Dead load (Ndl) = 5.00 kN Eccentricity (ecc) = 45 mm (+ve increases inward)
Live load (Nll) = 5.00 kN D/2 = 45 mm
Wind load (Nwl*) = kN (Comp.)
Bending
Wall area = 1.2 m² Apply wind reduction = N (Y)es,(N)o
Ws/Wu = 0.68 Wall area reduction (ka) = 1.00 AS/NZS 1170.2, Table 5.4
Deflections
Ireq'd WLs.in (L/250) = 1.7 x10⁶ mm⁴ < Critical δWLs.in = 3.3 mm Span / 820
Ireq'd WLs.out (L/250) = 1.0 x10⁶ mm⁴ δWLs.out = 2.0 mm Span / 1328
Deflection limits
Importance:
Category 1 House failure affecting < 25m², secondary building element
Category 2 Building, house failure affecting > 25m²
Category 3 Important
Duration:
Storage and passage durations used
are based on intermediate durations from Table 2.3
and used with engineering judgement.
Title =
k4 factor:
Partial seasoning factor
Refer Cl 2.4.2.2 & 2.4.2.3 for more information.
k6 factor:
Refer Cl 2.4.3 if designing structures near coastal
regions of Queensland north of 25°S and all other
regions north of 16°S
X-Axis Y-Axis
kN kN
øNc(dl) = 19.6 52.3
øNc = 32.3 86.2
øNcw = 34.4 91.7
Material constant:
Refer to Appendix E2
Bending ratio = 1.00
Compression ratio = 0.56
Compression/Bending:
Refer 3.5(1) & 3.5(2)
Service class:
Service class defined in AS/NZS 1328.1 1998 Glued Laminated Structural Timber
1 - Domestic houses, Commerical Offices
2 - Open sheds, exposed beams under soffits, porches, laundries
3 - Marine structures, Bridges
S - Severe/Adverse requires specialist advice