You are on page 1of 359

w 页码,1/359(W)

SMU02B
Product Version: V300R003C00
Library Version: 01
Date: 05/26/2015

For any question, please contact us.


Copyright © Huawei Technologies Co., Ltd. 2015. All rights reserved.

Site Alarm Reference


Contents
1 Site Alarm Reference
1.1 ESMU
1.1.1 Communication Failure
1.1.2 Board Hardware Fault
1.1.3 Discharge High Temperature Protection
1.1.4 Charge High Temperature Protection
1.1.5 Overcharge Protection
1.1.6 Overdischarge Protection
1.1.7 Battery Electrochemical Cell 1 Fault
1.1.8 Battery Electrochemical Cell 2 Fault
1.1.9 Battery Electrochemical Cell 3 Fault
1.1.10 Battery Electrochemical Cell 4 Fault
1.1.11 Battery Electrochemical Cell 5 Fault
1.1.12 Battery Electrochemical Cell 6 Fault
1.1.13 Battery Electrochemical Cell 7 Fault
1.1.14 Battery Electrochemical Cell 8 Fault
1.1.15 Battery Electrochemical Cell 9 Fault
1.1.16 Battery Electrochemical Cell10 Fault
1.1.17 Battery Electrochemical Cell11 Fault
1.1.18 Battery Electrochemical Cell12 Fault
1.1.19 Battery Electrochemical Cell13 Fault
1.1.20 Battery Electrochemical Cell14 Fault
1.1.21 Battery Electrochemical Cell15 Fault
1.1.22 Battery Electrochemical Cell16 Fault
1.1.23 Address Conflict
1.1.24 Upgrade Failed
1.2 ESS
1.2.1 All ESMU Communication Failure
1.2.2 Battery Overvoltage

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,2/359(W)

1.2.3 Battery Undervoltage


1.2.4 Battery Overvoltage Protection
1.2.5 Battery Undervoltage Protection
1.2.6 High Temperature Protection
1.2.7 Low Temperature Protection
1.2.8 Charge Overcurrent Protection
1.2.9 Battery Discharge Overcurrent
1.2.10 Discharge Overcurrent Protection
1.2.11 Battery Charge Overcurrent
1.2.12 High Battery Temperature
1.2.13 Low Battery Temperature
1.2.14 BLVD Disconnected
1.2.15 Battery Fuse Break
1.2.16 Battery Temperature Sensor 1 Missing
1.2.17 Battery Temperature Sensor 2 Missing
1.2.18 Battery Temperature Sensor 1 Fault
1.2.19 Battery Temperature Sensor 2 Fault
1.3 24V Module
1.3.1 Module Fault
1.3.2 Module Communication Failure
1.3.3 Module Protection
1.4 24V Module Group
1.4.1 All Rectifiers Fail to Communicate
1.4.2 Module Missing
1.5 EFUSE
1.5.1 EFUSE Communication Failure
1.5.2 EFUSE Board Fault
1.5.3 Input Undervoltage
1.5.4 Input Overvoltage
1.5.5 Load 0 Overcurrent Protection
1.5.6 Load 1 Overcurrent Protection
1.5.7 Load 2 Overcurrent Protection
1.5.8 Load 3 Overcurrent Protection
1.5.9 Load 4 Overcurrent Protection
1.5.10 Load 5 Overcurrent Protection
1.5.11 Load 6 Overcurrent Protection
1.5.12 Load 7 Overcurrent Protection
1.5.13 Load 8 Overcurrent Protection
1.5.14 Load 9 Overcurrent Protection
1.5.15 Load 0 Branch Fault
1.5.16 Load 1 Branch Fault
1.5.17 Load 2 Branch Fault
1.5.18 Load 3 Branch Fault
1.5.19 Load 4 Branch Fault
1.5.20 Load 5 Branch Fault
1.5.21 Load 6 Branch Fault
1.5.22 Load 7 Branch Fault
1.5.23 Load 8 Branch Fault
1.5.24 Load 9 Branch Fault
1.5.25 Load 0 Disconnected
1.5.26 Load 1 Disconnected
1.5.27 Load 2 Disconnected

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,3/359(W)

1.5.28 Load 3 Disconnected


1.5.29 Load 4 Disconnected
1.5.30 Load 5 Disconnected
1.5.31 Load 6 Disconnected
1.5.32 Load 7 Disconnected
1.5.33 Load 8 Disconnected
1.5.34 Load 9 Disconnected
1.5.35 Load 0 Control Fault
1.5.36 Load 1 Control Fault
1.5.37 Load 2 Control Fault
1.5.38 Load 3 Control Fault
1.5.39 Load 4 Control Fault
1.5.40 Load 5 Control Fault
1.5.41 Load 6 Control Fault
1.5.42 Load 7 Control Fault
1.5.43 Load 8 Control Fault
1.5.44 Load 9 Control Fault
1.6 BIM
1.6.1 Communication Failure
1.7 CIM
1.7.1 Communication Failure
1.8 Rectifier
1.8.1 Rectifier Fault
1.8.2 Rectifier Protection
1.8.3 Rectifier Communication Failure
1.8.4 Rectifier Power Failure
1.8.5 Rectifier Overvoltage
1.8.6 Rectifier Phase Failure
1.8.7 Rectifier Address Abnormal
1.9 Rectifier Group
1.9.1 Rectifier Missing
1.9.2 Insufficient Redundant Rectifiers
1.9.3 Rectifier Fault (Redundant)
1.9.4 Rectifier Fault (Non-redundant)
1.9.5 Multi-Rectifier Fault
1.9.6 All Rectifiers Fail to Communicate
1.9.7 Rectifier Hibernation Activated
1.9.8 High Rectifier Capacity
1.9.9 Low Rectifier Capacity
1.9.10 Rectifier Upgrade Fault
1.10 SSU
1.10.1 Communication Failure
1.10.2 SSU Fault
1.10.3 SSU Protection
1.10.4 PV Array Fault
1.10.5 SSU Update Failed
1.11 SSU Summary
1.11.1 All SSU Communication Failure
1.11.2 SSU Lost
1.12 TCUC
1.12.1 Air Exhaust Vent Temperature Sensor Fault
1.12.2 Air Intake Vent Temperature Sensor Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,4/359(W)

1.12.3 External Fan 1 Fault


1.12.4 External Fan 2 Fault
1.12.5 Internal Fan 1 Fault
1.12.6 Internal Fan 2 Fault
1.12.7 INFAN3 Fault
1.12.8 INFAN4 Fault
1.12.9 Air Exhaust Vent Overtemperature Alarm
1.12.10 Air Exhaust Vent Undertemperature Alarm
1.12.11 Air Intake Vent Overtemperature Alarm
1.12.12 Air Intake Vent Undertemperature Alarm
1.12.13 TEC Fault
1.12.14 Door Alarm
1.12.15 Smoke Alarm
1.12.16 Water Alarm
1.12.17 Reserved IN0 Alarm
1.12.18 Reserved IN1 Alarm
1.12.19 Battery String 1 Cell1 Imbalance
1.12.20 Battery String 1 Cell2 Imbalance
1.12.21 Battery String 1 Cell3 Imbalance
1.12.22 Battery String 1 Cell4 Imbalance
1.12.23 Battery String 2 Cell1 Imbalance
1.12.24 Battery String 2 Cell2 Imbalance
1.12.25 Battery String 2 Cell3 Imbalance
1.12.26 Battery String 2 Cell4 Imbalance
1.12.27 Battery String 3 Cell1 Imbalance
1.12.28 Battery String 3 Cell2 Imbalance
1.12.29 Battery String 3 Cell3 Imbalance
1.12.30 Battery String 3 Cell4 Imbalance
1.12.31 Battery String 4 Cell1 Imbalance
1.12.32 Battery String 4 Cell2 Imbalance
1.12.33 Battery String 4 Cell3 Imbalance
1.12.34 Battery String 4 Cell4 Imbalance
1.12.35 TCUC Communication Failure
1.12.36 Battery String 1 Mid-Point Imbalance
1.12.37 Battery String 2 Mid-Point Imbalance
1.12.38 Battery String 3 Mid-Point Imbalance
1.12.39 Battery String 4 Mid-Point Imbalance
1.12.40 Return Vent Temperature Sensor Fault
1.12.41 Return Vent Overtemperature Alarm
1.12.42 Return Vent Undertemperature Alarm
1.12.43 Battery String 1 Missing
1.12.44 Battery String 2 Missing
1.12.45 Battery String 3 Missing
1.12.46 Battery String 4 Missing
1.13 Battery String
1.13.1 Battery Fuse Break
1.13.2 Battery Middle Voltage Imbalance
1.13.3 Battery Missing
1.13.4 Battery Cell1 Voltage Imbalance
1.13.5 Battery Cell2 Voltage Imbalance
1.13.6 Battery Cell3 Voltage Imbalance
1.13.7 Battery Cell4 Voltage Imbalance

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,5/359(W)

1.14 Battery Cabinet


1.14.1 Battery Cabinet Communication Failure
1.14.2 Battery Temperature Sensor Fault
1.14.3 Battery Temperature Sensor Missing
1.14.4 Fan 1 Fault
1.14.5 Fan 2 Fault
1.14.6 Fan 3 Fault
1.14.7 Fan 4 Fault
1.14.8 Battery Cabinet High Temperature
1.14.9 Indoor Return Vent Temperature Sensor Fault
1.14.10 Outdoor Temperature Sensor Fault
1.14.11 Cabinet Return Air Temperature Sensor Fault
1.14.12 Internal Fan Fault
1.14.13 Frequent High Pressure
1.14.14 Air Conditioner Communication Failure
1.14.15 External Fan Fault
1.14.16 Air Conditioner Compressor Fault
1.14.17 Air Conditioner Evaporator Frozen
1.14.18 Door Alarm
1.14.19 Battery Cabinet Temp Sensor Fault
1.14.20 Air Conditioner Missing
1.15 Batt. Cell Detector
1.15.1 Battery1 Cell1 Imbalance
1.15.2 Battery1 Cell2 Imbalance
1.15.3 Battery1 Cell3 Imbalance
1.15.4 Battery1 Cell4 Imbalance
1.15.5 Battery1 Cell5 Imbalance
1.15.6 Battery1 Cell6 Imbalance
1.15.7 Battery1 Cell7 Imbalance
1.15.8 Battery1 Cell8 Imbalance
1.15.9 Battery1 Cell9 Imbalance
1.15.10 Battery1 Cell10 Imbalance
1.15.11 Battery1 Cell11 Imbalance
1.15.12 Battery1 Cell12 Imbalance
1.15.13 Battery1 Cell13 Imbalance
1.15.14 Battery1 Cell14 Imbalance
1.15.15 Battery1 Cell15 Imbalance
1.15.16 Battery1 Cell16 Imbalance
1.15.17 Battery1 Cell17 Imbalance
1.15.18 Battery1 Cell18 Imbalance
1.15.19 Battery1 Cell19 Imbalance
1.15.20 Battery1 Cell20 Imbalance
1.15.21 Battery1 Cell21 Imbalance
1.15.22 Battery1 Cell22 Imbalance
1.15.23 Battery1 Cell23 Imbalance
1.15.24 Battery1 Cell24 Imbalance
1.15.25 Detector Communication Fail
1.15.26 Abnormal Voltage Check
1.15.27 Battery2 Cell1 Imbalance
1.15.28 Battery2 Cell2 Imbalance
1.15.29 Battery2 Cell3 Imbalance
1.15.30 Battery2 Cell4 Imbalance

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,6/359(W)

1.15.31 Battery2 Cell5 Imbalance


1.15.32 Battery2 Cell6 Imbalance
1.15.33 Battery2 Cell7 Imbalance
1.15.34 Battery2 Cell8 Imbalance
1.15.35 Battery3 Cell1 Imbalance
1.15.36 Battery3 Cell2 Imbalance
1.15.37 Battery3 Cell3 Imbalance
1.15.38 Battery3 Cell4 Imbalance
1.15.39 Battery4 Cell1 Imbalance
1.15.40 Battery4 Cell2 Imbalance
1.15.41 Battery4 Cell3 Imbalance
1.15.42 Battery4 Cell4 Imbalance
1.16 Battery Group
1.16.1 Battery High Temperature
1.16.2 Battery Low Temperature
1.16.3 Battery Temperature Sensor 1 Missing
1.16.4 Battery Temperature Sensor 2 Missing
1.16.5 Battery Temperature Sensor 1 Fault
1.16.6 Battery Temperature Sensor 2 Fault
1.16.7 Battery Equalized Charging
1.16.8 BLVD Disconnected
1.16.9 Battery Equalized Charging Protection
1.16.10 BLVD Warning
1.16.11 Battery Discharging
1.16.12 Battery Temperature Compensation Activated
1.16.13 Battery Not Detected
1.16.14 Battery Reversely Connection
1.16.15 Battery Very High Temperature
1.16.16 Battery Very Low Temperature
1.16.17 Battery Forcibly Connection
1.16.18 Battery Test Cancelled
1.16.19 Battery Current Imbalance
1.16.20 Battery Charge Overcurrent
1.16.21 Low Battery Capacity
1.16.22 Battery Breaker Trip
1.16.23 Battery Test Negative
1.16.24 Battery Undervoltage
1.16.25 Battery Cell Deterioration
1.16.26 Battery Thermal Runaway
1.16.27 Battery Imbalance
1.16.28 Insufficient Backup
1.16.29 Battery Sub-health
1.16.30 Battery Deterioration
1.17 Power System
1.17.1 AC Surge Protector Fault
1.17.2 DC SPD Fault
1.17.3 AC Failure
1.17.4 AC Phase L1 Overvoltage
1.17.5 AC Phase L2 Overvoltage
1.17.6 AC Phase L3 Overvoltage
1.17.7 AC Phase L1 Undervoltage
1.17.8 AC Phase L2 Undervoltage

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,7/359(W)

1.17.9 AC Phase L3 Undervoltage


1.17.10 AC Phase L1 Failure
1.17.11 AC Phase L2 Failure
1.17.12 AC Phase L3 Failure
1.17.13 AC Overvoltage
1.17.14 AC Undervoltage
1.17.15 DC Overvoltage
1.17.16 DC Undervoltage
1.17.17 DC Ultra Overvoltage
1.17.18 DC Ultra Undervoltage
1.17.19 Load Fuse Broken
1.17.20 Load Fuse1 Broken
1.17.21 Load Fuse2 Broken
1.17.22 Load Fuse3 Broken
1.17.23 Load Fuse4 Broken
1.17.24 Load Fuse5 Broken
1.17.25 Load Fuse6 Broken
1.17.26 Load Fuse7 Broken
1.17.27 Load Fuse8 Broken
1.17.28 Load Fuse9 Broken
1.17.29 Load Fuse10 Broken
1.17.30 Load Fuse11 Broken
1.17.31 Load Fuse12 Broken
1.17.32 Load Fuse13 Broken
1.17.33 Load Fuse14 Broken
1.17.34 Load Fuse15 Broken
1.17.35 Load Fuse16 Broken
1.17.36 Load Fuse17 Broken
1.17.37 Load Fuse18 Broken
1.17.38 Load Fuse19 Broken
1.17.39 Load Fuse20 Broken
1.17.40 Load Fuse21 Broken
1.17.41 Load Fuse22 Broken
1.17.42 Load Fuse23 Broken
1.17.43 SMU Fault
1.17.44 Insufficient Alarm Space
1.17.45 Very High Ambient Temperature
1.17.46 Unknown System Type
1.17.47 Door Open Alarm
1.17.48 Water Alarm
1.17.49 Smoke Alarm
1.17.50 High Ambient Temperature
1.17.51 Low Ambient Temperature
1.17.52 High Ambient Humidity
1.17.53 Low Ambient Humidity
1.17.54 Ambient Temperature Sensor Missing
1.17.55 Ambient Temperature Sensor Fault
1.17.56 Ambient Humidity Sensor Missing
1.17.57 Ambient Humidity Sensor Fault
1.17.58 LLVD Warning
1.17.59 LLVD Disconnected
1.17.60 LLVD2 Warning

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,8/359(W)

1.17.61 LLVD2 Disconnected


1.17.62 LLVD3 Warning
1.17.63 LLVD3 Disconnected
1.17.64 Long Mains Failure
1.17.65 Temp1 Sensor Missing
1.17.66 Temp2 Sensor Missing
1.17.67 Temp1 Sensor Fault
1.17.68 Temp2 Sensor Fault
1.17.69 Temp1 High Temperature
1.17.70 Temp2 High Temperature
1.17.71 Temp1 Low Temperature
1.17.72 Temp2 Low Temperature
1.17.73 DIN1 Alarm
1.17.74 DIN2 Alarm
1.17.75 DIN3 Alarm
1.17.76 DIN4 Alarm
1.17.77 DIN5 Alarm
1.17.78 DIN6 Alarm
1.17.79 DIN7 Alarm
1.17.80 DIN8 Alarm
1.17.81 TEC Alarm
1.17.82 Heater Fault
1.17.83 Abnormal System Voltage Check
1.17.84 Abnormal System Current Check
1.17.85 TCUA Alarm
1.17.86 Load Breaker Trip
1.17.87 Main AC Breaker Trip
1.17.88 DCD Comm Fail
1.17.89 AC Phase L1 Failure
1.17.90 AC Phase L2 Failure
1.17.91 AC Phase L3 Failure
1.17.92 AC L1-L2 Overvoltage
1.17.93 AC L2-L3 Overvoltage
1.17.94 AC L3-L1 Overvoltage
1.17.95 AC L1-L2 Undervoltage
1.17.96 AC L2-L3 Undervoltage
1.17.97 AC L3-L1 Undervoltage
1.17.98 Custom Alarm 1
1.17.99 Custom Alarm 2
1.17.100 Custom Alarm 3
1.17.101 Custom Alarm 4
1.17.102 Custom Alarm 5
1.17.103 Custom Alarm 6
1.17.104 Custom Alarm 7
1.17.105 Custom Alarm 8
1.17.106 Custom Alarm 9
1.17.107 Custom Alarm 10
1.17.108 Custom Alarm 11
1.17.109 Custom Alarm 12
1.17.110 Custom Alarm 13
1.17.111 Custom Alarm 14
1.17.112 Custom Alarm 15

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,9/359(W)

1.17.113 Custom Alarm 16


1.17.114 Custom Alarm 17
1.17.115 Custom Alarm 18
1.17.116 Custom Alarm 19
1.17.117 Custom Alarm 20
1.17.118 Power System Undervoltage
1.17.119 Power System Overvoltage
1.17.120 Vibration Alarm
1.17.121 Illegal Door Open
1.18 Electronic Lock
1.18.1 Communication Failure
1.19 Fan Group
1.19.1 Fan 1 Fault
1.19.2 Fan 2 Fault
1.19.3 Fan 3 Fault
1.19.4 Fan 4 Fault
1.20 Heater Device
1.20.1 Heater Fault
1.21 AC Ammeter
1.21.1 Communication Failure
1.22 AC Air Conditioner
1.22.1 Air Conditioner Fault
1.23 Camera
1.23.1 Communication Failure
1.24 NIM01C
1.24.1 Communication Failure
1.25 TCU
1.25.1 Hardware Fault
1.25.2 TCU Communicate Failure
1.25.3 Internal Circular Fan Fault
1.25.4 External Circular Fan Fault
1.25.5 Return Vent Temperature Sensor Fault
1.25.6 Exhaust Vent Temperature Sensor Fault
1.25.7 TCU High Temperature
1.25.8 TCU Low Temperature
1.25.9 Door Alarm
1.25.10 Water Alarm
1.25.11 Smoke Alarm
1.25.12 TEC Alarm
1.25.13 Heater Fault
1.26 Temperature Control Group
1.26.1 Indoor Return Vent Temperature Sensor Missing
1.26.2 Outdoor Temperature Sensor Missing
1.26.3 Indoor Return Vent Temperature Sensor Fault
1.26.4 Outdoor Temperature Sensor Fault
1.26.5 Indoor Vent High Temperature
1.26.6 Air Conditioner Missing
1.26.7 System Noise Too Loud
1.27 Li-ion Battery
1.27.1 Module Communication Failure
1.27.2 Module Fault
1.27.3 Module Protection

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,10/359(W)

1.27.4 Module Minor Alarm


1.28 Min-Li-ion Battery
1.28.1 Battery Fuse Break
1.28.2 BLVD Disconnected
1.28.3 BLVD Warning
1.28.4 Battery Forcibly Connection
1.28.5 Battery Discharging
1.28.6 Battery Temperature Sensor 1 Fault
1.28.7 Battery Temperature Sensor 2 Fault
1.28.8 Battery High Temperature
1.28.9 Battery Low Temperature
1.28.10 Battery Temperature Sensor 1 Missing
1.28.11 Battery Temperature Sensor 2 Missing
1.29 Diesel Generator
1.29.1 Diesel Generator Start Fault
1.29.2 Diesel Generator Stop Fault
1.29.3 ATS Fault
1.30 DC Ammeter
1.30.1 Communicate Failure
1.31 Int. A/C
1.31.1 Internal Fan Fault
1.31.2 External Fan Fault
1.31.3 Compressor Fault
1.31.4 Cabinet Return Air Temperature Sensor Fault
1.31.5 Evaporator Frozen
1.31.6 Frequent High Pressure
1.31.7 Communicate Failure
1.32 AIM
1.32.1 Communicate Failure
1.32.2 Hardware Fault

1 Site Alarm Reference


ESMU

ESS

24V Module

24V Module Group

EFUSE

BIM

CIM

Rectifier

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,11/359(W)

Rectifier Group

SSU

SSU Summary

TCUC

Battery String

Battery Cabinet

Batt. Cell Detector

Battery Group

Power System

Electronic Lock

Fan Group

Heater Device

AC Ammeter

AC Air Conditioner

Camera

NIM01C

TCU

Temperature Control Group

Li-ion Battery

Min-Li-ion Battery

Diesel Generator

DC Ammeter

Int. A/C

AIM

Parent topic: SMU02B V300R003C00

1.1 ESMU

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,12/359(W)

Communication Failure

Board Hardware Fault

Discharge High Temperature Protection

Charge High Temperature Protection

Overcharge Protection

Overdischarge Protection

Battery Electrochemical Cell 1 Fault

Battery Electrochemical Cell 2 Fault

Battery Electrochemical Cell 3 Fault

Battery Electrochemical Cell 4 Fault

Battery Electrochemical Cell 5 Fault

Battery Electrochemical Cell 6 Fault

Battery Electrochemical Cell 7 Fault

Battery Electrochemical Cell 8 Fault

Battery Electrochemical Cell 9 Fault

Battery Electrochemical Cell10 Fault

Battery Electrochemical Cell11 Fault

Battery Electrochemical Cell12 Fault

Battery Electrochemical Cell13 Fault

Battery Electrochemical Cell14 Fault

Battery Electrochemical Cell15 Fault

Battery Electrochemical Cell16 Fault

Address Conflict

Upgrade Failed

Parent topic: Site Alarm Reference

1.1.1 Communication Failure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,13/359(W)

Description
This alarm is generated when the SMU fails to communicate with the device.

Attribute

Alarm ID Alarm Severity Alarm Type

13750 Minor ADAC

Impact on the System


The SMU cannot monitor the device.

Possible Causes
The device is faulty.
The communication cable is disconnected from the device.

Procedure
1. Check whether the device is powered on and works properly.
If yes, go to the next step.
If no, contact Huawei technical support.

2. Check whether the communication cable is disconnected from the device or loose.
If yes, reconnect the communication cable properly.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.2 Board Hardware Fault


Description
This alarm is generated when the SMU receives a fault alarm from the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13752 Major ADAC

Impact on the System


The device fails to work properly.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,14/359(W)

Possible Causes
The device is faulty.

Procedure
1. Replace the involved device, and check whether the alarm is cleared.

If yes, no further action is required.


If no, contact Huawei technical support.

Parent topic: ESMU

1.1.3 Discharge High Temperature


Protection
Description
This alarm is generated when the SMU receives a fault alarm from the ESMU due to
battery overtemperature.

Attribute

Alarm ID Alarm Severity Alarm Type

13757 Minor ADAC

Impact on the System


The power supply to the site may be disconnected because the power system may have
insufficient loading capacity.

Possible Causes
The battery temperature exceeds the upper threshold.
The device is faulty.

Procedure
1. Check whether the temperature control devices such as the fan and air conditioner
in the battery compartment are abnormal.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,15/359(W)

If no, contact Huawei technical support.

Parent topic: ESMU

1.1.4 Charge High Temperature Protection


Description
This alarm is generated when the SMU receives a fault alarm from the ESMU due to
battery overtemperature.

Attribute

Alarm ID Alarm Severity Alarm Type

13759 Minor ADAC

Impact on the System


The power supply to the site may be disconnected because the power system may have
insufficient loading capacity.

Possible Causes
The battery temperature exceeds the upper threshold.
The device is faulty.

Procedure
1. Check whether the temperature control devices such as the fan and air conditioner
in the battery compartment are abnormal.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.5 Overcharge Protection

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,16/359(W)

Description
This alarm is generated when the electrochemical cell voltage or battery string voltage
exceeds the overvoltage protection threshold during battery charge.

Attribute

Alarm ID Alarm Severity Alarm Type

13761 Minor ADAC

Impact on the System


Power backup is affected because the battery string fails to work properly.

Possible Causes
The battery voltage exceeds the upper threshold.
The device is faulty.

