You are on page 1of 148

AADvance

The Next Step in Automation

AADvance Controller

Solutions Handbook

Issue: 09

DOCUMENT: 553631
(ICSTT-RM447J_EN_P)
Solutions Handbook (AADvance Controller)

This page intentionally left blank

ii Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:
Notice
In no event will Rockwell Automation be responsible or liable for indirect or
consequential damages resulting from the use or application of this equipment. The
examples given in this manual are included solely for illustrative purposes. Because of
the many variables and requirements associated with any particular installation,
Rockwell Automation does not assume responsibility or reliability for actual use based
on the examples and diagrams.
No patent liability is assumed by Rockwell Automation, with respect to use of
information, circuits, equipment, or software described in this manual.
Reproduction of this manual in whole or in part, without written permission of
Rockwell Automation is prohibited.
All trademarks are acknowledged.

Disclaimer
It is not intended that the information in this publication covers every possible detail
about the construction, operation, or maintenance of a control system installation. You
should refer to your own (or supplied) system safety manual, installation instructions
and operator/maintenance manuals.

Revision and Updating Policy


This document is based on information available at the time of its publication; however,
the document contents are subject to change from time to time. You should contact
Rockwell Automation Technical Support by e-mail — icstsupport@ra.rockwell.com to
check if you have the latest version of this publication.
© Copyright Notice, Rockwell Automation 2012
This document contains proprietary information that is protected by copyright. All
rights are reserved.

Documentation Feedback
Your comments will help us to serve your documentation needs better. If you
discover any errors or have any suggestions on how to improve this publication send
your comments to our product support group: icstsupport@ra.rockwell.com

This manual is applicable to Release R1.3 of the AADvance controller.

Document: 553631 iii


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Notes and Symbols used in this manual

This symbol calls attention to items which "must" be considered and implemented
when designing and building an AADvance controller for use in a Safety
Instrumented Function (SIF). It appears extensively in the AADvance Safety Manual.

Note: Notes are used extensively to provide important information about the
product.

Standard Warnings and Cautions


WARNING ELECTRICAL ARCS AND EXPLOSION RISK IN HAZARDOUS
AREAS
If you connect or disconnect wiring, modules or communications cabling while
power is applied, an electrical arc can occur. This could cause an explosion in
hazardous location installations. Do not remove wiring, fuses, modules or
communications cabling while circuit is energized unless area is known to be
non hazardous.
Failure to follow these instructions may result in personal injury.

WARNING MAINTENANCE
Maintenance must be carried out only by qualified personnel.
Failure to follow these instructions may result in personal injury.

CAUTION RADIO FREQUENCY INTERFERENCE


Most electronic equipment is influenced by Radio Frequency Interference.
Caution should be exercised with regard to the use of portable communications
equipment around such equipment. Signs should be posted in the vicinity of the
equipment cautioning against the use of portable communications equipment.

CAUTION HEAT DISSIPATION AND ENCLOSURE POSITION


System and field power consumption by modules and termination assemblies is
dissipated as heat. You should consider this heat dissipation on the design and
positioning of your enclosure; e.g. enclosures exposed to continuous sunlight
will have a higher internal temperature that could affect the operating
temperature of the modules. Modules operating at the extremes of the
temperature band for a continuous period can have a reduced reliability.

iv Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:
Issue Record
Issue Date Comments
01 Dec 2008 First Issue

02 Feb 2009
03 Feb 2010
04 Mar 2010 Updates after peer review
05 June 2010 updates for release 1.1.1
06 Oct 2010 updates to meet UL requirements
07 Nov 2010 updates for ATEX and UL Certification and release 1.2
08 July 2012 Release 1.3 version
09 Aug 2013 Changes to TUV certification topic, add On-line update
feature and module specification data.

Document: 553631 v
(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Forward
This technical manual describes the features, performance and functionality of the
AADvance controller and systems. It sets out some guidelines on how to specify a
system to meet your application requirements.

Note: The AADvance controller is a logic solver. It uses processor modules and I/O
modules. An AADvance system is formed by one or more controllers, their power
sources, communications networks and workstations.

Who Should Use this Manual


This manual is intended primarily for system designers and technical sales people who
need to understand the capabilities of an AADvance controller. This manual will assist
you to design a suitable system.
The information contained in this manual is intended to be used in conjunction with
(and not as a substitute for) expertise and experience in safety-related systems. In
particular, it is expected that the reader has a thorough understanding of the intended
application and can understand the generic terms used within this manual and the
terminology specific to the integrator's or project's application area.

vi Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Contents
Chapter 1 The AADvance System ........................................................................... 1-1
The AADvance Controller .............................................................................................................................. 1-1
Performance and Electrical Specifications .............................................................................................. 1-3
Scan Times ..................................................................................................................................................... 1-4
Environmental Specifications ..................................................................................................................... 1-5
Controller TUV Certification ................................................................................................................... 1-7
Certification for use in Hazardous Environments................................................................................ 1-7
File No: E341697.......................................................................................................................................... 1-7
File No: E251761.......................................................................................................................................... 1-8
KCC-EMC Registration ........................................................................................................................... 1-12
Main Components ........................................................................................................................................... 1-13
Hardware Components............................................................................................................................ 1-13
AADvance Workstation Software and Application Development Environment ....................... 1-14
Controller Functionality ................................................................................................................................. 1-16
SNTP ............................................................................................................................................................. 1-16
CIP over EtherNet/IP ................................................................................................................................ 1-16
HART ............................................................................................................................................................ 1-17
SNCP Safety Networks ............................................................................................................................ 1-18
Peer-to-Peer................................................................................................................................................ 1-20
Serial Communication Interface ............................................................................................................. 1-22
Time Synchronization (SNTP) ................................................................................................................ 1-22
Modbus Master ........................................................................................................................................... 1-23
The OPC Portal Server ............................................................................................................................ 1-24
Controller IP Address Setting................................................................................................................. 1-25
Recovery Mode .......................................................................................................................................... 1-25
DiffServ Configuration .............................................................................................................................. 1-25
Ethernet Forwarding ................................................................................................................................. 1-26
Transparent Communication Interface (TCI) ..................................................................................... 1-27
Compiler Verification Tool ..................................................................................................................... 1-27
Technical Features ........................................................................................................................................... 1-28
TUV Approved Operating System......................................................................................................... 1-28
Internal Diagnostics ................................................................................................................................... 1-28
Controller Internal Bus Structure ......................................................................................................... 1-28
System Modification and On-line Updates........................................................................................... 1-29
ControlFLASH Firmware Upgrades ...................................................................................................... 1-31
Physical Features .............................................................................................................................................. 1-32
Product Dimensions .................................................................................................................................. 1-32
Compact Module Design.......................................................................................................................... 1-33
Module Polarization Keying ..................................................................................................................... 1-34
Module Locking Mechanism .................................................................................................................... 1-35
Termination Assemblies ........................................................................................................................... 1-35
Ethernet, Serial Data and Power Connections ................................................................................... 1-37

viii Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Serial Communications ............................................................................................................................. 1-37
Field Wiring Connections ........................................................................................................................ 1-38
Corrective Maintenance and Module Replacement .......................................................................... 1-38
Chapter 2 AADvance System Architectures .......................................................... 2-1
SIL2 Architectures ............................................................................................................................................. 2-1
SIL2 Fail-safe Architecture ......................................................................................................................... 2-2
SIL2 Fault Tolerant Input Architectures ................................................................................................. 2-3
SIL2 Output Architecture .......................................................................................................................... 2-4
SIL2 Fault Tolerant Input High Demand Architecture........................................................................ 2-5
SIL3 Architectures ............................................................................................................................................. 2-6
SIL3 Fail-safe I/O, Fault Tolerant Processor .......................................................................................... 2-7
SIL3 Fault Tolerant I/O Architectures .................................................................................................... 2-8
SIL3 TMR Input and Processor, Fault Tolerant Output ................................................................... 2-10
Planned Certified Configurations ................................................................................................................. 2-11
Chapter 3 Building Architectures with TUV Approved Modules ......................... 3-1
Fundamental Architectures ............................................................................................................................. 3-1
Simplex I/O Architecture ................................................................................................................................. 3-1
Dual Architecture for Fault Tolerant Applications.................................................................................... 3-5
Triple Modular Redundant Architecture ..................................................................................................... 3-7
Chapter 4 Mixed Architectures................................................................................ 4-1
Example Controllers ......................................................................................................................................... 4-1
Mixed I/O Architectures .................................................................................................................................. 4-3
Mixed Safety Integrity Levels........................................................................................................................... 4-4
Distributed Architectures................................................................................................................................ 4-5
Typical Network Applications ........................................................................................................................ 4-6
Specifying a Safety Network ...................................................................................................................... 4-6
Controller Network Connectors ............................................................................................................ 4-7
Chapter 5 AADvance Scalability .............................................................................. 5-1
I/O Channel Capacity........................................................................................................................................ 5-1
Simplex I/O Channel Capacity .................................................................................................................. 5-2
Dual I/O Channel Capacity ........................................................................................................................ 5-3
Triple Modular Redundant Channel Capacity ....................................................................................... 5-4
Adding I/O Channel Capacity ......................................................................................................................... 5-5
Bus Connectors and Expansion Cable .......................................................................................................... 5-5
Redundancy and Fault Tolerance ................................................................................................................... 5-6
Expansion using Distributed Controllers ..................................................................................................... 5-6
Chapter 6 Specifying a New Controller .................................................................. 6-1
Information to Specify a New Controller .................................................................................................... 6-1
Define a New System ....................................................................................................................................... 6-2
Choosing Termination Assemblies ................................................................................................................ 6-5
Specify I/O Base Units....................................................................................................................................... 6-5
Estimate AADvance Controller Weight ...................................................................................................... 6-6

Document: 553631 ix
(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Estimate Module Supply Power Dissipation and Field Loop Power Dissipation ................................ 6-7
Chapter 7 Module Overview and Specifications ..................................................... 7-1
T9110 Processor Module ................................................................................................................................ 7-2
Processor Module Specification ............................................................................................................... 7-4
T9100 Processor Base Unit............................................................................................................................. 7-5
T9100 Base Unit Specification .................................................................................................................. 7-7
T9300 I/O Base Unit (3 way) .......................................................................................................................... 7-8
T9300 Base Unit Specification .................................................................................................................. 7-9
T9310 Expansion Cable Assembly ............................................................................................................... 7-10
T9310 Extension Cable Specification .................................................................................................... 7-11
T9401/2 Digital Input Module, 24V dc, 8/16 channel .............................................................................. 7-12
T9401/2 Digital Input Module Specification ......................................................................................... 7-13
T9801/2/3 Termination Assemblies for Digital Inputs ............................................................................ 7-14
T9801/2/3 Digital Input Termination Assembly Specification ......................................................... 7-15
T9431/2 Analogue Input Module, 8/16 Channel....................................................................................... 7-16
T9431/2 Analogue Input Module Specification ................................................................................... 7-17
T9831/2/3 Termination Assemblies for Analogue Inputs....................................................................... 7-18
T9831/2/3 Analogue Input Termination Assembly Specification .................................................... 7-19
T9451 Digital Output Module, 24V dc, 8 channel ................................................................................... 7-20
T9451 Digital Output Module Specification ........................................................................................ 7-21
T9851/2 Termination Assemblies for Digital Outputs ........................................................................... 7-22
T9851/2 Digital Output Termination Assembly Specifications ....................................................... 7-23
T9481/2 Analogue Output Module ............................................................................................................. 7-24
T9481/2 Analogue Output Module Specification ............................................................................... 7-25
T9881/2 Termination Assembly for Analogue Output Module............................................................ 7-26
T9881/2 Analogue Output Termination Assembly Specification ................................................... 7-27
Chapter 8 Application (Resource) Development ................................................... 8-1
Programming Language Support ..................................................................................................................... 8-1
Program Management Facilities ...................................................................................................................... 8-1
Support for Variable Types ............................................................................................................................. 8-2
I/O Connection (Addressing of Physical I/O) ............................................................................................. 8-2
Off-line Simulation and Testing ...................................................................................................................... 8-2
Application (Resource) Program Security ................................................................................................... 8-2
Aids to Software Development ...................................................................................................................... 8-3
AADvance Workbench Licensing Options ................................................................................................. 8-3
DIN Rails Fitting ................................................................................................................................................. 8-4
Chapter 9 System Build ............................................................................................ 9-1
Free Space Around the Controller ............................................................................................................... 9-1
Base Units, DIN Rail installations and Expansion Cables ......................................................................... 9-3
Assemblies of Base Units ................................................................................................................................. 9-3

x Document: 553631
(ICSTT-RM447J_EN_P) Issue: 09:
Power Supply Requirements ........................................................................................................................... 9-4
Adding Cable Management .............................................................................................................................. 9-4
Chapter 10 Parts List ................................................................................................ 10-1
Chapter 11 Glossary of Terms ................................................................................. 11-1
Chapter 12 Additional Resources ............................................................................ 12-1

Document: 553631 xi
(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 1
The AADvance System
An AADvance system consists of an AADvance controller, an external operator's
workstation, field connections, power sources and external network connections. The
flexibility of the design allows a system to be built to suit your own requirements from
a standard range of modules and assemblies.
This chapter describes the main components that can be used to build an AADvance
controller.

In This Chapter
The AADvance Controller ............................................................................... 1-1
Main Components ............................................................................................ 1-13
Controller Functionality .................................................................................. 1-16
Technical Features ............................................................................................ 1-28
Physical Features ............................................................................................... 1-32

The AADvance Controller


The AADvance controller is specifically designed for functional safety and critical
control applications; it provides a flexible solution for your smaller scale requirements.
The system can be used for safety implement functions as well as applications that are
non-safety but still critical to a business process. This controller offers you the ability
to create a cost-effective system to suit any of the following applications:
 Critical process control
 Fire and gas protection systems
 Rotating machinery control systems
 Burner management
 Boiler and furnace control
 Distributed process monitoring and control
The AADvance controller is a logic solver and I/O processing device that consists of
processor modules, I/O modules and field termination assemblies that can easily be
assembled and configured. A system is built up from one or more controllers, a
combination of I/O modules, power sources, communications networks and user
workstations. How you configure the system determines the type of application it can
be used for.
An AADvance controller is particularly well suited to emergency shut down and fire
and gas detection protection applications by providing a system solution with
integrated and distributed fault tolerance. It is designed and validated to international
standards and is certified by TÜV for functional safety control installations.
A Frequency Input Module (not yet released) will provide the functionality to meet the
requirements of turbomachinary governor control and overspeed protection.

Document: 553631 1-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

The significant benefits of the AADvance controller are its performance and flexibility.
Being designed to IEC 61508 it meets both SIL2 and SIL3 application requirements
from the basic range of modules and mixed SIL rated applications can be covered by
this range of modules.
All of the configurations are readily achieved by combining modules and assemblies
without using special cables or interface units. System architectures are user
configurable and can be changed without major system modifications. Processor and
I/O redundancy is configurable so you can choose between fail safe and fault tolerant
solutions. This scalability is user configurable, therefore, there is no change to the
complexity of operations or programming if you choose to add redundant capacity to
create a fault tolerant solution.
A controller is built from a range of compact plug-in modules that are straightforward
to assemble into a system. They can be mounted onto DIN rails in a cabinet (see
photograph) or directly mounted onto a wall in a control room. They do not require
forced air cooling or special environmental control equipment. However, certain
consideration to the cabinet type must be applied when used in hazardous
environments.

A secure network communications protocol, developed by Rockwell Automation for


the AADvance system, permits distributed control using new or existing network
infrastructure while ensuring the security and integrity of the data. Individual sensors
and actuators can connect to a local controller, minimizing the lengths of dedicated
field cabling. There is no need for a large central equipment room; rather, the
complete distributed system can be administered from one or more PC workstations
placed at convenient locations.

1-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Single input modules are designed to meet SIL3 and in the most basic simplex
configuration they offer a fail-safe solution. The AADvance system has comprehensive
built-in diagnostics, while maintenance activities are straight forward operations which
maximize system availability.
The AADvance controller is developed and built for IEC 61131 compliance and
includes support for all five programming languages. Program access is secured by a
removable "Program Enable" key. Simulation software lets you prove a new application
before reprogramming and downloading, again maximizing system uptime.

Performance and Electrical Specifications

Table 1: Performance and Electrical Specifications

Attribute Value
Functional Characteristics

Number of processor modules 1 (non-safety applications, SIL1 and SIL2 safety


applications)
2 (SIL3 applications)
3 (SIL3 fault tolerant and TMR applications)
Maximum number of I/O modules 48 modules (16 base units) - Two I/O busses each
holds 24 modules (8 I/O base units)
External interfaces Network (10/100BASE-TX Ethernet)
Serial data communications (RS-485)
Inter-controller links High integrity communications using Safety Network
Control Protocol (SNCP)
Application software support All IEC 61131 languages
Displays Status LEDs on each module
User controls Fault Reset button on each processor module
Security Plug-in "Program Enable" key for access to application
project and system configuration tools.
Mounting DIN rail or flat panel
Performance Characteristics
Safety integrity level IEC 61508 SIL2
IEC 61508 SIL3
(depending on processor and I/O module
configuration)
Sequence of Event
Processor Module (for internal
variables)
Event Resolution 1ms
Time Stamp Accuracy Application Scan
Digital Input Module
Event Resolution 1ms

Document: 553631 1-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Time Stamp Accuracy 10ms

Safety accuracy limit 200μA for Analogue Inputs and 1.0V dc for Digital
Inputs.
Electrical Characteristics

Supply voltage Redundant 24V dc nominal, 18V dc to 32V dc range

Channel isolation (channel to channel


and channel to chassis)
Maximum withstanding ± 1.5kV dc withstand for one minute.
Power consumption, heat dissipation and weight depend on the arrangement of the
controller. You can estimate these values when you specify the controller using the
tables provided in this manual.
A typical module surface temperature measured against a processor module is 43°C ±
2°C.

