size end junction box in main LV room.

d. Install embedded pulling junction boxes in every 10-15mtr distance / corner portions.

B. Service Cabinet / Electric room connection / Single meter case for MSB / Single meter
case for LV panel connection

1) Provide 2 Nos. embedded 25mm PVC conduit between the electrical and water metering cabinets and
fix at allocated opening in both cabinets of respective premises (use pipe/cable entrance only in case of
no allocated opening) with pulling rope and install IP65, 100mm x 100mm x 50mm size embedded pulling

ADVANCED METERING INFRASTRUCTURE CODE (AMI)


junction boxes in every 20mtr distance / corner portions.

2) Provide 1 Nos. embedded 25mm PVC conduit between Landlord water meter and Landlord Electric
meter locations with pulling rope and install IP65, 100mm x 100mm x 50mm size embedded pulling
junction boxes in every 20mtr distance / corner portions.

Note: In all cases; Distant from relevant eclectic meter should not exceeds 90 meters.

Page 05 of 08
Issue : 0 16-10-2016 Unclassified
ADVANCED METERING INFRASTRUCTURE CODE (AMI)

Page
06 of 08
Advanced Metering Infrastructure Code

AMI requirement at building for following Method of connection: Multi meter case for MSB connection / Multi meter case for LV panel
connection
Same for Same for Same for
each floor each floor each floor

PVC 32 mm embedded conduit


Pulling
Pulling
Pulling
Rope

Issue : 0
Junction Junction
PVC 32 mm 150 mm
conduit 150 mm 100 mm
100 mm
10 – 15 m 10 – 15 m 10 – 15 m
150 mm

150 mm

16-10-2016
Juncti Pulling Pulling Junction
on box Rope Rope box

Water Water Water


meter meter meter

Unclassified
cabinet cabinet cabinet Pulling
Pulling
150 mm Junction
PVC 32 mm Junction 150 mm
100 100 mm
conduit mm 10 – 15 m 10 – 15 m 10 – 15 m
150 mm

150 mm
Juncti Pulling Pulling Junction
on box Rope PVC 32 mm embedded conduit Rope box
Field Requirements for AMI (Item A-1)

Group of Water Meters Electricity Meter


Room
CS-CSI-P1/C4
AMI requirement at building for following Method of connection: Multi meter case for MSB connection / Multi meter case for LV panel
connection
Main water chamber
Advanced Metering Infrastructure Code

150 mm PVC 32 mm heavy duty conduit with 5c. 2.5 mm2 150 mm rope Main DB
100 mm rope
cables for interconnecting power supply
IP65
IP65 20 – 25 m Junction
Junction box

150 mm
box

150 mm
rope
150x150
x100 mm

rope
32 mm conduit
25 mm conduit

5c. 2.5mm2 cables rope

Issue : 0
provision
(R,Y,B,N&E) from the
respective main LV
panels pulled in 3ph + n supply
a 32 mm conduit Surface mount
type junction box

16-10-2016
100mm x 100mm Data concentrator
500 mm

x 50mm
500 mm rope
38 mm conduit

Same for each Data

Unclassified
Concentrator
With minimum 300 mm
10-15 m

distance
Nearest ground floor electrical
room/Main LV room

100 mm 150 mm MDF


100 mm
Field Requirements for AMI (Item A-2, 3& 4)

rope
rope
IP65
IP65 20 – 25 m Junction
Junction
150 mm

box

32 mm conduit
box

50 mm
150x150
32 mm conduit
x100 mm
rope

Page
Field Requirements for AMI (Item A-2, 3& 4)
CS-CSI-P1/C4

07 of 08
ADVANCED METERING INFRASTRUCTURE CODE (AMI)
ADVANCED METERING INFRASTRUCTURE CODE (AMI)

Page
08 of 08
AMI requirement at building for following Method of connection:

Service Cabinet/ Electric room connection / Single meter case for MSB connection / Single meter case for LV panel connection
Advanced Metering Infrastructure Code

Water meter service cabinet IP65 Pull IP65 Pull Electrical meter service cabinet
junction box
junction box

20 m 20 m 20 m

rope rope
PVC 25 mm conduit
embedded

Issue : 0
IP65 Pull IP65 Pull
junction box junction box

20 m 20 m 20 m

16-10-2016
rope rope

Unclassified
IP65 Pull IP65 Pull
Landlord Water meter when exist Landlord Electric meter when exist
junction box junction box
Field Requirements for AMI( Item B)

20 m 20 m 20 m

rope
PVC 25 mm conduit rope

embedded

Field Requirements for AMI( Item B)


CS-CSI-P1/C4