Procedure
1. Rectify the rectifier faults and check whether the alarm is cleared.
If yes, no further action is required.
If no, go to the next step.

2. Charge the battery and check whether the alarm is cleared and battery backup time
is normal.
If yes, no further action is required.
If no, go to the next step.

3. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.6 Overdischarge Protection


Description
This alarm is generated when the electrochemical cell voltage or battery string voltage
is below the undervoltage protection threshold during battery discharge.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,17/359(W)

Alarm ID Alarm Severity Alarm Type

13763 Minor ADAC

Impact on the System


Power backup is affected because the battery string fails to work properly.

Possible Causes
The battery voltage is below the lower threshold.
The device is faulty.

Procedure
1. Check whether the AC input is abnormal.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.7 Battery Electrochemical Cell 1 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13768 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,18/359(W)

If no, contact Huawei technical support.

Parent topic: ESMU

1.1.8 Battery Electrochemical Cell 2 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13769 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.9 Battery Electrochemical Cell 3 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,19/359(W)

13770 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.10 Battery Electrochemical Cell 4 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13771 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,20/359(W)

1.1.11 Battery Electrochemical Cell 5 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13772 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.12 Battery Electrochemical Cell 6 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13773 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,21/359(W)

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.13 Battery Electrochemical Cell 7 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13774 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.14 Battery Electrochemical Cell 8 Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,22/359(W)

Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13775 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.15 Battery Electrochemical Cell 9 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13776 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,23/359(W)

1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.16 Battery Electrochemical Cell10 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13777 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.17 Battery Electrochemical Cell11 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,24/359(W)

Alarm ID Alarm Severity Alarm Type

13778 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.18 Battery Electrochemical Cell12 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13779 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,25/359(W)

Parent topic: ESMU

1.1.19 Battery Electrochemical Cell13 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13780 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.20 Battery Electrochemical Cell14 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13781 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,26/359(W)

The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.21 Battery Electrochemical Cell15 Fault


Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13782 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.22 Battery Electrochemical Cell16 Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,27/359(W)

Description
When detecting a fault in an electrochemical cell, the SMU receives a fault alarm from
the ESMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13783 Major ADAC

Impact on the System


The battery fails to work properly due to the faulty electrochemical cell.

Possible Causes
The electrochemical cell is faulty.

Procedure
1. Replace the involved battery, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.23 Address Conflict


Description
If multiple ESMU devices have the same hardware address DIP switch setting, the
SMU generates an Address Conflict alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13784 Minor ADAC

Impact on the System


During onsite operation, the corresponding relationship between the displayed and the
actual physical devices is indistinguishable.

Possible Causes
Multiple ESMU devices have the same hardware address DIP switch setting.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,28/359(W)

Procedure
1. Check whether the hardware DIP switch settings of the involved devices conflict.
If yes, reset the hardware DIP switch.
If no, contact Huawei technical support.

Parent topic: ESMU

1.1.24 Upgrade Failed


Description
This alarm is generated when the upgrade failed.

Attribute

Alarm ID Alarm Severity Alarm Type

13785 Major ADAC

Impact on the System


The ESMU continues to run the previous software version due to upgrade failure.

Possible Causes
The upgrade package is incorrect.
The SMU experiences a communication failure during upgrade.

Procedure
1. Check whether the upgrade package is faulty.
If yes, replace the upgrade package.
If no, contact Huawei technical support.

Parent topic: ESMU

1.2 ESS
All ESMU Communication Failure

Battery Overvoltage

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,29/359(W)

Battery Undervoltage

Battery Overvoltage Protection

Battery Undervoltage Protection

High Temperature Protection

Low Temperature Protection

Charge Overcurrent Protection

Battery Discharge Overcurrent

Discharge Overcurrent Protection

Battery Charge Overcurrent

High Battery Temperature

Low Battery Temperature

BLVD Disconnected

Battery Fuse Break

Battery Temperature Sensor 1 Missing

Battery Temperature Sensor 2 Missing

Battery Temperature Sensor 1 Fault

Battery Temperature Sensor 2 Fault

Parent topic: Site Alarm Reference

1.2.1 All ESMU Communication Failure


Description
This alarm is generated when the SMU fails to communicate with all devices.

Attribute

Alarm ID Alarm Severity Alarm Type

13800 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,30/359(W)

The SMU cannot monitor all device.

Possible Causes
The communication cables are disconnected from all devices.
All devices are faulty.

Procedure
1. Check the ESMU operation.
2. Check whether the communication cables are disconnected from all devices or
loose.
If yes, reconnect the communication cables properly.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.2 Battery Overvoltage


Description
This alarm is generated if any ESMU battery is overvoltage.

Attribute

Alarm ID Alarm Severity Alarm Type

13802 Major ADAC

Impact on the System


The battery performance may deteriorate, and the battery lifespan may be shortened.

Possible Causes
The battery voltage exceeds the upper threshold.
The device is faulty.

Procedure
1. Check whether the DC voltage is normal.
2. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,31/359(W)

Parent topic: ESS

1.2.3 Battery Undervoltage


Description
This alarm is generated if any ESMU battery is undervoltage.

Attribute

Alarm ID Alarm Severity Alarm Type

13803 Major ADAC

Impact on the System


The battery performance may deteriorate, and the battery lifespan may be shortened.

Possible Causes
The battery overdischarging causes battery undervoltage.
The device is faulty.

Procedure
1. Check whether the AC voltage is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.4 Battery Overvoltage Protection


Description
This alarm is generated if any ESMU battery is overvoltage and the metal oxide
semiconductor is disconnected.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,32/359(W)

Alarm ID Alarm Severity Alarm Type

13804 Major ADAC

Impact on the System


The battery is ejected. The power supply to the site may be disconnected because the
power system may have insufficient loading capacity.

Possible Causes
The battery voltage exceeds the upper threshold.
The device is faulty.

Procedure
1. Check whether the DC voltage is normal.
2. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.5 Battery Undervoltage Protection


Description
This alarm is generated if any ESMU battery is undervoltage and the metal oxide
semiconductor is disconnected.

Attribute

Alarm ID Alarm Severity Alarm Type

13805 Major ADAC

Impact on the System


The battery is ejected. The power supply to the site may be disconnected because the
power system may have insufficient loading capacity.

Possible Causes
The battery voltage is below the lower threshold.
The device is faulty.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,33/359(W)

Procedure
1. Check whether the AC voltage is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.6 High Temperature Protection


Description
This alarm is generated if any ESMU battery is overtemperature and the metal oxide
semiconductor is disconnected

Attribute

Alarm ID Alarm Severity Alarm Type

13806 Major ADAC

Impact on the System


The battery is ejected. The power supply to the site may be disconnected because the
power system may have insufficient loading capacity.

Possible Causes
The battery temperature exceeds the upper threshold.
The device is faulty.

Procedure
1. Check whether the temperature control devices such as the fan and air conditioner
in the battery compartment are abnormal.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,34/359(W)

If no, contact Huawei technical support.

Parent topic: ESS

1.2.7 Low Temperature Protection


Description
This alarm is generated if any ESMU battery is undertemperature and the metal oxide
semiconductor is disconnected.

Attribute

Alarm ID Alarm Severity Alarm Type

13807 Major ADAC

Impact on the System


The battery is ejected. The power supply to the site may be disconnected because the
power system may have insufficient loading capacity.

Possible Causes
The battery temperature is below the lower threshold.
The device is faulty.

Procedure
1. Check whether the temperature control devices such as the fan and air conditioner
in the battery compartment are abnormal.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.8 Charge Overcurrent Protection

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,35/359(W)

Description
This alarm is generated if any ESMU battery is charge overcurrent and the metal oxide
semiconductor is disconnected.

Attribute

Alarm ID Alarm Severity Alarm Type

13808 Major ADAC

Impact on the System


The battery is ejected. The power supply to the site may be disconnected because the
power system may have insufficient loading capacity.

Possible Causes
The battery charging current exceeds the upper threshold.
The device is faulty.

Procedure
1. Check whether a rectifier of the upstream power device is faulty.
If yes, repair the faulty rectifier.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.9 Battery Discharge Overcurrent


Description
This alarm is generated if any ESMU battery discharging current exceeds the upper
threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

13809 Major ADAC

Impact on the System


The battery performance may deteriorate, and the battery lifespan may be shortened.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,36/359(W)

The battery discharging current exceeds the upper threshold.


The device is faulty.

Procedure
1. Check whether the load current is too large or the battery configurations are
incorrect.
If yes, add batteries for an appropriate power backup.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.10 Discharge Overcurrent Protection


Description
This alarm is generated if any ESMU battery is discharge overcurrent and the metal
oxide semiconductor is disconnected.

Attribute

Alarm ID Alarm Severity Alarm Type

13810 Major ADAC

Impact on the System


The battery is ejected. The power supply to the site may be disconnected because the
power system may have insufficient loading capacity.

Possible Causes
The battery discharging current exceeds the upper threshold.
The device is faulty.

Procedure
1. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,37/359(W)

1.2.11 Battery Charge Overcurrent


Description
This alarm is generated if any ESMU battery charging current exceeds the upper
threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

13811 Major ADAC

Impact on the System


The battery performance may deteriorate, and the battery lifespan may be shortened.

Possible Causes
The battery charging current exceeds the upper threshold.
The device is faulty.

Procedure
1. Reset the ESMU device, and then check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.12 High Battery Temperature


Description
This alarm is generated when the battery temperature exceeds the high temperature
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

13812 Minor ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,38/359(W)

The battery performance may deteriorate, and the battery lifespan may be shortened.

Possible Causes
The battery temperature exceeds the upper threshold.
The battery high temperature alarm threshold is incorrectly set.
The temperature sensor is faulty.

Procedure
1. Check whether the temperature control devices such as the fan and air conditioner
in the battery compartment are abnormal.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Check whether the battery high temperature alarm threshold is incorrectly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the battery temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.13 Low Battery Temperature


Description
This alarm is generated when the battery temperature is below the low temperature
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

13813 Minor ADAC

Impact on the System


The battery performance may deteriorate, and the battery lifespan may be shortened.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,39/359(W)

The battery temperature is below the lower threshold.


The battery low temperature alarm threshold is incorrectly set.
The temperature sensor is faulty.

Procedure
Check whether the ambient temperature is too low. If the temperature is too low, take
heating measures. If heating measures are unavailable, modify the low temperature
alarm threshold.

1. Check whether the temperature control devices in the battery compartment are
abnormal, such as the fan and air conditioner.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Check whether the battery low temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the battery temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.14 BLVD Disconnected


Description
When detecting that batteries are disconnected, the SMU generates a BLVD
Disconnected alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13814 Major ADAC

Impact on the System


Power backup is compromised and the system may be disconnected.

Possible Causes
The AC power failure is too long.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,40/359(W)

The battery temperature exceeds the upper threshold.

Procedure
1. Check whether the AC power failure is too long.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Check whether a Very High Battery Temperature alarm is generated and


temperature control devices in the battery compartment are abnormal, such as the
fan and air conditioner.
If yes, maintain the temperature control devices.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.15 Battery Fuse Break


Description
This alarm is generated when the battery fuse is blown or the battery circuit breaker is
OFF.

Attribute

Alarm ID Alarm Severity Alarm Type

13816 Critical ADAC

Impact on the System


The power system fails to back up power because a battery fuse is blown.

Possible Causes
The battery fuse is blown or the battery circuit breaker is OFF.

Procedure
1. Check whether the battery fuse is blown or the battery circuit breaker is OFF.
If yes, close the circuit breaker.
If no, go to the next step.

2. Check whether the battery fuse detection cable is disconnected.


If yes, secure the cable.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,41/359(W)

If no, contact Huawei technical support.

Parent topic: ESS

1.2.16 Battery Temperature Sensor 1


Missing
Description
This alarm is generated when the sensor detects an open-circuit status.

Attribute

Alarm ID Alarm Severity Alarm Type

13817 Warning ADAC

Impact on the System


Battery temperatures cannot be monitored. The batteries need temperature
compensation, which may shorten the battery lifespan.

Possible Causes
The sensor is disconnected.
The sensor connector is loose.
The sensor is faulty.

Procedure
1. Check whether the sensor is disconnected.
If yes, install the sensor.
If no, go to the next step.

2. Check whether the sensor connector is loose.


If yes, secure the connector.
If no, go to the next step.

3. Replace the sensor and check whether the alarm is cleared.


If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,42/359(W)

1.2.17 Battery Temperature Sensor 2


Missing
Description
This alarm is generated when the sensor detects an open-circuit status.

Attribute

Alarm ID Alarm Severity Alarm Type

13818 Warning ADAC

Impact on the System


Battery temperatures cannot be monitored. The batteries need temperature
compensation, which may shorten the battery lifespan.

Possible Causes
The sensor is disconnected.
The sensor connector is loose.
The sensor is faulty.

Procedure
1. Check whether the sensor is disconnected.
If yes, install the sensor.
If no, go to the next step.

2. Check whether the sensor connector is loose.


If yes, secure the connector.
If no, go to the next step.

3. Replace the sensor and check whether the alarm is cleared.


If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.18 Battery Temperature Sensor 1 Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,43/359(W)

Description
This alarm is generated when the sensor detects a short-circuit status.

Attribute

Alarm ID Alarm Severity Alarm Type

13819 Major ADAC

Impact on the System


Battery temperatures cannot be monitored. The batteries need temperature
compensation, which may shorten the battery lifespan.

Possible Causes
The sensor is faulty.

Procedure
1. Replace the sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.2.19 Battery Temperature Sensor 2 Fault


Description
This alarm is generated when the sensor detects a short-circuit status.

Attribute

Alarm ID Alarm Severity Alarm Type

13820 Major ADAC

Impact on the System


Battery temperatures cannot be monitored. The batteries need temperature
compensation, which may shorten the battery lifespan.

Possible Causes
The sensor is faulty.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,44/359(W)

Procedure
1. Replace the sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: ESS

1.3 24V Module


Module Fault

Module Communication Failure

Module Protection

Parent topic: Site Alarm Reference

1.3.1 Module Fault


Description
This alarm is generated when the 24 V module is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

8700 Major ADAC

Impact on the System


The device fails to work properly.

Possible Causes
The device is faulty.

Procedure
1. Replace the faulty device.
If no, no further action is required.
If yes, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,45/359(W)

Parent topic: 24V Module

1.3.2 Module Communication Failure


Description
This alarm is generated when the SMU fails in communication.

Attribute

Alarm ID Alarm Severity Alarm Type

8701 Minor ADAC

Impact on the System


The SMU cannot monitor devices.

Possible Causes
The device is removed.
The device is faulty.
The device connection is loose.

Procedure
1. Check whether the faulty device is removed.
If yes, reinstall the device.
If no, go to the next step.

2. Reset the SMU and check whether the alarm persists.


If no, no further action is required.
If yes, go to the next step.

3. Check whether the device works properly.


If yes, contact Huawei technical support.
If no, replace the device.

Parent topic: 24V Module

1.3.3 Module Protection

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,46/359(W)

Description
This alarm is generated when the device is protected.

Attribute

Alarm ID Alarm Severity Alarm Type

8702 Minor ADAC

Impact on the System


The device fails to work properly.

Possible Causes
The device is faulty or protected due to other alarms.

Procedure
1. Check whether the AC input voltage is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Replace the device for which the protection alarm is generated and check whether
the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: 24V Module

1.4 24V Module Group


All Rectifiers Fail to Communicate

Module Missing

Parent topic: Site Alarm Reference

1.4.1 All Rectifiers Fail to Communicate


Description
This alarm is generated when the SMU fails to communicate with all rectifiers.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,47/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

8750 Major ADAC

Impact on the System


The SMU cannot monitor devices.

Possible Causes
The device is removed.
The device is faulty.
The device connection is loose.

Procedure
1. Check whether the faulty device is removed.
If yes, reinstall the device.
If no, go to the next step.

2. Reset the SMU and check whether the alarm persists.


If no, no further action is required.
If yes, go to the next step.

3. Check whether the device works properly.


If yes, contact Huawei technical support.
If no, replace the device.

Parent topic: 24V Module Group

1.4.2 Module Missing


Description
This alarm is generated when the SMU detects that certain devices are missing after the
SMU restarts.

Attribute

Alarm ID Alarm Severity Alarm Type

8752 Major ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,48/359(W)

Impact on the System


The power supply to the site may be disconnected because the power system may
supply insufficient power.

Possible Causes
The device is missing.
The device is faulty.

Procedure
1. Check whether a device is removed.
If yes, reinstall the device.
If no, go to the next step.

2. Check whether a device fails to work properly.


If yes, replace the device.
If no, contact Huawei technical support.

Parent topic: 24V Module Group

1.5 EFUSE
EFUSE Communication Failure

EFUSE Board Fault

Input Undervoltage

Input Overvoltage

Load 0 Overcurrent Protection

Load 1 Overcurrent Protection

Load 2 Overcurrent Protection

Load 3 Overcurrent Protection

Load 4 Overcurrent Protection

Load 5 Overcurrent Protection

Load 6 Overcurrent Protection

Load 7 Overcurrent Protection

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,49/359(W)

Load 8 Overcurrent Protection

Load 9 Overcurrent Protection

Load 0 Branch Fault

Load 1 Branch Fault

Load 2 Branch Fault

Load 3 Branch Fault

Load 4 Branch Fault

Load 5 Branch Fault

Load 6 Branch Fault

Load 7 Branch Fault

Load 8 Branch Fault

Load 9 Branch Fault

Load 0 Disconnected

Load 1 Disconnected

Load 2 Disconnected

Load 3 Disconnected

Load 4 Disconnected

Load 5 Disconnected

Load 6 Disconnected

Load 7 Disconnected

Load 8 Disconnected

Load 9 Disconnected

Load 0 Control Fault

Load 1 Control Fault

Load 2 Control Fault

Load 3 Control Fault

Load 4 Control Fault

Load 5 Control Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,50/359(W)

Load 6 Control Fault

Load 7 Control Fault

Load 8 Control Fault

Load 9 Control Fault

Parent topic: Site Alarm Reference

1.5.1 EFUSE Communication Failure


Description
This alarm is generated when the SMU fails to communicate with the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8400 Major ADAC

Impact on the System


The SMU cannot monitor devices.

Possible Causes
The communications cable is disconnected from the device.
The device is faulty.

Procedure
1. Check whether the communications cable is disconnected from the device.
If yes, reconnect the communications cable.
If no, go to the next step.

2. Reset the SMU and check whether the system works properly.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,51/359(W)

1.5.2 EFUSE Board Fault


Description
This alarm is generated when the SMU receives a component fault alarm from the
EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8457 Major ADAC

Impact on the System


The device fails to work properly.

Possible Causes
The device is faulty.

Procedure
1. Replace the faulty device.

Parent topic: EFUSE

1.5.3 Input Undervoltage


Description
This alarm is generated when the EFUSE input voltage is below the input undervoltage
threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8401 Minor ADAC

Impact on the System


The device experiences undervoltage.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,52/359(W)

The busbar voltage is below the lower threshold.


The device is faulty.

Procedure
1. Check whether the input voltage is collected in a normal way and below the
undervoltage alarm threshold.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.4 Input Overvoltage


Description
This alarm is generated when the EFUSE input voltage exceeds the input overvoltage
threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8402 Minor ADAC

Impact on the System


The device works in overvoltage condition.

Possible Causes
The busbar voltage is exceeds the upper threshold.
The device is faulty.

Procedure
1. Check whether the input voltage is collected in a normal way and above the
overvoltage alarm threshold.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,53/359(W)

1.5.5 Load 0 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8405 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,54/359(W)

1.5.6 Load 1 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8406 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,55/359(W)

1.5.7 Load 2 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8407 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,56/359(W)

1.5.8 Load 3 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8408 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,57/359(W)

1.5.9 Load 4 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

7859 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,58/359(W)

1.5.10 Load 5 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8410 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,59/359(W)

1.5.11 Load 6 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8411 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,60/359(W)

1.5.12 Load 7 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8412 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,61/359(W)

1.5.13 Load 8 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8413 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,62/359(W)

1.5.14 Load 9 Overcurrent Protection


Description
This alarm is generated when the EFUSE output current exceeds 1.2 times the load
overcurrent threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

8414 Major ADAC

Impact on the System


The load route protects against overcurrent and power supply to the load will be
disconnected.

Possible Causes
The load current exceeds the upper threshold.
The overcurrent threshold is not properly set.
The device is faulty.

Procedure
1. Check whether the load overcurrent threshold is not properly set.
If yes, reset the overcurrent threshold.
If no, go to the next step.

2. Power on the load by pressing the button on the panel or setting a manual control
mode on the SMU. Then check whether the load current exceeds 1.2 times the load
overcurrent threshold.
If yes, no further action is required.
If no, go to the next step.

3. Check whether overcurrent protection occurs again.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,63/359(W)

1.5.15 Load 0 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8468 Minor ADAC

Impact on the System


The route fails to work properly.

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

1.5.16 Load 1 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8469 Minor ADAC

Impact on the System


The route fails to work properly.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,64/359(W)

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

1.5.17 Load 2 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8470 Minor ADAC

Impact on the System


The route fails to work properly.

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,65/359(W)

1.5.18 Load 3 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8471 Minor ADAC

Impact on the System


The route fails to work properly.

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

1.5.19 Load 4 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8472 Minor ADAC

Impact on the System


The route fails to work properly.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,66/359(W)

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

1.5.20 Load 5 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8473 Minor ADAC

Impact on the System


The route fails to work properly.

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,67/359(W)

1.5.21 Load 6 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8474 Minor ADAC

Impact on the System


The route fails to work properly.

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

1.5.22 Load 7 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8475 Minor ADAC

Impact on the System


The route fails to work properly.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,68/359(W)

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

1.5.23 Load 8 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8476 Minor ADAC

Impact on the System


The route fails to work properly.

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,69/359(W)

1.5.24 Load 9 Branch Fault


Description
This alarm is generated when the SMU receives a route fault alarm from the EFUSE.

Attribute

Alarm ID Alarm Severity Alarm Type

8477 Minor ADAC

Impact on the System


The route fails to work properly.

Possible Causes
The load route is faulty.
The device is faulty.

Procedure
1. Check whether load cables are connected in compliance with specifications.
If yes, contact Huawei technical support.
If no, connect load cables according to specifications.

Parent topic: EFUSE

1.5.25 Load 0 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8478 Major ADAC

Impact on the System


The load is disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,70/359(W)

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.26 Load 1 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8479 Major ADAC

Impact on the System


The load is disconnected.

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,71/359(W)

1.5.27 Load 2 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8480 Major ADAC

Impact on the System


The load is disconnected.

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.28 Load 3 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8481 Major ADAC

Impact on the System


The load is disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,72/359(W)

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.29 Load 4 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8482 Major ADAC

Impact on the System


The load is disconnected.

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,73/359(W)

1.5.30 Load 5 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8483 Major ADAC

Impact on the System


The load is disconnected.

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.31 Load 6 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8484 Major ADAC

Impact on the System


The load is disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,74/359(W)

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.32 Load 7 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8485 Major ADAC

Impact on the System


The load is disconnected.

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,75/359(W)

1.5.33 Load 8 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8486 Major ADAC

Impact on the System


The load is disconnected.

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.34 Load 9 Disconnected


Description
This alarm is generated when the SMU disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8487 Major ADAC

Impact on the System


The load is disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,76/359(W)

Possible Causes
The battery voltage has dropped to the load low voltage disconnection (LLVD) voltage
after a continuous AC power failure.

Procedure
1. Check whether the battery voltage drops to the LLVD voltage after a continuous
AC power failure.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.35 Load 0 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8488 Major ADAC

Impact on the System


The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,77/359(W)

1.5.36 Load 1 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8489 Major ADAC

Impact on the System


The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.37 Load 2 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8490 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,78/359(W)

The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.38 Load 3 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8491 Major ADAC

Impact on the System


The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,79/359(W)

1.5.39 Load 4 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8492 Major ADAC

Impact on the System


The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.40 Load 5 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8493 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,80/359(W)

The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.41 Load 6 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8494 Major ADAC

Impact on the System


The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,81/359(W)

1.5.42 Load 7 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8495 Major ADAC

Impact on the System


The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.43 Load 8 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8496 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,82/359(W)

The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

1.5.44 Load 9 Control Fault


Description
This alarm is generated when the SMU detects that the actual load status is different
from the state under control after the SMU connects or disconnects a load route.

Attribute

Alarm ID Alarm Severity Alarm Type

8497 Major ADAC

Impact on the System


The load cannot be correctly connected or disconnected.

Possible Causes
The load status is controlled by the button on the panel.
The device is faulty.

Procedure
1. Check whether the load status is controlled by the button on the panel.
If yes, manually connect or disconnect the load.
If no, contact Huawei technical support.

Parent topic: EFUSE

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,83/359(W)

1.6 BIM
Communication Failure

Parent topic: Site Alarm Reference

1.6.1 Communication Failure


Description
This alarm is generated when an BIM fails to communicate with the SMU.

Attribute

Alarm ID Alarm Severity Alarm Type

14350 Major ADAC

Impact on the System


The SMU fails to detect the information of the components connected to the BIM, such
as the camera and electronic door lock. If wireless networking is used, the site
information cannot be monitored remotely.

Possible Causes
The communication cable is disconnected from the device or loose.
The BIM is faulty.

Procedure
1. Check whether the communication cable is properly connected.
If yes, go to the next step.
If yes, reconnect the communication cable.