Scan Times
The following scan times were taken from a test system consisting of production
modules.
Module Scan Time
T9401 Digital input module, 24V dc, 8 channel
Single 1.23ms
Dual 1.73ms
Triple 2.08ms
T9431 Analogue input module 24V dc, 8 channel
Single 1.26ms
Dual 1.91ms
Triple 2.33ms
T9451 Digital output module, 24V dc, 8 channel
Single 1.43ms
Dual 2.44ms
AADvance Workbench Sleep Period 57.2ms
Scan overhead per module 0.09ms
The tests did not measure the effect of logic complexity and communications loading.
The scan time is:
 6 (Number of module groups x scan time shown above) + Sleep Period + (Total
modules x scan overhead)
The scan time will vary by up to +/- 5ms (not including the effect of logic and
communications).

1-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Throughput time is the time from input change to output action. Due to the discrete
nature of the scan, the throughput time will vary between one and two scans.

Note: The AADvance application scan time is limited to a minimum of 64ms to allow
all processes to run. Small applications will report a scan time of approximately 57 -
61ms. Large applications may have longer scan times but each scan time will be
consistent to within approximately 5ms.

An example configuration scan time:


T9431 Analogue input simplex modules x 30
T9451 Digital output simplex modules x 18
Total I/O modules = 48
Estimated scan time = (30 x 1.23ms) + (18 x 1.43ms) + 57.2ms + (48 x 0.09ms)
= 125.1ms
Throughput time:
min = 125.1ms
Avg = 187.6ms
Max = 250.1ms

Environmental Specifications
The following environmental specification defines the minimum recommended
environmental conditions for an AADvance controller installation. Additional
conditions apply to installations in a Hazardous environment.

Table 2: Environmental Specification

Attribute Value
Operating Temperature Range:
For use in Hazardous Environments (UL
Certification):
Processor Modules –25 °C to 60 °C (–13 °F to 140 °F)
I/O Modules and Assemblies –25 °C to 70 °C (–13 °F to 158 °F)
For use in Non-Hazardous Environments
(TUV Certification)
All Modules and Assemblies –25 °C to 70 °C (–13 °F to 158 °F)
Storage and Transport Temperature –40 °C to 70 °C (–40 °F to 158 °F)
Module Surface Temperature (during normal 43° C (109 °F) ± 2 °C
operation)
Humidity
Operating 10% to 95% RH, non-condensing
Storage and Transport 10% to 95% RH, non-condensing
Vibration

Document: 553631 1-5


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Functional Stress 5Hz to 9Hz


Continuous 1.7mm amplitude
Occasional 3.5mm amplitude
Withstand 10Hz to 150Hz
Acceleration 0.1g in 3 axes
Endurance 10Hz to 150Hz
Acceleration 0.5g in 3 axes
Shock 15g peak, 11ms duration, ½ sine
Altitude
Operating 0 to 2000m (0 to 6,600 ft.)
Storage and Transport 0 to 3000m (0 to 10,000 ft.)
This equipment must not be transported in
unpressurized aircraft flown above 10,000 ft.
Electromagnetic Interference Tested to the following standards: EN 61326-
1:2006, Class A; EN 61326-3-1:2008, EN 54-4:
1997, A1; EN 61131-2:2007; EN 62061:2005.

Hazardous Location Capability Suitable for Class I Div 2 and Zone 2

Note:
Casing: Standard AADvance modules also have a plastic casing and are rated IP20:
Protected against solid objects over 12mm (1/2in.) for example "fingers". There is no
specific protection against liquids.

1-6 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Controller TUV Certification

TÜV Certification
TÜV is the safety certifying authority for an AADvance controller. The AADvance
system is certified to the following standard:
IEC 61508, Part 1-7:1998-2000 EN 50178:1997
IEC 61511-1:2004 EN 50156-1:2004
EN 61131-2:2007 EN 54-2:1997, A1:2006 (†)
EN 61326-3-1:2008 NFPA 72:2007
EN 61000-6-2:2005 NFPA 85:2007
EN 61000-6-4:2007 NFPA 86:2007
(†) The analogue output modules are not certified to EN 54-2.
You can download a copy of the TUV certificate from www.tuvasi.com.
The Euro Controller version of the AADvance product is also tested to Q1 Extended
Design levels of ISO 13628-6: 2006 Sub Sea Production Control System.

Certification for use in Hazardous Environments


The AADvance controller has been investigated and approved by UL (UL508) for use
as Industrial Control Equipment in a general industrial environment and for use in
hazardous locations, Class I, Division 2, Groups A, B, C and D. The UL file numbers
are: E341697 and E251761.

File No: E341697


The AADvance controller investigation and approval is contained in the following files:
NRAQ.E341697: Programmable Controllers investigated to ANSI/UL 508.
The products have been investigated using requirements contained in the following
standards:
 UL508, Industrial Control Equipment, Seventeenth edition, with revisions through
and including April 15, 2010.
NRAQ7.E341697: Programmable Controllers Certified for Canada
The products have been investigated using requirements contained in the following
standards:
 CSA C22.2 No 142-M1987, Process Control equipment, Edition 1 - Revision date
1990-09-01

Document: 553631 1-7


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Products Covered
The products investigated and approved:
Programmable Logic Controllers Models: 9110 Processor Module; 9401/2 Digital
Output Module; 9431/2 Analogue Input module; 9451 Digital output module; 9482
Analogue Output Module.
Listed Accessories for use with PLCs: 9100 Processor Backplane, 9300 I/O Backplane,
9801 Digital Input Termination Assembly, Simplex; 9802 Digital Input Termination
Assembly, Dual; 9803 Digital Input Termination Assembly, TMR; 9831 Analogue input
Termination Assembly, Simplex; 9832, Analogue Input Termination Assembly, Dual;
9833 Analogue Input Termination Assembly, TMR 9851 Digital Output Termination
Assembly, Simplex and 9852 Digital Output Termination Assembly, Dual; 9881
Analogue Output Termination Assembly, Simplex; 9882 Analogue Output Termination
Assembly, Dual.

File No: E251761


The AADvance controller investigation and approval is contained in the following file
certifications:
NRAG.E251761: Programmable Controllers for Use in Hazardous Locations Class I,
Division 2, Groups A, B, C and D.
The products have been investigated using requirements contained in the following
standards:
 ANSI/ISA 12.12.01-20007, Nonincendive Electrical Equipment for use in Class I and
II, Division 2 and Class III, Division 1 and 2 Hazardous Locations.
 UL508, Industrial Control Equipment, Seventeenth edition, with revisions through
and including April 15, 2010.

NRAG7.E251761: Programmable Controllers for Use in Hazardous Locations


Certified for Canada; Class I, Division 2, Groups A, B, C and D
The products have been investigated using requirements contained in the following
standards:
 CSA C22.2 No 213-M1987, Nonincendive Control Equipment for Use in Class I,
Division 2, Hazardous Locations.
 CSA C22.2 No 142-M1987, Process Control equipment, Edition 1 - Revision date
1990-09-01

Products Covered
The products investigated and approved:
Programmable Logic Controllers Models: 9110 Processor Module; 9401/2 Digital
Output Module; 9431/2 Analogue Input module; 9451 Digital output module; 9482
Analogue Output Module.

1-8 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Listed Accessories for use with PLCs: 9100 Processor Backplane, 9300 I/O Backplane,
9801 Digital Input Termination Assembly, Simplex; 9802 Digital Input Termination
Assembly, Dual; 9803 Digital Input Termination Assembly, TMR; 9831 Analogue input
Termination Assembly, Simplex; 9832, Analogue Input Termination Assembly, Dual;
9833 Analogue Input Termination Assembly, TMR 9851 Digital Output Termination
Assembly, Simplex and 9852 Digital Output Termination Assembly, Dual; 9881
Analogue Output Termination Assembly, Simplex; 9882 Analogue Output Termination
Assembly, Dual.

Document: 553631 1-9


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Certificate
The AADvance controller modules have been evaluated to the requirements of EN
60079-0: 2009 and EN 60079-15: 2010 under Certificate Number: DEMKO 11 ATEX
1129711X .

1-10 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
The AADvance controller has also been evaluated under certificate IECEx UL
12.0032X to the standards IEC 60079-0; (5th Edition) and IEC 60079-15 (4th Edition).

[ certificate to be supplied]

For a system that is located in a Zone 2 Hazardous environment where ATEX


certification is required, all modules should be installed in an ATEX and IECEx
Certified, tool accessible IP54 enclosure. The enclosure is to be marked with the
following: "Warning - Do not open when energized". After installation of the modules
into the enclosure, access to termination compartments shall be dimensioned so that
conductors can be readily connected. The modules and assemblies are for use in an
area of not more than pollution degree 2 in accordance with IEC 60664-1

Module label

Document: 553631 1-11


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

KCC-EMC Registration

KCC- EMC Registration

1-12 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Main Components

Hardware Components
Each controller is built from a standard range of modules and assemblies; it consists of
processor modules, a processor base unit, digital and analogue I/O modules, I/O base
units and termination assemblies all of which are assembled as follows:
 A processor module is installed into a processor base unit that can hold up to 3
processor modules.
 3-way I/O base units are connected to the processor base unit and to each other.
Each I/O base unit holds up to three I/O modules and termination assemblies. A
controller can have up to 8 I/O base units on each of two I/O busses, giving a total
capacity for up to 48 I/O modules.
 I/O modules are connected to field devices through external connectors on the
termination assemblies.
The processor module and base units are designed for use as either single, dual or
triple redundant processor module arrangements. The base processor base unit
provides external connections for Serial and Ethernet networks and the dual
redundant system power inputs.
The I/O base unit plugs directly into the processor base unit and carries the redundant
system power for the modules, the processor commands across a command bus and
I/O data across individual data response busses.
I/O base units also directly plug into each other and are secured and held in place by a
clamping arm and retaining clips; hence, a controller becomes a complete mechanically
and electrically interconnected assembly without the need for additional wiring or
cabling. The I/O modules are also designed for use in single or dual or triple redundant
configurations.
Termination assemblies are matched to a specific type of I/O module and have terminal
blocks that provide 8 or 16 connections for the wiring to the field elements. The
termination assemblies for dual and triple arrangements have channel to channel
isolation. Termination assemblies for simplex input modules and termination
assemblies for simplex and dual output modules are single ended (non-isolated) with a
common return.
An expansion cable can be used to connect the processor base unit or an I/O base unit
to another I/O base unit. This is useful for to breaking long runs of interconnected
base units and provides some flexibility in the physical layout of a controller
installation, particularly if the controller is installed in a cabinet.

Document: 553631 1-13


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

AADvance Workstation Software and Application Development Environment

Workstation Software
The AADvance workstation uses software that enables you to design the complete
control strategy as one, then to target parts of the strategy at each controller.
Interaction between the resources is automatic, significantly reducing the complexity of
configuration in a multi-resource solution.
The workstation software, known as the Workbench is compliant with IEC61131
industrial standard and has the following powerful features:
 the regulation of the flow of control decisions for an interacting distributed control
system
 providing for the consistency of data
 providing a means for synchronous operation between devices
 eliminating the need to have separate synchronous schemes
 easing the development and maintenance of robust systems
The Workbench lets you create local and distributed control applications using the
five languages of IEC 61131-3. Engineers can choose one language or a combination of
languages that best suits their knowledge and programming style and the nature of the
application.
It is also a secure development environment that requires a hardware (USB Dongle) or
software license to run on a PC. There is also a Program Enable key (not applicable
to a Euro Controller) that must be plugged into the processor base unit to allow the
user to modify and download the application resource or access the
AADvanceDiscover utility to check the status of the controller IP address. The
Program Enable key when it is removed protects the application from unauthorized
access.
The development environment includes:
 tools for program development
 program documentation
 function block library management
 application archiving
 database configuration
 import/export utilities
 on-line monitoring
 off-line simulation and controlled on-line changes.

1-14 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Programs can be simulated and tested and tested on the computer before downloading
to the controller hardware. Also provided is a set of configuration tools that enables
you to define the hardware architecture in the software; set up the processor
functionality; and connect application variables to the Workbench application
resource program that will monitor processor and I/O module status information and
report I/O channel data values to the Workbench. Resource Control applications can
be distributed across several hardware platforms, communicating with each other
through secure networks.
CAUTION WORKBENCH FOR USE IN SAFETY APPLICATIONS

If the Workbench is used for safety related applications then you must follow
the guidelines given in the AAdavnce Safety Manual (Doc No: 553630).

Operating System
The 9110 Processor Module must have an operating system with the following
specification:
 Windows XP with Service Pack 3
 Windows Vista, Windows 7 & Server 2003 in both 32-bit and 64-bit versions
Note: Work Bench Licensing –Windows 64-bit version will only work with the
USB Licensing option (dongle option).
 Network port (10/100 Base T Ethernet)
 Access to a CD-ROM drive, for software installation
Note: If the application adopts the USB (dongle) licensing option for the
Workbench software, the processor module will also require one free USB port.

CAUTION WORKBENCH OPERATING SYSTEM

Do not use XP Professional x64 edition.

AADvanceDiscover Utility
The AADvanceDiscover utility is installed when you install the
<DevelopmentSoftwareTools>, and appears on the Start menu of the computer. it
displays a list of the <ProductName> controllers on the broadcast network, and
reports a status for each one.

Importing and Exporting Data


The AADvance Workbench can import and export existing data in standard file
formats such as Microsoft Excel.

Document: 553631 1-15


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Controller Functionality

SNTP
The AADvance controller supports the Simple Network Time Protocol (SNTP)
service that can circulate an accurate time around the network. As an SNTP client the
controller will accept the current time from external Network Time Protocol
(NTP) and SNTP network time servers.
SNTP clients settings tell the controller the IP address of the external server; the
version of SNTP offered by the server; and the operating mode for the time
synchronization signal that the processors will use for their real time clock.
An AADvance controller can also fulfill the role of one or more SNTP servers (one for
each processor) to provide a network time signal throughout the network. To enable
server time on an interface it is necessary to specify the direct broadcast address for
that interface. This works for broadcast or unicast modes. This method of configuring
is derived from the NTP configuration command language.

CIP over EtherNet/IP


The Common Industrial Protocol (CIP) over EtherNet/IP protocol enables
AADvance controllers to exchange data with ControlLogix controllers programmed
by RSLogix 5000. The exchange of data uses the produce/consume tag method
currently used for sharing data between Logix-based controllers; this mechanism is
similar to the variable bindings mechanism used by the AADvance controller.
The AADvance controller supports produce and consume communications to
redundancy systems. The support for produce/consume variables is non-interfering; a
failure of the EtherNet/IP stack will not interfere with the safe operation of the
controller.
To use CIP over EtherNet/IP you have to first define a CIP network. Then you
configure the exchange of data by defining a produce variable (or structure) for
AADvance controller and a corresponding consume variable (or structure) for the
ControlLogix controller. At runtime, the controller with the consume variable pulls
data from the controller with the produce variable.

Note: The AADvance Controller will support the following number of connections
and variables:

 Connections: Maximum 255


 A maximum of 128 producer and 128 consumer variables can be defined.

1-16 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Note: The CIP Protocol is intended to allow AADvance users to exchange data
between AADvance controllers and the Allen Bradley Logix family controllers, using
produce/consume messaging. Produce/Consume messaging does not support
downloading to or for monitoring AADvance controllers. It is not recommended to
use the CIP network to exchange data between AADvance controllers unless this is
exclusively for non-safety data. The SNCP network should be used for Safety related
data exchange between AADvance Controllers (see SNCP and variable Bindings in this
publication).

HART
The AADvance controller supports utilizing dedicated HART modems on each
analogue input and output channel allowing HART field device status, diagnostics and
process data to be integrated into the application logic, thus increasing the level of SIF
diagnostics significantly.
The AADvance analogue input/output modules use HART commands #03 to collect
data from the field device as defined by Revision 5 of the HART specification. The
application can be configured to use HART information to monitor and respond to
device conditions. It may also be used to provide diagnostic information such as
comparison and error reporting.
An additional feature of the AADvance controller is that it also combines with the
AADvance DTM to enable asset management software (ASM) to communicate with
HART devices.

Note: The AADvance system does not alter the messages passed between the asset
management software and the field device and acts as a transport mechanism only.

AADvance HART Features


 Provides passthru support for HART Standards 5, 6 and 7.
 Variables can be configured for each Analogue input and output channel to
monitor HART device information.
 HART support is available on each Analogue Input or Output channel.
 AADvance uses a single dedicated Ethernet port for HART passthru
communication.
 Supports the AADvance DTM provided by Rockwell Automation.
A typical HART set up is shown below:

Document: 553631 1-17


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Figure 1: Example HART Pass-through System

SNCP Safety Networks


SNCP (Safety Network Control Protocol) is the Safety Protocol that allows
elements of an AADvance System to exchange data. AADvance SNCP is a SIL 3
certified protocol which provides a safety layer for the Ethernet network making it a
"Black Channel". Data is exchanged by creating a relationship between variables in
different AADvance controllers; this is called "Binding Variables". Once variables are
bound between controllers the SNCP protocol provides a transparent SIL 3 Certified
layer allowing safety related data to be passed between AADvance controllers.
The bindings are based on a producer/consumer model. The controller consuming the
data establishes a binding link with the Controller producing the data, and manages the
entire exchange of data, including scheduling the data exchange, providing the
diagnostics, managing the safety response in the event of faults and managing the
communications redundancy.
SNCP Networks can be configured as Simplex (Fail Safe) or Redundant (Fault tolerant),
the choice of network configuration is dependent on the applications safety and
availability requirements. The data exchange is independent of the physical; network
configuration as the connection between the controllers is treated as a logical
network.

