Professional Documents
Culture Documents
Acoustic Valve
Inspection
(NAVI)
FACTORS IMPACT
• The NAVI hardware takes the sound measurement signals, processes and
displays them as a signature most suitable to identify and quantify the leaks.
• Test requirements
• Valve to be tested must be in closed position
• There is a differential pressure across the valve, at least 1 barg.
If a valve is in open position, A tight valve makes a very A passing valve creates
there will be laminar flow little or no noise. turbulent flow and acoustic
that generates little or no noise. The AE is transmitted
noise. into the valve body.
Differential
Signature
VALVE PASSING
Analysis
• If Pressure Noise is greater than Background Noise, then the valve leaks.
• If Pressure Noise is equal to Background Noise, then the valve is tight.
Differential
Signature
VALVE TIGHT
Analysis
• If Pressure Noise is greater than Background Noise, then the valve leaks.
• If Pressure Noise is equal to Background Noise, then the valve is tight.
PASSING NO PASSING
Continue Monitoring
Small Medium Large 6-Monthly
Large
Small
Medium
Leak
Leak
Leak
––24
1 –to
dB
109and
to
dB23 above
dB
Valve
Continue
Valverecommended
NeedMonitoring
Repairing
Estimation ofto
6-Monthly
be replaced
Leak Rate
Tolerable Leak Threshold for Various
Type of Valves (Shell IMP 3.02 Table 1)
Action Items:
• Mobilized Amserve to conduct non-intrusive acoustic valve inspection on MOVs to
determine leakage rate; and check for any passing from kicker line and vent line.
• Mob valve maintenance vendor to conduct MOVs alignment, perform greasing and
sealing.
• Amserve to verify passing valves and final leakage rates.
MOV290X2 MOV290X1
• NAVI was conducted again, result shows MOV290X2 is still passing and confirmed
by continuous passing of gas at body vent.
• MOV290X1 shows minimal passing, and greatly reduced passing from body vent.
Most of riser pressure is being contained by MOV290X1.
Action Items:
Amserve to carry out NAVI. Pump was let run until
reach consistent desired discharge pressure, then
stopped to create backflow.
Result:
Passing valves were identified. Leak severity ranged
from small to medium leak, however estimated leakage
rates are still within tolerable leak threshold for check
valves (0.3 kg/s).
Action Items:
Amserve was notified on the situation and was
mobilized to site.
Result:
It is found that the valve passing and the estimated leak
rate is still within the allowable leak rate. OIM and
maintenance team were notified on our findings.
Safety
Environment
• Reduced flaring/emission