2. Replace the involved BIM, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: BIM

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,84/359(W)

1.7 CIM
Communication Failure

Parent topic: Site Alarm Reference

1.7.1 Communication Failure


Description
This alarm is generated when an CIM fails to communicate with the SMU.

Attribute

Alarm ID Alarm Severity Alarm Type

14250 Major ADAC

Impact on the System


The SMU fails to detect the information of the components connected to the CIM.

Possible Causes
The communication cable is disconnected from the device or loose.
The CIM is faulty.

Procedure
1. Check whether the communication cable is properly connected.
If yes, go to the next step.
If yes, reconnect the communication cable.

2. Replace the involved CIM, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: CIM

1.8 Rectifier

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,85/359(W)

Rectifier Fault

Rectifier Protection

Rectifier Communication Failure

Rectifier Power Failure

Rectifier Overvoltage

Rectifier Phase Failure

Rectifier Address Abnormal

Parent topic: Site Alarm Reference

1.8.1 Rectifier Fault


Description
When detecting that a rectifier is faulty, the SMU generates a Rectifier Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

1604 Major ADAC

Impact on the System


The rectifier fails to work.

Possible Causes
The rectifier is faulty.

Procedure
1. Replace the rectifier whose indicator is red and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Rectifier

1.8.2 Rectifier Protection

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,86/359(W)

Description
When detecting that rectifiers are protected, the SMU generates a Rectifier Protection
alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

1603 Minor ADAC

Impact on the System


Rectifiers cannot supply power after protected.

Possible Causes
AC overvoltage occurs.
AC undervoltage occurs.
Certain rectifiers are faulty.

Procedure
1. Check whether the AC input voltage is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Replace the rectifiers for which the protection alarm is generated and check
whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Rectifier

1.8.3 Rectifier Communication Failure


Description
When detecting that the communication to a rectifier fails, the SMU generates a
Rectifier Communication Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

1602 Minor ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,87/359(W)

Impact on the System


The SMU fails to control the rectifier that fails in communication.

Possible Causes
The rectifier is removed.
The rectifier is faulty.

Procedure
1. Check whether the rectifier is removed.
If yes, reinstall the rectifier.
If no, go to the next step.

2. Replace the rectifier and check whether the alarm persists.


If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Rectifier

1.8.4 Rectifier Power Failure


Description
When detecting that the AC input to a rectifier fails, the SMU generates a Rectifier
Power Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

1607 Major ADAC

Impact on the System


The rectifier fails to work because the power supply to it is disconnected.

Possible Causes
The rectifier is faulty.
The power system has a rectifier circuit breaker and the circuit breaker is OFF.

Procedure
1. Replace the rectifier for which the alarm is generated and check whether the alarm

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,88/359(W)

persists.
If no, no further action is required.
If yes, go to the next step.

2. Check whether the power system has a rectifier circuit breaker and the circuit
breaker is OFF.
If yes, switch on the circuit breaker.
If no, contact Huawei technical support.

Parent topic: Rectifier

1.8.5 Rectifier Overvoltage


Description
When detecting that the rectifier output voltage exceeds the overvoltage alarm
threshold, the SMU generates a Rectifier Overvoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

1608 Major ADAC

Impact on the System


The rectifier fails to work because it experiences overvoltage.

Possible Causes
The rectifier is faulty.

Procedure
1. Replace the rectifier for which the alarm is generated and check whether the alarm
persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Rectifier

1.8.6 Rectifier Phase Failure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,89/359(W)

Description
This alarm is generated when the SMU detects that a phase is open for a rectifier that
supports three-phase input.

Attribute

Alarm ID Alarm Severity Alarm Type

1609 Major ADAC

Impact on the System


The rectifier fails to deliver output properly and the output power of the power system
decreases.

Possible Causes
The AC input on a phase is abnormal.

Procedure
1. Check whether the phase voltage for phase L1, L2, or L3 is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Check whether the circuit breaker for phase L1, L2, or L3 is OFF.
If yes, check and repair the AC power distribution, and then switch on the circuit
breaker.
If no, contact Huawei technical support.

Parent topic: Rectifier

1.8.7 Rectifier Address Abnormal


Description
If the hardware addresses of multiple rectifiers conflict, the SMU generates a Rectifier
Hard Addr Abnormal alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

1610 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,90/359(W)

The displayed hardware address is incorrect, but the functions are not affected.

Possible Causes
The address line is floated.
The DIP switch setting is incorrect.

Procedure
1. Check whether the address line is unplugged.
If yes, reconnect the address line.
If no, go to the next step.

2. Check whether the DIP switch setting is incorrect.


If yes, toggle the switch again.
If no, go to the next step.

3. Replace the involved rectifiers and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Rectifier

1.9 Rectifier Group


Rectifier Missing

Insufficient Redundant Rectifiers

Rectifier Fault (Redundant)

Rectifier Fault (Non-redundant)

Multi-Rectifier Fault

All Rectifiers Fail to Communicate

Rectifier Hibernation Activated

High Rectifier Capacity

Low Rectifier Capacity

Rectifier Upgrade Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,91/359(W)

Parent topic: Site Alarm Reference

1.9.1 Rectifier Missing


Description
When detecting that certain rectifiers are missing after the SMU restarts, the SMU
generates a Rectifier Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

8802 Major ADAC

Impact on the System


Power supply to the site may be disconnected because the power system may supply
insufficient power.

Possible Causes
Certain rectifiers are not detected.
Certain rectifiers are faulty.

Procedure
1. Check whether certain rectifiers are removed.
If yes, reinstall the rectifiers.
If no, go to the next step.

2. Check whether certain rectifiers fail to work.


If yes, replace faulty rectifiers.
If no, contact Huawei technical support.

Parent topic: Rectifier Group

1.9.2 Insufficient Redundant Rectifiers


Description
When detecting that the number of redundant rectifiers is insufficient, the SMU
generates an Insufficient Redundant Rectifiers alarm.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,92/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

8803 Warning ADAC

Impact on the System


Power supply to the site may be disconnected because the power system may supply
insufficient power.

Possible Causes
Certain rectifiers are removed.
Certain rectifiers are faulty.

Procedure
1. Check whether certain rectifiers are removed.
If yes, reinstall the rectifiers.
If no, go to the next step.

2. Check whether certain rectifiers in the rectifier subrack are faulty.


If yes, replace faulty rectifiers.
If no, contact Huawei technical support.

Parent topic: Rectifier Group

1.9.3 Rectifier Fault (Redundant)


Description
When detecting that one rectifier is faulty and the power system is in redundant mode,
the SMU generates a Rectifier Fault (Redundant) alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

8804 Minor ADAC

Impact on the System


The rectifier fails to work.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,93/359(W)

One rectifier is faulty.

Procedure
1. Replace the rectifier whose indicator is red and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Rectifier Group

1.9.4 Rectifier Fault (Non-redundant)


Description
When detecting that one rectifier is faulty and the power system is in non-redundant
mode, the SMU generates a Rectifier Fault (Non-redundant) alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

8805 Major ADAC

Impact on the System


The rectifier fails to work and the power system may have insufficient loading
capability. The rectifier needs to be replaced as soon as possible.

Possible Causes
One rectifier is faulty.

Procedure
1. Replace the rectifier whose indicator is red and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Rectifier Group

1.9.5 Multi-Rectifier Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,94/359(W)

Description
When detecting that multiple rectifiers are faulty, the SMU generates a Multi-Rectifier
Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

8806 Major ADAC

Impact on the System


The power system may have insufficient loading capability.

Possible Causes
Multiple rectifiers are faulty.

Procedure
1. Replace the rectifiers whose indicators are red and check whether the alarm
persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Rectifier Group

1.9.6 All Rectifiers Fail to Communicate


Description
When detecting that the communication to all rectifiers fails, the SMU generates an All
Rectifiers Fail to Communicate alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

8800 Major ADAC

Impact on the System


No rectifier can be monitored.

Possible Causes
All rectifiers are faulty.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,95/359(W)

The SMU is faulty.

Procedure
1. Replace all rectifiers and check whether the alarm persists.
If no, no further action is required.
If yes, go to the next step.

2. Reset the SMU and check whether the alarm persists.


If no, no further action is required.
If yes, go to the next step.

3. Replace the SMU and check whether the alarm persists.


If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Rectifier Group

1.9.7 Rectifier Hibernation Activated


Description
When detecting that rectifier hibernation is activated, the SMU generates a Rectifier
Hibernation Activated alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

8808 Warning ADAC

Impact on the System


None.

Possible Causes
Certain rectifiers hibernate.

Procedure
No measure is required.

Parent topic: Rectifier Group

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,96/359(W)

1.9.8 High Rectifier Capacity


Description
When detecting that the load power is below the light load alarm threshold, the SMU
generates a High Rectifier Capacity alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

8810 Minor ADAC

Impact on the System


Rectifiers work at low efficiency.

Possible Causes
The load power is below the lower threshold.
The light load alarm threshold is not properly set.

Procedure
1. Check whether the load power is below the lower threshold.
If yes, no further action is required.
If no, reset the light load alarm threshold.

Parent topic: Rectifier Group

1.9.9 Low Rectifier Capacity


Description
When detecting that the load power exceeds the heavy load alarm threshold, the SMU
generates a Low Rectifier Capacity alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

8809 Critical ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,97/359(W)

The load power exceeds the alarm threshold.

Possible Causes
The heavy load alarm threshold is not properly set.

Procedure
1. Check whether the load power exceeds the alarm threshold.
If yes, no further action is required.
If no, reset the alarm threshold.

Parent topic: Rectifier Group

1.9.10 Rectifier Upgrade Fault


Description
When detecting that rectifiers fail to be loaded, the SMU generates a Rectifier Upgrade
Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

8811 Major ADAC

Impact on the System


Rectifiers fail to work.

Possible Causes
Certain rectifiers are faulty.

Procedure
1. Replace rectifiers, load new rectifiers, and check whether the loading is abnormal.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Rectifier Group

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,98/359(W)

1.10 SSU
Communication Failure

SSU Fault

SSU Protection

PV Array Fault

SSU Update Failed

Parent topic: Site Alarm Reference

1.10.1 Communication Failure


Description
This alarm is generated when the SMU does not receive any data from the SSU for 8 to
10 seconds.

Attribute

Alarm ID Alarm Severity Alarm Type

1652 Minor ADAC

Impact on the System


The SMU fails to control the SSU, which affects voltage regulation and current
limiting.

Possible Causes
The SSU is removed or the backplane circuit has a fault.

Procedure
1. Check whether the SSU is not connected properly.
If yes, reconnect the cable.
If no, go to the next step.

2. Check whether the SSU is removed.


If yes, insert the SSU.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,99/359(W)

If no, go to the next step.

3. Replace the SSU and check whether the alarm is cleared.


If yes, the SSU is faulty. Contact Huawei technical support and return the faulty
SSU to Huawei.
If no, go to the next step.

4. Insert the SSU into another slot and check whether the alarm is cleared.
If yes, the slot circuit may have a fault. Contact Huawei technical support.
If no, contact Huawei technical support.

Parent topic: SSU

1.10.2 SSU Fault


Description
This alarm is generated when the fan is faulty or the MOSFET is short-circuited.

Attribute

Alarm ID Alarm Severity Alarm Type

1650 Major ADAC

Impact on the System


The SSU may shut down and fail to convert solar energy into electric energy.

Possible Causes
The fan is faulty or the MOSFET is short-circuited.

Procedure
Contact Huawei technical support.

Parent topic: SSU

1.10.3 SSU Protection


Description
This alarm is generated when the SSU locks out due to output overvoltage.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,100/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

1653 Minor ADAC

Impact on the System


The SSU fails to convert solar energy into electric energy.

Possible Causes
The SSU experiences output overvoltage due to an internal fault or an external cause.

Procedure
1. Check whether other SSUs in the system are normal.
If yes, go to the next step.
If no, contact Huawei technical support.

2. Insert the SSU into another slot and check whether it is still protected.
If yes, go to the next step.
If no, contact Huawei technical support.

3. Replace the SSU and check whether the alarm is cleared.


If yes, return the faulty SSU for repair.
If no, contact Huawei technical support.

Parent topic: SSU

1.10.4 PV Array Fault


Description
This alarm is generated when the SMU detects that the input voltage of each PV
module string is lower than 20 V for 24 hours.

Attribute

Alarm ID Alarm Severity Alarm Type

1654 Warning ADAC

Impact on the System


Reliable power supply to the system is affected due to an insufficient power supply.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,101/359(W)

Possible Causes
The photovoltaic distribution unit (PVDU) input circuit breaker is OFF.
The cable between the solar junction box (SJB) and the PVDU is loose.
The SJB is faulty.
The PV module is faulty.

Procedure
1. Switch on the PVDU input circuit breaker if it is OFF and check whether the alarm
is cleared.
If yes, no further action is required.
If no, go to the next step.

2. Reconnect the input power cable to the PVDU and check whether the alarm is
cleared.
If yes, no further action is required.
If no, go to the next step.

3. Check whether the PVDU input circuit breaker is OFF.


If yes, switch on the circuit breaker. No further action is required.
If no, go to the next step.

4. Check whether the input voltage of each PV module in the SJB ranges from 90 V
to 120 V.
If yes, replace the PV module string. No further action is required.
If no, contact Huawei technical support.

Parent topic: SSU

1.10.5 SSU Update Failed


Description
This alarm is generated when the SMU fails to upgrade an SSU.

Attribute

Alarm ID Alarm Severity Alarm Type

1658 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,102/359(W)

The SSU fails to be upgraded.

Possible Causes
The SSU experiences a power failure during upgrade.
The SSU experiences a communication failure during upgrade.

Procedure
1. Check whether the SSU experiences a power failure.
If yes, ensure the normal power supply to the SSU.
If no, go to the next step.

2. After ensuring that the communication between the SSU and the SMU is normal,
continue with the upgrade.

Parent topic: SSU

1.11 SSU Summary


All SSU Communication Failure

SSU Lost

Parent topic: Site Alarm Reference

1.11.1 All SSU Communication Failure


Description
This alarm is generated when all SSUs fail in communication.

Attribute

Alarm ID Alarm Severity Alarm Type

8852 Major ADAC

Impact on the System


The SMU cannot control SSUs, which affects the current limiting function in solar
scenarios.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,103/359(W)

Possible Causes
The SSU is removed or the backplane circuit has a fault.

Procedure
1. Check whether the SSU is not connected properly.
If yes, reconnect the cable.
If no, go to the next step.

2. Check whether the SSU is removed.


If yes, reinstall the SSU.
If no, contact Huawei technical support.

Parent topic: SSU Summary

1.11.2 SSU Lost


Description
This alarm is generated when the SMU detects less SSUs after restart than those before
restart.

Attribute

Alarm ID Alarm Severity Alarm Type

8854 Warning ADAC

Impact on the System


The number of detected SSUs decreases, which affects the maximum of output power
of PV modules.

Possible Causes
The SSU is removed or certain SSUs' backplane circuits have faults.

Procedure
1. Check whether SSUs are not connected properly.
If yes, reconnect the cables to ensure normal communication.
If no, go to the next step.

2. Check whether SSUs are removed.


If yes, reinstall the SSUs.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,104/359(W)

If no, clear the alarm manually.

Parent topic: SSU Summary

1.12 TCUC
Air Exhaust Vent Temperature Sensor Fault

Air Intake Vent Temperature Sensor Fault

External Fan 1 Fault

External Fan 2 Fault

Internal Fan 1 Fault

Internal Fan 2 Fault

INFAN3 Fault

INFAN4 Fault

Air Exhaust Vent Overtemperature Alarm

Air Exhaust Vent Undertemperature Alarm

Air Intake Vent Overtemperature Alarm

Air Intake Vent Undertemperature Alarm

TEC Fault

Door Alarm

Smoke Alarm

Water Alarm

Reserved IN0 Alarm

Reserved IN1 Alarm

Battery String 1 Cell1 Imbalance

Battery String 1 Cell2 Imbalance

Battery String 1 Cell3 Imbalance

Battery String 1 Cell4 Imbalance

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,105/359(W)

Battery String 2 Cell1 Imbalance

Battery String 2 Cell2 Imbalance

Battery String 2 Cell3 Imbalance

Battery String 2 Cell4 Imbalance

Battery String 3 Cell1 Imbalance

Battery String 3 Cell2 Imbalance

Battery String 3 Cell3 Imbalance

Battery String 3 Cell4 Imbalance

Battery String 4 Cell1 Imbalance

Battery String 4 Cell2 Imbalance

Battery String 4 Cell3 Imbalance

Battery String 4 Cell4 Imbalance

TCUC Communication Failure

Battery String 1 Mid-Point Imbalance

Battery String 2 Mid-Point Imbalance

Battery String 3 Mid-Point Imbalance

Battery String 4 Mid-Point Imbalance

Return Vent Temperature Sensor Fault

Return Vent Overtemperature Alarm

Return Vent Undertemperature Alarm

Battery String 1 Missing

Battery String 2 Missing

Battery String 3 Missing

Battery String 4 Missing

Parent topic: Site Alarm Reference

1.12.1 Air Exhaust Vent Temperature

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,106/359(W)

Sensor Fault
Description
This alarm is generated when the sensor is disconnected.

Attribute

Alarm ID Alarm Severity Alarm Type

13850 Major ADAC

Impact on the System


The temperature cannot be monitored.

Possible Causes
The sensor is disconnected.
The sensor connector is loose.
The sensor is faulty.

Procedure
1. Check whether the sensor is connected.
If no, install the sensor.
If yes, go to the next step.

2. Check whether the sensor connector is loose.


If yes, secure the connector.
If no, go to the next step.

3. Replace the sensor and check whether the alarm persists.


If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.2 Air Intake Vent Temperature Sensor


Fault
Description

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,107/359(W)

This alarm is generated when the sensor is disconnected.

Attribute

Alarm ID Alarm Severity Alarm Type

13851 Major ADAC

Impact on the System


The temperature cannot be monitored.

Possible Causes
The sensor is disconnected.
The sensor connector is loose.
The sensor is faulty.

Procedure
1. Check whether the sensor is connected.
If no, install the sensor.
If yes, go to the next step.

2. Check whether the sensor connector is loose.


If yes, secure the connector.
If no, go to the next step.

3. Replace the sensor and check whether the alarm persists.


If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.3 External Fan 1 Fault


Description
This alarm is generated when the fan is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,108/359(W)

13852 Major ADAC

Impact on the System


The system temperature cannot be adjusted.

Possible Causes
The fan is faulty.

Procedure
1. Power on the fan and check whether the fan stops rotating.
If yes, replace the fan.
If no, go to the next step.

2. Power off the fan and check whether the fan cable is properly connected.
If yes, contact Huawei technical support.
If no, connect the fan cable.

Parent topic: TCUC

1.12.4 External Fan 2 Fault


Description
This alarm is generated when the fan is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

13853 Major ADAC

Impact on the System


The system temperature cannot be adjusted.

Possible Causes
The fan is faulty.

Procedure
1. Power on the fan and check whether the fan stops rotating.
If yes, replace the fan.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,109/359(W)

If no, go to the next step.

2. Power off the fan and check whether the fan cable is properly connected.
If yes, contact Huawei technical support.
If no, connect the fan cable.

Parent topic: TCUC

1.12.5 Internal Fan 1 Fault


Description
This alarm is generated when the fan is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

13854 Major ADAC

Impact on the System


The system temperature cannot be adjusted.

Possible Causes
The fan is faulty.

Procedure
1. Power on the fan and check whether the fan stops rotating.
If yes, replace the fan.
If no, go to the next step.

2. Power off the fan and check whether the fan cable is properly connected.
If yes, contact Huawei technical support.
If no, connect the fan cable.

Parent topic: TCUC

1.12.6 Internal Fan 2 Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,110/359(W)

Description
This alarm is generated when the fan is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

13855 Major ADAC

Impact on the System


The system temperature cannot be adjusted.

Possible Causes
The fan is faulty.

Procedure
1. Power on the fan and check whether the fan stops rotating.
If yes, replace the fan.
If no, go to the next step.

2. Power off the fan and check whether the fan cable is properly connected.
If yes, contact Huawei technical support.
If no, connect the fan cable.

Parent topic: TCUC

1.12.7 INFAN3 Fault


Description
This alarm is generated when the fan is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

13895 Major ADAC

Impact on the System


The system temperature cannot be adjusted.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,111/359(W)

The fan is faulty.

Procedure
1. Power on the fan and check whether the fan stops rotating.
If yes, replace the fan.
If no, go to the next step.

2. Power off the fan and check whether the fan cable is properly connected.
If yes, contact Huawei technical support.
If no, connect the fan cable.

Parent topic: TCUC

1.12.8 INFAN4 Fault


Description
This alarm is generated when the fan is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

13896 Major ADAC

Impact on the System


The system temperature cannot be adjusted.

Possible Causes
The fan is faulty.

Procedure
1. Power on the fan and check whether the fan stops rotating.
If yes, replace the fan.
If no, go to the next step.

2. Power off the fan and check whether the fan cable is properly connected.
If yes, contact Huawei technical support.
If no, connect the fan cable.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,112/359(W)

Parent topic: TCUC

1.12.9 Air Exhaust Vent Overtemperature


Alarm
Description
This alarm is generated when the temperature exceeds the high temperature alarm
threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

13856 Critical ADAC

Impact on the System


Power system performance and reliability deteriorate because the power system
operates at high temperatures.

Possible Causes
The temperature exceeds the upper threshold.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
malfunctioning.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Replace the ambient temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: TCUC

1.12.10 Air Exhaust Vent


Undertemperature Alarm

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,113/359(W)

Description
This alarm is generated when the ambient temperature is below the low temperature
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

13857 Warning ADAC

Impact on the System


Power system performance and reliability deteriorate because the power system
operates at low temperatures.

Possible Causes
The ambient temperature is below the lower threshold.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
malfunctioning.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Replace the ambient temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: TCUC

1.12.11 Air Intake Vent Overtemperature


Alarm
Description
This alarm is generated when the temperature exceeds the high temperature alarm
threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,114/359(W)

13858 Critical ADAC

Impact on the System


Power system performance and reliability deteriorate because the power system
operates at high temperatures.

Possible Causes
The temperature exceeds the upper threshold.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
malfunctioning.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Replace the ambient temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: TCUC

1.12.12 Air Intake Vent Undertemperature


Alarm
Description
This alarm is generated when the ambient temperature is below the low temperature
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

13859 Warning ADAC

Impact on the System


Power system performance and reliability deteriorate because the power system
operates at low temperatures.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,115/359(W)

Possible Causes
The ambient temperature is below the lower threshold.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
malfunctioning.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Replace the ambient temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: TCUC

1.12.13 TEC Fault


Description
This alarm is generated when the thermoelectric cooler (TEC) works abnormally.

Attribute

Alarm ID Alarm Severity Alarm Type

13860 Major ADAC

Impact on the System


The system temperature cannot be adjusted.

Possible Causes
The TEC is not properly connected.
The TEC is abnormal.

Procedure
1. Check whether the TEC is not properly connected.
If yes, reconnect the TEC.
If no, go to the next step.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,116/359(W)

2. Check whether the TEC is abnormal.


If yes, maintain the TEC.
If no, go to the next step.

3. Check whether the alarm persists.


If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: TCUC

1.12.14 Door Alarm


Description
When detecting that the cabinet door is open, the SMU generates a Door Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13861 Minor ADAC

Impact on the System


The power system has potential troubles.

Possible Causes
The cabinet door is open.
The connector on the door status sensor cable is loose.
The door status sensor is faulty.

Procedure
1. Close the cabinet door and check whether the alarm is cleared.
If yes, no further action is required.
If no, go to the next step.

2. Check whether the connector on the door status sensor cable is loose.
If yes, secure the connector.
If no, go to the next step.

3. Replace the door status sensor and close the cabinet door, and then check whether

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,117/359(W)

the alarm is cleared.


If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: TCUC

1.12.15 Smoke Alarm


Description
When detecting smoke in the cabinet, the SMU generates a Smoke Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13862 Critical ADAC

Impact on the System


The power system has potential troubles.

Possible Causes
There is smoke inside the cabinet.
The smoke sensor is faulty.

Procedure
1. Check whether there is smoke inside the cabinet.
If yes, shut down the power system and rectify the fault.
If no, go to the next step.

2. Replace the smoke sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.16 Water Alarm

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,118/359(W)

Description
When detecting water in the cabinet, the SMU generates a Water Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13863 Critical ADAC

Impact on the System


The power system has potential troubles.

Possible Causes
Water intrudes into the cabinet.
The water sensor is faulty.

Procedure
1. Check whether water intrudes into the cabinet.
If yes, eliminate water from the cabinet.
If no, go to the next step.

2. Replace the water sensor and check whether the alarm persists.
If yes, secure the connector.
If no, go to the next step.

3. Replace the water sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.17 Reserved IN0 Alarm


Description
This alarm is generated when the IN0 dry contact on the TCUC receives an alarm
signal.

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,119/359(W)

13864 Minor ADAC

Impact on the System


The impact depends on the accessed signal.

Possible Causes
The accessed signal indicates an alarm.
The cable is disconnected.

Procedure
1. Check whether the device connected to the dry contact input generates an alarm.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.18 Reserved IN1 Alarm


Description
This alarm is generated when the IN1 dry contact on the TCUC receives an alarm
signal.

Attribute

Alarm ID Alarm Severity Alarm Type

13865 Minor ADAC

Impact on the System


The impact depends on the accessed signal.