1-18 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
The physical network is considered a "Black Channel" so the design of the Ethernet
network and the equipment used does not impact the SIL rating of the
communications interface, but the design of the network does affect the reliability of
the network and does impact the spurious trip rate. SNCP Network data can be
combined on a common network resulting in safety and non-safety data sharing in a
common physical network; this does not compromise the SIL rating of the network
but again does introduce failure modes and possibly security risks which can increase
the spurious trip rate, careful consideration should be given to the network topology
during the applications specification and design phase.

Document: 553631 1-19


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Peer-to-Peer
AADvance provides the capability for a SIL 3 certified Peer-to-Peer data connections,
allowing safety data to be transferred between AADvance and Trusted Controllers.
The Trusted Peer-to-Peer network protocol enables you to share safety data between
AADvance systems or AADvance and Trusted TM systems across an Ethernet network.
Data can be transferred between individual systems or from one to several systems at
the same time using multicast network connections. Peer-to-Peer communication is
configured by defining a peer network controller and I/O devices within the application
program.

Note: AADvance currently supports multicast network connections on the left most
port only.

For safety related applications it is recommended that the Peer-to-Peer


communications use redundant networks (for availability) and separate networks (from
general purpose, for security and integrity). Any of the AADvance or Trusted ports
can be used for Peer-to-Peer data connections see Example shown.
The Trusted Peer-to-Peer protocol is a master/slave interaction. For each peer
communications subnet one system acts as a master while the others act as slaves.
During the Peer-to-Peer communication cycle the master sends a command to the
first slave to transmit its data. When the slave completes this task it acknowledges this
back to the master. The master repeats this with the next and all slaves in turn. Finally
the master transmits its own data then repeats the cycle with the slaves.

1-20 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Safety Related Peer-to-Peer Configurations
The following Peer-to-Peer configurations are approved for use in a safety Related
Function:

Table 3:

Peer-to-Peer TÜV Certified Conditions


Settings Configuration
Software Board Certified for use over Certified as safety-related and can be used for safety
Definitions: a single critical communications in SIL 3 applications.
communication
Dxpdi16
network or multiple
Dxpdo16
networks
Dxpao16
Dxpdi128
Dxpdi128 & dxpnc40

Document: 553631 1-21


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Peer-to-Peer TÜV Certified Conditions


Settings Configuration
Software Board Certified for use over Certified as safety-related and can be used for safety
Definitions: a single critical communications in SIL 3 applications
communication provided to separate Dxpai128 & Dxpao128 board
Dxpai128
network or multiple definitions are used for safety values, the safety
Dxpao128
networks values from the tw oDxpai128 boards (or digital trip
points from the values) shall have a 1oo2 vote
within the receiving application.

Serial Communication Interface


Two serial ports on each processor module support the following signal modes
depending upon use:
 RS485fd: A four-wire full duplex connection that features separate busses for
transmit and receive. This selection should also be used when the controller is
acting as a Modbus master using the optional four-wire definition described in
Section 3.3.3 of the Modbus-over-serial standard.
 RS485fdmux: A four-wire full-duplex connection with tri-state outputs on the
transmit connections. This should be used when the controller is acting as a
Modbus slave on a four-wire bus.
 RS485hdmux: A two-wire half duplex connection appropriate for or master slave
or slave use. This is shown in the Modbus-over-serial standard.

Time Synchronization (SNTP)


The AADvance controller supports the Simple Network Time Protocol (SNTP)
service that can circulate an accurate time around the network. It can be configured to
operate as a SNTP client or server.
As an SNTP client the controller will accept the current time from external Network
Time Protocol (NTP) and SNTP network time servers. The SNTP clients settings
tell the controller the IP address of the external server; the version of SNTP offered
by the server; and the operating mode for the time synchronization signal that the
processors will use for their real time clock. As a client the processor module can be
configured as a unicast or broadcast client.
The AADvance controller can also fulfill the role of one or more SNTP servers (one
for each processor module) to provide a network time signal throughout the network.
To enable server time on an interface it is necessary to specify the direct broadcast
address for that interface. This works for broadcast or unicast modes and when
configured as a broadcast server it can respond to Unicast requests from clients.

Note: To set up SNTP you need to connect your controller to a suitable network
using one of the Ethernet ports. The network must be connected to an external NTP
server or have NTP loaded on to it.

1-22 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Modbus Master
The AADvance controller can be used as a Modbus master to one or more Modbus
slave devices. Slave devices can include programmable logic controllers, remote devices
(typically with little or no processing capability) and, more rarely, other functional
safety controllers (Trusted or AADvance).
The controller supports the Modbus RTU and Modbus TCP protocols, and a subset
of Modbus commands. You can use Modbus RTU with point-to-point and multi-drop
serial links, and Modbus TCP with Ethernet.

Note: The AADvance controller does not support the Modbus ASCII protocol.

You can set up an individual list of messages (commands) for each slave device.
Modbus read commands cause data to read from the slave device to the Modbus
master, while Modbus write commands cause data to be copied from the Modbus
master to the slave device. You can also define a sequence of broadcast write
commands, which a Modbus master can send to multiple Modbus RTU slaves without
requiring an acknowledgement. The AADvance controller can control and monitor
individual Modbus master objects and their slave links.
The Modbus master functionality has a safety integrity level of zero (SIL0) and should
only be used for non-safety applications.

Document: 553631 1-23


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Modbus Master Hardware and Physical Connections


The Modbus master functionality is built into the T9110 Processor Module; the
physical communication ports are located on the T9100 Processor Base Unit. You do
not need to add any extra hardware to the AADvance controller except to make the
physical connections to the processor base unit. The illustration shows some possible
arrangements of Modbus master connections.

The Modbus RTU slave devices are connected to one or more of the serial ports on
the controller; a typical arrangement will use a multi-drop (RS-485) arrangement. The
engineering workstation and the Modbus TCP devices are shown connected to the
Ethernet ports on separate networks; alternatively these can be combined onto one
network.

The OPC Portal Server


The OPC Portal Server is a windows-based application that allows OPC compatible
clients, such as HMIs and SCADA systems, to connect to one or more AADvance
controllers to access process data.

1-24 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Controller IP Address Setting
The AADvanceDiscover Utilility uses a discovery and configuration protocol
(proprietary to Rockwell Automation) to set the controller IP address within the
AADvance Workbench and to scan the broadcast domain for other AADvance
controllers. The utility locates each controller by its unique MAC Address. Having
located a particular controller to be configured, the utility lets you configure the
resource number and IP Address to be stored in the controller; after you have done
this, the AADvance Workbench can communicate with the other controller.

Recovery Mode
Recovery Mode is a shutdown mode and uses a base level firmware. It is entered
automatically when a critical firmware failure occurs or it can be entered manually by
pressing the processor Fault Reset button immediately after the module has booted
up. The Recovery Mode is also used when you want to download a new firmware
upgrade.
As an alternative firmware version it allows the following maintenance activities:
 Update the firmware using the ControlFLASH utility
 Program the processor IP Address with the AADvance Discover utility
 Extract diagnostic information

Note: When in Recovery Mode the I/O communications are disabled and the
Application code is not running. The inputs and outputs will revert to their fail-safe
settings.

DiffServ Configuration
This option allows you to specify the priority of IP traffic and is particularly useful for
ensuring that high priority services are either not affected or less affected during
periods of network congestion.
When you set up this option you apply a priority value to a service and therefore
differentiate it from less important services. You can do this by setting a suitable
configuration of routers, or switches able to inspect IP headers and prioritize by the
Type of Service (ToS) header option. Network devices will then apply their rules to
prioritize IP traffic; AADvance simply maintains the priority when responding to
incoming messages and sets a priority according to the configuration for messages it
initiates.

Document: 553631 1-25


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Ethernet Forwarding
When enabled, the "Ethernet Forwarding" feature will forward all Ethernet packets
destined for a host (3rd Party Device) connected to one of the AADvance’s Ethernet
ports along with any broadcast and multicast Ethernet traffic. Incoming messages on
the other port will be forwarded directly to the second. The forwarded messages will
be unaltered by the AADvance controller.
This feature can be enabled using the AADvance Discover utility. Packets intended for
the AADvance itself (i.e. the destination MAC address of the packet matches the
processor’s receiving port MAC address) as well as broadcasts and multicasts are still
sent to the AADvance application as normal.

Note: The Ethernet network carrying Safety Data on a Safety application is considered
to be a black channel, therefore, it is unaffected by this function. However, by
implementing Ethernet Forwarding you may be forwarding non-safety data onto a
safety network and could effectively bridge a safety and non-safety segregated network
through the AADvance.

1-26 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Transparent Communication Interface (TCI)
The AADvance controller processor module provides a Transparent Communications
Interface (TCI) function. This functionality will establish a pass-through
communications link between an Ethernet link to a Serial port allowing devices
attached to a serial port to be communicated with and for them to reply. The
controller does not tamper with or inspect the data passed over the channel.
TCI uses a TCP port number to represent a serial port. All six serial ports are
represented by each controller, so any serial port can be reached from any controller.
Traffic is routed through TCP to the relevant serial port and in reverse. However, TCI
communication from the serial ports is only available when the controller is not
executing an application.
Users can enable and disable the function and set the Inactivity Timeout and Idle Time
values.

Important Note: To use the TCI function you must stop the resource. This will
have a serious effect on a Safety Related application.

Compiler Verification Tool


The Compiler Verification Tool (CVT) is a software utility that validates the output of
the application compilation process. It is automatically enabled for resources when a
project is created and when you add a resource to an existing project. This process in
conjunction with the validated execution code produced by the AADvance
Workbench confirms that there are no errors introduced by the Compiler during the
development of the application.
To achieve this CVT decompiles the application project file and then compares each
individual application project (POU) source files with its decomposed version. The
CVT analysis is displayed in the Workbench window.

Document: 553631 1-27


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Technical Features

TUV Approved Operating System


The AADvance system runs an IEC 61508 approved operating system and the overall
system is certified to IEC 61508, Part 1-7: 19T98 - 2000 SIL3.

Internal Diagnostics
The AADvance controller contains comprehensive internal diagnostic systems to
identify faults that develop during operation and raise appropriate alarm and status
indications. The diagnostic systems run automatically and check for system faults
associated with the controller, and field faults associated with field I/O circuits.
Serious problems are reported immediately, but faults on non-essential items are
filtered to avoid spurious alarms. The diagnostic systems monitor such non-essential
items only periodically, and need a number of occurrences of a potential fault before
reporting it as a problem.
The diagnostic systems use simple LED status indications to report a problem. The
LED indications identify the module and can also identify the channel where the fault
has occurred. There is also a summary system healthy indication for the whole
controller.
The application software uses its variable structures to report a problem; these
variables proved status reports and are configured using the AADvance Workbench.
A Fault Reset button on each processor module serves to clear a fault indication.
However, the diagnostic systems will report a serious problem again so quickly there
will be no visible change in the status indications. Pressing the Fault Reset button when
no fault is indicated has no effect.

Controller Internal Bus Structure


Internal communication between the processor modules and I/O modules is supported
by command and response busses that are routed through the processor and I/O base
units.
The processor modules acts like a communications master, sending commands to its
I/O modules and processing their returned responses. The two command busses IO
Bus 1 and IO Bus 2 carry the commands from the processor to the I/O modules on a
multi-drop basis. An inter-processor link (IPL) provides the communication links
between dual or triple processor modules.
Each I/O module has a dedicated response line back to the processor. The unique
response line for each I/O module provides an unambiguous identification of the
source of the I/O data and assists with fault containment.

1-28 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
System Modification and On-line Updates
The AADvance controller has a modular design which allows you to change the I/O
hardware configuration. An on-line update feature also allows you to make the
required changes to the workbench I/O configuration.
The following changes can be made by an on-line update:
x Add new I/O base units, termination assemblies and extra I/O modules.
x Delete modules from the system
x Change the size of a termination assembly to change the configuration to
either increase the size or reduce the size of the module configuration.
x Move a module to a different slot.
x Change the variables for an I/O configuration change.
Making on-line changes after the system has been commissioned is the responsibility of
users and can have safety integrity implications the safety guidelines in the Safety
Manual need to be consulted before doing an on-line update.
On-line modifications must follow the end users' MOC process as required by the
applicable industry safety standards. On-line modifications must include any specific
checks recommended by Rockwell Automation for the product.

NOTE: If you are still using an earlier product release the I/O module configuration
cannot be changed with an on-line update.

Expansion Cable

Document: 553631 1-29


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

When new I/O modules need to be added and there is not enough space in the
existing row of modules, you can use an Expansion Cable to install a new row of
modules. A typical arrangement using an expansion cable is shown below.

1-30 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
ControlFLASH Firmware Upgrades
The AADvance controller supports upgrades of processor module firmware by using
the ControlFLASH utility. You need the ControlFLASH firmware upgrade kit that
includes and RSLinx Classic Lite software or better. To install and configure the
ControlFLASH utility refer to the Rockwell Automation ControlFLASH Firmware
Upgrade Kit documentation, Publication No: 1756-UM105C-EN-E March 2012
available from the Rockwell Automation Literature Library. This document defines
what you will need to carry out the procedures.

Note: I/O module upgrades using ControlFLASH are not currently supported in this
release.

Upgrading the processors is a two stage process:


 Stage 1: Run the 350720_102_ControlFLASH.msi program to install the
ControlFLASH firmware upgrade kit for the Recovery Mode on your PC. Then
run the ControlFLASH utility to upgrade your processor module and install the
Recovery Mode. If your module is delivered with the Recovery Mode installed then
this stage is not necessary.
 Stage 2: Reboot the processor and enter the Recovery Mode. The run
354400_0199_ControlFLASH.msi program to install the ControlFLASH to
upgrade your processor's OS, FPGA, LSP and BUSP.

WARNING FIRMWARE UPGRADE DANGER TO A RUNNING SYSTEM


Do not attempt to upgrade firmware on a running system. Control
FLASH will not warn you that a system is running and you will lose
control of the application when the system reboots.

Document: 553631 1-31


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Physical Features
An innovative feature of the AADvance controller is the design of the hardware.
Everything fits together easily without any need for inter-module wiring.

Product Dimensions

Overall Dimensions of Modules with Base Units

Table 4: Summary of Dimensions

Attribute Value

Base unit dimensions (H × W × D), approx. 233 × 126 × 18mm (see text)
(9-¼ in × 5 × ¾ in)
Module dimensions (H × W × D), approx. 166 × 42 × 118mm
(6-½ in × 1-⅝ in × 4-⅝ in)

1-32 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
The depth of the base unit (18mm) excludes the parts of the backplane connectors
that mate inside the module connectors. Adding the depth of module (118mm) to the
depth of the base unit gives the overall depth of the controller assembly, which is
136mm.

Module Dimensions
All modules have the same dimensions.

Compact Module Design


Each processor and I/O module is enclosed in a flame-retardant and impact-resistant
plastic cover. The cover is designed to assist ventilation and heat dissipation.
Processor and I/O modules fit onto a series of standardized base units. Base units are
securely held together by specially designed plastic clips which cannot corrode or
seize. Modules are retained by a locking latch accessible from the front panel, and
corrective maintenance activities need only a standard screwdriver.

Document: 553631 1-33


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Base units are moulded from a similar material. Each base unit can be mounted onto
standard DIN rails or directly onto a panel or wall. The moldings incorporate slots and
clamps for DIN rail mountings, and holes for screw fixing.

CAUTION HEAT DISSIPATION AND ENCLOSURE POSITION


System and field power consumption by modules and termination assemblies is
dissipated as heat. You should consider this heat dissipation on the design and
positioning of your enclosure; e.g. enclosures exposed to continuous sunlight
will have a higher internal temperature that could affect the operating
temperature of the modules. Modules operating at the extremes of the
temperature band for a continuous period can have a reduced reliability.

Module Polarization Keying


For each I/O Module there is a matched termination assembly set. The controller
incorporates module polarization keying to ensure they are matched when installed.
Modules have polarized sockets that align and mate with coding pegs located on the
termination assembly. The alignment of the sockets and pegs ensure only the matched
I/O module type can be fitted into each associated termination assembly and only a
processor can be installed on a processor base unit.

1-34 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Module Locking Mechanism
Each module carries a locking mechanism, which secures the module onto its base unit.
The locking mechanism is in the form of a clamp screw, visible on the front panel of
the module and engaged by a quarter turn of a flat blade screwdriver. The module
senses the locking mechanism position and notifies the controller accordingly. This acts
as an interlock device and prevents the module from going on-line when it is not in the
locked position.

Termination Assemblies
The AADvance system provides a range of termination assemblies to connect field
wiring to the I/O modules. A termination assembly is a printed circuit equipped with
screw terminal blocks for the field wiring (in some cases fuses) and connectors for the
plug-in I/O modules. Termination assemblies are matched to their relevant I/O
modules by the coding pegs and sockets and come in three types: simplex, dual or
triple. Therefore, they can accommodate one two or three I/O modules. Each
assembly provides connections for up to 16 channels but can accommodate 8 or 16
channel modules.
Termination assembly design gives the controller greater flexibility for building
redundant and fault tolerant systems. I/O module(s) plugged into its matched
termination assembly can provide simplex, dual or triple modular redundant
configurations.
The version illustrated is a simplex termination assembly for a digital input module.
The field wiring connectors are located to the left, the fuses have a cover (shown
open) and the module sockets are to the right.

Document: 553631 1-35


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Part No: Digital Input Fuses T9901: No 396/TE5 50mA time lag fuse; UL 248-14, 125
V,T Leadfree; manufactured by Littlefuse.
Part No: Digital Output Fuses T9902: SMF Omni-Block, Surface Mount Fuse Block
154 010, with a 10A, 125V Fast Acting Fuse, Littlefuse.