Possible Causes
The accessed signal indicates an alarm.
The cable is disconnected.

Procedure
1. Check whether the device connected to the dry contact input generates an alarm.
If no, no further action is required.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,120/359(W)

If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.19 Battery String 1 Cell1 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13866 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.20 Battery String 1 Cell2 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13867 Warning ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,121/359(W)

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.21 Battery String 1 Cell3 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13868 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,122/359(W)

1.12.22 Battery String 1 Cell4 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13869 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.23 Battery String 2 Cell1 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13870 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,123/359(W)

A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.24 Battery String 2 Cell2 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13871 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.25 Battery String 2 Cell3 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,124/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

13872 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.26 Battery String 2 Cell4 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13873 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,125/359(W)

Parent topic: TCUC

1.12.27 Battery String 3 Cell1 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13874 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.28 Battery String 3 Cell2 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13875 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,126/359(W)

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.29 Battery String 3 Cell3 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13876 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.30 Battery String 3 Cell4 Imbalance


Description

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,127/359(W)

This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13877 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.31 Battery String 4 Cell1 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13878 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,128/359(W)

If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.32 Battery String 4 Cell2 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13879 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.33 Battery String 4 Cell3 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13880 Warning ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,129/359(W)

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.34 Battery String 4 Cell4 Imbalance


Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13881 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,130/359(W)

1.12.35 TCUC Communication Failure


Description
This alarm is generated when the SMU fails to communicate with the TCUC.

Attribute

Alarm ID Alarm Severity Alarm Type

13882 Minor ADAC

Impact on the System


The SMU fails to monitor the faulty device.

Possible Causes
The device is removed.
The device is faulty.
The communications cable is loose.

Procedure
1. Check whether the communications cable between the device and the SMU is
connected correctly.
If yes, go to the next step.
If no, reconnect the communications cable.

2. Reset the SMU and check whether the alarm persists.


If no, no further action is required.
If yes, go to the next step.

3. Check whether the device works properly.


If yes, contact Huawei technical support.
If no, replace the device.

Parent topic: TCUC

1.12.36 Battery String 1 Mid-Point


Imbalance

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,131/359(W)

Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13883 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.37 Battery String 2 Mid-Point


Imbalance
Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13884 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,132/359(W)

1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.38 Battery String 3 Mid-Point


Imbalance
Description
This alarm is generated when the battery voltage is unbalanced.

Attribute

Alarm ID Alarm Severity Alarm Type

13885 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.39 Battery String 4 Mid-Point


Imbalance
Description
This alarm is generated when the battery voltage is unbalanced.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,133/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

13886 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery voltage is unbalanced.

Possible Causes
A battery is faulty.

Procedure
1. Replace the faulty battery and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.40 Return Vent Temperature Sensor


Fault
Description
This alarm is generated when the sensor is not properly connected.

Attribute

Alarm ID Alarm Severity Alarm Type

13887 Major ADAC

Impact on the System


The temperature cannot be monitored.

Possible Causes
The sensor is disconnected.
The sensor connector is loose.
The sensor is faulty.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,134/359(W)

1. Check whether the sensor is connected.


If no, connect the sensor.
If yes, go to the next step.

2. Check whether the sensor connector is loose.


If yes, secure the connector.
If no, go to the next step.

3. Replace the sensor and check whether the alarm persists.


If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCUC

1.12.41 Return Vent Overtemperature


Alarm
Description
This alarm is generated when the temperature exceeds the high temperature alarm
threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

13888 Critical ADAC

Impact on the System


Power system performance and reliability deteriorate because the power system
operates at high temperatures.

Possible Causes
The temperature exceeds the upper threshold.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
malfunctioning.
If yes, maintain the temperature control devices.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,135/359(W)

If no, go to the next step.

2. Replace the ambient temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: TCUC

1.12.42 Return Vent Undertemperature


Alarm
Description
This alarm is generated when the ambient temperature is below the low temperature
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

13889 Warning ADAC

Impact on the System


Power system performance and reliability deteriorate because the power system
operates at low temperatures.

Possible Causes
The temperature is below the lower threshold.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
malfunctioning.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Replace the ambient temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: TCUC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,136/359(W)

1.12.43 Battery String 1 Missing


Description
This alarm is generated when batteries are not detected.

Attribute

Alarm ID Alarm Severity Alarm Type

13891 Major ADAC

Impact on the System


Batteries fail to supply backup power.

Possible Causes
Batteries are missing.
The battery detection cable is loose.

Procedure
1. Check whether batteries are missing.
If yes, install batteries.
If no, go to the next step.

2. Check whether the battery detection cable is loose.


If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: TCUC

1.12.44 Battery String 2 Missing


Description
This alarm is generated when batteries are not detected.

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,137/359(W)

13892 Major ADAC

Impact on the System


Batteries fail to supply backup power.

Possible Causes
Batteries are missing.
The battery detection cable is loose.

Procedure
1. Check whether batteries are missing.
If yes, install batteries.
If no, go to the next step.

2. Check whether the battery detection cable is loose.


If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: TCUC

1.12.45 Battery String 3 Missing


Description
This alarm is generated when batteries are not detected.

Attribute

Alarm ID Alarm Severity Alarm Type

13893 Major ADAC

Impact on the System


Batteries fail to supply backup power.

Possible Causes
Batteries are missing.
The battery detection cable is loose.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,138/359(W)

1. Check whether batteries are missing.


If yes, install batteries.
If no, go to the next step.

2. Check whether the battery detection cable is loose.


If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: TCUC

1.12.46 Battery String 4 Missing


Description
This alarm is generated when batteries are not detected.

Attribute

Alarm ID Alarm Severity Alarm Type

13894 Major ADAC

Impact on the System


Batteries fail to supply backup power.

Possible Causes
Batteries are missing.
The battery detection cable is loose.

Procedure
1. Check whether batteries are missing.
If yes, install batteries.
If no, go to the next step.

2. Check whether the battery detection cable is loose.


If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: TCUC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,139/359(W)

1.13 Battery String


Battery Fuse Break

Battery Middle Voltage Imbalance

Battery Missing

Battery Cell1 Voltage Imbalance

Battery Cell2 Voltage Imbalance

Battery Cell3 Voltage Imbalance

Battery Cell4 Voltage Imbalance

Parent topic: Site Alarm Reference

1.13.1 Battery Fuse Break


Description
This alarm is generated when the battery fuse is disconnected or the battery circuit
breaker is OFF.

Attribute

Alarm ID Alarm Severity Alarm Type

0903 Critical ADAC

Impact on the System


The power system does not have sufficient backup power because a battery fuse is
disconnected.

Possible Causes
The battery fuse is disconnected or the battery circuit breaker is OFF.
The battery fuse detection cable is disconnected.

Procedure
1. Check whether the battery fuse is disconnected or the battery circuit breaker is
OFF.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,140/359(W)

If yes, switch on the circuit breaker.


If no, go to the next step.

2. Check whether the battery fuse detection cable is disconnected.


If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Battery String

1.13.2 Battery Middle Voltage Imbalance


Description
When detecting that the battery middle point voltage is unbalanced, the SMU generates
a Battery Middle Voltage Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

0904 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery middle point voltage is
unbalanced.

Possible Causes
Batteries are faulty.

Procedure
1. Replace batteries and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery String

1.13.3 Battery Missing


Description

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,141/359(W)

When not detecting batteries, the SMU generates a Battery Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

0905 Major ADAC

Impact on the System


Backup power cannot be supplied.

Possible Causes
Batteries are missing.
The battery detection cable is disconnected.

Procedure
1. Check whether batteries are missing.
If yes, install batteries.
If no, go to the next step.

2. Check whether the battery detection cable is disconnected.


If yes, secure the connector.
If no, contact Huawei technical support.

Parent topic: Battery String

1.13.4 Battery Cell1 Voltage Imbalance


Description
When detecting that battery voltage is unbalanced, the SMU generates a Battery Cell 1
Voltage Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

0906 Warning ADAC

Impact on the System


The battery backup function deteriorates because battery voltage is unbalanced.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,142/359(W)

Possible Causes
Batteries are faulty.

Procedure
1. Replace batteries and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery String

1.13.5 Battery Cell2 Voltage Imbalance


Description
When detecting that battery voltage is unbalanced, the SMU generates a Battery Cell 2
Voltage Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

0907 Warning ADAC

Impact on the System


The battery backup function deteriorates because battery voltage is unbalanced.

Possible Causes
Batteries are faulty.

Procedure
1. Replace batteries and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery String

1.13.6 Battery Cell3 Voltage Imbalance

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,143/359(W)

Description
When detecting that battery voltage is unbalanced, the SMU generates a Battery Cell 3
Voltage Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

0908 Warning ADAC

Impact on the System


The battery backup function deteriorates because battery voltage is unbalanced.

Possible Causes
Batteries are faulty.

Procedure
1. Replace batteries and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery String

1.13.7 Battery Cell4 Voltage Imbalance


Description
When detecting that battery voltage is unbalanced, the SMU generates a Battery Cell 4
Voltage Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

0909 Warning ADAC

Impact on the System


The battery backup function deteriorates because battery voltage is unbalanced.

Possible Causes
Batteries are faulty.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,144/359(W)

1. Replace batteries and check whether the alarm persists.


If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery String

1.14 Battery Cabinet


Battery Cabinet Communication Failure

Battery Temperature Sensor Fault

Battery Temperature Sensor Missing

Fan 1 Fault

Fan 2 Fault

Fan 3 Fault

Fan 4 Fault

Battery Cabinet High Temperature

Indoor Return Vent Temperature Sensor Fault

Outdoor Temperature Sensor Fault

Cabinet Return Air Temperature Sensor Fault

Internal Fan Fault

Frequent High Pressure

Air Conditioner Communication Failure

External Fan Fault

Air Conditioner Compressor Fault

Air Conditioner Evaporator Frozen

Door Alarm

Battery Cabinet Temp Sensor Fault

Air Conditioner Missing

Parent topic: Site Alarm Reference

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,145/359(W)

1.14.1 Battery Cabinet Communication


Failure
Description
When failing to communicate with the monitoring board of the battery cabinet, the
SMU generates a Battery Cabinet Communication Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13101 Major ADAC

Impact on the System


The SMU fails to detect the information about the battery cabinet.

Possible Causes
The communication cable is unconnected or loosened.
The monitoring board of the battery cabinet is powered off or faulty.

Procedure
1. Check whether the communication cable is incorrectly connected.
If yes, reconnect the communication cable.
If no, go to the next step

2. Check whether the monitoring board of the battery cabinet is working normally.
If yes, contact Huawei technical support.
If no, replace the monitoring board of the battery cabinet.

Parent topic: Battery Cabinet

1.14.2 Battery Temperature Sensor Fault


Description
When detecting that battery temperature sensor is faulty, the SMU generates a Battery
Temperature Sensor Fault alarm.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,146/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

13102 Major ADAC

Impact on the System


Battery temperatures cannot be monitored.

Possible Causes
Battery temperature sensor is faulty.

Procedure
1. Replace battery temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Cabinet

1.14.3 Battery Temperature Sensor Missing


Description
When detecting that battery temperature sensor is disconnected, the SMU generates a
Battery Temperature Sensor Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13103 Warning ADAC

Impact on the System


Battery temperatures cannot be monitored.

Possible Causes
Battery temperature sensor is disconnected.
The connector on the battery temperature sensor cable is disconnected.
Battery temperature sensor is faulty.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,147/359(W)

1. Check whether battery temperature sensor is connected.


If no, connect battery temperature sensor to the power system.
If yes, go to the next step.

2. Check whether the connector on the battery temperature sensor cable is


disconnected.
If yes, secure the connector.
If no, go to the next step.

3. Replace battery temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Cabinet

1.14.4 Fan 1 Fault


Description
When detecting that fan 1 is faulty, the SMU generates a Fan 1 Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13104 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes
Fan 1 is faulty.

Procedure
1. Check whether a fan is abnormal.
If yes, replace the fan.
If no, contact Huawei technical support.

Parent topic: Battery Cabinet

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,148/359(W)

1.14.5 Fan 2 Fault


Description
When detecting that fan 2 is faulty, the SMU generates a Fan 2 Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13105 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes
Fan 2 is faulty.

Procedure
1. Check whether a fan is abnormal.
If yes, replace the fan.
If no, contact Huawei technical support.

Parent topic: Battery Cabinet

1.14.6 Fan 3 Fault


Description
When detecting that fan 3 is faulty, the SMU generates a Fan 3 Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13106 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,149/359(W)

Fan 3 is faulty.

Procedure
1. Check whether a fan is abnormal.
If yes, replace the fan.
If no, contact Huawei technical support.

Parent topic: Battery Cabinet

1.14.7 Fan 4 Fault


Description
When detecting that fan 4 is faulty, the SMU generates a Fan 4 Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13107 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes
Fan 4 is faulty.

Procedure
1. Check whether a fan is abnormal.
If yes, replace the fan.
If no, contact Huawei technical support.

Parent topic: Battery Cabinet

1.14.8 Battery Cabinet High Temperature


Description
When detecting that the temperature at the return air vent in the cabinet exceeds the

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,150/359(W)

high temperature alarm threshold, the SMU generates an Battery Cabinet High
Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13108 Critical ADAC

Impact on the System


Power system performance and reliability will deteriorate.

Possible Causes
The temperature control system is faulty.
The ambient temperature sensor is faulty.

Procedure
1. Check whether the temperature control system is abnormal.
If no, maintain the temperature control system.
If yes, go to the next step.

2. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery Cabinet

1.14.9 Indoor Return Vent Temperature


Sensor Fault
Description
When detecting that the ambient temperature sensor at the return air vent in the cabinet
is faulty, the SMU generates an Indoor Return Vent Temperature Sensor Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13109 Major ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,151/359(W)

Impact on the System


Temperature at the return air vent in the cabinet cannot be monitored.

Possible Causes
The ambient temperature sensor at the return air vent in the cabinet is faulty.

Procedure
1. Replace the ambient temperature sensor at the return air vent and check whether the
alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery Cabinet

1.14.10 Outdoor Temperature Sensor Fault


Description
When detecting that the ambient temperature sensor outside the cabinet is faulty, the
SMU generates an Outdoor Temperature Sensor Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13110 Warning ADAC

Impact on the System


The ambient temperature outside the cabinet cannot be monitored.

Possible Causes
The ambient temperature sensor outside the cabinet is faulty.

Procedure
1. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery Cabinet

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,152/359(W)

1.14.11 Cabinet Return Air Temperature


Sensor Fault
Description
The sensor at the return air vent of the air conditioner is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

13111 Minor ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Battery Cabinet

1.14.12 Internal Fan Fault


Description
The indoor unit is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

13112 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,153/359(W)

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Battery Cabinet

1.14.13 Frequent High Pressure


Description
The air conditioner frequently works under high pressure.

Attribute

Alarm ID Alarm Severity Alarm Type

13113 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Battery Cabinet

1.14.14 Air Conditioner Communication


Failure
Description
The air conditioner fails to communicate with the SMU.

Attribute

Alarm ID Alarm Severity Alarm Type

13114 Major ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,154/359(W)

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Battery Cabinet

1.14.15 External Fan Fault


Description
The outdoor unit is faulty

Attribute

Alarm ID Alarm Severity Alarm Type

13115 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Battery Cabinet

1.14.16 Air Conditioner Compressor Fault


Description
The DC meter fails to communicate with the SMU.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,155/359(W)

Alarm ID Alarm Severity Alarm Type

13116 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Battery Cabinet

1.14.17 Air Conditioner Evaporator Frozen


Description
The evaporator is frozen.

Attribute

Alarm ID Alarm Severity Alarm Type

13117 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Battery Cabinet

1.14.18 Door Alarm

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,156/359(W)

Description
When detecting that the cabinet door is open, the SMU generates a Door Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

13118 Minor ADAC

Impact on the System


The power system has potential troubles.

Possible Causes
The cabinet door of the power system is open.
The connector on the door status sensor cable is loose.
The door status sensor is faulty.

Procedure
1. Close the cabinet door of the power system and check whether the alarm is cleared.
If yes, no further action is required.
If no, go to the next step.

2. Check whether the connector on the door status sensor cable is loose.
If yes, secure the connector.
If no, go to the next step.

3. Replace the door status sensor and close the cabinet door, and then check whether
the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Cabinet

1.14.19 Battery Cabinet Temp Sensor Fault


Description
When detecting that battery temperature sensor is faulty, the SMU generates a Battery
Temperature Sensor Fault alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,157/359(W)

Alarm ID Alarm Severity Alarm Type

13119 Major ADAC

Impact on the System


Battery temperatures cannot be monitored.

Possible Causes
Battery temperature sensor is faulty.

Procedure
1. Replace battery temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Cabinet

1.14.20 Air Conditioner Missing


Description
The SMU generates an alarm that the air conditioner is not detected.

Attribute

Alarm ID Alarm Severity Alarm Type

13128 Major ADAC

Impact on the System


The temperature for the battery cabinet cannot be adjusted.

Possible Causes
The air conditioner is not connected, or the connection is loose.
The air conditioner is faulty.

Procedure
1. Check whether the air conditioner is not connected, or the connection is loose.
If yes, connect the air conditioner or secure the connection.
If no, go to the next step.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,158/359(W)

2. Replace the air conditioner and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Cabinet

1.15 Batt. Cell Detector


Battery1 Cell1 Imbalance

Battery1 Cell2 Imbalance

Battery1 Cell3 Imbalance

Battery1 Cell4 Imbalance

Battery1 Cell5 Imbalance

Battery1 Cell6 Imbalance

Battery1 Cell7 Imbalance

Battery1 Cell8 Imbalance

Battery1 Cell9 Imbalance

Battery1 Cell10 Imbalance

Battery1 Cell11 Imbalance

Battery1 Cell12 Imbalance

Battery1 Cell13 Imbalance

Battery1 Cell14 Imbalance

Battery1 Cell15 Imbalance

Battery1 Cell16 Imbalance

Battery1 Cell17 Imbalance

Battery1 Cell18 Imbalance

Battery1 Cell19 Imbalance

Battery1 Cell20 Imbalance

Battery1 Cell21 Imbalance

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,159/359(W)

Battery1 Cell22 Imbalance

Battery1 Cell23 Imbalance

Battery1 Cell24 Imbalance

Detector Communication Fail

Abnormal Voltage Check

Battery2 Cell1 Imbalance

Battery2 Cell2 Imbalance

Battery2 Cell3 Imbalance

Battery2 Cell4 Imbalance

Battery2 Cell5 Imbalance

Battery2 Cell6 Imbalance

Battery2 Cell7 Imbalance

Battery2 Cell8 Imbalance

Battery3 Cell1 Imbalance

Battery3 Cell2 Imbalance

Battery3 Cell3 Imbalance

Battery3 Cell4 Imbalance

Battery4 Cell1 Imbalance

Battery4 Cell2 Imbalance

Battery4 Cell3 Imbalance

Battery4 Cell4 Imbalance

Parent topic: Site Alarm Reference

1.15.1 Battery1 Cell1 Imbalance


Description
This alarm is generated when the average battery voltage of a battery string exceeds the
battery imbalance alarm threshold.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,160/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

9198 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.2 Battery1 Cell2 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell2 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9199 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,161/359(W)

The battery detection cable is incorrectly connected.


A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.3 Battery1 Cell3 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell3 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9200 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,162/359(W)

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.4 Battery1 Cell4 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell4 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9201 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,163/359(W)

1.15.5 Battery1 Cell5 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell5 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9202 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.6 Battery1 Cell6 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell6 Imbalance alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,164/359(W)

Alarm ID Alarm Severity Alarm Type

9203 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.7 Battery1 Cell7 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell7 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9204 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,165/359(W)

A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.8 Battery1 Cell8 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell8 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9205 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,166/359(W)

If yes, contact Huawei technical support.


If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.9 Battery1 Cell9 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell9 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9206 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.10 Battery1 Cell10 Imbalance

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,167/359(W)

Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell10 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9207 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.11 Battery1 Cell11 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell11 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9208 Warning ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,168/359(W)

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.12 Battery1 Cell12 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell12 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9209 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,169/359(W)

1. Check whether the battery detection cable is correctly connected.


If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.13 Battery1 Cell13 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell13 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9210 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,170/359(W)

Parent topic: Batt. Cell Detector

1.15.14 Battery1 Cell14 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell14 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9211 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.15 Battery1 Cell15 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell5 Imbalance alarm.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,171/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

9212 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.16 Battery1 Cell16 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell16 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9213 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,172/359(W)

The battery detection cable is incorrectly connected.


A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.17 Battery1 Cell17 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell17 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9214 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,173/359(W)

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.18 Battery1 Cell18 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell18 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9215 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,174/359(W)

1.15.19 Battery1 Cell19 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell19 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9216 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.20 Battery1 Cell20 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell20 Imbalance alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,175/359(W)

Alarm ID Alarm Severity Alarm Type

9217 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.21 Battery1 Cell21 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell21 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9218 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,176/359(W)

A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.22 Battery1 Cell22 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell22 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9219 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,177/359(W)

If yes, contact Huawei technical support.


If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.23 Battery1 Cell23 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell23 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9220 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.24 Battery1 Cell24 Imbalance

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,178/359(W)

Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery1 Cell24 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9221 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.25 Detector Communication Fail


Description
When detecting that communication between the intelligent battery detector and
monitoring unit fails, the SMU generates a Detector Communication Fail alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9222 Major ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,179/359(W)

Impact on the System


The SMU cannot monitor the battery health condition.

Possible Causes
The communication cable is incorrectly connected.
The intelligent battery detector is powered off, lost, or damaged.

Procedure
1. Check whether the communication cable between the intelligent battery detector
and monitoring unit is correctly connected.
If yes, go to the next step.
If no, reconnect the communication cable.

2. Repower on the intelligent battery detector and check whether the alarm is cleared.
If yes, no further action is required.
If no, replace the intelligent battery detector.

Parent topic: Batt. Cell Detector

1.15.26 Abnormal Voltage Check


Description
When detecting that the battery voltage is less than 0.2 V, the SMU generates an
Abnormal Voltage Check alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9223 Warning ADAC

Impact on the System


The battery cannot properly back up power.

Possible Causes
The intelligent battery detector mistakenly detects configurations of the number of
battery strings.
The detection cable is incorrectly connected.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,180/359(W)

1. Check whether the number of battery strings is consistent with that of actual cables.
If yes, go to the next step.
If no, reconfigure parameters for detecting the number of battery strings.

2. Check whether the detection cable is correctly connected.


If yes, contact Huawei technical support.
If no, reconnect the detection cable.

Parent topic: Batt. Cell Detector

1.15.27 Battery2 Cell1 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery2 Cell1 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9224 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,181/359(W)

1.15.28 Battery2 Cell2 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery2 Cell2 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9225 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.29 Battery2 Cell3 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery2 Cell3 Imbalance alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,182/359(W)

Alarm ID Alarm Severity Alarm Type

9226 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.30 Battery2 Cell4 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery2 Cell4 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9227 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,183/359(W)

A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.31 Battery2 Cell5 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery2 Cell5 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9228 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,184/359(W)

If yes, contact Huawei technical support.


If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.32 Battery2 Cell6 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery2 Cell6 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9229 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.33 Battery2 Cell7 Imbalance

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,185/359(W)

Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery2 Cell7 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9230 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.34 Battery2 Cell8 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery2 Cell8 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9231 Warning ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,186/359(W)

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.35 Battery3 Cell1 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery3 Cell1 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9232 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,187/359(W)

1. Check whether the battery detection cable is correctly connected.


If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.36 Battery3 Cell2 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery3 Cell2 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9233 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,188/359(W)

Parent topic: Batt. Cell Detector

1.15.37 Battery3 Cell3 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery3 Cell3 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9234 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.38 Battery3 Cell4 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery3 Cell4 Imbalance alarm.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,189/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

9235 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.39 Battery4 Cell1 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery4 Cell1 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9236 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,190/359(W)

The battery detection cable is incorrectly connected.


A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.40 Battery4 Cell2 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery4 Cell2 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9237 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,191/359(W)

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.15.41 Battery4 Cell3 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery4 Cell3 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9238 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,192/359(W)

1.15.42 Battery4 Cell4 Imbalance


Description
When detecting that the average battery voltage of a battery string exceeds the battery
imbalance alarm threshold, the SMU generates a Battery4 Cell4 Imbalance alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9239 Warning ADAC

Impact on the System


The power system has insufficient backup time because batteries are damaged.

Possible Causes
The battery detection cable is incorrectly connected.
A battery is faulty.

Procedure
1. Check whether the battery detection cable is correctly connected.
If yes, go to the next step.
If no, reconnect the detection cable.

2. Check whether the voltage of the battery for which the alarm is generated is normal
using a multimeter.
If yes, contact Huawei technical support.
If no, replace the battery.

Parent topic: Batt. Cell Detector

1.16 Battery Group


Battery High Temperature

Battery Low Temperature

Battery Temperature Sensor 1 Missing

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,193/359(W)

Battery Temperature Sensor 2 Missing

Battery Temperature Sensor 1 Fault

Battery Temperature Sensor 2 Fault

Battery Equalized Charging

BLVD Disconnected

Battery Equalized Charging Protection

BLVD Warning

Battery Discharging

Battery Temperature Compensation Activated

Battery Not Detected

Battery Reversely Connection

Battery Very High Temperature

Battery Very Low Temperature

Battery Forcibly Connection

Battery Test Cancelled

Battery Current Imbalance

Battery Charge Overcurrent

Low Battery Capacity

Battery Breaker Trip

Battery Test Negative

Battery Undervoltage

Battery Cell Deterioration

Battery Thermal Runaway

Battery Imbalance

Insufficient Backup

Battery Sub-health

Battery Deterioration

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,194/359(W)

Parent topic: Site Alarm Reference

1.16.1 Battery High Temperature


Description
When detecting that the battery temperature exceeds the high temperature alarm
threshold, the SMU generates a Battery High Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11300 Minor ADAC

Impact on the System


Battery performance will deteriorate and battery lifespan will be shortened.

Possible Causes
The battery temperature exceeds the high temperature alarm threshold.
The battery high temperature alarm threshold is not properly set.
The battery temperature sensor is faulty.

Procedure
1. Check whether temperature control devices in the battery compartment, such as the
fan and air conditioner, are abnormal.
If yes, maintain the devices.
If no, go to the next step.

2. Check whether the battery high temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the battery temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Group

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,195/359(W)

1.16.2 Battery Low Temperature


Description
When detecting that the battery temperature is below the low temperature alarm
threshold, the SMU generates a Battery Low Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11301 Warning ADAC

Impact on the System


Backup power reliability is compromised because battery performance deteriorates.

Possible Causes
The battery temperature is below the low temperature alarm threshold.
The battery low temperature alarm threshold is not properly set.
The battery temperature sensor is faulty.

Procedure
1. Check whether the heater in the battery compartment is abnormal.
If yes, maintain the heater.
If no, go to the next step.

2. Check whether the battery low temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the battery temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.3 Battery Temperature Sensor 1


Missing

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,196/359(W)

Description
When detecting that battery temperature sensor 1 is disconnected, the SMU generates a
Battery Temperature Sensor 1 Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11302 Warning ADAC

Impact on the System


Battery temperatures cannot be monitored.

Possible Causes
Battery temperature sensor 1 is disconnected.
The connector on the battery temperature sensor 1 cable is disconnected.
Battery temperature sensor 1 is faulty.

Procedure
1. Check whether battery temperature sensor 1 is connected.
If no, connect battery temperature sensor 1 to the power system.
If yes, go to the next step.

2. Check whether the connector on the battery temperature sensor 1 cable is


disconnected.
If yes, secure the connector.
If no, go to the next step.

3. Replace battery temperature sensor 1 and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.4 Battery Temperature Sensor 2


Missing
Description
When detecting that battery temperature sensor 2 is disconnected, the SMU generates a

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,197/359(W)

Battery Temperature Sensor 2 Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11352 Warning ADAC

Impact on the System


Battery temperatures cannot be monitored.

Possible Causes
Battery temperature sensor 2 is disconnected.
The connector on the battery temperature sensor 2 cable is disconnected.
Battery temperature sensor 2 is faulty.

Procedure
1. Check whether battery temperature sensor 2 is connected.
If no, connect battery temperature sensor 2 to the power system.
If yes, go to the next step.

2. Check whether the connector on the battery temperature sensor 2 cable is


disconnected.
If yes, secure the connector.
If no, go to the next step.

3. Replace battery temperature sensor 2 and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.5 Battery Temperature Sensor 1 Fault


Description
When detecting that battery temperature sensor 1 is faulty, the SMU generates a Battery
Temperature Sensor 1 Fault alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,198/359(W)

Alarm ID Alarm Severity Alarm Type

11344 Major ADAC

Impact on the System


Battery temperatures cannot be monitored.

Possible Causes
Battery temperature sensor 1 is faulty.

Procedure
1. Replace battery temperature sensor 1 and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.6 Battery Temperature Sensor 2 Fault


Description
When detecting that battery temperature sensor 2 is faulty, the SMU generates a Battery
Temperature Sensor 2 Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11355 Major ADAC

Impact on the System


Battery temperatures cannot be monitored.

Possible Causes
Battery temperature sensor 2 is faulty.

Procedure
1. Replace battery temperature sensor 2 and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,199/359(W)

Parent topic: Battery Group

1.16.7 Battery Equalized Charging


Description
When detecting that batteries are being charged in equalized mode, the SMU generates
a Battery Equalized Charging alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11303 Warning ADAC

Impact on the System


Batteries are in equalized charging mode.

Possible Causes
Batteries are in equalized charging mode.

Procedure
No measure is required.

Parent topic: Battery Group

1.16.8 BLVD Disconnected


Description
When detecting that the battery low voltage disconnection (BLVD) route is
disconnected, the SMU generates a BLVD Disconnected alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11304 Major ADAC

Impact on the System


Batteries fail to supply power to the power system because the BLVD route is
disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,200/359(W)

Possible Causes
The battery voltage drops to the BLVD voltage because AC power fails for a long
time.
The battery temperature exceeds the very high temperature alarm threshold and
Very High Temperature Protection Mode is Disconnect Battery.

Procedure
1. Check whether the battery voltage drops to the BLVD voltage because AC power
fails for a long time.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether a Battery Very High Temperature alarm is generated and whether
temperature control devices in the battery compartment, such as the fan and air
conditioner, are abnormal.
If yes, maintain the devices.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.9 Battery Equalized Charging


Protection
Description
When detecting that the battery equalized charging protection time expires, the SMU
generates a Battery Equalized Charging Protection alarm. After the time expires,
batteries start to be charged in float mode.

Attribute

Alarm ID Alarm Severity Alarm Type

11305 Major ADAC

Impact on the System


Batteries start to be charged in float mode after equalized charging protection time
expires.

Possible Causes
The battery equalized charging protection time is not properly set.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,201/359(W)

Procedure
1. Check whether the battery equalized charging protection time is not properly set.
If yes, reset the time.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.10 BLVD Warning


Description
When detecting that batteries are about to disconnect, the SMU generates a BLVD
Warning alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11330 Major ADAC

Impact on the System


Batteries will fail to supply power to the power system because the BLVD route is
about to disconnect.

Possible Causes
The battery voltage drops to the BLVD voltage because AC power fails for a long
time.
The battery temperature exceeds the very high temperature alarm threshold and
Very High Temperature Protection Mode is Disconnect Battery.

Procedure
1. Check whether the battery voltage drops to the BLVD voltage because AC power
fails for a long time.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether a Battery Very High Temperature alarm is generated and whether
temperature control devices in the battery compartment, such as the fan and air
conditioner, are abnormal.
If yes, maintain the devices.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,202/359(W)

Parent topic: Battery Group

1.16.11 Battery Discharging


Description
When detecting that batteries are discharging, the SMU generates a Battery Discharging
alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11331 Warning ADAC

Impact on the System


The battery backup time reduces due to battery discharge.

Possible Causes
An AC power failure occurs.

Procedure
1. Check whether an AC power failure occurs.
If yes, troubleshoot power grid failures.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.12 Battery Temperature


Compensation Activated
Description
When detecting that battery temperature compensation is activated, the SMU generates
a Battery Temperature Compensation Activated alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11332 Warning ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,203/359(W)

Impact on the System


The SMU automatically adjusts the output voltage after battery temperature
compensation is activated.

Possible Causes
Battery temperature compensation is activated.

Procedure
No measure is required.

Parent topic: Battery Group

1.16.13 Battery Not Detected


Description
When detecting no batteries, the SMU generates a Battery Not Detected alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11341 Warning ADAC

Impact on the System


Power supply to the site will be disconnected if an AC power failure occurs because
batteries are disconnected.

Possible Causes
Batteries are not installed.
The battery circuit breaker is OFF.

Procedure
1. Check whether batteries are installed.
If no, determine whether batteries are required. If they are not required, disable
the alarm.
If yes, go to the next step.

2. Check whether the battery circuit breaker is OFF.


If yes, switch on the battery circuit breaker.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,204/359(W)

Parent topic: Battery Group

1.16.14 Battery Reversely Connection


Description
When detecting that batteries are reversely connected, the SMU generates a Battery
Reversely Connection alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11343 Major ADAC

Impact on the System


Batteries fail to back up power because they are reversely connected.

Possible Causes
Batteries are reversely connected.

Procedure
1. Check whether battery cables are incorrectly connected.
If yes, connect the cables correctly.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.15 Battery Very High Temperature


Description
When detecting that the battery temperature exceeds the very high temperature alarm
threshold, the SMU generates a Battery Very High Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11345 Major ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,205/359(W)

Impact on the System


Battery performance will deteriorate and battery lifespan will be shortened.

Possible Causes
The battery temperature exceeds the very high temperature alarm threshold.
The battery very high temperature alarm threshold is not properly set.
The battery temperature sensor is faulty.

Procedure
1. Check whether temperature control devices in the battery compartment, such as the
fan and air conditioner, are abnormal.
If yes, maintain the devices.
If no, go to the next step.

2. Check whether the battery very high temperature alarm threshold is not properly
set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the battery temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.16 Battery Very Low Temperature


Description
When detecting that the battery temperature is below the very low temperature alarm
threshold, the SMU generates a Battery Very Low Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11346 Minor ADAC

Impact on the System


Backup power reliability is compromised because battery performance deteriorates.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,206/359(W)

Possible Causes
The battery temperature is below the very low temperature alarm threshold.
The battery very low temperature alarm threshold is not properly set.
The battery temperature sensor is faulty.

Procedure
1. Check whether the heater in the battery compartment is abnormal.
If yes, maintain the heater.
If no, go to the next step.

2. Check whether the battery very low temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the battery temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery Group

1.16.17 Battery Forcibly Connection


Description
When detecting that batteries are manually connected, the SMU generates a Battery
Forcibly Connection alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11347 Major ADAC

Impact on the System


Batteries may be permanently damaged.

Possible Causes
Batteries are manually connected.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,207/359(W)

If manual battery connection is not required, flip the battery switch to OFF.

Parent topic: Battery Group

1.16.18 Battery Test Cancelled


Description
When detecting that a battery test is canceled, the SMU generates a Battery Test
Cancelled alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11348 Warning ADAC

Impact on the System


Battery status cannot be monitored.

Possible Causes
The battery test is manually canceled.
Certain alarms about battery tests are generated.

Procedure
1. Check whether the battery test is manually canceled.
If yes, no further action is required.
If no, go to the next step.

2. Check whether certain alarms about battery tests are generated.


If no, clear the alarms.
If yes, contact Huawei technical support.

Parent topic: Battery Group

1.16.19 Battery Current Imbalance


Description
During a short test, when detecting that the absolute value of the difference between the

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,208/359(W)

currents of two shunts is greater than the maximum current difference in the short test
multiplied by rated battery capacity, the SMU generates a Battery Current Imbalance
alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11349 Warning ADAC

Impact on the System


The battery backup function deteriorates because the battery current is unbalanced.

Possible Causes
Batteries are faulty.

Procedure
1. Replace batteries and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Battery Group

1.16.20 Battery Charge Overcurrent


Description
When detecting that the battery charge current exceeds the charge overcurrent alarm
threshold, the SMU generates a Battery Charge Overcurrent alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11356 Major ADAC

Impact on the System


Battery performance will deteriorate and battery lifespan will be shortened because
batteries are prone to damage due to battery charge overcurrent.

Possible Causes
A battery is faulty.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,209/359(W)

The rectifier fails in communication.

Procedure
1. Switch off the battery circuit breaker and check whether the battery voltage is
abnormal.
If yes, replace faulty batteries.
If no, go to the next step.

2. Check whether a Battery Equalized Charging Protection alarm is generated.


If yes, rectify the fault in the same way as clearing a Battery Equalized Charging
Protection alarm.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.21 Low Battery Capacity


Description
When detecting that the remaining battery capacity is below the over low capacity
alarm threshold, the SMU generates a Low Battery Capacity alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11357 Warning ADAC

Impact on the System


Power supply reliability will deteriorate because the power system backup time is short.

Possible Causes
The remaining battery capacity is below the over low capacity alarm threshold
because AC power fails for a long time.
The over low capacity alarm threshold is not properly set.

Procedure
1. Check whether the remaining battery capacity is below the over low capacity alarm
threshold because AC power fails for a long time.
If yes, troubleshoot power grid failures.
If no, go to the next step.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,210/359(W)

2. Check whether the over low capacity alarm threshold is not properly set.
If no, reset the alarm threshold.
If yes, contact Huawei technical support.

Parent topic: Battery Group

1.16.22 Battery Breaker Trip


Description
When detecting that the battery circuit breaker is OFF, the SMU generates a Battery
Breaker Trip alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10721 Critical ADAC

Impact on the System


The power system cannot backup power.

Possible Causes
The battery circuit breaker is switched off manually.
The battery circuit breaker detection cable is loosened.
The battery circuit breaker protects itself against overcurrent due to the abnormal
battery.
The battery circuit breaker is faulty.

Procedure
1. Check that whether the battery circuit breaker is switched off manually.
If yes, clear the alarm.
If no, go to the next step.

2. Check that whether the battery circuit breaker detection cable is loosened.
If yes, secure the battery circuit breaker detection cable.
If no, go to the next step.

3. Check that whether the battery is abnormal.


If yes, maintenance the battery.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,211/359(W)

If no, go to the next step.

4. Check that whether the battery circuit breaker is faulty.


If yes, replace the battery circuit breaker.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.23 Battery Test Negative


Description
1. The test type is a standard test.
2. The test data is the discharge test result used for check.
3. The test ends because the battery voltage reaches the end-of-discharge (EOD)
voltage.

Attribute

Alarm ID Alarm Severity Alarm Type

11361 Major ADAC

Impact on the System


Batteries may have insufficient backup power.

Possible Causes
Batteries are damaged due to high temperatures or years of use.

Procedure
Replace batteries with new ones or use more special means to test whether the batteries
can back up sufficient power.

Parent topic: Battery Group

1.16.24 Battery Undervoltage


Description
This alarm is generated if the voltage of any battery is low.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,212/359(W)

Attribute
Alarm ID Alarm Severity Alarm Type
10723 Major ADAC

Impact on the System


Battery performance will deteriorate and the battery lifespan will be shortened.

Possible Causes
Battery overdischarging causes battery undervoltage.
The device is faulty.

Procedure
1. Check whether the AC input is abnormal.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.25 Battery Cell Deterioration


Description
This alarm is generated when the discharging voltage of a single battery is 20% less
than the average voltage of the whole string for more than 1 minute.

Attribute

Alarm ID Alarm Severity Alarm Type

11367 Major ADAC

Impact on the System


The power backup time reduces.

Possible Causes
The electrochemical cell is damaged.
The single battery cable is incorrectly connected or loose.
The electrochemical cells of the whole battery string deteriorate.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,213/359(W)

Procedure
1. Check whether the battery exterior is abnormal such as leakage.
If yes, replace the electrochemical cell.
If no, go to the next step.

2. Check whether the single battery cable is incorrectly or not securely connected.
If yes, reconnect the cable.
If no, go to the next step.

3. Replace the battery, reset the battery capacity, and check whether the alarm is
cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.26 Battery Thermal Runaway


Description
This alarm is generated when the temperature of a single battery is 20ºC greater than
the average temperature of the whole string for more than 10 minutes.

Attribute

Alarm ID Alarm Severity Alarm Type

11366 Critical ADAC

Impact on the System


There is a risk of fire at the site.

Possible Causes
The battery is faulty.

Procedure
1. Check whether the single battery cable is incorrectly connected or loose.
If yes, reconnect the cable.
If no, go to the next step.

2. Check whether the battery is leaking or damaged.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,214/359(W)

If yes, replace the single battery.


If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.27 Battery Imbalance


Description
This alarm is generated if the charging voltage of a single battery deviates more than
10% of the whole string's average voltage for more than 10 minutes.

Attribute

Alarm ID Alarm Severity Alarm Type

11365 Warning ADAC

Impact on the System


The battery backup time reduces due to damage of a single battery.

Possible Causes
The battery voltage is imbalanced.
The sampling is abnormal.

Procedure
1. Check whether the single battery is connected abnormally.
If yes, reconnect the cable.
If no, go to the next step.

2. Check whether the battery voltage is abnormal.


If yes, replace the single battery.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.28 Insufficient Backup


Description

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,215/359(W)

After the battery is fully charged, it discharges to the time for LLVD or BLVD, to the
point where its capacity is insufficient to provide the configured expected power
backup time, or to the capacity alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

11364 Warning ADAC

Impact on the System


The battery backup time is insufficient due to battery deterioration.

Possible Causes
The battery backup time is insufficient.

Procedure
1. Check whether the parameter configurations of the battery and loads are incorrectly
set.
If yes, modify the LLVD or BLVD expected backup time, or the capacity alarm
threshold.
If no, go to the next step.

2. Start the equalized charging to fully charge the battery. Discharge the battery
afterwards and determine whether the battery backup is abnormal.
If yes, replace the battery.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.16.29 Battery Sub-health


Description
The SOH is equal or less than the SOH sub-health value.

Attribute

Alarm ID Alarm Severity Alarm Type

11363 Minor ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,216/359(W)

The power backup time is insufficient.

Possible Causes
The actual battery capacity drops due to battery deterioration or damage.

Procedure
1. Check whether the battery performs abnormally.
If yes, check whether the battery needs to be replaced.
If no, no further action is required.

Parent topic: Battery Group

1.16.30 Battery Deterioration


Description
The SOH is equal or less than the SOH self-load value.

Attribute

Alarm ID Alarm Severity Alarm Type

11362 Major ADAC

Impact on the System


The power backup time is insufficient.

Possible Causes
The actual battery capacity drops due to battery deterioration or damage.

Procedure
1. Check whether the battery exterior is damaged such as leakage.
If yes, replace the battery and reset the battery capacity.
If no, go to the next step.

2. Tightly secure the battery connection, and start the equalized charging. After that,
start the standard battery test. (This process may take over ten hours.) Check
whether the alarm is cleared afterwards.
If yes, no further action is required.
If no, go to the next step.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,217/359(W)

3. Replace the battery, reset the battery capacity, and check whether the alarm is
cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Battery Group

1.17 Power System


AC Surge Protector Fault

DC SPD Fault

AC Failure

AC Phase L1 Overvoltage

AC Phase L2 Overvoltage

AC Phase L3 Overvoltage

AC Phase L1 Undervoltage

AC Phase L2 Undervoltage

AC Phase L3 Undervoltage

AC Phase L1 Failure

AC Phase L2 Failure

AC Phase L3 Failure

AC Overvoltage

AC Undervoltage

DC Overvoltage

DC Undervoltage

DC Ultra Overvoltage

DC Ultra Undervoltage

Load Fuse Broken

Load Fuse1 Broken

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,218/359(W)

Load Fuse2 Broken

Load Fuse3 Broken

Load Fuse4 Broken

Load Fuse5 Broken

Load Fuse6 Broken

Load Fuse7 Broken

Load Fuse8 Broken

Load Fuse9 Broken

Load Fuse10 Broken

Load Fuse11 Broken

Load Fuse12 Broken

Load Fuse13 Broken

Load Fuse14 Broken

Load Fuse15 Broken

Load Fuse16 Broken

Load Fuse17 Broken

Load Fuse18 Broken

Load Fuse19 Broken

Load Fuse20 Broken

Load Fuse21 Broken

Load Fuse22 Broken

Load Fuse23 Broken

SMU Fault

Insufficient Alarm Space

Very High Ambient Temperature

Unknown System Type

Door Open Alarm

Water Alarm

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,219/359(W)

Smoke Alarm

High Ambient Temperature

Low Ambient Temperature

High Ambient Humidity

Low Ambient Humidity

Ambient Temperature Sensor Missing

Ambient Temperature Sensor Fault

Ambient Humidity Sensor Missing

Ambient Humidity Sensor Fault

LLVD Warning

LLVD Disconnected

LLVD2 Warning

LLVD2 Disconnected

LLVD3 Warning

LLVD3 Disconnected

Long Mains Failure

Temp1 Sensor Missing

Temp2 Sensor Missing

Temp1 Sensor Fault

Temp2 Sensor Fault

Temp1 High Temperature

Temp2 High Temperature

Temp1 Low Temperature

Temp2 Low Temperature

DIN1 Alarm

DIN2 Alarm

DIN3 Alarm

DIN4 Alarm

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,220/359(W)

DIN5 Alarm

DIN6 Alarm

DIN7 Alarm

DIN8 Alarm

TEC Alarm

Heater Fault

Abnormal System Voltage Check

Abnormal System Current Check

TCUA Alarm

Load Breaker Trip

Main AC Breaker Trip

DCD Comm Fail

AC Phase L1 Failure

AC Phase L2 Failure

AC Phase L3 Failure

AC L1-L2 Overvoltage

AC L2-L3 Overvoltage

AC L3-L1 Overvoltage

AC L1-L2 Undervoltage

AC L2-L3 Undervoltage

AC L3-L1 Undervoltage

Custom Alarm 1

Custom Alarm 2

Custom Alarm 3

Custom Alarm 4

Custom Alarm 5

Custom Alarm 6

Custom Alarm 7

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,221/359(W)

Custom Alarm 8

Custom Alarm 9

Custom Alarm 10

Custom Alarm 11

Custom Alarm 12

Custom Alarm 13

Custom Alarm 14

Custom Alarm 15

Custom Alarm 16

Custom Alarm 17

Custom Alarm 18

Custom Alarm 19

Custom Alarm 20

Power System Undervoltage

Power System Overvoltage

Vibration Alarm

Illegal Door Open

Parent topic: Site Alarm Reference

1.17.1 AC Surge Protector Fault


Description
When detecting that an AC surge protective device (SPD) is faulty, the SMU generates
an AC SPD Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10200 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,222/359(W)

The power system may be damaged in thunderstorms.

Possible Causes
The AC SPD is faulty.
The signal cable for monitoring the AC SPD is loose.
The signal cable for monitoring the AC SPD is incorrectly connected.

Procedure
1. Check whether the indication window on the AC SPD turns red.
If yes, replace the AC SPD.
If no, go to the next step.

2. Check whether the signal cable for monitoring the AC SPD is loose.
If yes, secure the connector.
If no, go to the next step.

3. Check whether the signal cable for monitoring the AC SPD connects to the NC
terminal.
If no, connect the signal cable to the NC terminal.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.2 DC SPD Fault


Description
When detecting that a DC surge protective device (SPD) is faulty, the SMU generates a
DC SPD Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10201 Major ADAC

Impact on the System


The power system may be damaged in thunderstorms.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,223/359(W)

The DC SPD is faulty.


The signal cable for monitoring the DC SPD is loose.

Procedure

NOTICE:
Before performing the following operations, power off the power system.

Check whether the signal cable for monitoring the DC SPD is loose.

If yes, secure the connector.


If no, replace the DC SPD.

Parent topic: Power System

1.17.3 AC Failure
Description
When detecting that an AC power failure occurs, the SMU generates an AC Failure
alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10202 Major ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
The AC power fails.
The AC input circuit breaker is OFF.

Procedure
1. Check whether the AC input voltage is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the AC input circuit breaker is OFF.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,224/359(W)

If yes, check and repair the power distribution, and then switch on the circuit
breaker.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.4 AC Phase L1 Overvoltage


Description
When detecting that the AC phase voltage for phase L1 exceeds the overvoltage alarm
threshold, the SMU generates an AC Phase L1 Overvoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10203 Minor ADAC

Impact on the System


The equipment may be damaged and the power supply may be disconnected.

Possible Causes
The phase voltage for phase L1 exceeds the overvoltage alarm threshold.
The AC overvoltage alarm threshold is not properly set on the SMU.

Procedure
1. Check whether the phase voltage for phase L1 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the AC overvoltage alarm threshold is not properly set on the SMU.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.5 AC Phase L2 Overvoltage

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,225/359(W)

Description
When detecting that the AC phase voltage for phase L2 exceeds the overvoltage alarm
threshold, the SMU generates an AC Phase L2 Overvoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10204 Minor ADAC

Impact on the System


The equipment may be damaged and the power supply may be disconnected.

Possible Causes
The phase voltage for phase L2 exceeds the overvoltage alarm threshold.
The AC overvoltage alarm threshold is not properly set on the SMU.

Procedure
1. Check whether the phase voltage for phase L2 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the AC overvoltage alarm threshold is not properly set on the SMU.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.6 AC Phase L3 Overvoltage


Description
When detecting that the AC phase voltage for phase L3 exceeds the overvoltage alarm
threshold, the SMU generates an AC Phase L3 Overvoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10205 Minor ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,226/359(W)

The equipment may be damaged and the power supply may be disconnected.

Possible Causes
The phase voltage for phase L3 exceeds the overvoltage alarm threshold.
The AC overvoltage alarm threshold is not properly set on the SMU.

Procedure
1. Check whether the phase voltage for phase L3 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the AC overvoltage alarm threshold is not properly set on the SMU.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.7 AC Phase L1 Undervoltage


Description
When detecting that the AC phase voltage for phase L1 is below the undervoltage alarm
threshold, the SMU generates an AC Phase L1 Undervoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10206 Minor ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
The phase voltage for phase L1 is below the undervoltage alarm threshold.
The AC undervoltage alarm threshold is not properly set on the SMU.

Procedure
1. Check whether the phase voltage for phase L1 is abnormal.
If yes, troubleshoot power grid failures.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,227/359(W)

If no, go to the next step.

2. Check whether the AC undervoltage alarm threshold is not properly set on the
SMU.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.8 AC Phase L2 Undervoltage


Description
When detecting that the AC phase voltage for phase L2 is below the undervoltage alarm
threshold, the SMU generates an AC Phase L2 Undervoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10207 Minor ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
The phase voltage for phase L2 is below the undervoltage alarm threshold.
The AC undervoltage alarm threshold is not properly set on the SMU.