WARNING FUSE REMOVAL or REPLACEMENT


When the controller is installed in a Hazardous environment do not remove or
replace a fuse when energized.

1-36 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Ethernet, Serial Data and Power Connections
The external connections for Earthing, Ethernet (E1-1 to E3-2), serial data (S1-1 to
S3-2) and the +24V dc Redundant powers supplies (PWR-1 and PWR-2) are all
located on the T9100 Processor Base Unit. There are two serial data and two
Ethernet connectors for each processor module. Two connectors for the dual
redundant power supplies, a stud for the Earth and a connector for the security device
(KEY) also known as the Program Enable Key.

Note: The FLT connector is not used.

Serial Communications
The serial ports (S1-1 & S1-2, S2-1 & S2-2, S3-1 & S3-2) support the following
signal modes depending upon use:
 RS485fd: A four-wire full duplex connection that features separate busses for
transmit and receive. This selection should also be used when the controller is
acting as a Modbus master using the optional four-wire definition described in
Section 3.3.3 of the Modbus-over-serial standard.
 RS485fdmux: A four-wire full-duplex connection with tri-state outputs on the
transmit connections. This should be used when the controller is acting as a
Modbus slave on a four-wire bus.
 RS485hdmux: A two-wire half duplex connection appropriate for or master slave
or slave use. This is shown in the Modbus-over-serial standard.

Document: 553631 1-37


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Field Wiring Connections


Field connections are made using industry-standard screw terminal blocks. Terminals
are readily accessible for future wiring modifications without needing to dismantle any
assemblies. This illustration shows field wiring to four simplex termination assemblies:

Corrective Maintenance and Module Replacement


Corrective maintenance is by module replacement. In dual and triple modular
redundant configurations, you can remove a module and install a new one without
interrupting the system opetration. In simplex configurations removing a module will
interupt the system operation.
Field connection wiring is attached at the connectors on the termination assemblies.
Ethernet and Serial data connections are made at the T9100 Processor Base Unit.
There are no physical links needed to be set up on any modules or base units.
Standard modules are used for all the different configurations.
The guidelines for replacing modules are given in the AADvance Safety Manual (Doc
no 553630).

Note: Processor modules must be replaced with a module containing the same
firmware revision, you cannot use processor modules with different firmware
revisions.

1-38 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 2
AADvance System Architectures
An AADvance controller can be configured to manage non-safety up to SIL 3 safety
related system requirements and low demand or high demand fault tolerant
applications.
This chapter describes the different system architectures that can be configured for an
AADvance controller to meet this variety of requirements.

Note: Architectures are independent of I/O module capacity therefore 8 or 16


channel I/O modules can be used.

In This Chapter
SIL2 Architectures .............................................................................................. 2-1
SIL3 Architectures .............................................................................................. 2-6
Planned Certified Configurations .................................................................. 2-11

SIL2 Architectures
SIL2 architectures are recommended for fail-safe low demand applications. All SIL2
architectures can be used for energize or de-energize to trip applications. In any
configuration when a faulty processor or input module is replaced then the previous
fault tolerance level is restored. For example in a fault tolerant input arrangement and
one module is faulty then the system will degrade to 1oo1D, by replacing the faulty
module the configuration is restored to 1oo2D.
Definitions:
Low Demand Mode - in this mode the frequency of demands on the safety-related
system is no greater than twice the proof test interval. Where the proof test interval
refers to how often the safety system is completely tested and ensures it is fully
operational. For the AADvance System the default manual test interval is the value
used to calculate the PFH and PFD values.
High Demand Mode - sometimes called continuous mode, is where the frequency of
demands for operation made on a safety-related system is greater than twice the
manual test interval.

Document: 553631 2-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

SIL2 Fail-safe Architecture


The following is a simplex fail-safe SIL2 architecture, where I/O modules operate in
1oo1D under no fault conditions and will fail-safe on the first detected fault. The
processor module operates in 1oo1D and will degrade to fail safe on the first detected
fault.

Note: A simplex configuration can only be used for "low demand"

Table 5: Modules for SIL2 Fail-Safe Architecture

Position Module Type


I/P A T9401/2 Digital Input Module, 24V dc, 8/16 Channel +
T9801 Digital Input TA, 16 Channel, Simplex. or
T9431/2 Analogue Input Module,
8/16 Channel +
T9831 Analogue Input TA, 16 Channel, Simplex
T9300 I/O Base Unit
CPU A 1 x T9110 Processor Module, T9100 Processor Base
Unit,
O/P A T9451 Digital Output Module, 24V dc, 8 Channel,
isolated +
T9851 Digital Output TA, 24V dc 8 Channel, Simplex

2-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
SIL2 Fault Tolerant Input Architectures
A SIL2 fault tolerant input architecture can have dual or triple input modules with a
single processor and single output modules. The illustration shows a dual input
arrangement where the dual input modules operate in 1oo2D under no fault
conditions, they degrade to 1oo1D on detection of the first fault in either module of
the redundant pair, and when a fault occurs on the second module it will fail-safe.
The processor module operates in 1oo1D under no fault conditions and degrades to
fail safe on the first detected fault. The output module operates in 1oo1D under no
fault conditions and will fail-safe on the first detected fault.
When a triple input module arrangement is configured the group of input modules
operate in 2oo3D under no fault conditions, degrade to 1oo2D on the detection of
first fault in any module, then degrade to 1oo1D on the detection of faults in any two
modules, and will fail-safe when there are faults on all three modules.

Table 6: Modules for SIL2 Architecture

Position Module Type


I/P A and B 2 × T9401/2 Digital Input Module, 24V dc, 8/16 Channel +
T9802 Digital Input TA, 16 Channel, Dual or 2 × T9431/2
Analogue Input Module, 8/16 Channel, Isolated, + T9832
Analogue Input TA, 16 Channel, Dual
T9300 I/O Base Unit
CPU A 1 x T9110 Processor Module, T9100 Base Unit
O/P A T9451 Digital Output Module, 24V dc, 8 Channel +
T9851 Digital Output TA, 24V dc, 8 Channel, Simplex
T9300 I/O Base Unit

Document: 553631 2-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

SIL2 Output Architecture


A SIL2 output architecture has a single output module with single processor and single
or redundant input modules.
 In de-energize to trip operation, the output modules operate in 1oo2D no fault
conditions and degrade to 1oo1D on detection of the first fault in either module
and fail-safe when there are faults on both output modules.
 In energize to action operation, the output module operates in 1oo2D under no
fault conditions, degrade to 1oo1D on the detection of the first fault in either
module, and they fail-safe when there are faults on both modules.
The illustration shows a SIL2 single output arrangement where the output and
processor modules operate in 1oo1D under no fault conditions and will fail-safe on the
first detected fault.

Table 7: Modules for SIL2 Fault Tolerant Output Architecture

Position Module Type


I/P A T9401/2 Digital Input Module, 24V dc, 8/16 Channel. +
T9801 Digital Input TA, 16 Channel, Simplex
or
T9431/2 Analogue Input Module, 8/16 Channel +
T9831 Analogue Input TA, 16 Channel, Simplex
T9300 Base Unit
CPU A 1 x T9110 Processor Module, T9100 Processor Base Unit
and 9300 I/O Base Unit
O/P A 1 × T9451 Digital Output Module, 24V dc, 8 Channel +
T9851 Digital Output TA, 24V dc, 8 Channel, Dual

2-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
SIL2 Fault Tolerant Input High Demand Architecture
A SIL2 fault tolerant "High Demand" architecture has dual input, dual processor and
dual output modules. In a dual arrangement the input modules operate in 1oo2D
under no fault conditions, degrade to 1oo1D on the detection of the first fault in
either module, and will fail-safe when there are faults on both modules.
A triple input module arrangement can also be configured if it is required to increase
the fault tolerance of the input. When a triple input module arrangement is configured
the input modules operate in a 2oo3D under no fault conditions, degrade to 1oo2D on
detection of the first fault in any module, then degrade to 1oo1D on the detection of
faults in any two modules, and will fail-safe when there are faults on all three modules.
The processor will operate in 1oo2D under non-faulted conditions and will degrade to
1oo1D on the first detected fault. For high demand applications the processor must be
repaired within the MTTR assumed in the PFD calculations or the high demand safety
instrumented functions must be shut down.

For High Demand applications you must use a minimum of a dual processor
configuration.

Table 8: Modules for SIL2 Fault Tolerant High demand Architecture

Document: 553631 2-5


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Position Module Type


I/P A 2 × T9401/2 Digital Input Module, 24V dc, 8/16 Channel +
T9802 Digital Input TA, 16 Channel, Dual or
2 × T9431/2 Analogue Input Module, 8/16 channel + T9832
Analogue Input TA, 16 Channel, Dual
2 × T9300 I/O Base unit
CPU A & 2 x T9110 Processor,, T9100 Processor Base Unit
CPU B
O/P A 2 × T9451 Digital Output Module, 24V dc, 8 Channel + T9852
Digital Output TA, 24V dc, 8 channel,
T9300 Base unit

SIL3 Architectures
SIL3 architectures have at least two processor modules and are suitable for use with:
 SIL3 de-energize to trip applications
 SIL3 energize to action applications when fitted with dual output modules
Faulted input modules in a SIL3 arrangement may be replaced without a time limit;
faulted output modules must be replaced within the MTTR assumed in the PFD
calculations.
In all SIL3 architectures, when the processor modules have degraded to 1oo1D on the
first detected fault, the system must be restored to at least 1oo2D by replacing the
faulty processor module within the MTTR assumed in the PFD calculations or all SIL3
safety instrumented function and high demand safety instrumented functions must be
shut down.

2-6 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
SIL3 Fail-safe I/O, Fault Tolerant Processor
A SIL3, fail-safe I/O with a fault tolerant processor architecture has a simplex input and
output arrangement with dual or triple processor modules. The dual processor
modules operate in 1oo2D under no fault conditions and degrade to 1oo1D on
detection of the first fault in either module. When there are faults on both modules
the configuration will fail-safe.

If required you can configure triple processor modules as a variation of this SIL3
architecture. Using this arrangement the processor modules operate in 2oo3D under
no fault conditions and 1oo2D on the detection of the first fault in any module. They
degrade to 1oo1D on the detection of faults in any two modules, and will fail-safe
when there are faults on all three modules.

Document: 553631 2-7


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Table 9: Modules for SIL3 Fail-safe I/O, Fault Tolerant Processor

Position Module Type


I/P A T9401/2 Digital Input Module, 24V c, 8/16 Channel +
T9802 Digital Input TA, 16 Channel, Dual or
T9431/2 Analogue Input Module, 8/16 channel + T9832
Analogue Input TA, 16 Channel, Dual
T9300 Base unit
CPU A & 2 x T9110 Processor Module, T9100 Base Unit
CPU B
O/P A T9451 Digital Output Module, 24V dc, 8 Channel + T9851
Digital Output TA, 24V dc, 8 Channel, Simplex

SIL3 Fault Tolerant I/O Architectures


A SIL3 fault tolerant processor and I/O is achieved by dual input and output module
configurations with dual or triple processor modules. The processor modules operate
in 1oo2D under no fault conditions, degrade to 1oo1D on the detection of the first
fault in either module and fail-safe when there are faults on both modules.
Similarly the input modules operate in 1oo2D under non faulted conditions and 1oo1D
on detection of the first fault in either module and will fail-safe when there are faults
on both modules.
The processor will operate in 1oo2D under non-faulted conditions and will degrade to
1oo1D on the first detected fault. For high demand applications the processor must be
repaired within the MTTR assumed in the PFD calculations or SIL3 safety instrumented
functions must be shut down.

For SIL3 applications you must use a minimum of a dual processor


configuration.

For de-energize to action operation one 9451 digital output module is sufficient for
SIL3 requirements. However, for energize to action operation, dual digital output
modules are required.
The single output module operates in 1oo1D under no fault conditions and fail-safe
when there is a fault on the module. For energize to action operation, the output
modules operate in 1oo2D under no fault conditions, degrade to 1oo1D on the
detection of the first fault in either module and fail-safe when there are faults on both
modules.

2-8 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Table 10: Modules for SIL3 Fault Tolerant Architectures

Position Module Type


I/P A 2 × T9401/2 Digital Input Module, 24V dc, 8/16 Channel,
+ T9802 Digital Input TA, 16 Channel, Dual or
and
2 × T9431/2 Analogue Input Module, 8/16 Channel +
I/P B
T9832 Analogue Input TA, 16 Channel, Dual
2 x T9300 I/O Base Unit
CPU A & 2 × T9110 Processor Module, 9100 Processor Base Unit,
CPU B
O/P A 1 × T9451 Digital Output Module, 24V dc, 8 Channel +
T9851 Single Digital Output TA, 24V dc, 8 Channel for de-
and
energize to action.
O/P B
T9300 Base unit
2 x T9451 Digital Output Module, 24V dc, 8 Channel +
T9852 Dual Digital Output TA for energize to action.

Document: 553631 2-9


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

SIL3 TMR Input and Processor, Fault Tolerant Output


A SIL3 TMR architecture offers the highest level of fault tolerance for an AADvance
controller and consists of triple input modules, triple processors and dual output
modules.
 The input and processor modules operate in a 2oo3D under no fault conditions,
degrade to 1oo2D on detection of the first fault in any module, and degrade to
1oo1D on the detection of faults in any two modules and will fail-safe when there
are faults on all three modules.
 For de-energized to action operation the output modules operate in 2oo2D under
non faulted conditions and degrade to 1oo1D on detection of the first fault in
either module and fail-safe when there are faults on both modules.
 For energize to action operation the output modules operate a 1oo2D under no
fault conditions and degrade to 1oo1D on the detection of the first fault in either
module and fail-safe when there are faults on both modules.
In the event of a failure in any element of a channel, the channel processor will still
produce a valid output which could be voted on because of the coupling between the
channels. This is why the triple modular redundant implementation provides a
configuration that is inherently better than a typical 2oo3 voting system.

Table 11: Modules for TMR Input and Processor, Fault Tolerant Output

Position Module Type


I/P A 3 × T9401/2 Digital Input Module, 24V dc, 8/16 Channel +
T9803 Digital Input TA, 16 Channel, TMR
or
3 × T9431/2 Analogue Input Module, 8/16 Channel +
T9833 Analogue Input TA, 16 Channel, TMR
2 × T9300 I/O Base Unit

2-10 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
CPU A & 3 × T9110 Processor Module, T9100 Processor Base Unit,
CPU B

O/P A 2 × T9451 Digital Output Module, 24V dc, 8 Channel +


9852 Digital Output TA, 24V dc 8 Channel, Dual

Note: All configurations that use dual or triplicate processor modules are suitable for
SIL3 architectures with de-energize to trip outputs. Dual outputs are also required for
SIL3 energize to action outputs.

Planned Certified Configurations

Table 12: Central Modules

Modules TÜV Certified Conditions


Configuration
Processor Module 1oo1D, 1oo2D, Safety-related and can be used for safety-critical
T9110 2oo3D applications in SIL2 with 1 module fitted and SIL3
applications with 2 or 3 modules fitted.
Note: For High Demand applications you must use
a minimum of two processors.

Table 13: Input Modules

Modules TÜV Certified Conditions


Configuration
Digital Inputs 1oo1D, 1oo2D, Within a specified safety accuracy limit of 1.0V dc.
T9401/2, 24V dc, 2oo3D De-energized to action (normally energized): SIL3
8/16 Channel, with 1, 2 or 3 modules fitted.
isolated.
Energize to action (normally de-energized): with 1, 2
+ or 3 modules fitted
T9801/2/3 Digital Note: when the integrity level is at 1oo1D then the
Input TA, 16 channel, faulty module must be replaced to restore the
Simplex/Dual/TMR integrity level back to 1oo2D.
Analogue Inputs 1oo1D, 1oo2D, Within the manufactures specified safety accuracy
T9431/2, 8/16 2oo3D limits of 200μA. The safety state of the analogue
Channel, isolated input has to be set to a safe value which is a
calculated value based on a count value of 0mA.
+
(refer to the AADvance Configuration Guide Doc
T9831/2/3 Analogue no: 553633 for more details)
Input TA, 16
SIL3 with 1, 2 or 3 modules fitted.
Channel,
Simplex/Dual/TMR Note: when the integrity level is at 1oo1D then the
faulty module must be replaced within the MTTR
assumed for the PFD calculations to restore the
integrity level back to 1oo2D.

Document: 553631 2-11


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Table 14: Output Modules

Modules TÜV Certified Conditions


Configuration
Digital Outputs 1oo1D, 1oo2 or De-energize to action (normally energized): SIL3
2oo2D with 1 or 2 modules fitted. 2oo2D with dual output
T8451, 24V dc, 8
modules fitted.
channel.
Energize to action (normally de-energized): SIL2
+
with 1 module fitted and SIL3 with 2 modules fitted.
T9851/2 TA,24V dc,
Note: Faulty modules must be repaired or replaced
8 Channel,
within the MTTR assumed for the PFD calculations
Simplex/Dual
for energize-to-action applications.

Table 15: Auxiliary Modules

Modules Conditions
Processor Base Safety-related and can be used for safety critical applications in Fault
tolerant/High demand SIL2 applications with 2 modules fitted or
T9100
SIL3 applications with 2 or 3 modules fitted.
I/O Base Safety-related and can be used for safety critical applications in SIL3.
T9300 (3-way)

Note: Revisions of modules are subject to change. A list of the released versions is
held by TÜV or can be obtained from Rockwell Automation.

2-12 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
This page intentionally left blank

Document: 553631 2-13


(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 3
Building Architectures with TUV Approved Modules
The controller supports a range of architectures. This chapter describes how to build a
range of architectures configurations and includes selected examples that illustrate the
alternative options. The modular construction of the controller makes it easy to create
module arrangements and these can be tailored for a particular application.