Procedure
1. Check whether the phase voltage for phase L2 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the AC undervoltage alarm threshold is not properly set on the
SMU.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,228/359(W)

1.17.9 AC Phase L3 Undervoltage


Description
When detecting that the AC phase voltage for phase L3 is below the undervoltage alarm
threshold, the SMU generates an AC Phase L3 Undervoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10208 Minor ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
The phase voltage for phase L3 is below the undervoltage alarm threshold.
The AC undervoltage alarm threshold is not properly set on the SMU.

Procedure
1. Check whether the phase voltage for phase L3 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the AC undervoltage alarm threshold is not properly set on the
SMU.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.10 AC Phase L1 Failure


Description
When detecting that AC input phase L1 is open, the SMU generates an AC Phase L1
Failure alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,229/359(W)

Alarm ID Alarm Severity Alarm Type

10209 Major ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
Power supply to phase L1 is disconnected.
The circuit breaker for phase L1 is OFF.

Procedure
1. Check whether the phase voltage for phase L1 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the circuit breaker for phase L1 is OFF.


If yes, check and repair the power distribution, and then switch on the circuit
breaker.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.11 AC Phase L2 Failure


Description
When detecting that AC input phase L2 is open, the SMU generates an AC Phase L2
Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10210 Major ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
Power supply to phase L2 is disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,230/359(W)

The circuit breaker for phase L2 is OFF.

Procedure
1. Check whether the phase voltage for phase L2 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the circuit breaker for phase L2 is OFF.


If yes, check and repair the power distribution, and then switch on the circuit
breaker.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.12 AC Phase L3 Failure


Description
When detecting that AC input phase L3 is open, the SMU generates an AC Phase L3
Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10213 Major ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
Power supply to phase L3 is disconnected.
The circuit breaker for phase L3 is OFF.

Procedure
1. Check whether the phase voltage for phase L3 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the circuit breaker for phase L3 is OFF.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,231/359(W)

If yes, check and repair the power distribution, and then switch on the circuit
breaker.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.13 AC Overvoltage
Description
When detecting that the AC input voltage exceeds the overvoltage alarm threshold, the
SMU generates an AC Overvoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10214 Minor ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
The AC voltage exceeds the alarm threshold.
The AC overvoltage alarm threshold is not properly set on the SMU.

Procedure
1. Check whether the AC input voltage is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the AC overvoltage alarm threshold is not properly set on the SMU.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.14 AC Undervoltage

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,232/359(W)

Description
When detecting that the AC input voltage is below the undervoltage alarm threshold,
the SMU generates an AC Undervoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10215 Minor ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
The AC voltage is below the undervoltage alarm threshold.
The AC undervoltage alarm threshold is not properly set on the SMU.

Procedure
1. Check whether the AC input voltage is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the AC undervoltage alarm threshold is not properly set on the
SMU.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.15 DC Overvoltage
Description
When detecting that the DC voltage exceeds the overvoltage alarm threshold, the SMU
generates a DC Overvoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10152 Minor ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,233/359(W)

Impact on the System


The loads may be damaged or the power supply to loads may be disconnected.

Possible Causes
Rectifiers are faulty.
The DC overvoltage alarm threshold is not properly set.

Procedure
1. Check whether certain rectifiers are faulty.
If yes, replace faulty rectifiers.
If no, go to the next step.

2. Check whether the DC overvoltage alarm threshold is not properly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.16 DC Undervoltage
Description
When detecting that the DC voltage is below the undervoltage alarm threshold, the
SMU generates a DC Undervoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10153 Major ADAC

Impact on the System


The power system will stop powering loads for a short time.

Possible Causes
The battery voltage is below the undervoltage alarm threshold because AC power
fails for a long time.
The DC undervoltage alarm threshold is not properly set.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,234/359(W)

1. Check whether the battery voltage is below the undervoltage alarm threshold
because AC power fails for a long time.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the DC undervoltage alarm threshold is not properly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.17 DC Ultra Overvoltage


Description
When detecting that the DC voltage exceeds the ultra overvoltage alarm threshold, the
SMU generates a DC Ultra Overvoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10154 Major ADAC

Impact on the System


The loads may be damaged or the power supply to loads may be disconnected.

Possible Causes
Rectifiers are faulty.
The DC ultra overvoltage alarm threshold is not properly set.

Procedure
1. Check whether certain rectifiers are faulty.
If yes, replace faulty rectifiers.
If no, go to the next step.

2. Check whether the DC ultra overvoltage alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,235/359(W)

1.17.18 DC Ultra Undervoltage


Description
When detecting that the DC voltage is below the ultra undervoltage alarm threshold, the
SMU generates a DC Ultra Undervoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10155 Critical ADAC

Impact on the System


The power system will stop powering loads for a short time.

Possible Causes
The battery voltage is below the ultra undervoltage alarm threshold because AC
power fails for a long time.
The DC ultra undervoltage alarm threshold is not properly set.

Procedure
1. Check whether the battery voltage is below the ultra undervoltage alarm threshold
because AC power fails for a long time.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the DC ultra undervoltage alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.19 Load Fuse Broken


Description
When detecting that the load fuse is blown or the load circuit breaker is OFF, the SMU
generates a Load Fuse Break alarm.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,236/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

10169 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit breaker is OFF.
The load fuse or circuit breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit breaker is OFF.
If yes, check and repair the load, and then switch on the circuit breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.20 Load Fuse1 Broken


Description
When detecting that the load fuse is blown or the load circuit breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10170 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit breaker or fuse is disconnected.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,237/359(W)

The load fuse is blown or the load circuit breaker is OFF.


The load fuse or circuit breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit breaker is OFF.
If yes, check and repair the load, and then switch on the circuit breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.21 Load Fuse2 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10171 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,238/359(W)

If yes, secure the cable.


If no, contact Huawei technical support.

Parent topic: Power System

1.17.22 Load Fuse3 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10172 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.23 Load Fuse4 Broken


Description

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,239/359(W)

When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10173 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.24 Load Fuse5 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10175 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,240/359(W)

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.25 Load Fuse6 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10176 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,241/359(W)

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.26 Load Fuse7 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10177 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.27 Load Fuse8 Broken

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,242/359(W)

Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10178 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.28 Load Fuse9 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10179 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,243/359(W)

Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.29 Load Fuse10 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10180 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,244/359(W)

If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.30 Load Fuse11 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10181 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,245/359(W)

1.17.31 Load Fuse12 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10182 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.32 Load Fuse13 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,246/359(W)

Alarm ID Alarm Severity Alarm Type

10183 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.33 Load Fuse14 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10184 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,247/359(W)

The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.34 Load Fuse15 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10185 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,248/359(W)

If no, contact Huawei technical support.

Parent topic: Power System

1.17.35 Load Fuse16 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10186 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.36 Load Fuse17 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,249/359(W)

generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10187 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.37 Load Fuse18 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10188 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,250/359(W)

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.38 Load Fuse19 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Broken alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10189 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,251/359(W)

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.39 Load Fuse20 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Break alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10190 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.40 Load Fuse21 Broken

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,252/359(W)

Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Break alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10191 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.41 Load Fuse22 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Break alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10192 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,253/359(W)

Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.
If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.42 Load Fuse23 Broken


Description
When detecting that the load fuse is blown or the load circuit Breaker is OFF, the SMU
generates a Load Fuse Break alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10193 Major ADAC

Impact on the System


Power supply to the load connecting to the load circuit Breaker or fuse is disconnected.

Possible Causes
The load fuse is blown or the load circuit Breaker is OFF.
The load fuse or circuit Breaker detection cable is disconnected.

Procedure
1. Check whether the load fuse is blown or the load circuit Breaker is OFF.
If yes, check and repair the load, and then switch on the circuit Breaker.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,254/359(W)

If no, go to the next step.

2. Check whether the load fuse or circuit Breaker detection cable is disconnected.
If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.43 SMU Fault


Description
When detecting a fault in itself, the SMU generates an SMU Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10216 Major ADAC

Impact on the System


The system operating status cannot be monitored.

Possible Causes
The SMU is faulty.

Procedure
Replace the SMU and check whether the alarm persists.

If no, no further action is required.


If yes, contact Huawei technical support.

Parent topic: Power System

1.17.44 Insufficient Alarm Space


Description
The SMU generates an alarm when the space for storing historical alarms will soon be
used up.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,255/359(W)

Attribute
Alarm ID Alarm Severity Alarm Type
10242 Warning ADAC

Impact on the System


Earlier historical alarms will be overwritten and need to be exported in time.

Possible Causes
The number of historical alarms is about to reach the upper threshold.

Procedure
1. Export historical alarms in time.

Parent topic: Power System

1.17.45 Very High Ambient Temperature


Description
When detecting that the ambient temperature exceeds the very high temperature alarm
threshold, the SMU generates a Very High Ambient Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10211 Major ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at high temperatures.

Possible Causes
The ambient temperature exceeds the alarm threshold.
The ambient very high temperature alarm threshold is not properly set.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
abnormal.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,256/359(W)

If yes, maintain the devices.


If no, go to the next step.

2. Check whether the ambient very high temperature alarm threshold is not properly
set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.46 Unknown System Type


Description
When detecting that no power system type is selected, the SMU generates an Unknown
System Type alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10131 Critical ADAC

Impact on the System


The SMU controls the power system by using default parameter values that may not
match the power system.

Possible Causes
No power system type is selected.

Procedure
Set the power system type or contact Huawei technical support.

Parent topic: Power System

1.17.47 Door Open Alarm

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,257/359(W)

Description
When detecting that the cabinet door of the power system is open, the SMU generates a
Door Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10217 Minor ADAC

Impact on the System


The power system has potential troubles.

Possible Causes
The cabinet door of the power system is open.
The connector on the door status sensor cable is loose.
The door status sensor is faulty.

Procedure
1. Close the cabinet door of the power system and check whether the alarm is cleared.
If yes, no further action is required.
If no, go to the next step.

2. Check whether the connector on the door status sensor cable is loose.
If yes, secure the connector.
If no, go to the next step.

3. Replace the door status sensor and close the cabinet door, and then check whether
the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.48 Water Alarm


Description
When detecting water in the power system cabinet, the SMU generates a Water Alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,258/359(W)

Alarm ID Alarm Severity Alarm Type

10218 Critical ADAC

Impact on the System


The power system has potential troubles.

Possible Causes
Water intrudes into the cabinet.
The water sensor is faulty.

Procedure
1. Check whether water intrudes into the cabinet.
If yes, eliminate water from the cabinet.
If no, go to the next step.

2. Replace the water sensor and check whether the alarm persists.
If yes, secure the connector.
If no, go to the next step.

3. Replace the water sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.49 Smoke Alarm


Description
When detecting smoke in the power system cabinet, the SMU generates a Smoke
Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10219 Critical ADAC

Impact on the System


The power system has potential troubles.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,259/359(W)

Possible Causes
There is smoke inside the cabinet.
The smoke sensor is faulty.

Procedure
1. Check whether there is smoke inside the cabinet.
If yes, shut down the power system and rectify the fault.
If no, go to the next step.

2. Replace the smoke sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.50 High Ambient Temperature


Description
When detecting that the ambient temperature exceeds the high temperature alarm
threshold, the SMU generates a High Ambient Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10220 Minor ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at high temperatures.

Possible Causes
The ambient temperature exceeds the alarm threshold.
The high ambient temperature alarm threshold is not properly set.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
abnormal.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,260/359(W)

If yes, maintain the temperature control devices.


If no, go to the next step.

2. Check whether the high ambient temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.51 Low Ambient Temperature


Description
When detecting that the ambient temperature is below the low temperature alarm
threshold, the SMU generates a Low Ambient Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10221 Warning ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at low temperatures.

Possible Causes
The ambient temperature is below the alarm threshold.
The low ambient temperature alarm threshold is not properly set.
The ambient temperature sensor is faulty.

Procedure
1. Check whether the heater is abnormal.
If yes, maintain the heater.
If no, go to the next step.

2. Check whether the low ambient temperature alarm threshold is not properly set.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,261/359(W)

If yes, reset the alarm threshold.


If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.52 High Ambient Humidity


Description
When detecting that the ambient humidity exceeds the high humidity alarm threshold,
the SMU generates a High Ambient Humidity alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10222 Warning ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at high humidity.

Possible Causes
The ambient humidity exceeds the alarm threshold.
The ambient high humidity alarm threshold is not properly set.
The ambient temperature and humidity sensor is faulty.

Procedure
1. Check whether all cable holes are sealed and the cabinet door is closed.
If no, seal all cable holes and close the cabinet door.
If yes, go to the next step.

2. Check whether the ambient high humidity alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature and humidity sensor and check whether the alarm

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,262/359(W)

persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.53 Low Ambient Humidity


Description
When detecting that the ambient humidity is below the low humidity alarm threshold,
the SMU generates a Low Ambient Humidity alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10223 Warning ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at low humidity.

Possible Causes
The ambient humidity is below the alarm threshold.
The low ambient humidity alarm threshold is not properly set.
The ambient temperature and humidity sensor is faulty.

Procedure
1. Check whether the ambient humidity is below the alarm threshold.
If yes, no further action is required.
If no, go to the next step.

2. Check whether the low ambient humidity alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature and humidity sensor and check whether the alarm
persists.
If no, no further action is required.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,263/359(W)

If yes, contact Huawei technical support.

Parent topic: Power System

1.17.54 Ambient Temperature Sensor


Missing
Description
When detecting that an ambient temperature sensor is disconnected, the SMU generates
an Ambient Temperature Sensor Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10114 Warning ADAC

Impact on the System


The ambient temperature cannot be monitored.

Possible Causes
The ambient temperature sensor is disconnected.
The connector on the ambient temperature sensor cable is disconnected.
The ambient temperature sensor is faulty.

Procedure
1. Check whether the ambient temperature sensor is connected.
If no, connect the ambient temperature sensor.
If yes, go to the next step.

2. Check whether the connector on the ambient temperature sensor cable is


disconnected.
If yes, secure the connector.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,264/359(W)

Parent topic: Power System

1.17.55 Ambient Temperature Sensor Fault


Description
When detecting that an ambient temperature sensor is faulty, the SMU generates an
Ambient Temperature Sensor Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10115 Major ADAC

Impact on the System


The ambient temperature cannot be monitored.

Possible Causes
The ambient temperature sensor is faulty.

Procedure
Replace the ambient temperature sensor and check whether the alarm persists.

If no, no further action is required.


If yes, contact Huawei technical support.

Parent topic: Power System

1.17.56 Ambient Humidity Sensor Missing


Description
When detecting that an ambient temperature and humidity sensor is disconnected, the
SMU generates an Ambient Humidity Sensor Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10110 Warning ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,265/359(W)

Impact on the System


The ambient humidity cannot be monitored.

Possible Causes
The ambient temperature and humidity sensor is disconnected.
The connector on the ambient temperature and humidity sensor cable is
disconnected.
The ambient temperature and humidity sensor is faulty.

Procedure
1. Check whether the ambient temperature and humidity sensor is connected.
If no, connect the ambient temperature and humidity sensor.
If yes, go to the next step.

2. Check whether the connector on the ambient temperature and humidity sensor
cable is disconnected.
If yes, secure the connector.
If no, go to the next step.

3. Replace the ambient temperature and humidity sensor and check whether the alarm
is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.57 Ambient Humidity Sensor Fault


Description
When detecting that an ambient temperature and humidity sensor is faulty, the SMU
generates an Ambient Humidity Sensor Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10111 Minor ADAC

Impact on the System


The ambient humidity cannot be monitored.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,266/359(W)

Possible Causes
The ambient temperature and humidity sensor is faulty.

Procedure
Replace the ambient temperature and humidity sensor and check whether the alarm
persists.

If no, no further action is required.


If yes, contact Huawei technical support.

Parent topic: Power System

1.17.58 LLVD Warning


Description
When detecting that the load low voltage disconnection (LLVD) route is about to
disconnect because the battery voltage drops to the LLVD voltage, the SMU generates
an LLVD Warning alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10100 Major ADAC

Impact on the System


The LLVD route is about to disconnect.

Possible Causes
The battery voltage drops to the LLVD voltage because AC power fails for a long time.

Procedure
Check whether the battery voltage drops to the LLVD voltage because AC power fails
for a long time.

If yes, troubleshoot power grid failures.


If no, contact Huawei technical support.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,267/359(W)

1.17.59 LLVD Disconnected


Description
When detecting that the load low voltage disconnection (LLVD) route is disconnected,
the SMU generates an LLVD Disconnected alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10224 Major ADAC

Impact on the System


The LLVD route is disconnected.

Possible Causes
The battery voltage drops to the LLVD voltage because AC power fails for a long time.

Procedure
Check whether the battery voltage drops to the LLVD voltage because AC power fails
for a long time.

If yes, troubleshoot power grid failures.


If no, contact Huawei technical support.

Parent topic: Power System

1.17.60 LLVD2 Warning


Description
When detecting that the load low voltage disconnection 2 (LLVD2) route is about to
disconnect because the battery voltage drops to the LLVD2 voltage, the SMU generates
an LLVD2 Warning alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10225 Major ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,268/359(W)

The LLVD2 route is about to disconnect.

Possible Causes
The battery voltage drops to the LLVD2 voltage because AC power fails for a long
time.

Procedure
Check whether the battery voltage drops to the LLVD2 voltage because AC power fails
for a long time.

If yes, troubleshoot power grid failures.


If no, contact Huawei technical support.

Parent topic: Power System

1.17.61 LLVD2 Disconnected


Description
When detecting that the load low voltage disconnection 2 (LLVD2) route is
disconnected, the SMU generates an LLVD2 Disconnected alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10226 Major ADAC

Impact on the System


The LLVD2 route is disconnected.

Possible Causes
The battery voltage drops to the LLVD2 voltage because AC power fails for a long
time.

Procedure
Check whether the battery voltage drops to the LLVD2 voltage because AC power fails
for a long time.

If yes, troubleshoot power grid failures.


If no, contact Huawei technical support.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,269/359(W)

1.17.62 LLVD3 Warning


Description
The power-off conditions are met, and the load low voltage disconnection (LLVD)
route is about to power off.

Attribute
Alarm ID Alarm Severity Alarm Type
15256 Major ADAC

Impact on the System


The LLVD route is about to power off.

Possible Causes
The battery discharges due to a long AC power failure.

Procedure
1. Check whether an AC power failure occurs.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.63 LLVD3 Disconnected


Description
Power-off conditions are met, and the power-off delay time expires.

Attribute
Alarm ID Alarm Severity Alarm Type
15257 Major ADAC

Impact on the System


The LLVD route powers off.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,270/359(W)

The battery discharges due to a long AC power failure.

Procedure
1. Check whether an AC power failure occurs.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.64 Long Mains Failure


Description
When detecting that an AC power failure lasts for more than 10 minutes, the SMU
generates a Long Mains Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10212 Major ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
An AC power failure occurs.
The AC input circuit breaker is OFF.

Procedure
1. Check whether the AC input voltage is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the AC input circuit breaker is OFF.


If yes, check and repair the power distribution, and then switch on the circuit
breaker.
If no, contact Huawei technical support.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,271/359(W)

1.17.65 Temp1 Sensor Missing


Description
When detecting that a temperature sensor1 is disconnected, the SMU generates a
Temperature Sensor1 Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10233 Major ADAC

Impact on the System


The temperature sensor1 temperature cannot be monitored.

Possible Causes
The temperature sensor1 is disconnected.
The connector on the temperature sensor1 cable is disconnected.
The temperature sensor1 is faulty.

Procedure
1. Check whether the temperature sensor1 is connected.
If no, connect the temperature sensor1.
If yes, go to the next step.

2. Check whether the connector on the temperature sensor1 cable is disconnected.


If yes, secure the connector.
If no, go to the next step.

3. Replace the temperature sensor1 and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.66 Temp2 Sensor Missing

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,272/359(W)

Description
When detecting that a temperature sensor2 is disconnected, the SMU generates a
Temperature Sensor2 Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10234 Warning ADAC

Impact on the System


The temperature sensor2 temperature cannot be monitored.

Possible Causes
The temperature sensor2 is disconnected.
The connector on the temperature sensor2 cable is disconnected.
The temperature sensor2 is faulty.

Procedure
1. Check whether the temperature sensor2 is connected.
If no, connect the temperature sensor2.
If yes, go to the next step.

2. Check whether the connector on the temperature sensor2 cable is disconnected.


If yes, secure the connector.
If no, go to the next step.

3. Replace the temperature sensor2 and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.67 Temp1 Sensor Fault


Description
When detecting that a temperature sensor is faulty, the SMU generates a Temperature
Sensor1 Fault alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,273/359(W)

Alarm ID Alarm Severity Alarm Type

10235 Major ADAC

Impact on the System


The ambient temperature cannot be monitored.

Possible Causes
The ambient temperature sensor is faulty.

Procedure
Replace the ambient temperature sensor and check whether the alarm persists.

If no, no further action is required.


If yes, contact Huawei technical support.

Parent topic: Power System

1.17.68 Temp2 Sensor Fault


Description
When detecting that a temperature sensor is faulty, the SMU generates a Temperature
Sensor2 Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10236 Warning ADAC

Impact on the System


The ambient temperature cannot be monitored.

Possible Causes
The ambient temperature sensor is faulty.

Procedure
Replace the ambient temperature sensor and check whether the alarm persists.

If no, no further action is required.


If yes, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,274/359(W)

Parent topic: Power System

1.17.69 Temp1 High Temperature


Description
When detecting that the ambient temperature exceeds the high temperature alarm
threshold, the SMU generates a High Temperature1 alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10237 Minor ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at high temperatures.

Possible Causes
The ambient temperature exceeds the alarm threshold.
The high ambient temperature alarm threshold is not properly set.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
abnormal.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Check whether the high ambient temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,275/359(W)

1.17.70 Temp2 High Temperature


Description
When detecting that the ambient temperature exceeds the high temperature alarm
threshold, the SMU generates a High Temperature2 alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10238 Minor ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at high temperatures.

Possible Causes
The ambient temperature exceeds the alarm threshold.
The high ambient temperature alarm threshold is not properly set.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
abnormal.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Check whether the high ambient temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.71 Temp1 Low Temperature

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,276/359(W)

Description
When detecting that the ambient temperature is below the low temperature alarm
threshold, the SMU generates a Low Ambient Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10239 Minor ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at low temperatures.

Possible Causes
The ambient temperature below the alarm threshold.
The low ambient temperature alarm threshold is not properly set.
The ambient temperature sensor is faulty.

Procedure
1. Check whether the heater is abnormal.
If yes, maintain the heater.
If no, go to the next step.

2. Check whether the low ambient temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.72 Temp2 Low Temperature


Description
When detecting that the ambient temperature is below the low temperature alarm
threshold, the SMU generates a Low Ambient Temperature alarm.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,277/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

10241 Minor ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at low temperatures.

Possible Causes
The ambient temperature below the alarm threshold.
The low ambient temperature alarm threshold is not properly set.
The ambient temperature sensor is faulty.

Procedure
1. Check whether the heater is abnormal.
If yes, maintain the heater.
If no, go to the next step.

2. Check whether the low ambient temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Power System

1.17.73 DIN1 Alarm


Description
When detecting that the detection level for the dry contact is consistent with the alarm
condition, the SMU generates a DIN1 Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,278/359(W)

10227 Minor ADAC

Impact on the System


The devices connecting to the dry contact inputs cannot work properly.

Possible Causes
Devices connecting to the dry contact inputs are faulty.
Alarm conditions for the dry contact inputs are incorrectly set.

Procedure
1. Maintain the device connecting to the dry contact input and check whether the
alarm persists.
If no, no further action is required.
If yes, go to the next step.

2. Check whether the alarm condition for the dry contact input is incorrectly set.
If yes, reset the alarm condition.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.74 DIN2 Alarm


Description
When detecting that the detection level for the dry contact is consistent with the alarm
condition, the SMU generates a DIN2 Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10228 Minor ADAC

Impact on the System


The devices connecting to the dry contact inputs cannot work properly.

Possible Causes
Devices connecting to the dry contact inputs are faulty.
Alarm conditions for the dry contact inputs are incorrectly set.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,279/359(W)

Procedure
1. Maintain the device connecting to the dry contact input and check whether the
alarm persists.
If no, no further action is required.
If yes, go to the next step.

2. Check whether the alarm condition for the dry contact input is incorrectly set.
If yes, reset the alarm condition.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.75 DIN3 Alarm


Description
When detecting that the detection level for the dry contact is consistent with the alarm
condition, the SMU generates a DIN3 Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10229 Minor ADAC

Impact on the System


The devices connecting to the dry contact inputs cannot work properly.

Possible Causes
Devices connecting to the dry contact inputs are faulty.
Alarm conditions for the dry contact inputs are incorrectly set.

Procedure
1. Maintain the device connecting to the dry contact input and check whether the
alarm persists.
If no, no further action is required.
If yes, go to the next step.

2. Check whether the alarm condition for the dry contact input is incorrectly set.
If yes, reset the alarm condition.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,280/359(W)

If no, contact Huawei technical support.

Parent topic: Power System

1.17.76 DIN4 Alarm


Description
When detecting that the detection level for the dry contact is consistent with the alarm
condition, the SMU generates a DIN4 Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10230 Minor ADAC

Impact on the System


The devices connecting to the dry contact inputs cannot work properly.