In This Chapterr
Fundamental Architectures .............................................................................. 3-1
Simplex I/O Architecture.................................................................................. 3-1
Dual Architecture for Fault Tolerant Applications..................................... 3-5
Triple Modular Redundant Architecture ...................................................... 3-7

Fundamental Architectures
The standard AADvance modules can be arranged to provide three fundamental
architectures based on simplex, dual and triple modular redundant processors
modules. To these can be added I/O modules for redundant and/or fault tolerant
configurations based on the following arrangements:
 Input modules in simplex, dual and triple modular redundant formations
 Output modules in simplex and dual arrangements
An AADvance system can mix different I/O architectures within one controller — for
example simplex and dual input modules with dual processor modules. The modular
construction of the controller enables you to create numerous other arrangements
that can be tailored for a particular application.
Once a system has been built and commissioned it can be expanded using any of the
architectures described in this chapter. However, this expansion can be carried out
with an on-line update.

Simplex I/O Architecture


A simplex configuration uses one input module for a field input, one output module for
a field output, and one processor module. Each module will fail safe on the first
detected fail danger fault and the process under control will shut down.

NOTE: To keep these examples simple the illustrations show only T9401 digital input
modules being used; however, T9431 analogue input modules or a mixture of the two
can be used instead.

Document: 553631 3-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Low Demand SIL2 Architecture


This is an example of a SIL2 controller which is suited to low demand mode
applications with de-energize and energize to action outputs. The T9801 and T9851
illustrated are the associated simplex termination assemblies that mate with the T9401
and T9451 I/O modules. This arrangement is also suitable for non-safety applications.

This example supports 8 field inputs and 8 outputs. There is space for two more
processor modules and one more I/O module. To further expand the I/O capacity you
would need to add I/O base units then the required number of I/O modules and
termination assemblies.

3-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Data Input and Output
A controller can support up to 48 I/O modules in total (on 16 I/O base units); as an
example, here is a controller with four 8 channel T9401 digital input modules and two
8 channel T9451 Digital Output Modules, giving 32 inputs and 16 outputs.

Document: 553631 3-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Adding a 2nd Processor for a Higher SIL Rating Configuration


A single processor module is rated SIL2, while two or three in a redundant
arrangement are rated SIL3. Returning to the first example and adding a second
processor module creates a controller suitable for high as well as low demand mode
applications at SIL3.
The T9401/2 digital input module (identical to the module for the SIL2 controller) is
rated SIL3 as it stands. The only constraint is that the simplex output stage will not
drive anenergize to action output for SIL3 - this requires a dual arrangement of output
modules. This output configuration is suitable for a de-energize to action output at
SIL3.
The second processor module provides the increased fault tolerance and gives the
configuration its SIL3 rating. If either processor module should fail, the controller
retains its SIL3 integrity but the module must be replaced within the MTTR.
This controller suits many applications needing a mixture of SIL3 de-energize to action
and SIL2 outputs which do not need the additional fault tolerance offered by dual and
triple modular redundant configurations. The possibilities for expansion are identical to
those for the SIL2 controller.

3-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Dual Architecture for Fault Tolerant Applications

Fault Tolerant Input and SIL3 Outputs


A dual architecture configuration shown uses two dual redundant modules for each
stage. The use of two processor modules provides SIL3 integrity for the processor
stage, (as for the previous example), while the addition of the second input module
provides fault tolerance for the inputs.
A SIL3 fault tolerant processor and I/O is achieved by dual input and output module
configurations with dual or triple processor modules. The processor modules operate
in 1oo2D under no fault conditions, degrade to 1oo1D on the detection of the first
fault in either module and fail-safe when there are faults on both modules.
The input modules operate in 1oo2D under non faulted conditions and 1oo1D on
detection of the first fault in either module and will fail-safe when there are faults on
both modules.
The processor will operate in 1oo2D under non-faulted conditions and will degrade to
1oo1D on the first detected fault. For high demand applications the processor must be
repaired within the MTTR or SIL3 safety instrumented functions must be shut down.
For de-energize to action operation one T9451 digital output module is sufficient for
SIL3 requirements. However, for energize to action operation, dual digital output
modules are required.
The single output module operates in 1oo1D under no fault conditions and fail-safe
when there is a fault on the module. For energize to action operation, the output
modules operate in 1oo2D under no fault conditions, degrade to 1oo1D on the
detection of the first fault in either module and fail-safe when there are faults on both
modules.

Document: 553631 3-5


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Increasing I/O Capacity


The capacity of this controller is increased by adding pairs of I/O modules and
associated dual termination assemblies. The next example shows how to provide 16
inputs and 16 outputs (this could also be 32 inputs if 16 channel input modules are
used). The outputs shown are digital output modules.

Note: The T9852 dual termination assembly can be used with both 8 channel and 16
channel input modules.

3-6 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Triple Modular Redundant Architecture
A SIL3 TMR architecture offers the highest level of fault tolerance for an AADvance
controller and consists of triple input modules, triple processors and dual output
modules.
 The input and processor modules operate in a 2oo3D under no fault conditions,
degrade to 1oo2D on detection of the first fault in any module, and degrade to
1oo1D on the detection of faults in any two modules and will fail-safe when there
are faults on all three modules.
 For de-energized to action operation the output modules operate in 2oo2D under
non faulted conditions and degrade to 1oo1D on detection of the first fault in
either module and fail-safe when there are faults on both modules.
 For energize to action operation the output modules operate a 1oo2D under no
fault conditions and degrade to 1oo1D on the detection of the first fault in either
module and fail-safe when there are faults on both modules.
In the event of a failure in any element of a channel, the channel processor will still
produce a valid output which could be voted on because of the coupling between the
channels. This is why the triple modular redundant implementation provides a
configuration that is inherently better than a typical 2oo3 voting system.

IMPORTANT: All configurations that use dual or triplicate processor modules are
suitable for SIL3 architectures with de-energize to action outputs. Dual output
modules are required for SIL3 energize to action outputs.

Document: 553631 3-7


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

You can add further groups of three input modules and pairs of output modules to
provide additional I/O capacity. For example, a triple modular redundant controller
using 8-channel modules for 16 inputs and 16 outputs could be arranged like this. For
16 channel TMR input you should use the T9402 16 channel digital input modules in
the same arrangement.

Using an Expansion Cable


In the example a T9310 expansion cable assembly is used to connect the right-hand
I/O base unit to a further I/O base unit and modules.

3-8 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 4
Mixed Architectures
It is straightforward to implement single, dual and triple I/O architectures for a
controller. This can provide a mixed level of redundancy, fault tolerance and safety
integrity level an application needs, without over-specifying some of the I/O or the
need to provide a second controller.

In This Chapter
Example Controllers .......................................................................................... 4-1
Mixed I/O Architectures ................................................................................... 4-3
Mixed Safety Integrity Levels ........................................................................... 4-4
Distributed Architectures................................................................................. 4-5
Typical Network Applications ......................................................................... 4-6

Example Controllers
The following example shows a process protected by one distributed AADvance
system. It uses an 8000 Series Trusted controller to handle bulk I/O, and four
AADvance controllers for other parts of the plant.
Controllers 1 and 2 represent two similar controllers applied to identical, duplicated
areas of plant. The duplication of plant (represented by the two compressors K1 and
K2) in this system allows controllers 1 and 2 to be fail safe designs.
The parts of the plant managed by Controllers 3 and 5 are assumed (for the sake of
this illustration) to need safety instrumented systems certified to a mixture of SIL2 and
SIL3. Controller 3 exploits the flexibility of the AADvance system to provide mixed
SILs within one controller.
Controller 4 manages the fire and gas system throughout the plant. The example uses
an 8000 Series Trusted controller here in a role which uses a large quantity of field
devices. The 8000 Series Trusted controller is completely integrated into the system
and shares the applications with the AADvance controllers.

Document: 553631 4-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

4-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Mixed I/O Architectures
An application might readily justify a dual processor and dual I/O for some field
circuits, but not for all. It is easy and economical to configure one controller to
provide a solution. Consider a dual processor system that needs 16 inputs and 16
outputs, half of which must be duplicated and half of which can be simplex. The
requirement would be fulfilled by a controller architecture like this.

Document: 553631 4-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Mixed Safety Integrity Levels


Such is the flexibility of AADvance that a single controller can support mixed safety
integrity levels; for example, if a system needs SIL3 energize to trip outputs alongside
SIL2 outputs.
The following example shows how a small a viable controller for mixed integrity levels
can be when built from AADvance modules. There are 16 inputs (or 32), two
duplicated 8 channel inputs (or duplicated 16 channel versions), and two groups of 8
outputs (one dual, one simplex) for field devices.

4-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Distributed Architectures
AADvance is designed to support a distributed safety architecture. Using an SNCP
network a SIL 3 architecture can be maintained across multiple controllers by sharing
safety data over an Ethernet network shown in the example below:

Document: 553631 4-5


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Typical Network Applications


A typical distributed AADvance system uses two networks:
 An information network, which provides connectivity to the BPCS (basic process
control system) and to OPC devices
 A dedicated safety network, which handles data shared between the AADvance
controllers

The engineering workstation may connect to the safety network (as illustrated), to the
information network or to both networks.
As drawn, the OPC portal server collects data from the controllers and displays it on
the HMIs and, conversely, delivers commands from the HMIs to the controllers. The
information network carries real time data (Modbus TCP) from the BPCS to the
controllers.

Specifying a Safety Network


Once a system uses distributed controllers with shared data, the topology of the safety
network must provide some robustness. To do this, make sure the network has no
single point of failure, and refer to the AAdvance Safety Manual (Document: 553630).

4-6 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Controller Network Connectors
The controller features six autosensing 10/100BASE-TX Ethernet ports which allow it
to connect to a local area network through standard RJ45 Ethernet cable. There are
two ports for each processor module.
The controller Ethernet ports are located on the T9110 processor base unit and
identified like this:

Table 16: Allocation of 10/100BASE-TX Ports to Processor Modules

10/100BASE-TX Ports T9110 Processor Module


E1–1, E1–2 Processor A
E2–1, E2–2 Processor B (if fitted)
E3–1, E3–2 Processor C (if fitted)

Document: 553631 4-7


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

This page intentionally left blank

4-8 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 5
AADvance Scalability
The AADvance design concept provides an expandable solution for every application
through its current range of I/O modules and termination assemblies. Increased I/O
capacity is possible because of the ease and simplicity for adding new modules and the
flexibility for creating different architectures.
This chapter describes how you can expand the I/O capacity of a controller.

In This Chapter
I/O Channel Capacity ........................................................................................ 5-1
Adding I/O Channel Capacity .......................................................................... 5-5
Bus Connectors and Expansion Cable........................................................... 5-5
Redundancy and Fault Tolerance .................................................................... 5-6
Expansion using Distributed Controllers ...................................................... 5-6

I/O Channel Capacity


The maximum I/O channel capacity of a controller depends on whether you arrange
I/O modules in simplex, dual or triple modular redundant configurations. The total
capacity of an AADvance system remains unlimited, because there are no restrictions
on the number of distributed controllers you can integrate through a network.
By adding new termination assemblies and I/O modules that simply plug together you
can increase the I/O capacity of a controller. You can also use 16 channel modules on
any existing termination assembly and thus increase the I/O channel capacity per
module from 8 channels to 16 channels. The T9310 expansion cable allows you to use
IO Bus 2 and increase the controller capacity by 24 I/O modules giving a total of 48
I/O modules per controller.
An AADvance system offers horizontal scalability with no technical constraints on the
number of distributed controllers within a single system. The system supports and
integrates fully with existing Modbus subsystems and, through its own server, provides
interoperability with HMIs and other OPC devices.

Document: 553631 5-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Simplex I/O Channel Capacity


When you need I/O modules arranged in only simplex configurations you should use
the simplex termination assembly for each module type. You can use any physical
arrangement of 8-channel and 16-channel input modules with their simplex termination
assemblies, also any arrangement of output modules with simplex termination
assemblies. For example, you might place all digital inputs together in a rack and all
analogue inputs together, or mix them together.
The maximum number of simplex I/O channels is limited only by the choice of
modules. For example, 16 x 16 Channel input modules and 32 x 8 Channel output
modules, equals a maximum of 512 channels

5-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Dual I/O Channel Capacity
When you need I/O modules arranged in dual redundant formations, each pair of
modules shares a dual termination assembly and occupies two-thirds of an I/O base
unit. The termination assemblies can bridge adjacent I/O base units, so two base units
will hold three pairs of dual redundant module configurations, while three base units
will hold four pairs. Arrange base units in groups of two or four to optimize capacity
for dual redundant modules.
If you arrange base units in groups of two or four, a single controller supports 24 pairs
of I/O modules. The capacity using for example eight pairs of 16-channel input modules
and sixteen pairs of output modules is 256 I/O channels (8 x 16 = 128, 16 x 8 = 128).
The capacity using 8-channel modules throughout in dual configurations (24 pairs) is 24
× 8 = 192 I/O channels. This might, for example, represent 64 digital inputs, 64
analogue inputs and 64 digital outputs, or any combination of these values with a
granularity of eight, the capacity of one I/O module.

Document: 553631 5-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Triple Modular Redundant Channel Capacity


When you need input modules arranged in triple modular redundant formations, each
group of three modules will share a single triple termination assembly and occupies a
whole I/O base unit. A single controller supports 16 groups of three modules, so a
hypothetical controller using 16-channel input modules and needing no output channels
would have a capacity of 16 x 16 = 256 input channels.
A solution using 8-channel modules and needing dual output modules as well as
triplicated input modules would, with a ratio of 2:1 of inputs to outputs, provide 96
input channels and 48 output channels. These capacities are derived like this:

Input Channels
 12 groups of three 8-channel input modules occupy 12 base units and yield 12 x 8
= 96 input channels.

Output Channels
 6 pairs of output modules occupy the remaining 4 base units and yield 6 x 8 = 48
output channels.

5-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Adding I/O Channel Capacity
You can specify a new controller to have the precise quantity of I/O channels that you
need and also configure spare I/O channels that you anticipate you may need in the
future. Having done this, it is possible add the hardware to expand the controller.
(Refer to the Technical Feature “System Modification and Expansion”)

Bus Connectors and Expansion Cable


The T9100 processor base unit command and response busses and system power for
I/O modules are output by the two connectors on each side of the base unit:
 The right-hand connector (designated IO bus 1 in the project tree configuration)
mates with a connector on the T9300 I/O base unit. IO bus 1 supports up to
eight I/O base units and up to 24 I/O modules.
 The left-hand connector (designated IO bus 2 in the project tree configuration),
mates with the T9310-02 Backplane Expansion Cable, which will connect it to a
further T9300 I/O base unit. IO Bus 2 supports up to 8 I/O base units and has
response lines for up to 24 I/O modules.
The expansion cable carries module power, command busses and individual response
busses for each I/O module.

Document: 553631 5-5


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Redundancy and Fault Tolerance


A significant advantage of the AADvance design is the option to add redundant
modules to increase fault tolerance as an when they are required. Redundant
configurations allow you to replace faulty modules without affecting the system
operation.
This flexibility and operational persistence is made possible by Termination Assemblies
that provide redundant I/O module capacity. By installing a triple termination assembly
you can configure the I/O and use it in a simplex, dual or triple redundant
arrangement.
The AADvance controller therefore provides an economical solution for redundancy
and fault tolerance expansion. You can install the termination assemblies and base units
for additional future capacity, then add the extra I/O modules only when you actually
need them.

Expansion using Distributed Controllers


You can expand any AADvance system by adding extra controllers. The internal
protocols used by the controller do not place limits on the number of controllers you
can have in a system. The AADvance Discover (Discovery and Configuration utility)
enables you to connect to external controllers.

5-6 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 6
Specifying a New Controller
This chapter provides a list of key information needed to specify a new AADvance
controller. The flowcharts and tables that follow will guide you through the process of
defining a suitable system for your application and requirements.

In This Chapter
Information to Specify a New Controller..................................................... 6-1
Define a New System ........................................................................................ 6-2
Choosing Termination Assemblies ................................................................. 6-5
Specify I/O Base Units ....................................................................................... 6-5
Estimate AADvance Controller Weight ....................................................... 6-6
Estimate Module Supply Power Dissipation and Field Loop Power
Dissipation ............................................................................................................ 6-7

Information to Specify a New Controller


The following sets of information are needed to specify a new controller:
 The intended safety integrity level (SIL2 or SIL3) for your application
 The degree of fault tolerance needed
 Whether any final elements are energize to action (affects output module
arrangements for SIL3 requirements)
 The type and quantity of inputs and outputs
 The process safety time for each safety function
All of these items should be assessed and known for the particular plant and the
intended application.

Document: 553631 6-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Define a New System


The charts use minimal designs to illustrate particular solutions.

6-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Document: 553631 6-3
(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

6-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Choosing Termination Assemblies
The use of termination assemblies gives the AADvance system exceptional flexibility
for creating different architectures and expanding the system. Each termination
assembly is a very simple circuit that is matched to a type of I/O module and to a
particular module configuration. This table shows a summary of the termination
assemblies which are available and the associated I/O module configurations.