Possible Causes
Devices connecting to the dry contact inputs are faulty.
Alarm conditions for the dry contact inputs are incorrectly set.

Procedure
1. Maintain the device connecting to the dry contact input and check whether the
alarm persists.
If no, no further action is required.
If yes, go to the next step.

2. Check whether the alarm condition for the dry contact input is incorrectly set.
If yes, reset the alarm condition.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.77 DIN5 Alarm


Description

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,281/359(W)

When detecting that the detection level for the dry contact is consistent with the alarm
condition, the SMU generates a DIN5 Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10231 Minor ADAC

Impact on the System


The devices connecting to the dry contact inputs cannot work properly.

Possible Causes
Devices connecting to the dry contact inputs are faulty.
Alarm conditions for the dry contact inputs are incorrectly set.

Procedure
1. Maintain the device connecting to the dry contact input and check whether the
alarm persists.
If no, no further action is required.
If yes, go to the next step.

2. Check whether the alarm condition for the dry contact input is incorrectly set.
If yes, reset the alarm condition.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.78 DIN6 Alarm


Description
When detecting that the detection level for the dry contact is consistent with the alarm
condition, the SMU generates a DIN6 Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10232 Minor ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,282/359(W)

The devices connecting to the dry contact inputs cannot work properly.

Possible Causes
Devices connecting to the dry contact inputs are faulty.
Alarm conditions for the dry contact inputs are incorrectly set.

Procedure
1. Maintain the device connecting to the dry contact input and check whether the
alarm persists.
If no, no further action is required.
If yes, go to the next step.

2. Check whether the alarm condition for the dry contact input is incorrectly set.
If yes, reset the alarm condition.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.79 DIN7 Alarm


Description
When detecting that the detection level for the dry contact is consistent with the alarm
condition, the SMU generates a DIN7 Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10307 Minor ADAC

Impact on the System


The devices connecting to the dry contact inputs cannot work properly.

Possible Causes
Devices connecting to the dry contact inputs are faulty.
Alarm conditions for the dry contact inputs are incorrectly set.

Procedure
1. Maintain the device connecting to the dry contact input and check whether the

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,283/359(W)

alarm persists.
If no, no further action is required.
If yes, go to the next step.

2. Check whether the alarm condition for the dry contact input is incorrectly set.
If yes, reset the alarm condition.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.80 DIN8 Alarm


Description
When detecting that the detection level for the dry contact is consistent with the alarm
condition, the SMU generates a DIN8 Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10308 Minor ADAC

Impact on the System


The devices connecting to the dry contact inputs cannot work properly.

Possible Causes
Devices connecting to the dry contact inputs are faulty.
Alarm conditions for the dry contact inputs are incorrectly set.

Procedure
1. Maintain the device connecting to the dry contact input and check whether the
alarm persists.
If no, no further action is required.
If yes, go to the next step.

2. Check whether the alarm condition for the dry contact input is incorrectly set.
If yes, reset the alarm condition.
If no, contact Huawei technical support.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,284/359(W)

1.17.81 TEC Alarm


Description
When detecting that the thermoelectric cooler (TEC) does not run properly, the SMU
generates a TEC Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10243 Major ADAC

Impact on the System


The TEC does not run properly.

Possible Causes
The power supply is faulty.
The TEC is faulty.

Procedure
1. Check whether the power supply is faulty.
If yes, rectify the fault and restore the power supply.
If no, go to the next step

2. Check whether the TEC is malfunctioning.


If yes, maintain the TEC.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.82 Heater Fault


Description
When detecting that the heater is faulty, the SMU generates a Heater Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,285/359(W)

10244 Major ADAC

Impact on the System


The heater fails to heat.

Possible Causes
The heater is faulty.

Procedure
1. Check whether the heater is abnormal.
If yes, maintain the heater.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.83 Abnormal System Voltage Check


Description
When detecting an abnormal system voltage, the SMU generates an Abnormal System
Voltage Check alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10247 Major ADAC

Impact on the System


The SMU fails to monitor and control the system voltage.

Possible Causes
The system hardware is faulty.

Procedure
1. Contact Huawei technical support.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,286/359(W)

1.17.84 Abnormal System Current Check


Description
When detecting an abnormal system current, the SMU generates an Abnormal System
Current Check alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10245 Major ADAC

Impact on the System


The SMU fails to monitor and control the system current.

Possible Causes
The system hardware is faulty.

Procedure
1. Contact Huawei technical support.

Parent topic: Power System

1.17.85 TCUA Alarm


Description
When detecting that the TCUA does not run properly, the SMU generates a TCUA
Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10249 Major ADAC

Impact on the System


TCUA does not run properly.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,287/359(W)

The power supply is faulty.


The communication cable between the SMU and the TCUA is disconnected or loose.
The TCUA is faulty.

Procedure
1. Check whether the power supply is faulty.
If yes, rectify the fault and restore the power supply.
If no, go to the next step

2. Check whether the communication cable between the SMU and the TCUA is
connected correctly.
If yes, reconnect the communication cable.
If no, go to the next step

3. Check whether the TCUA is malfunctioning.


If yes, maintain the TCUA.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.86 Load Breaker Trip


Description
When detecting that the load circuit breaker is OFF, the SMU generates a Load Breaker
Trip alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10250 Critical ADAC

Impact on the System


The load will not work.

Possible Causes
The load circuit breaker is switched off manually.
The load circuit breaker detection cable is loosened.
The load circuit breaker protects itself against overcurrent due to the abnormal load.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,288/359(W)

The load circuit breaker is faulty.

Procedure
1. Check that whether the load circuit breaker is switched off manually.
If yes, clear the alarm.
If no, go to the next step.

2. Check that whether the load circuit breaker detection cable is loosened.
If yes, secure the load circuit breaker detection cable.
If no, go to the next step.

3. Check that whether the load is abnormal.


If yes, maintenance the load.
If no, go to the next step.

4. Check that whether the load circuit breaker is faulty.


If yes, replace the load circuit breaker.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.87 Main AC Breaker Trip


Description
When detecting that the main AC circuit breaker is OFF, the SMU generates a Main
AC Breaker Trip alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10251 Critical ADAC

Impact on the System


The power system will not work.

Possible Causes
The main AC circuit breaker is switched off manually.
The main AC circuit breaker detection cable is loosened.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,289/359(W)

The main AC circuit breaker protects itself against overcurrent due to the abnormal
power system.
The main AC circuit breaker is faulty.

Procedure
1. Check that whether the main AC circuit breaker is switched off manually.
If yes, clear the alarm.
If no, go to the next step.

2. Check that whether the main AC circuit breaker detection cable is loosened.
If yes, secure the main AC circuit breaker detection cable.
If no, go to the next step.

3. Check that whether power system is abnormal.


If yes, maintenance power system.
If no, go to the next step.

4. Check that whether the main AC circuit breaker is faulty.


If yes, replace the main AC circuit breaker.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.88 DCD Comm Fail


Description
When detecting that communication between the DC distribution cabinet and the SMU
fails, the SMU generates a DCD Comm Fail alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10252 Major ADAC

Impact on the System


The SMU will not receive the information about the DC distribution cabinet.

Possible Causes
The communication cable between the SMU and the detecting board of the DC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,290/359(W)

distribution cabinet is loosened.


The power supply to the detecting board of the DC distribution cabinet is faulty.
The detecting board of the DC distribution cabinet is faulty

Procedure
1. Check that whether the communication cable between the SMU and the detecting
board of the DC distribution cabinet is loosened.
If yes, secure the cable.
If no, go to next step.

2. Check that whether the power supply to the detecting board of the DC distribution
cabinet is faulty.
If yes, find the reason and repower the detecting board of the DC distribution
cabinet.
If no, go to next step.

3. Check that whether the detecting board of the DC distribution cabinet is abnormal.
If yes, replace the detecting board.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.89 AC Phase L1 Failure


Description
When detecting that AC input phase L1 is open, the SMU generates an AC Phase L1
Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10254 Major ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
Power supply to phase L1 is disconnected.
The circuit breaker for phase L1 is OFF.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,291/359(W)

Procedure
1. Check whether the phase voltage for phase L1 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the circuit breaker for phase L1 is OFF.


If yes, check and repair the power distribution, and then switch on the circuit
breaker.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.90 AC Phase L2 Failure


Description
When detecting that AC input phase L2 is open, the SMU generates an AC Phase L2
Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10255 Major ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
Power supply to phase L2 is disconnected.
The circuit breaker for phase L2 is OFF.

Procedure
1. Check whether the phase voltage for phase L2 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the circuit breaker for phase L2 is OFF.


If yes, check and repair the power distribution, and then switch on the circuit
breaker.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,292/359(W)

If no, contact Huawei technical support.

Parent topic: Power System

1.17.91 AC Phase L3 Failure


Description
When detecting that AC input phase L3 is open, the SMU generates an AC Phase L3
Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10256 Major ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
Power supply to phase L3 is disconnected.
The circuit breaker for phase L3 is OFF.

Procedure
1. Check whether the phase voltage for phase L3 is abnormal.
If yes, troubleshoot power grid failures.
If no, go to the next step.

2. Check whether the circuit breaker for phase L3 is OFF.


If yes, check and repair the power distribution, and then switch on the circuit
breaker.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.92 AC L1-L2 Overvoltage


Description

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,293/359(W)

The SMU generates an alarm when the AC L1-L2 line voltage exceeds the overvoltage
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

10257 Minor ADAC

Impact on the System


The equipment may be damaged, and a power failure may occur.

Possible Causes
The L1 or L2 phase voltage exceeds the overvoltage alarm threshold.
The AC overvoltage alarm threshold is not properly set.

Procedure
1. Check whether the L1 or L2 phase voltage is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Check whether the AC overvoltage alarm threshold is not properly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.93 AC L2-L3 Overvoltage


Description
The SMU generates an alarm when the AC L2-L3 line voltage exceeds the overvoltage
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

10258 Minor ADAC

Impact on the System


The equipment may be damaged, and a power failure may occur.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,294/359(W)

Possible Causes
The L2 or L3 phase voltage exceeds the overvoltage alarm threshold.
The AC overvoltage alarm threshold is not properly set.

Procedure
1. Check whether the L2 or L3 phase voltage is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Check whether the AC overvoltage alarm threshold is not properly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.94 AC L3-L1 Overvoltage


Description
The SMU generates an alarm when the AC L3-L1 line voltage exceeds the overvoltage
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

10259 Minor ADAC

Impact on the System


The equipment may be damaged, and a power failure may occur.

Possible Causes
The L3 or L1 phase voltage exceeds the overvoltage alarm threshold.
The AC overvoltage alarm threshold is not properly set.

Procedure
1. Check whether the L3 or L1 phase voltage is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,295/359(W)

2. Check whether the AC overvoltage alarm threshold is not properly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.95 AC L1-L2 Undervoltage


Description
The SMU generates an alarm that the AC L1-L2 line voltage is below the undervoltage
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

10260 Minor ADAC

Impact on the System


The power system may experience a power failure.

Possible Causes
The L1 or L2 phase voltage is below the undervoltage alarm threshold.
The AC undervoltage alarm threshold is not properly set.

Procedure
1. Check whether the L1 or L2 phase voltage is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Check whether the AC undervoltage alarm threshold is not properly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.96 AC L2-L3 Undervoltage

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,296/359(W)

Description
The SMU generates an alarm that the AC L2-L3 line voltage is below the undervoltage
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

10261 Minor ADAC

Impact on the System


The power system may experience a power failure.

Possible Causes
The L2 or L3 phase voltage is below the undervoltage alarm threshold.
The AC undervoltage alarm threshold is not properly set.

Procedure
1. Check whether the L2 or L3 phase voltage is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Check whether the AC undervoltage alarm threshold is not properly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.97 AC L3-L1 Undervoltage


Description
The SMU generates an alarm that the AC L3-L1 line voltage is below the undervoltage
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

10262 Minor ADAC

Impact on the System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,297/359(W)

The power system may experience a power failure.

Possible Causes
The L3 or L1 phase voltage is below the undervoltage alarm threshold.
The AC undervoltage alarm threshold is not properly set.

Procedure
1. Check whether the L3 or L1 phase voltage is abnormal.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Check whether the AC undervoltage alarm threshold is not properly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.98 Custom Alarm 1


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15403 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,298/359(W)

1.17.99 Custom Alarm 2


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15404 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.100 Custom Alarm 3


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15405 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,299/359(W)

Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.101 Custom Alarm 4


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15406 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.102 Custom Alarm 5


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15407 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,300/359(W)

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.103 Custom Alarm 6


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15408 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.104 Custom Alarm 7


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15409 Major ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,301/359(W)

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.105 Custom Alarm 8


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15410 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.106 Custom Alarm 9


Description
The alarm is user-configured on a PLC module.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,302/359(W)

Alarm ID Alarm Severity Alarm Type

15411 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.107 Custom Alarm 10


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15412 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.108 Custom Alarm 11

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,303/359(W)

Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15413 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.109 Custom Alarm 12


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15414 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,304/359(W)

1.17.110 Custom Alarm 13


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15415 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.111 Custom Alarm 14


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15416 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,305/359(W)

Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.112 Custom Alarm 15


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15417 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.113 Custom Alarm 16


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15418 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,306/359(W)

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.114 Custom Alarm 17


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15419 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.115 Custom Alarm 18


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15420 Major ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,307/359(W)

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.116 Custom Alarm 19


Description
The alarm is user-configured on a PLC module.

Attribute

Alarm ID Alarm Severity Alarm Type

15421 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.117 Custom Alarm 20


Description
The alarm is user-configured on a PLC module.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,308/359(W)

Alarm ID Alarm Severity Alarm Type

15422 Major ADAC

Impact on the System


The user-configured alarm is abnormal.

Possible Causes
The user-configured alarm affects the system normal functions.

Procedure
Check whether the source of the user-configured alarm is abnormal.

Parent topic: Power System

1.17.118 Power System Undervoltage


NOTE:
Only for the Japanese KDDI system.

Description
When detecting that the DC voltage is below the ultra undervoltage alarm threshold, the
SMU generates a Power System Undervoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

15423 Minor ADAC

Impact on the System


The power system will stop powering loads for a short time.

Possible Causes
The battery voltage is below the ultra undervoltage alarm threshold because AC
power fails for a long time.
The DC ultra undervoltage alarm threshold is incorrectly set.

Procedure
1. Check whether the battery voltage is below the ultra undervoltage alarm threshold
because AC power fails for a long time.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,309/359(W)

If yes, rectify the power grid fault.


If no, go to the next step.

2. Check whether the DC ultra undervoltage alarm threshold is incorrectly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

Parent topic: Power System

1.17.119 Power System Overvoltage


NOTE:
Only for the Japanese KDDI system.

Description
When detecting that the DC voltage exceeds the overvoltage alarm threshold, the SMU
generates a Power System Overvoltage alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

15424 Minor ADAC

Impact on the System


Loads may be damaged or experience a power failure.

Possible Causes
A rectifier is faulty.
The DC overvoltage alarm threshold is incorrectly set.

Procedure
1. Check whether a rectifier is faulty.
If yes, replace the rectifier.
If no, go to the next step.

2. Check whether the DC overvoltage alarm threshold is incorrectly set.


If yes, reset the alarm threshold.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,310/359(W)

Parent topic: Power System

1.17.120 Vibration Alarm


Description
The SMU generates this alarm when the door is closed, and the vibration sensor detects
three vibration signals within 1 minute.

Attribute

Alarm ID Alarm Severity Alarm Type

15401 Major ADMC

Impact on the System


The devices have the risk of being stolen or damaged.

Possible Causes
The cabinet is opened forcibly.
Construction work is near the cabinet.
The vibration sensor is faulty.
The cabinet door is opened.

Procedure
1. Check whether the cabinet is opened forcibly.
If yes, go to the site as soon as possible.
If no, go to the next step.

2. Check whether construction work is near the cabinet.


If yes, manually rectify the alarm when the construction work is finished.
If no, go to the next step.

3. Manually rectify the vibration alarm. Check whether the alarm is cleared.
If yes, no further action is required.
If no, go to the next step.

4. Replace the vibration sensor, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,311/359(W)

Parent topic: Power System

1.17.121 Illegal Door Open


Description
The SMU generates this alarm when the door opening status is changed (from close to
open) within four minutes after a vibration alarm is generated, provided an intelligent
door lock is installed. The opening is unauthorized. (Opening by card, mobile
application, and remote opening are authorized opening methods.)

Attribute

Alarm ID Alarm Severity Alarm Type

15402 Major ADMC

Impact on the System


The devices have the risk of being stolen or damaged.

Possible Causes
The cabinet door is opened illegally.

Procedure
1. Check whether the cabinet is opened forcibly.
If yes, go to the site as soon as possible, and manually rectify the alarm
afterwards.
If no, contact Huawei technical support.

Parent topic: Power System

1.18 Electronic Lock


Communication Failure

Parent topic: Site Alarm Reference

1.18.1 Communication Failure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,312/359(W)

Description
This alarm is generated when the SMU fails to communicate with the device.

Attribute

Alarm ID Alarm Severity Alarm Type

5852 Major ADAC

Impact on the System


The SMU fails to control the opening of the electronic lock.

Possible Causes
The cables of the electronic lock are faulty or loose.
The controller is faulty.
The electronic lock is faulty.

Procedure
1. Check whether the cables are loose.
If yes, replace or reconnect the cables of the involved electronic lock, and check
whether the alarm is cleared.
If no, go to the next step.

2. Replace the electronic lock, and check whether the alarm is cleared.
If yes, no further action is required.
If no, go to the next step.

3. Replace or reconnect the communication expansion board, and check whether the
alarm is cleared.
If yes, no further action is required.
If no, go to the next step.

4. Replace the SMU and check whether the alarm is cleared.


If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Electronic Lock

1.19 Fan Group

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,313/359(W)

Fan 1 Fault

Fan 2 Fault

Fan 3 Fault

Fan 4 Fault

Parent topic: Site Alarm Reference

1.19.1 Fan 1 Fault


Description
When detecting that fan 1 is faulty, the SMU generates a Fan 1 Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

5100 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes
Fan 1 is faulty.

Procedure
1. Check whether a fan is abnormal.
If yes, replace the fan.
If no, contact Huawei technical support.

Parent topic: Fan Group

1.19.2 Fan 2 Fault


Description
When detecting that fan 2 is faulty, the SMU generates a Fan 2 Fault alarm.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,314/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

5101 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes
Fan 2 is faulty.

Procedure
1. Check whether a fan is abnormal.
If yes, replace the fan.
If no, contact Huawei technical support.

Parent topic: Fan Group

1.19.3 Fan 3 Fault


Description
When detecting that fan 3 is faulty, the SMU generates a Fan 3 Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

5102 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes
Fan 3 is faulty.

Procedure
1. Check whether a fan is abnormal.
If yes, replace the fan.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,315/359(W)

Parent topic: Fan Group

1.19.4 Fan 4 Fault


Description
When detecting that fan 4 is faulty, the SMU generates a Fan 4 Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

5103 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes
Fan 4 is faulty.

Procedure
1. Check whether a fan is abnormal.
If yes, replace the fan.
If no, contact Huawei technical support.

Parent topic: Fan Group

1.20 Heater Device


Heater Fault

Parent topic: Site Alarm Reference

1.20.1 Heater Fault


Description
When detecting that the heater is faulty, the SMU generates a Heater Fault alarm.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,316/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

12500 Major ADAC

Impact on the System


The heater fails to heat.

Possible Causes
The heater is faulty.

Procedure
1. Check whether the heater is abnormal.
If yes, maintain the heater.
If no, contact Huawei technical support.

Parent topic: Heater Device

1.21 AC Ammeter
Communication Failure

Parent topic: Site Alarm Reference

1.21.1 Communication Failure


Description
This alarm is generated when the SMU fails to communicate with the device.

Attribute

Alarm ID Alarm Severity Alarm Type

12400 Minor ADAC

Impact on the System


The SMU fails to obtain measurement information from the AC meter.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,317/359(W)

Possible Causes
The communication cable is disconnected from the device or loose.
The device fails to work properly.

Procedure
1. Check whether the communication cable is loose.
If yes, reconnect the communication cable.
If no, go to the next step.

2. Check whether the device fails to work properly.


If yes, replace the device.
If no, contact Huawei technical support.

Parent topic: AC Ammeter

1.22 AC Air Conditioner


Air Conditioner Fault

Parent topic: Site Alarm Reference

1.22.1 Air Conditioner Fault


Description
When detecting that an AC air conditioner is faulty, the SMU generates an Air
Conditioner Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

12450 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,318/359(W)

The AC air conditioner is faulty.

Procedure
1. Check whether the AC air conditioner is abnormal.
If yes, rectify the fault.
If no, contact Huawei technical support.

Parent topic: AC Air Conditioner

1.23 Camera
Communication Failure

Parent topic: Site Alarm Reference

1.23.1 Communication Failure


Description
This alarm is generated when the SMU fails to communicate with the device.

Attribute

Alarm ID Alarm Severity Alarm Type

1601 Major ADAC

Impact on the System


The image capture function is disabled.

Possible Causes
The communication cable is disconnected from the device or loose.
The device fails to work properly.

Procedure
1. Check whether the communication cable is loose.
If yes, reconnect the communication cable.
If no, go to the next step.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,319/359(W)

2. Check whether the device fails to work properly.


If yes, replace the device.
If no, contact Huawei technical support.

Parent topic: Camera

1.24 NIM01C
Communication Failure

Parent topic: Site Alarm Reference

1.24.1 Communication Failure


Description
This alarm is generated when a communication expansion board fails to communicate
with the SMU.

Attribute

Alarm ID Alarm Severity Alarm Type

15051 Major ADAC

Impact on the System


The SMU fails to detect the information of the components connected to the
communication expansion board, such as the camera and electronic door lock. If
wireless networking is used, the site information cannot be monitored remotely.

Possible Causes
The communication cable is disconnected from the device or loose.
The communication expansion board is faulty.

Procedure
1. Check whether the communication cable is properly connected.
If yes, go to the next step.
If no, reconnect the communication cable.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,320/359(W)

2. Replace the involved communication expansion board, and check whether the
alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: NIM01C

1.25 TCU
Hardware Fault

TCU Communicate Failure

Internal Circular Fan Fault

External Circular Fan Fault

Return Vent Temperature Sensor Fault

Exhaust Vent Temperature Sensor Fault

TCU High Temperature

TCU Low Temperature

Door Alarm

Water Alarm

Smoke Alarm

TEC Alarm

Heater Fault

Parent topic: Site Alarm Reference

1.25.1 Hardware Fault


Description
When detecting that the temperature control unit (TCU) hardware is faulty, the SMU
generates a Hardware Fault alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,321/359(W)

Alarm ID Alarm Severity Alarm Type

10819 Major ADAC

Impact on the System


The system temperature cannot be controlled.

Possible Causes
The TCU hardware is faulty.

Procedure
1. Replace the TCU and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: TCU

1.25.2 TCU Communicate Failure


Description
When failing to communicate with the TCU, the SMU generates a TCU Communicate
Failure alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10800 Minor ADAC

Impact on the System


The SMU fails to detect the temperature control board.

Possible Causes
The communication cable between the temperature control board and the SMU is
disconnected or loose.
The temperature control board is powered off or faulty.

Procedure
1. Check whether the communication cable between the temperature control board
and the SMU is connected correctly.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,322/359(W)

If yes, go to the next step.


If no, reconnect the communications cable.

2. Check whether the temperature control board functions properly.


If yes, contact Huawei technical support.
If no, replace the temperature control board.

Parent topic: TCU

1.25.3 Internal Circular Fan Fault


Description
When detecting that the internal circulation fan is faulty, the SMU generates an Internal
Circular Fan Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10807 Major ADAC

Impact on the System


The system temperature cannot be adjusted.

Possible Causes
The internal circulation fan is faulty.

Procedure
1. Power on the fan and check whether the fan stops rotating.
If yes, replace the fan.
If no, go to the next step.

2. Power off the fan and check whether the fan cable is properly connected.
If yes, contact Huawei technical support.
If no, reconnect the fan cable.

Parent topic: TCU

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,323/359(W)

1.25.4 External Circular Fan Fault


Description
When detecting that the external circulation fan is faulty, the SMU generates an
External Circular Fan Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10806 Major ADAC

Impact on the System


The system temperature cannot be adjusted.

Possible Causes
The external circulation fan is faulty.

Procedure
1. Power on the fan and check whether the fan stops rotating.
If yes, replace the fan.
If no, go to the next step.

2. Power off the fan and check whether the fan cable is properly connected.
If yes, contact Huawei technical support.
If no, reconnect the fan cable.

Parent topic: TCU

1.25.5 Return Vent Temperature Sensor


Fault
Description
When detecting that the ambient temperature sensor at the air return vent is
disconnected, the SMU generates an Return Vent Temperature Sensor Fault alarm.

Attribute

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,324/359(W)

Alarm ID Alarm Severity Alarm Type

10820 Major ADAC

Impact on the System


The temperature at the air return vent cannot be monitored.

Possible Causes
The ambient temperature sensor at the air return vent is disconnected.
The connector on the cable for the ambient temperature sensor at the air return vent
is disconnected.
The ambient temperature sensor at the air return vent is faulty.

Procedure
1. Check whether the ambient temperature sensor at the air return vent is connected.
If yes, go to the next step.
If no, connect the ambient temperature sensor.

2. Check whether the connector on the cable for the ambient temperature sensor at the
air return vent is loose.
If yes, secure the connector.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: TCU

1.25.6 Exhaust Vent Temperature Sensor


Fault
Description
When detecting that the ambient temperature sensor at the air exhaust vent is
disconnected, the SMU generates an Exhaust Vent Temperature Sensor Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,325/359(W)

10808 Major ADAC

Impact on the System


The temperature at the air exhaust vent cannot be monitored.

Possible Causes
The ambient temperature sensor at the air exhaust vent is disconnected.
The connector on the cable for the ambient temperature sensor at the air exhaust vent
is disconnected.
The ambient temperature sensor at the air exhaust vent is faulty.

Procedure
1. Check whether the ambient temperature sensor at the air exhaust vent is connected.
If yes, go to the next step.
If no, connect the ambient temperature sensor.

2. Check whether the connector on the cable for the ambient temperature sensor at the
air exhaust vent is loose.
If yes, secure the connector.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: TCU

1.25.7 TCU High Temperature


Description
When detecting that the ambient temperature exceeds the very high temperature alarm
threshold, the SMU generates a TCU High Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10802 Critical ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,326/359(W)

Impact on the System


Power system performance and reliability will deteriorate because the power system
operates at high temperatures.

Possible Causes
The ambient temperature exceeds the alarm threshold.
The ambient very high temperature alarm threshold is not properly set.
The ambient temperature sensor is faulty.

Procedure
1. Check whether temperature control devices such as the fan and air conditioner are
abnormal.
If yes, maintain the devices.
If no, go to the next step.

2. Check whether the ambient very high temperature alarm threshold is not properly
set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCU

1.25.8 TCU Low Temperature


Description
When detecting that the ambient temperature is below the very low temperature alarm
threshold, the SMU generates a TCU Low Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10811 Warning ADAC

Impact on the System


Power system performance and reliability will deteriorate because the power system

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,327/359(W)

operates at low temperatures.

Possible Causes
The ambient temperature is below the alarm threshold.
The low ambient temperature alarm threshold is not properly set.
The ambient temperature sensor is faulty.

Procedure
1. Check whether the heater is abnormal.
If yes, maintain the heater.
If no, go to the next step.

2. Check whether the low ambient temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCU

1.25.9 Door Alarm


Description
When detecting that the cabinet door of the power system is open, the SMU generates a
Door Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10821 Minor ADAC

Impact on the System


The power system has potential troubles.

Possible Causes
The cabinet door of the power system is open.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,328/359(W)

The connector on the door status sensor cable is loose.


The door status sensor is faulty.

Procedure
1. Close the cabinet door of the power system and check whether the alarm is cleared.
If yes, no further action is required.
If no, go to the next step.

2. Check whether the connector on the door status sensor cable is loose.
If yes, secure the connector.
If no, go to the next step.

3. Replace the door status sensor and close the cabinet door, and then check whether
the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: TCU

1.25.10 Water Alarm


Description
When detecting water in the power system cabinet, the SMU generates a Water Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10822 Critical ADAC

Impact on the System


The power system has potential troubles.

Possible Causes
Water intrudes into the cabinet.
The water sensor is faulty.

Procedure
1. Check whether water intrudes into the cabinet.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,329/359(W)

If yes, eliminate water from the cabinet.


If no, go to the next step.

2. Replace the water sensor and check whether the alarm persists.
If yes, secure the connector.
If no, go to the next step.

3. Replace the water sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: TCU

1.25.11 Smoke Alarm


Description
When detecting smoke in the power system cabinet, the SMU generates a Smoke
Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10823 Critical ADAC

Impact on the System


The power system has potential troubles.

Possible Causes
There is smoke inside the cabinet.
The smoke sensor is faulty.

Procedure
1. Check whether there is smoke inside the cabinet.
If yes, shut down the power system and rectify the fault.
If no, go to the next step.

2. Replace the smoke sensor and check whether the alarm persists.
If no, no further action is required.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,330/359(W)

If yes, contact Huawei technical support.

Parent topic: TCU

1.25.12 TEC Alarm


Description
When detecting that the thermoelectric cooler (TEC) does not run properly, the SMU
generates a TEC Alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

10824 Major ADAC

Impact on the System


The TEC does not run properly.

Possible Causes
The power supply is faulty.
The TEC is faulty.

Procedure
1. Check whether the power supply is faulty.
If yes, rectify the fault and restore the power supply.
If no, go to the next step

2. Check whether the TEC is malfunctioning.


If yes, maintain the TEC.
If no, contact Huawei technical support.

Parent topic: TCU

1.25.13 Heater Fault


Description
When detecting that the heater is faulty, the SMU generates a Heater Fault alarm.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,331/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

10825 Major ADAC

Impact on the System


The heater fails to heat.

Possible Causes
The heater is faulty.

Procedure
1. Check whether the heater is abnormal.
If yes, maintain the heater.
If no, contact Huawei technical support.

Parent topic: TCU

1.26 Temperature Control Group


Indoor Return Vent Temperature Sensor Missing

Outdoor Temperature Sensor Missing

Indoor Return Vent Temperature Sensor Fault

Outdoor Temperature Sensor Fault

Indoor Vent High Temperature

Air Conditioner Missing

System Noise Too Loud

Parent topic: Site Alarm Reference

1.26.1 Indoor Return Vent Temperature


Sensor Missing

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,332/359(W)

Description
When detecting that the ambient temperature sensor at the return air vent in the cabinet
is disconnected, the SMU generates an Indoor Return Vent Temperature Sensor
Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9962 Major ADAC

Impact on the System


Temperature at the return air vent in the cabinet cannot be monitored.

Possible Causes
The ambient temperature sensor at the return air vent in the cabinet is disconnected.
The connector on the cable for the ambient temperature sensor at the return air vent
in the cabinet is disconnected.
The ambient temperature sensor at the return air vent in the cabinet is faulty.

Procedure
1. Check whether the ambient temperature sensor at the return air vent in the cabinet
is disconnected.
If no, connect the ambient temperature sensor.
If yes, go to the next step.

2. Check whether the connector on the cable for the ambient temperature sensor at the
return air vent in the cabinet is loose.
If yes, secure the connector.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Temperature Control Group

1.26.2 Outdoor Temperature Sensor


Missing

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,333/359(W)

Description
When detecting that the ambient temperature sensor outside the cabinet is disconnected,
the SMU generates an Outdoor Temperature Sensor Missing alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9963 Warning ADAC

Impact on the System


The ambient temperature outside the cabinet cannot be monitored.

Possible Causes
The ambient temperature sensor outside the cabinet is disconnected.
The connector on the cable for the ambient temperature sensor outside the cabinet is
disconnected.
The ambient temperature sensor outside the cabinet is faulty.

Procedure
1. Check whether the ambient temperature sensor outside the cabinet is disconnected.
If no, connect the ambient temperature sensor.
If yes, go to the next step.

2. Check whether the connector on the cable for the ambient temperature sensor
outside the cabinet is disconnected.
If yes, secure the connector.
If no, go to the next step.

3. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Temperature Control Group

1.26.3 Indoor Return Vent Temperature


Sensor Fault
Description

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,334/359(W)

When detecting that the ambient temperature sensor at the return air vent in the cabinet
is faulty, the SMU generates an Indoor Return Vent Temperature Sensor Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9964 Major ADAC

Impact on the System


Temperature at the return air vent in the cabinet cannot be monitored.

Possible Causes
The ambient temperature sensor at the return air vent in the cabinet is faulty.

Procedure
1. Replace the ambient temperature sensor at the return air vent and check whether the
alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Temperature Control Group

1.26.4 Outdoor Temperature Sensor Fault


Description
When detecting that the ambient temperature sensor outside the cabinet is faulty, the
SMU generates an Outdoor Temperature Sensor Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9965 Warning ADAC

Impact on the System


The ambient temperature outside the cabinet cannot be monitored.

Possible Causes
The ambient temperature sensor outside the cabinet is faulty.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,335/359(W)

1. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Temperature Control Group

1.26.5 Indoor Vent High Temperature


Description
When detecting that the temperature at the return air vent in the cabinet exceeds the
high temperature alarm threshold, the SMU generates an Indoor Vent High
Temperature alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

9954 Critical ADAC

Impact on the System


Power system performance and reliability will deteriorate.

Possible Causes
The temperature control system is faulty.
The ambient temperature sensor is faulty.

Procedure
1. Check whether the temperature control system is abnormal.
If no, maintain the temperature control system.
If yes, go to the next step.

2. Replace the ambient temperature sensor and check whether the alarm persists.
If no, no further action is required.
If yes, contact Huawei technical support.

Parent topic: Temperature Control Group

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,336/359(W)

1.26.6 Air Conditioner Missing


Description
The SMU generates an alarm that the air conditioner is not detected.

Attribute

Alarm ID Alarm Severity Alarm Type

9958 Major ADAC

Impact on the System


The temperature for the power system cannot be adjusted.

Possible Causes
The air conditioner is not connected, or the connection is loose.
The air conditioner is faulty.

Procedure
1. Check whether the air conditioner is not connected, or the connection is loose.
If yes, connect the air conditioner or secure the connection.
If no, go to the next step.

2. Replace the air conditioner and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Temperature Control Group

1.26.7 System Noise Too Loud


Description
The temperature control is in the silent mode, and the system noise detected exceeds the
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,337/359(W)

9968 Major ADAC

Impact on the System


The system noise is loud, interfering with the environment.

Possible Causes
The air conditioner, TEC, or fan is faulty.
The temperature control curve or the target temperature value is incorrectly set.

Procedure
1. Check whether the temperature control device causing the noise is abnormal, such
as the air conditioner, TEC, or fan.
If yes, maintain or replace the temperature control device.
If no, go to the next step.

2. Check whether the temperature control mode is set correctly or the alarm threshold
for the noise level is set incorrectly.
If yes, modify the relevant configuration parameters.
If no, contact Huawei technical support.

Parent topic: Temperature Control Group

1.27 Li-ion Battery


Module Communication Failure

Module Fault

Module Protection

Module Minor Alarm

Parent topic: Site Alarm Reference

1.27.1 Module Communication Failure


Description
This alarm is generated when the SMU fails to communicate with the module.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,338/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

0970 Major ADAC

Impact on the System


The SMU fails to monitor the faulty device.

Possible Causes
The device is removed.
The device is faulty.
The communications cable is loose.

Procedure
1. Check whether the communications cable between the device and the SMU is
connected correctly.
If yes, go to the next step.
If no, reconnect the communications cable.

2. Reset the SMU and check whether the alarm persists.


If no, no further action is required.
If yes, go to the next step.

3. Check whether the device works properly.


If yes, contact Huawei technical support.
If no, replace the device.

Parent topic: Li-ion Battery

1.27.2 Module Fault


Description
This alarm is generated when the module is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

0971 Minor ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,339/359(W)

Impact on the System


The device fails to work properly.

Possible Causes
The heater is faulty.
The service life expires.
The board is faulty.

Procedure
1. Rectify each fault based on the possible causes and then check whether the alarm
persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: Li-ion Battery

1.27.3 Module Protection


Description
This alarm is generated when the device is protected.

Attribute

Alarm ID Alarm Severity Alarm Type

0972 Major ADAC

Impact on the System


The device fails to work properly.

Possible Causes
The device protects against low temperatures.
The device protects against electrochemical cell discharge high temperature.
The device protects against electrochemical cell charge high temperature.
The device protects against battery string charge overvoltage.
The device protects against battery string discharge undervoltage.
The device protects against battery string charge overcurrent.
The device protects against battery string discharge overcurrent.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,340/359(W)

Procedure
1. Rectify each fault based on the possible causes and then check whether the alarm
persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: Li-ion Battery

1.27.4 Module Minor Alarm


Description
This alarm is generated when the module has a minor alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

0973 Major ADAC

Impact on the System


The module may work abnormally, which reduces the system power backup capability.

Possible Causes
The module generates an electrochemical cell discharge high temperature alarm.
The module generates an electrochemical cell charge high temperature alarm.
The module generates a battery string charge overvoltage alarm.
The module generates a battery string discharge undervoltage alarm.
The module generates a battery string charge overcurrent alarm.
The module generates a battery string discharge overcurrent alarm.
The module generates a low temperature alarm.

Procedure
1. Rectify each fault based on the possible causes and then check whether the alarm
persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: Li-ion Battery

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,341/359(W)

1.28 Min-Li-ion Battery


Battery Fuse Break

BLVD Disconnected

BLVD Warning

Battery Forcibly Connection

Battery Discharging

Battery Temperature Sensor 1 Fault

Battery Temperature Sensor 2 Fault

Battery High Temperature

Battery Low Temperature

Battery Temperature Sensor 1 Missing

Battery Temperature Sensor 2 Missing

Parent topic: Site Alarm Reference

1.28.1 Battery Fuse Break


Description
This alarm is generated when the battery fuse is disconnected or the battery circuit
breaker is OFF.

Attribute

Alarm ID Alarm Severity Alarm Type

14701 Critical ADAC

Impact on the System


The power system does not have sufficient backup power because a battery fuse is
disconnected.

Possible Causes
The battery fuse is disconnected or the battery circuit breaker is OFF.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,342/359(W)

The battery fuse detection cable is disconnected.

Procedure
1. Check whether the battery fuse is disconnected or the battery circuit breaker is
OFF.
If yes, switch on the circuit breaker.
If no, go to the next step.

2. Check whether the battery fuse detection cable is disconnected.


If yes, secure the cable.
If no, contact Huawei technical support.

Parent topic: Min-Li-ion Battery

1.28.2 BLVD Disconnected


Description
This alarm is generated when batteries are disconnected.

Attribute

Alarm ID Alarm Severity Alarm Type

14703 Critical ADAC

Impact on the System


Batteries fail to supply power to the power system because the batteries are
disconnected.

Possible Causes
Check whether the battery voltage drops to the battery low voltage disconnection
(BLVD) voltage because AC power has failed for a long time.
The battery temperature exceeds the upper threshold and Very High Temperature
Protection Mode is Disconnect Battery.

Procedure
1. Check whether the battery voltage drops to the BLVD voltage because AC power
has failed for a long time.
If yes, rectify the power grid fault.
If no, go to the next step.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,343/359(W)

2. Check whether a Battery Very High Temperature alarm is generated and


temperature control devices in the battery compartment are abnormal, such as the
fan and air conditioner.
If yes, maintain the temperature control devices.
If no, contact Huawei technical support.

Parent topic: Min-Li-ion Battery

1.28.3 BLVD Warning


Description
This alarm is generated when batteries are about to disconnect.

Attribute

Alarm ID Alarm Severity Alarm Type

14702 Major ADAC

Impact on the System


Batteries will fail to supply power to the power system because the batteries are about
to disconnect.

Possible Causes
The battery voltage drops to the battery low voltage disconnection (BLVD) voltage
because AC power has failed for a long time.
The battery temperature exceeds the upper threshold and Very High Temperature
Protection Mode is Disconnect Battery.

Procedure
1. Check whether the battery voltage drops to the BLVD voltage because AC power
has failed for a long time.
If yes, rectify the power grid fault.
If no, go to the next step.

2. Check whether a Battery Very High Temperature alarm is generated and


temperature control devices in the battery compartment are abnormal, such as the
fan and air conditioner.
If yes, maintain the temperature control devices.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,344/359(W)

Parent topic: Min-Li-ion Battery

1.28.4 Battery Forcibly Connection


Description
This alarm is generated when batteries are forcibly connected.

Attribute

Alarm ID Alarm Severity Alarm Type

14705 Major ADAC

Impact on the System


If the AC power becomes abnormal, forcible battery connection may permanently
damage batteries.

Possible Causes
Batteries are forcibly connected.

Procedure
If forcible battery connection is not required, flip the battery switch to OFF.

Parent topic: Min-Li-ion Battery

1.28.5 Battery Discharging


Description
This alarm is generated when batteries are discharging.

Attribute

Alarm ID Alarm Severity Alarm Type

14704 Warning ADAC

Impact on the System


The battery backup time reduces due to battery discharge.

Possible Causes

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,345/359(W)

The AC power fails or the AC input is abnormal.

Procedure
1. Check whether an AC power failure occurs.
If yes, rectify the power grid fault.
If no, contact Huawei technical support.

Parent topic: Min-Li-ion Battery

1.28.6 Battery Temperature Sensor 1 Fault


Description
This alarm is generated when the sensor is not properly connected.

Attribute

Alarm ID Alarm Severity Alarm Type

14710 Major ADAC

Impact on the System


The temperature at the air exhaust vent cannot be monitored.

Possible Causes
The temperature sensor is disconnected.
The temperature sensor connector is loose.
The temperature sensor is faulty.

Procedure
1. Check whether the sensor is connected.
If yes, go to the next step.
If no, connect the sensor.

2. Check whether the sensor connector is loose.


If yes, secure the connector.
If no, go to the next step.

3. Replace the temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,346/359(W)

If no, no further action is required.

Parent topic: Min-Li-ion Battery

1.28.7 Battery Temperature Sensor 2 Fault


Description
This alarm is generated when the sensor is not properly connected.

Attribute

Alarm ID Alarm Severity Alarm Type

14711 Major ADAC

Impact on the System


The temperature at the air exhaust vent cannot be monitored.

Possible Causes
The temperature sensor is disconnected.
The temperature sensor connector is loose.
The temperature sensor is faulty.

Procedure
1. Check whether the sensor is connected.
If yes, go to the next step.
If no, connect the sensor.

2. Check whether the sensor connector is loose.


If yes, secure the connector.
If no, go to the next step.

3. Replace the temperature sensor and check whether the alarm persists.
If yes, contact Huawei technical support.
If no, no further action is required.

Parent topic: Min-Li-ion Battery

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,347/359(W)

1.28.8 Battery High Temperature


Description
This alarm is generated when the battery temperature exceeds the high temperature
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

14706 Minor ADAC

Impact on the System


Battery performance will deteriorate and battery lifespan will be shortened.

Possible Causes
The battery temperature exceeds the upper threshold.
The battery high temperature alarm threshold is not properly set.
The temperature sensor is faulty.

Procedure
1. Check whether the temperature control devices in the battery compartment are
abnormal, such as the fan and air conditioner.
If yes, maintain the temperature control devices.
If no, go to the next step.

2. Check whether the battery high temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Min-Li-ion Battery

1.28.9 Battery Low Temperature

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,348/359(W)

Description
This alarm is generated when the battery temperature is below the low temperature
alarm threshold.

Attribute

Alarm ID Alarm Severity Alarm Type

14707 Warning ADAC

Impact on the System


Backup power reliability is compromised because battery performance deteriorates.

Possible Causes
The battery temperature is below the lower threshold.
The battery low temperature alarm threshold is not properly set.
The temperature sensor is faulty.

Procedure
1. Check whether the heater in the battery compartment is abnormal.
If yes, maintain the heater.
If no, go to the next step.

2. Check whether the battery low temperature alarm threshold is not properly set.
If yes, reset the alarm threshold.
If no, go to the next step.

3. Replace the temperature sensor and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Min-Li-ion Battery

1.28.10 Battery Temperature Sensor 1


Missing
Description
This alarm is generated when the sensor is disconnected.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,349/359(W)

Attribute

Alarm ID Alarm Severity Alarm Type

14708 Warning ADAC

Impact on the System


The temperature cannot be monitored.

Possible Causes
The sensor is disconnected.
The sensor connector is loose.
The sensor is faulty.

Procedure
1. Check whether the sensor is connected.
If yes, connect the sensor.
If no, go to the next step.

2. Check whether the sensor connector is loose.


If yes, secure the connector.
If no, go to the next step.

3. Replace the sensor and check whether the alarm is cleared.


If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Min-Li-ion Battery

1.28.11 Battery Temperature Sensor 2


Missing
Description
This alarm is generated when the sensor is disconnected.

Attribute

Alarm ID Alarm Severity Alarm Type

14709 Warning ADAC

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,350/359(W)

Impact on the System


The temperature cannot be monitored.

Possible Causes
The sensor is disconnected.
The sensor connector is loose.
The sensor is faulty.

Procedure
1. Check whether the sensor is connected.
If yes, connect the sensor.
If no, go to the next step.

2. Check whether the sensor connector is loose.


If yes, secure the connector.
If no, go to the next step.

3. Replace the sensor and check whether the alarm is cleared.


If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: Min-Li-ion Battery

1.29 Diesel Generator


Diesel Generator Start Fault

Diesel Generator Stop Fault

ATS Fault

Parent topic: Site Alarm Reference

1.29.1 Diesel Generator Start Fault


Description
When detecting that the diesel generator (D.G.) fails to start, the SMU generates a

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,351/359(W)

Diesel Generator Start Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11200 Critical ADAC

Impact on the System


Power supply to the site may be disconnected.

Possible Causes
The D.G. is faulty.

Procedure
1. Check whether the D.G. starts abnormally.
If yes, maintain the D.G.
If no, contact Huawei technical support.

Parent topic: Diesel Generator

1.29.2 Diesel Generator Stop Fault


Description
When detecting that the diesel generator (D.G.) fails to stop, the SMU generates a
Diesel Generator Stop Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11201 Critical ADAC

Impact on the System


The D.G. cannot stop.

Possible Causes
The D.G. is faulty.

Procedure
1. Check whether the D.G. stops abnormally.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,352/359(W)

If yes, maintain the D.G.


If no, contact Huawei technical support.

Parent topic: Diesel Generator

1.29.3 ATS Fault


Description
When detecting that the AC transfer switch (ATS) is faulty, the SMU generates an ATS
Fault alarm.

Attribute

Alarm ID Alarm Severity Alarm Type

11202 Critical ADAC

Impact on the System


The ATS cannot work properly.

Possible Causes
The ATS is faulty.

Procedure
1. Check whether the ATS is abnormal.
If yes, maintain the ATS.
If no, contact Huawei technical support.

Parent topic: Diesel Generator

1.30 DC Ammeter
Communicate Failure

Parent topic: Site Alarm Reference

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,353/359(W)

1.30.1 Communicate Failure


Description
The DC meter fails to communicate with the SMU.

Attribute

Alarm ID Alarm Severity Alarm Type

9401 Minor ADAC

Impact on the System


The DC information about the power system fails to be monitored, such as DC
voltages, currents, and power consumption.

Possible Causes
The communications cable between the DC meter and the SMU is disconnected or
loose.
The DC meter is powered off or faulty.

Procedure
1. Check whether the communications cable is properly connected.
If yes, go to the next step.
If no, reconnect the communications cable.

2. Check whether DC meter works properly.


If yes, contact Huawei technical support.
If no, replace the DC meter.

Parent topic: DC Ammeter

1.31 Int. A/C


Internal Fan Fault

External Fan Fault

Compressor Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,354/359(W)

Cabinet Return Air Temperature Sensor Fault

Evaporator Frozen

Frequent High Pressure

Communicate Failure

Parent topic: Site Alarm Reference

1.31.1 Internal Fan Fault


Description
The indoor unit is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

9350 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Int. A/C

1.31.2 External Fan Fault


Description
The outdoor unit is faulty

Attribute

Alarm ID Alarm Severity Alarm Type

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,355/359(W)

9351 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Int. A/C

1.31.3 Compressor Fault


Description
The compressor is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

9353 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Int. A/C

1.31.4 Cabinet Return Air Temperature


Sensor Fault

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,356/359(W)

Description
The sensor at the return air vent of the air conditioner is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

9356 Minor ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Int. A/C

1.31.5 Evaporator Frozen


Description
The evaporator is frozen.

Attribute

Alarm ID Alarm Severity Alarm Type

9364 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Int. A/C

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,357/359(W)

1.31.6 Frequent High Pressure


Description
The air conditioner frequently works under high pressure.

Attribute

Alarm ID Alarm Severity Alarm Type

9365 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure
For details, see the user manual related to the air conditioner.

Parent topic: Int. A/C

1.31.7 Communicate Failure


Description
The air conditioner fails to communicate with the SMU.

Attribute

Alarm ID Alarm Severity Alarm Type

9354 Major ADAC

Impact on the System


The air conditioner operating information cannot be monitored.

Possible Causes
For details, see the user manual related to the air conditioner.

Procedure

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,358/359(W)

For details, see the user manual related to the air conditioner.

Parent topic: Int. A/C

1.32 AIM
Communicate Failure

Hardware Fault

Parent topic: Site Alarm Reference

1.32.1 Communicate Failure


Description
This alarm is generated when the SMU fails to communicate with the device.

Attribute

Alarm ID Alarm Severity Alarm Type

12400 Minor ADAC

Impact on the System


The SMU fails to obtain measurement information from the AC meter.

Possible Causes
The communication cable is disconnected from the device or loose.
The device fails to work properly.

Procedure
1. Check whether the communication cable is loose.
If yes, reconnect the communication cable.
If no, go to the next step.

2. Check whether the device fails to work properly.


If yes, replace the device.
If no, contact Huawei technical support.

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12


w 页码,359/359(W)

Parent topic: AIM

1.32.2 Hardware Fault


Description
This alarm is generated when the device hardware is faulty.

Attribute

Alarm ID Alarm Severity Alarm Type

12401 Major ADAC

Impact on the System


The SMU fails to obtain measurement information from the AC meter, or the value is
invalid.

Possible Causes
The device hardware is faulty.

Procedure
1. Replace the involved device, and check whether the alarm is cleared.
If yes, no further action is required.
If no, contact Huawei technical support.

Parent topic: AIM

http://localhost:7890/printtopics.html?time=Thu May 12 20:11:08 EST 2016 2016/5/12