Table 17: Choosing a Termination Assembly

Simplex I/O Module Dual I/O Module Triple I/O Module


Configuration Configuration Configuration
Digital input T9801, Digital Input T9802, Digital Input T9803, Digital Input
TA, 16 channel, TA, 16 channel, TA, 16 channel, Triple
Simplex Commoned Dual
(non-isolated)
Analogue input T9831, Analogue Input T9832, Analogue T9833, Analogue Input
TA, 16 channel, Input TA, 16 TA, 16 channel, Triple
Simplex, commoned channel, Dual
(non-isolated)
Digital output T9851, Digital Output T9852, Digital Not applicable
TA, 8 channel, Simplex, Output TA, 8
commoned channel, Dual
(non-isolated) (non-isolated)
Analogue Output T9881, Analogue T9882, Analogue Not applicable
Output TA, 8 Channel, Output TA, 8
Simplex, commoned channel, Dual

IMPORTANT: The termination assemblies for inputs accommodate 8-channel I/O


modules and 16-channel I/O modules. A dual or triple arrangement can be made of 8-
or 16-channel modules, but not a mixture of the two.

You need one termination assembly for each group of associated modules. For
example:
 Four T9401 digital input modules used in two, dual redundant configurations need
two T9802 termination assemblies — one for each pair of modules
 Four T9401 digital input modules used for simplex inputs need four T9801
termination assemblies — one for each module

Specify I/O Base Units


The T9300 I/O base unit (3 way) is a single, standardized design which suits all
termination assemblies and I/O modules. The base unit can accommodate one triple
modular redundant assembly, one dual assembly and one simplex assembly or up to
three to simplex assemblies. The dual and triple modular redundant assemblies can
bridge adjacent base units, so two base units can (for example) hold three dual
assemblies.

Document: 553631 6-5


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Estimate AADvance Controller Weight


Use the following table to estimate the weight of your system.

Table 18: AADvance Controller Module Weight

Item Number Weight Allowance Subtotal


Used g (oz.)
T9100 Processor Base Unit × 460g (16 oz.)
T9110 Processor Module × 430g (15oz)
T9401 Digital input module, 24V dc, 8 channel × 280g (10oz)
T9402 Digital input module, 24V dc, 16 channel × 340g (12oz)
T9431 Analogue input module, 8 channel × 280g (10oz)
T9432 Analogue input module, 16 channel × 340g (12oz)
T9451 Digital output module, 24V dc, 8 channel × 340g (12oz)
T9482 Analogue output module, 8 channel × 290g (10.5oz)
T9300 I/O base unit (3 way) × 133g (5 oz.)
T98x1 Simplex Termination assembly × 133g (5 oz.)
T98x2 Dual Termination Assembly × 260g (10oz)
T98x3 Triple Termination Assembly × 360g (13oz)
T9310 Expansion cable assembly and 2m cable × 670g (24 oz.)
T9841 Termination Assemblies (average weight) × 175g (6 oz.)

Total estimated controller weight

6-6 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Estimate Module Supply Power Dissipation and Field Loop Power Dissipation
Module supply voltage and field power consumption is dissipated as heat. Use these
tables to estimate the supply voltage and field power heat dissipation of your system.

Note: All figures given are worst-case estimates based upon maximum operating field
current and voltages.

Table 19: Estimating Module Supply Power Dissipation

Item Number Power Dissipation Subtotal


of (W/BTU/hr)
Modules
T9110 Processor Module × 8.0W (27.3BTU/hr) =
T9401 Digital Input Module 24V dc, 8 channel × 3.3W (11.3BTU/hr) =
T9402 Digital Input Module 24V dc, 16 channel × 4.0W (13.6BTU/hr) =
T9431 Analogue Input Module, 8 channel × 3.3W (11.3BTU/hr) =
T9432 Analogue Input Module, 16 channel × 4.0W (13.6BTU/hr) =
T9451 Digital Output Module, 24V dc, 8 channel × 3.0W (10.2BTU/h) =
T9482 Analogue Output Module, 8 channel, isolated × 3.6W (12.3BTU/hr) =

Total:

Table 20: Estimating Field Loop Power Dissipation

Item Number Maximum Field Subtotal


of Field Loop Power (W/BTU/hr)
loops Dissipation
T9801/2/3 Digital Input Termination Assembly (powered by × 0.2W (0.68BTU/hr) =
the T9401/2 module)
T9831/2/3 Analogue Input Termination Assembly (powered × 0.08W =
by the T9431/2 module) (0.27BTU/hr)
T9451 Digital Output Module, 24V dc, 8 channel (1A load) x 0.57W (1.94 =
BTU/hr)
T9482 Analogue Output Module, 8 channel, isolated × 0.77W =
(2.63BTU/hr)

Total:

Document: 553631 6-7


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

This page intentionally left blank

6-8 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 7
Module Overview and Specifications
This chapter provides a brief technical overview and technical specification of each
module and its associated termination assembly. Each module has a set of front panel
LEDs to provide status and failure indications. Also, variables included with the
application software can be set up to also monitor and report on the system and
module status.

In This Chapter
T9110 Processor Module ................................................................................. 7-2
T9100 Processor Base Unit ............................................................................. 7-5
T9300 I/O Base Unit (3 way) ........................................................................... 7-8
T9310 Expansion Cable Assembly ................................................................ 7-10
T9401/2 Digital Input Module, 24V dc, 8/16 channel ............................... 7-12
T9801/2/3 Termination Assemblies for Digital Inputs ............................. 7-14
T9431/2 Analogue Input Module, 8/16 Channel ....................................... 7-16
T9831/2/3 Termination Assemblies for Analogue Inputs ....................... 7-18
T9451 Digital Output Module, 24V dc, 8 channel .................................... 7-20
T9851/2 Termination Assemblies for Digital Outputs ............................ 7-22
T9481/2 Analogue Output Module .............................................................. 7-24
T9881/2 Termination Assembly for Analogue Output Module ............ 7-26

Document: 553631 7-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9110 Processor Module

The T9110 processor module is the central processing unit of an


AADvance controller. The processor module carries out the
following critical process and safety controller tasks:
 Execution of the AADvance Safety Kernel to solve
application logic
 Interfacing with the controller I/O modules, reading and
processing input data and writing output data
 Communication with other processor modules, both locally
and across the control network
 Initiation of periodic diagnostics for the controller
 Communication with other systems such as HMIs
 Message encapsulation and verification for secure channel
communication to other nodes
The processor module is galvanically isolated from external
power supplies and data links so that any faults developed in the
field cannot cause the module to fail. The module will continue
to operate in the event of failure of one of its dual redundant
24V dc power supplies. The module incorporates under- and
over-voltage protection for its internal power supplies, which
provide a 'power valid' signal to the modules own diagnostics
microprocessor.
A processor module has two functionally independent,
electrically isolated Ethernet ports. Each port is separately
configurable for multiple protocols such as Modbus RTU, Open
Modbus/TCP and proprietary AADvance protocols, and its data
is available to every processor in the controller.
In addition to the front panel LEDs a Fault Reset button is
provided for the user to reset any fault indications on an I/O
module before the controller is restarted.
Two serial communications ports per processor are provided for Modbus RTU slave
communications. These ports are also functionally and electrically isolated from each
other. They support RS-485 (4– and 2–wire) communications and can be configured to
support asynchronous data rates from 1,200 to 115,200 baud.
The processor periodically initiates internal diagnostic tests which, together with a
watchdog circuit, monitor the processor internal performance. If the tests detect a
serious fault, the processor module will shut down. A controller can use one, two or
three processor modules. Using two or three processor modules provides a fault
tolerant processor architecture.

7-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
If a controller uses two or three processor modules, and one processor module
develops a fault, plant maintenance personnel can fit a new processor module while the
controller is on-line. The new processor module automatically carries out self-
education and synchronizes with the other processors. Fault detection and fail-over in
redundant processor configurations is automatic and has no impact on controller
operation.

Document: 553631 7-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Processor Module Specification

Table 21: Processor Module Specification

Attribute Value
Functional Characteristics
Degradation 1oo1D, 1oo2D and 2oo3D
Processor clock 400MHz
Memory
Boot flash 512kB
SRAM 512kB
Bulk flash 64MB
SDRAM 32MB
Sequence of events (for internal variables)
Event resolution 1ms
Time-stamp accuracy Application Scan
Performance Characteristics
Safety Integrity Level (SIL) 1 processor: non-safety applications up to SIL1
and SIL2 safety applications
2 Processors: up to SIL3 safety applications
3 Processors: up to SIL3 fault tolerant and
TMR safety applications.
I/O Modules supported 48
Electrical Characteristics
Module supply voltage:
Voltage Redundant + 24V dc nominal; 18V dc to 32V
dc range
Module supply power dissipation 8W (27.3 BTu/h)
Typical Surface Temperature of an 43°C ± 5°C
Operating Module
Mechanical Specification
Dimensions (height × width × depth) 166mm × 42mm × 118mm
(6-½ in. × 1-5/8 in. × 4-5/8 in.)
Weight 430g (15 oz.)
Casing Plastic, non-flammable

7-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9100 Processor Base Unit
Every AADvance controller has one T9100 processor base unit. A processor base unit
supports one, two or three modules depending on the architecture chosen for the
application.

Document: 553631 7-5


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

The processor base unit provides the electrical connections between the T9110
processor modules, and the rest of the controller modules and has the following
connections:
 Command and response bus connections for up to 48 I/O modules
 Inter-processor links
 Two Ethernet 100 BaseT connectors per processor
 Two serial data connections per processor
 Dual +24v System power
 Ground stud
 Program enable key
The processor base unit holds the IP address of each processor module separately in a
BUSP (U1 shown in above illustration) which is installed during manufacture. This
means that you can remove a defective processor module and install a new one
without needing to set up the IP address of the new module.

7-6 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9100 Base Unit Specification

Table 22: T9100 Processor Base Unit Specification

Attribute Value
Electrical Specification
Supply voltage requirements Redundant + 24V dc nominal; 18V dc to 32V
dc range
Number of processor modules supported 1, 2 or 3
Number of I/O base units supported 16: 8 per I/O bus
E1-1, E1-2; E2-1, E2-2; E3-1, E3-2 Connectors for Ethernet Ports 1 & 2 for
Processor A, B and C
S1-1, S1-2; S2-1,S2-2; S3-1, S3-2 Connectors for Serial Ports 1 & 2 for
Processor A, B and C
PWR-1, PWR-2 Connectors for Redundant +24V dc Power
Supplies
FLT Not used
KEY Connector for the Program Enable Key
Mechanical Specification
Dimensions (height × width × depth) 235mm x 126mm
(9 1/4 in x 5 in)
Weight 460g (16 oz.)

Document: 553631 7-7


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9300 I/O Base Unit (3 way)


The AADvance controller has T9300 I/O base units for the I/O modules. An I/O base
unit supports up to three I/O modules (of any type), and their associated termination
assemblies.
It contains a passive backplane that provides the electrical connections between the
I/O modules and the T9100 processor base unit; i.e. the command and response buses
and the system power.

7-8 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
The bus and power connections from the processor base unit enter the backplane at
the left connector and are routed direct to the module connectors. The backplane
provides a connector at the right for the next I/O backplane. The connection to the
left of the backplane can connect to a processor base unit or another I/O base unit.
Adjacent base units clip together and are held in position by a plastic retaining clip.
Alternatively rows of I/O base units can be connected together using a T9310
expansion cable assembly.

T9300 Base Unit Specification

Table 23: 9300 Base Unit Specification

Attribute Value
Electrical Specification
Supply voltage requirements Redundant + 24V dc nominal; 18V dc to 32V
dc range (from Processor Base unit)
Physical Specification
Number of I/O modules supported 1, 2 or 3
Command busses One
Response busses 24
Buses per system 2
Base units per bus 8
I/O Modules per bus 24 individual modules (not counting grouping)
(e.g. 12 dual or 8 triple module groups)
Mechanical Specification
Dimensions (height × width × depth) 235mm x 126mm
(9 1/4 in x 5 in)
Weight 133g (5 oz.)

Document: 553631 7-9


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9310 Expansion Cable Assembly


The T9310 expansion cable assembly connects a T9300 I/O base unit to another I/O
base unit or to the T9100 processor base unit. The assembly consists of a cable,
terminated by multi-way plugs, and a pair of adaptors.
One end has a cable socket assembly and the other end a cable plug assembly that
connects to the right-hand bus connector of an I/O base unit or to IO Bus2 (the left
hand connector) of a processor base unit. The socket connects to the left-hand bus
connector of an I/O base unit.
The expansion cable offers the following features:
 Two meter cable length
 Secured with retaining screws and screw cap screws
 Connects all command and response signals and system power
 Screened to reduce resonance emissions

7-10 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9310 Extension Cable Specification

Table 24: T9310 Extension Cable Specification

Attribute Value
Electrical Specification
Carries the following Signals: Command Bus
I/O Response Bus x 24
Backplane 0V Return
Redundant System +24V DC_1 & 2 power
supplies
Mechanical Specification
Length 2m (78.74 ins)
Weight
SCS1-3 Cable Assembly 57gm, 2 oz
Cable Plug Assembly 50gm, 2oz
Cable Socket 50gm, 2oz

Document: 553631 7-11


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9401/2 Digital Input Module, 24V dc, 8/16 channel

The T9401/2 digital input module monitors eight (T9401) or


sixteen (T9402) isolated digital input channels and measures
input voltages in the range 0V to 32V dc. Each channel provides
both digital state and voltage data to the processor module for
field device state, line monitoring and field fault detection.
Input modules provide module and individual channel status
indications through the front panel LEDs. These status
indications are also connected to application variables and
viewed at the Workbench. Comprehensive diagnostics at both
system and module levels generate clear fault indications which
help rapid maintenance and repair.
Signal and power isolation circuits separate each input channel
from the rest of the system, protecting the controller from field
faults. An independent watchdog arrangement monitors the
module operation and provides additional fault containment by a
shutdown mechanism should a fault occur.
These modules mate with the T9801/2/3 Digital input
termination assemblies. When digital input modules are installed
in a dual or TMR configuration they provide fault tolerant input
functionality. Hence, plant maintenance personnel can replace
input module without interrupting the input signal flow to the
processor modules.

7-12 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9401/2 Digital Input Module Specification

Table 25: T9401/2 Digital Input Module Specification

Attribute Value
Functional Characteristics
Input Channels T9401: 8
T9402: 16
Performance Characteristics
Safety integrity level IEC 61508 SIL3 *
Safety level degradation 1oo1D, 1oo2D,2oo3D
Safety accuracy limit 1V
Self test interval < 1 hour; system dependent
Sample update interval (no filter) 6ms
Sequence of events
Event resolution 1ms
Time-stamp accuracy 10ms
Electrical Characteristics
Module Supply Voltage:
Voltage Redundant + 24V dc nominal; 18V to 32V dc
range
Module supply power dissipation T9401: 3.3W (11.3 BTU/hr)
T9402: 4.0W (13.6 BTU/hr)
Input data voltage range 0V to 32V dc
Channel load see TA specification
Input voltage measurement accuracy ± 0.5V
Input voltage resolution 5mV 13-bit
Field loop power dissipation (see T9801/2/3 Termination Assembly)
Channel Isolation-maximum withstand ± 1.5KV dc for 1 minute
Mechanical Specification
Dimensions 166mm x 42mm x 118mm
(6½ in. × 1 21/32 in. × 4 21/32 in.)
Weight T9401: 280g (10 oz.)
T9402: 340g (12 oz.)
Casing Plastic, non-flammable

* SIL3 is the maximum achievable for a single channel. Selected CPU, input and output voting
configurations may increase or decrease the actual SIL achieved.

Document: 553631 7-13


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9801/2/3 Termination Assemblies for Digital Inputs


There are three termination assemblies for use with digital input modules that provide
simplex, dual and triple modular redundant configurations.
A T9801 termination assembly is for a simplex application and provides terminations
for 16 non-isolated digital inputs; it has connections for one T9401 or T9402 digital
input module. The T9802 and T9803 termination assemblies support 16 isolated digital
inputs for dual and triple modular redundant arrangements of digital input modules.
Illustrated is the T9802 dual termination assembly:

The termination assembly protects each channel input by a fuse. Fuses can be replaced
without removing a module or the termination assembly.

7-14 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9801/2/3 Digital Input Termination Assembly Specification

Table 26: T9801/2/3 Digital Input TA Specification

Attribute Value
Functional Characteristics
Field Connections 16
Input modules supported
T9801 One T9401/2
T9802 Two T9401/2
T9803 Three T9401/2
Electrical Characteristics
Input channel fuses 50mA, 125V, Type T

Channel load 5.125k: ± 0.2%


Measurement voltage resolution 5mV, 13 bit
Channel isolation
T9801 None
T9802, T9803: ± 1.5kV dc maximum withstanding for 1 minute
Maximum field loop power dissipation 0.2W per field loop (0.68 BTU/hr)
Mechanical Specification
Dimensions (height × width)
T9801 132mm × 42mm (5-¼ in. × 1-21/32 in.)
T9802 132mm × 84mm (5-¼ in. × 3-5/16 in.)
T9803 132mm × 126mm (5-¼ in. × 5 in.)
Weight
T9801 133g (5 oz.)
T9802 260g (10oz)
T9803 360g (13oz)

Document: 553631 7-15


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9431/2 Analogue Input Module, 8/16 Channel

The T9431/2 analogue input module monitors eight (T9431) or


sixteen (T9432) isolated analogue input channels and measures
input current in the range 0mA to 24mA. Each channel provides
digital state and analogue data to the processor for process
monitoring, line monitoring and field fault detection.
The input module provides local module and channel status
indications through its front panel LEDs, the same indications
can be connected to application variables and viewed at the
Workbench. Comprehensive diagnostics at both system and
module levels provide clear indications which help rapid
maintenance and repair.
The module incorporates signal and power isolation circuits,
which separate each input channel from the rest of the system,
protecting the controller from field faults. An independent
watchdog arrangement monitors the module operation and
provides additional fault containment by a shutdown mechanism
should a fault occur.
These modules mate with the T9831/2/3 Analogue Input
termination assemblies. When analogue modules are installed in
a dual or TMR configuration they provide fault tolerant input
functionality. Hence, plant maintenance personnel can replace
input modules without interrupting the input data flow to the
processor modules.

Analogue Input Line Monitoring


Each analogue input module is set up through the AADvance Workbench. Monitoring
levels for each analogue input channel are configurable at the module and the channel
level. The default parameters are
 Fault: 0 to 3.8mA
 Normal: 3.8 to 22.0mA
 Fault: > 22.0mA
Each input has five configurable voltage bands (there are eight distinct switching
thresholds to allow hysteresis), each of which can be adjusted to provide line
monitoring and field device diagnostics.

7-16 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9431/2 Analogue Input Module Specification

Table 27: Analogue Input Module Specification

Attribute Value
Functional Characteristics
Input channels: T9431: 8
T9432: 16
Degradation 1oo1D, 1oo2D and 2oo3D
Performance Characteristics
Safety integrity level IEC 61508 SIL3 *
Safety level degradation 1oo1D, 1oo2D and 2oo3D
Safety accuracy limit 200μA
Self test interval < 1 hour system dependent
Sample update interval (no filter) 6ms
Value of least significant bit 0.98μA
Error at 25°C ± 2ºC
After 1 year at 40°C 0.21% + 10μA
After 2 years at 40°C 0.22% + 10μA
After 5 years at 40ºC 0.23% + 10μA
Temperature drift (0.01% + 0.3μA)°C
Electrical Characteristics
Module supply voltage:
Voltage Redundant +24V dc nominal
Module supply power dissipation T9431: 3.3W (11.3 BTU/hr)
T9432: 4.0W (13.6 BTU/hr)
Input Current
Nominal 4 to 20mA dc
Maximum range 0 to 24mA dc
Input channel load see TA Specification
Resolution 0.98μA, 15-bit
Measurement calibrated accuracy at 25°C ± 0.05mA
Field loop power dissipation see 9831/2/3 TA Specification
Channel isolation - maximum ± 1.5kV dc for 1 minute
withstanding
Mechanical Specification
Dimensions (height × width × depth) 166mm × 42mm × 118mm
(6-½ in. × 1-21/32 in. × 4-21/32 in.)

Document: 553631 7-17


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Weight T9431: 280g (10 oz.)


T9432: 340g (12 oz.)
Casing Plastic, non-flammable

* SIL3 is the maximum achievable for a single channel. Selected CPU, input and output voting
configurations may increase or decrease the actual SIL achieved. Refer to the Safety Manual
for further details.

T9831/2/3 Termination Assemblies for Analogue Inputs


There are three termination assemblies for use with analogue input modules for
simplex, dual and triple modular redundant configurations.
A T9831 termination assembly is for a simplex application and provides terminations
for 16 non-isolated analogue inputs. It supports one T9431 or T9432 analogue input
module. The T9832 and T9833 termination assemblies support 16 isolated analogue
inputs for dual and triple modular redundant arrangements of analogue input modules.
Illustrated is the T9832 termination assembly:

The termination assembly protects each sensor input signal by a 50mA fuse. Fuses can
be replaced without removing an I/O module or termination assembly.

7-18 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9831/2/3 Analogue Input Termination Assembly Specification

Table 28: Analogue Input Termination Assembly

Attribute Value
Functional Characteristics
Field connections 16
Number of input modules supported
T9831 One
T9832 Two
T9833 Three
Electrical Characteristics
Input channel fuses 50mA per channel
Channel load 135: ± 2:
Channel isolation:
T9831 None
T9832/T9833 ± 1.5kV dc Maximum withstanding for 1 minute
Maximum field loop power dissipation 0.08W per field loop (0.27BTU/hr)
Mechanical Specification
Dimensions (height × width)
T9831 132mm × 42mm (5-¼ in. × 1-21/32 in.)
T9832 132mm × 84mm (5-¼ in. × 3-5/16 in.)
T9833 132mm × 126mm (5-¼ in. × 5 in.)
Weight
T9831 133g (5oz)
T9832 260g (10oz)
T9833 360g (13oz)

Document: 553631 7-19


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9451 Digital Output Module, 24V dc, 8 channel

The T9451 digital output module interfaces up to eight final


elements and can switch 1A at 32V dc for each device. It
features voltage and load current monitoring on each channel,
reverse current protection and short and open circuit line
monitoring. It is designed to always be able to switch off an
output when demanded. No single failure within the module can
cause a stuck-on failure. The module supports dual redundant
power feeds for field devices without the need for external
diodes.
The output module isolates the processor module from the
output channel control and data management circuits, thus
protecting the processor module from potential faults in the
output control circuits and field connections.
The output channel protection activates when the channel load
exceeds a safe limit. The reverse voltage protection circuit in
each output channel ensures that externally applied voltages do
not generate current flow into the module outputs.
The module has self-checking functionality. Short circuit and
open circuit line monitoring is provided on all outputs. Internal
diagnostics carry out ongoing functionality checks ensuring that
the output channel command data is correctly transferred to the
output. In addition, the processor module initiates a test
sequence on each output channel, checking for 'stuck-on' and
'stuck-off' conditions on the output switch pairs.
Front panel LEDs provide module, channel and field connection
status indications. These status indications can be connected to
application variables and viewed at the Workbench.

When a controller uses a pair of digital output modules in a dual configuration, the two
fail-safe output switches on each channel are combined in a parallel arrangement so
that they automatically form a fault-tolerant output configuration.

7-20 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9451 Digital Output Module Specification

Table 29: Digital Output Module Specification

Attribute Value
Functional Characteristics
Output channels 8
Performance Characteristics
Safety integrity level IEC 61508 SIL3 *
Safety level degradation 1oo1D, 1oo2D
Self-test interval <30 mins (30s per module)
Electrical Characteristics
Module supply voltage:
Voltage Redundant +24V dc nominal;
18V dc to 32V dc range
Module supply power dissipation 3.0W (10.2BTU/hr)
Output Voltage:
Maximum voltage without damage –1V to +60V dc
Operating field supply voltage 18 - 32V dc
Output current: 1A continuous per channel
Minimum current required for line monitoring 10mA per module (20mA for dual
pair)
Maximum voltage drop 1V dc
Maximum current at de-rated temperature 8A all channels @ 60°C
De-rated current at maximum temperature 6A all channels @ 70°C
Output off resistance (effective leakage) 50K:
Voltage monitoring accuracy ± 0.5V
Current monitoring accuracy ± 10mA
Output overload protection
Surge 2A for up to 50ms
Continuous 1.5A
Maximum field loop power dissipation 0.57W per field loop (1.94BTU/hr)
Mechanical Specification
Dimensions (height × width × depth) 166mm × 42mm × 118mm
(6-½ in. × 1-21/32 in. × 4-21/32 in.)
Weight 340g (12 oz.)
Casing Plastic, non flammable

Document: 553631 7-21


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

* SIL3 is the maximum achievable for a single channel. Selected CPU, input and output voting
configurations may increase or decrease the actual SIL achieved. Refer to the Safety Manual
for further details.

T9851/2 Termination Assemblies for Digital Outputs


There are two termination assemblies for use with digital output modules - for simplex
and dual applications. A T9851 termination assembly (pictured) is for a simplex
application and provides terminations for 8 digital outputs. It supports one T9451
digital output module. A T9852 termination assembly is a dual assembly, again for 8
outputs, which supports two T9451 digital output modules.

The termination assembly routes the output channels for final elements from the
digital output module to terminal blocks for field connections. The terminal blocks also
accept two 24V dc power sources for field power. The termination assembly
incorporates two replaceable 10A fuses, one for each power source. These fuses can
protect the output module against some field faults.

7-22 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9851/2 Digital Output Termination Assembly Specifications

Table 30: Digital Output Termination Assembly Specificcation

Attribute Value
Functional Characteristics
Field connections 8
Modules supported T9851 : One
T9852 : two
Electrical Characteristics
Dual field supply voltage +24Vdc
Field supply fuses 10A for each field supply
Mechanical Specification
Dimensions (height x width)
T9851 132mm × 42mm (5-¼ in. × 1-21/32 in.)
T9852 132mm × 84mm (5-¼ in. × 3-5/16 in.)
Weight
T9851 133g (5oz)
T9852 260g (10oz)

Document: 553631 7-23


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9481/2 Analogue Output Module

The T9481 and 9482 analogue output modules are compact


and versatile modules that provide 4 – 20mA output current
for field devices.
Each channel is a current sink device and in simplex mode a
channel drops the full demanded current. In dual module
operation each channel drops half the output current.
The module features voltage and load current channel
monitoring, reverse current protection and short and open
circuit line monitoring. It is designed to always be able to
switch off an output when demanded.
Internal diagnostics carry out continuous functionality checks.
All module, channel and status information is displayed on front
panel indicators and status data is routed to the AADvance
where it can be viewed and checked.
The module has a user configurable failure mode that can be
set outputs to hold last state, fail safe, or a user defined output
state.
In dual mode both modules communicate with each other by
an inter-module link to maintain fault tolerant operation
Features:
 Supports 3 or 8 field devices
 Secure communication
 Suitable for safety and non-safety applications
 Operates in a single or dual redundant module
configuration
 Current sink device
 Supports transmission and receipt of HART messages

7-24 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9481/2 Analogue Output Module Specification

Table 31: Analogue Output Module Specification

Attribute Value
Functional Characteristics
Output channels T9481: 3
T9482: 8
Performance Characteristics
Safety integrity level awaiting approval
Safety level degradation 1oo1D, 1oo2D
Safety accuracy 200PA
Self-test interval < 1 hour, system dependent
Value of Least significant bit (control) 0.98PA
Value of least significant bit (monitor) 3.9PA
Error at 25°C ± 2°C
After 1 year at 40°C 0.30% + 10PA
Aftter 2 years at 40°C 0.35% + 10PA
After 3 years at 40°C 0.44% + 10PA
Temperature drift (0.01% + 0.1PA) per °C
Electrical Characteristics
Module supply voltage:
Voltage Redundant +24V dc nominal;
18 V dc to 32V dc range
Module supply power dissipation 3.6W (12.3BTU/hr)
Output voltage:
Maximum voltage without damage ± 60V dc
Operating field supply voltage 18 - 32V dc

Output current
Nominal 4 - 20mA
Maximum range 0.1mA - 24mA
Calibrated accuracy at 25°C 10PA
Output current control resolution 0.98μA, 15-bit
Output current control accuracy at 25°C ± 10μA
Output current monitoring resolution 3.9μA, 13-bit
Compliance voltage 3V to 32V dc
Load impedance

Document: 553631 7-25


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Maximum range 0: - 750:limited by compliance


voltage
Typical 250:
Maximum field loop power dissipation 0.77W per field loop (2.63BTU/hr)
Mechanical Specification
Dimensions (height × width × depth) 166mm × 42mm × 118mm
(6-½ in. × 1-21/32 in. × 4-21/32 in.)
Weight 290g (10.5oz.)
Casing Plastic, non flammable

T9881/2 Termination Assembly for Analogue Output Module


There are two Termination Assemblies for use with the analogue output modules, one
for simplex configuration (T9881) and a dual one for the redundant module
configuration (T9882). Each channel has a capacitor in series with the output
termination.

7-26 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9881/2 Analogue Output Termination Assembly Specification

Table 32: Analogue Output Module Termination Assembly Specification

Attribute Value
Functional Characteristics
Field connections 8
Modules supported T9881: One
T9882: Two
Electrical Characteristics
Channel isolation ± 1.5kV dc maximum withstand for 1 minute
Mechanical Specification
Dimensions (height x width)
T9881 132mm × 42mm (5-¼ in. × 1-21/32 in.)
T9882 132mm × 84mm (5-¼ in. × 3-5/16 in.)
Weight
T9881 133g (5oz)
T9882 260g (10oz)

Document: 553631 7-27


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

This page intentionally left blank

7-28 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 8
Application (Resource) Development
The AADvance Workbench environment facilitates the task of automation throughout
the life-cycle of your system, from system design to commissioning and the day to day
operation and maintenance. For application (resource) development the AADvance
Workbench provides powerful and intuitive features and functionality to enhance ease
of use.
This chapter introduces the AADvance Workbench and describes basic software
features.

In This Chapter
Programming Language Support...................................................................... 8-1
Program Management Facilities ....................................................................... 8-1
Support for Variable Types .............................................................................. 8-2
I/O Connection (Addressing of Physical I/O) .............................................. 8-2
Off-line Simulation and Testing ....................................................................... 8-2
Application (Resource) Program Security .................................................... 8-2
Aids to Software Development....................................................................... 8-3
AADvance Workbench Licensing Options .................................................. 8-3
DIN Rails Fitting .................................................................................................. 8-4

Programming Language Support


The AADvance Workbench is IEC 61131-3 compliant, offering all five languages of the
standard:
 Ladder diagram (graphical)
 Function block diagram (graphical)
 Structured text (textual)
 Instruction list (textual)
 Sequential function chart (graphical)

Program Management Facilities


The development environment is designed for collaborative working. A group of
engineers can work together, with shared ownership of a project. Each contributor can
simply 'check out' the part of the application on which they wish to work.
Program management facilities let you define each functional module (program
organization unit) and its operations, and the interactions between modules to form
the complete application. This modular approach can help future reuse of code units.
Engineers can debug their own modules independently from each other.
Programs can be simulated and tested on the computer before downloading to the
controller hardware.

Document: 553631 8-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Support for Variable Types


For each controller, you can declare variables using all types defined in IEC 61131-3,
including boolean, 16-bit integer (signed and unsigned) and 32-bit real. Controller-
specific types include structures to hold multiple variables for each I/O application.
Variables are easily imported from external databases if required.
Variables are defined in a data dictionary. The development environment provides a
hierarchical tree of variables and a grid-like representation of their definitions.

I/O Connection (Addressing of Physical I/O)


To establish the links between the hardware-independent logical variables of the
AADvance application program and the physical I/O channel available on the
controller, the AADvance Workbench provides a powerful I/O connection editor. I/O
channel links are easily defined between the logical programming and the I/O wiring
configuration. The I/O configuration can be tested separately from the application
execution such that each module can be debugged separately.
Any I/O device can be represented either as a single module or a group of redundant
modules. Different data types are accommodated. You can work directly on a pre-
defined I/O configuration, expand and change the configuration, and the workbench
fully supports directly represented I/O variables as described in the IEC 61131-3
standard.

Off-line Simulation and Testing


An engineer can validate a complete application off-line, without the target hardware
platform. The powerful simulator within the development environment can perform
structural and functional tests of each module and of the whole application.

Application (Resource) Program Security


The AADvance controller includes a Program Enable key that protects the
application from unauthorized access and change. The key must be fitted to the KEY
connector on the T9100 processor base unit before you can download and make
changes to an application (resource). The program enable key is supplied with the
processor base unit and is fitted as shown.

8-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Aids to Software Development
The development environment automatically verifies the syntax of the source code
entered in each of its supported languages. It performs checks at each stage of
development, correcting or prompting the user with the correct use of the language.
There is also extensive on-line help, which includes a cross-referenced explanation of
the IEC 61131-3 standard.

AADvance Workbench Licensing Options


You can use the AADvance Workbench for a trial period of 30 days with a
promotional license. To use a fully operational version you must purchase a license key
from Rockwell Automation. License keys come in two forms:
 T9082/3U Single User Hardware License: a hardware license key is a dongle
that is delivered with the software. To activate the license you insert the dongle
into the USB port of your computer. This type of license allows the license to be
moved to other PC's, but only the PC with the USB Dongle installed will allow the
Workbench to be started.
 T9082/3D Single User Software License: a software license key (hard disk
key) is obtained and activated through the AADvance License Manager. This
type of license establishes the license on a specific PC or another PC, but only the
PC with the software key activated will allow the Workbench to be started.
When you purchase a single user license you can choose from the following feature
sets:
 T9082 Multiscan (PRS): Single user, single controller license.
 T9083 Distributed (PRD): Single user, multiple controller license.
Network licenses are also available:
 T9084U Network User License: A network license (USB dongle) allows the
users to license copies of the AADvance Workbench on PCs so long as they have
a continuous network connection to a central license server.

Document: 553631 8-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

DIN Rails Fitting


You can install the AADvance controller onto a pair of parallel DIN rails. The DIN
rails must be TS35 rail, which is 35mm × 7.5mm standard symmetric rail.
Alternatively, you can install the controller onto a flat panel. The fixing dimensions are
given below for both methods.
A typical DIN rail arrangement is shown below:
An application using DIN rails must provide the DIN rail free space to the left to fit an
end stop on the upper DIN rail.

8-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 9
System Build
The AADvance controller is supplied as 'open' type equipment, ready for installation
on a wall or panel or within a cabinet. This chapter provides an overview of some
features of a system build to demonstrate the ease and simplicity of the process; refer
to the AADvance System Build Manual for more detailed information about
constructing a system.

In This Chapter
Free Space Around the Controller ................................................................ 9-1
Base Units, DIN Rail installations and Expansion Cables .......................... 9-3
Assemblies of Base Units .................................................................................. 9-3
Power Supply Requirements ............................................................................ 9-4
Adding Cable Management ............................................................................... 9-4

Free Space Around the Controller


The controller requires a free space at least 140mm deep (from front to back)
between the rear panel of an enclosure and the inside of an enclosure door. If you
wish to mount the controller on DIN rails, increase this allowance by the additional
depth of the DIN rails.
You must allow sufficient free space around the base units. Every application needs
space on at least three sides, as follows:
 Space above, to manipulate and install field wiring
 Space below, to enable modules to fit and to be able to grasp a module during
removal
 Space to the right, to move an I/O base unit during assembly or in the event of
installing a new base unit
If an expansion cable is to connect to the left-most base unit, the controller also needs
space to the left, to fit the expansion cable adapter.
This illustration shows the minimum recommended clearances for a flat panel or DIN
rail mounting.

Document: 553631 9-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

CAUTION HEAT DISSIPATION AND ENCLOSURE POSITION


System and field power consumption by modules and termination assemblies is
dissipated as heat. You should consider this heat dissipation on the design and
positioning of your enclosure; e.g. enclosures exposed to continuous sunlight
will have a higher internal temperature that could affect the operating
temperature of the modules. Modules operating at the extremes of the
temperature band for a continuous period can have a reduced reliability.

9-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Base Units, DIN Rail installations and Expansion Cables
Base units fit together side by side. One I/O base unit can be fitted directly onto the
right hand edge of the processor base unit. The second and subsequent base units
connect directly to the right of this first I/O base unit. If required, termination
assemblies can bridge adjacent I/O base units to save space.
Using Expansion Cables
A further eight I/O base units can be connected through an expansion cable to the left-
hand edge of the processor base unit.

The expansion bus accessed from the right hand edge of the 9100 processor base unit
is designated bus 1, while the bus accessed from the left hand edge is designated bus 2.
The module positions (slots) within the I/O base units are numbered from 01 to 24,
the left most position being slot 01. Any individual module position within the
controller can thus be uniquely identified by the combination of its bus and slot
numbers, for example 1-01.
The expansion cable assemblies are two metres long. The maximum possible length of
an entire bus (the combination of I/O base units and expansion cables) is 8 metres.
This is limited by the electrical characteristics of the interface.

Assemblies of Base Units


When base units are installed adjacent to each other they are physically connected by
mating connectors and retaining clips so the entire unit forms a single mechanical
assembly. Once the base units and termination assemblies have been installed, the
insertion and removal of modules will not disturb other electrical connections.

Document: 553631 9-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

Power Supply Requirements


A controller requires the following power supply sources:
 A dual redundant power supply of + 24V dc with an operating range of 18V dc to
32V dc.

Note: An AADvance controller is designed to accept supply transient and interference


according to IEC 61131 part 2.n

An over current fault in the controller must not result in the whole system losing
power. Consequently, the power sources must be able to deliver the peak current
needed to open any over current protection devices (such as fuses) without
themselves failing.
The power supply protection of the controller is within the modules, the power
distribution arrangement must provide a circuit breaker on the input side of each
power source.

Note: A controller is designed to withstand a reverse polarity connection without


permanent damage.

The power sources should come from a commercially available industrial un-
interruptible power supply (UPS) system. A suitable UPS should have capacity sufficient
to meet the entire system load (including field devices as well as the controller) and a
suitable contingency allowance for any projected future expansion.

Adding Cable Management


The field, power and other system wiring will be connected to terminals along the top
of the base units. It is recommended a length of trunking or similar be located above
each set of base units, for cable management.

9-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Document: 553631 9-5
(ICSTT-RM447J_EN_P) Issue: 09:
Chapter 10
Parts List
Bases
Part No. Part Description
T9100 Processor base unit
T9300 I/O base unit (3 way)

Modules
Part No. Part Description
T9110 Processor module

T9401 Digital input module, 24Vdc, 8 channel, isolated


T9402 Digital input module, 24Vdc, 16 channel, isolated
T9451 Digital output module, 24Vdc, 8 channel, isolated, commoned

T9431 Analogue input module, 8 channel, isolated


T9432 Analogue input module, 16 channel, isolated

T9481 Analogue output module, 3 channel, isolated


T9482 Analogue output module, 8 channel, isolated

Special Application Modules


Part No. Part Description
Frequency Input Module (Product not yet released. Contact Sales for
T9441 more information)

Termination Assemblies
Part No. Part Description
T9801 Digital input TA, 16 channel, simplex, commoned
T9802 Digital input TA, 16 channel, dual
T9803 Digital input TA, 16 channel, TMR

Document: 553631 10-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9831 Analogue input TA, 16 channel, simplex, commoned


T9832 Analogue input TA, 16 channel, dual
T9833 Analogue input TA, 16 channel, TMR

T9851 Digital output TA, 24Vdc, 8 channel, simplex, commoned


T9852 Digital output TA, 24Vdc, 8 channel, dual

T9881 Analogue output TA, 8 channel, simplex commoned


T9882 Analogue output TA, 8 channel, dual

T9844 Frequency Input Module TA, Simplex, Active (not yet released)
T9845 Frequency Input Module TA, Dual, Active (not yet released)
T9846 Frequency Input Module TA, TMR, Active (not yet released)
T9847 Frequency Input Module TA, Simplex, Passive (not yet released)
T9848 Frequency Input Module TA, Dual, Passive (not yet released)
T9849 Frequency Input Module TA, TMR, Passive (not yet released)
Expansion Cable Assembly
Expansion cable assembly, comprising expansion cable and two adaptors
Part No. Part Description
T9310-02 Backplane expansion cable, 2 metre

Blanking Covers
Part No. Part Description
T9191 Blanking cover (tall) for I/O positions with no TA fitted
T9193 Blanking cover (short) for I/O positions with TA or a Processor

Spares & Tools


Part No. Part Description
Replacement input fuse 50mA (pack of 20)* see notes (for T9801/2/3 and
T9901 T9831/2/3)
T9902 Replacement output fuse 10A (pack of 20) * see notes (for T9851/2)

10-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
T9903 Replacement coding pegs (pack of 20)
T9904 Replacement backplane clips (pack of 20)
T9905 Replacement processor 3V lithium cell (pack of 20) *see notes
T9906 Replacement program enable key

T9907 Installation tool kit


T9908 Fuse Extractor Tool

Software
Part No. Part Description
T9082U IEC 61131 Workbench, USB key, single user, single controller
T9082D IEC 61131 Workbench, hard disk key, single user, single controller

Part No. Part Description


T9083U IEC 61131 Workbench, USB key, multiple controllers
T9083D IEC 61131 Workbench, hard disk key, multiple controllers

Part No. Part Description


T9084U IEC 61131 Workbench, 5 user USB key, multiple controllers
T9085 5 additional user licenses, for use with T9084U

Part No. Part Description


T9030 OPC portal server
T9033 AADvance DTM (for use with HART Passthru feature)

Demonstration Unit
Part No. Part Description
T9141 AADvance Demonstration Unit (Including HMI)

Micellaneous Items
Part No. Part Description
T9020 Euro BUSP Kit

Notes:
T9901: No 396/TE5 50mA time lag fuse; UL 248-14, 125 V,T Leadfree; manufactured
by Littlefuse.

Document: 553631 10-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

T9902: SMF Omni-Block, Surface Mount Fuse Block 154 010, with a 10A, 125V Fast
Acting Fuse, Littlefuse.
T9905: Poly-carbonmonofluride Lithium Coin Battery, BR3032, 20mm dia; Nominal
voltage 3V; Nominal capacity (mAh) 190; Continuous standard load (mA) 0.03;
Operating temperature 30°C to 80°C, supplied by Panasonic

10-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Glossary of Terms

Glossary of Terms
A asynchronous
accuracy A data communications term describing a
serial transmission protocol. A start signal is
The degree of conformity of a measure to a
sent before each byte or character and a
standard or a true value. See also
stop signal is sent after each byte or
'resolution'.
character. An example is ASCII over RS-
achievable safe state 232-C. See also 'RS-232-C, RS-422, RS-485'.
A safe state that is achievable. availability
Note: Sometimes, a safe state cannot be
The probability that a system will be able to
achieved. An example is a non-recoverable
carry out its designated function when
fault such as a voting element with a shorted
required for use — normally expressed as a
switch and no means to bypass the effect of
percentage.
the short.
actuator
B
backplane clip
A device which causes an electrical,
mechanical or pneumatic action to occur A sprung, plastic device to hold together
when required within a plant component. two adjacent AADvance base units. Part
Examples are valves and pumps. number 9904. Used in pairs.
AITA base unit
Analogue input termination assembly. One of two designs which form the
supporting parts of an AADvance controller.
alarms and events (AE)
See 'I/O base unit' and 'processor base unit'.
An OPC data type that provides time
bindings
stamped alarm and event notifications.
Bindings describe a "relationship" between
allotted process safety time
variables in different AADvance controllers.
The portion of the total process safety time Once a variable is "bound" to another
allotted to a sub function of that process. variable, a unique and strong relationships is
created between the two variables and the
application software SIL 3 Certified SNCP protocol is used to
Software specific to the user application, ensure that the consuming variable is
typically using logic sequences, limits and updated with the data from the producing
expressions to read inputs, make decisions variable.
and control outputs to suit the
black channel
requirements of the system for functional
safety. A communication path whose layer (i.e.
cabling, connections, media converters,
architecture routers/switches and associated
Organizational structure of a computing firmware/software, etc.) has no requirement
system which describes the functional to maintain the integrity of safety critical
relationship between board level, device data transferred over it. Measures to detect
level and system level components. and compensate for any errors introduced
into the black channel must be implemented
by the safety critical sender and receiver (by
software and/or hardware means) to make
sure the data retains its integrity.

Document: 553631 11-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

blanking cover C
A plastic moulding to hide an unused slot in CIP
an AADvance base unit.
Common Industrial Protocol. A
boolean communications protocol, formally known
as 'CIP over Ethernet/IP', created by
A type of variable that can accept only the
Rockwell Automation for the Logix
values 'true' and 'false'.
controller family, and which is also
BPCS supported by the AADvance controller.
AADvance controllers use the protocol to
Basic process control system. A system
exchange data with Logix controllers. The
which responds to input signals and
data exchange uses a consumer/producer
generates output signals causing a process
model.
and associated equipment to operate in a
desired manner, but which does not clearance
perform any safety instrumented functions
The shortest distance in air between two
with a claimed safety integrity level of 1 or
conductive parts.
higher.
Refer to IEC 61511 or to ANSI/ISA— coding peg
84.00.01—2004 Part 1 (IEC 61511-1 Mod)
A polarization key, fitted to the 9100
for a formal definition.
processor base unit and to each termination
Equivalent to the Process Control System
assembly, which ensures only a module of
(PCS) defined by IEC 61508.
the correct type may be fitted in a particular
breakdown voltage slot. Part number 9903.
The maximum voltage (AC or DC) that can coil
be continuously applied between isolated
In IEC 61131-3, a graphical component of a
circuits without a breakdown occurring.
Ladder Diagram program, which represents
BS EN 54 the assignment of an output variable. In
Modbus language, a discrete output value.
A standard for fire detection and fire alarm
systems. Compiler Verification Tool (CVT)
BS EN 60204 The Compiler Verification Tool (CVT) is an
automatic software utility that validates the
A standard for the electrical equipment of
output of the application compilation
machines, which promotes the safety of
process. This process, in conjunction with
persons and property, consistency of
the validated execution code produced by
control response and ease of maintenance.
the AADvance Workbench, ensures a high
bus degree of confidence that there are no
errors introduced by the Workbench or the
A group of conductors which carry related
compiler during the compilation of the
data. Typically allocated to address, data and
application.
control functions in a microprocessor-based
system. configuration
bus arbitration A grouping of all the application software
and settings for a particular AADvance
A mechanism for deciding which device has
controller. The grouping must have a
control of a bus.
'target', but for an AADvance controller it
can have only one 'resource'.

11-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Glossary of Terms

consumer dictionary
The consuming controller requests the tag The set of internal input and output
from the producing controller. variables and defined words used in a
program.
contact
discrepancy
A graphical component of a Ladder Diagram
program, which represents the status of an A condition that exists if one or more of the
input variable. elements disagree.
continuous mode DITA
See high demand mode. Digital input termination assembly.
controller DOTA
A logic solver; the combination of Digital output termination assembly.
application execution engine and I/O
hardware.
E
controller system element
A set of input conditioning, application
One or more controllers, their power
processing and output conditioning.
sources, communications networks and
workstations. energise to action
coverage A safety instrumented function circuit where
the outputs and devices are de-energized
The percentage of faults that will be
under normal operation. Application of
detected by automated diagnostics. See also
power activates the field device.
'SFF'.
creepage distance EUC
Equipment Under Control. The machinery,
The shortest distance along the surface of
apparatus or plant used for manufacturing,
an insulating material between two
process, transportation, medical or other
conductive parts.
activities.
cross reference
expansion cable assembly
Information calculated by the AADvance
A flexible interconnection carrying bus
Workbench relating to the dictionary of
signals and power supplies between
variables and where those variables are used
AADvance base units, available in a variety
in a project.
of lengths. Used in conjunction with a cable
D socket assembly (at the left hand side of a
base unit) and a cable plug assembly (at the
data access (DA)
right hand side of a base unit).
An OPC data type that provides real-time
data from AADvance controllers to OPC
F
clients. fail operational state
de-energize to action A state in which the fault has been masked.
See 'fault tolerant'.
A safety instrumented function circuit where
the devices are energized under normal fail safe
operation. Removal of power de-activates
The capability to go to a pre-determined
the field devices.
safe state in the event of a specific
malfunction.

Document: 553631 11-3


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

fault reset button function block diagram


The momentary action push switch located An IEC 61131 language that describes a
on the front panel of the 9110 processor function between input variables and output
module. variables. Input and output variables are
connected to blocks by connection lines.
fault tolerance
See 'limited variability language'.
Built-in capability of a system to provide
functional safety
continued correct execution of its assigned
function in the presence of a limited number The ability of a system to carry out the
of hardware and software faults. actions necessary to achieve or to maintain
a safe state for the process and its
fault tolerant
associated equipment.
The capability to accept the effect of a single
arbitrary fault and continue correct
G
operation. group
fault warning receiving station A collection of two or three input modules
(or two output modules), arranged together
A centre from which the necessary
to provide enhanced availability for their
corrective measures can be initiated.
respective input or output channels.
fault warning routing equipment
H
Intermediate equipment which routes a fault
warning signal from the control and hand-held equipment
indicating equipment to a fault warning Equipment which is intended to be held in
receiving station. one hand while being operated with the
field device other hand.

Item of equipment connected to the field


HART
side of the I/O terminals. Such equipment HART (Highway Addressable Remote
includes field wiring, sensors, final control Transducer) is an open protocol for process
elements and those operator interface control instrumentation. It combines digital
devices hard-wired to I/O terminals. signals with analogue signals to provide field
fire alarm device device control and status information. The
HART protocol also provides diagnostic
A component of a fire alarm system, not data. (For more details of HART devices
incorporated in the control and indicating refer to the HART Application Guide,
equipment which is used to give a warning created by the HART Communication
of fire — for example a sounder or visual Foundation, and their detailed HART
indicator. specifications. You can download documents
from www.hartcomm.org.)
fire alarm receiving station
A centre from which the necessary fire
high demand mode
protection or fire fighting measures can be Where the frequency of demands for
initiated at any time. operation made on a safety-related system is
greater than once per year or greater than
fire alarm routing equipment
twice the proof test interval. Applies to
Intermediate equipment which routes an safety-related systems that implement
alarm signal from control and indicating continuous control to maintain functional
equipment to a fire alarm receiving station. safety. Sometimes known as 'continuous
mode'.

11-4 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Glossary of Terms

hot swap instruction list


See live insertion. An IEC 61131 language, similar to the simple
textual language of PLCs. See 'limited
I variability language'.
I/O base unit integer
A backplane assembly which holds up to
A variable type defined by the IEC 61131
three I/O modules and their associated
standard.
termination assembly or assemblies in an
AADvance controller. Part number 9300. IXL
See 'I/O module' and 'termination assembly'.
IXL stands for ISaGRAF eXchange
I/O module Layer.This is the communication protocol
between ISaGRAF based components.
A collation of interfaces for field sensors
(inputs) or final elements (outputs), K
arranged in a self-contained and
key connector
standardized physical form factor.
The receptacle on the AADvance controller
IEC 61000
for the program enable key. A 9-way 'D'
A series of international standards giving type socket, located on the 9100 processor
test and measurement techniques for base unit.
electromagnetic compatibility.
L
IEC 61131
ladder diagram
An international standard defining
An IEC 61131 language composed of
programming languages, electrical
contact symbols representing logical
parameters and environmental conditions
equations and simple actions. The main
for programmable logic controllers. Part 3,
function is to control outputs based on
which is entitled 'Programming Languages',
input conditions. See 'limited variability
defines several limited variability languages.
language'.
IEC 61508
LAN
An international standard for functional
Local area network. A computer network
safety, encompassing electrical, electronic
covering a small physical area, characterised
and programmable electronic systems;
by a limited geographic range and lack of a
hardware and software aspects.
need for leased telecommunication lines.
IEC 61511
live insertion
An international standard for functional
The removal and then reinsertion of an
safety and safety instrumented systems (SIS)
electronic module into a system while the
for the process industry, encompassing
system remains powered. The assumption is
electrical, electronic and programmable
that removal of the module and reinsertion
electronic systems, hardware and software
will cause no electrical harm to the system.
aspects.
Also referred to as 'hot swap'.
indicator
low demand mode
A device which can change its state to give
Where the frequency of demands for
information.
operation made on a safety-related system is
input (Workbench variable) no greater than one per year and no greater
than twice the proof-test frequency.
In the context of an AADvance Workbench
variable, this term describes a quantity
passed to the Workbench from a controller.

Document: 553631 11-5


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

M OPC
manual call point A series of standards specifications which
support open connectivity in industrial
A component of a fire detection and fire
automation.
alarm system which is used for the manual
initiation of an alarm. output (Workbench variable)
Modbus In the context of an AADvance Workbench
variable, this term describes a quantity
An industry standard communications
passed from the Workbench to a controller.
protocol developed by Modicon. Used to
communicate with external devices such as P
distributed control systems or operator
peer to peer
interfaces.
A Peer to Peer network consists of one or
Modbus object
more Ethernet networks connecting
A representation of the configuration together a series of AADvance and/or
settings for a Modbus master or for its Trusted controllers to enable application
associated slave links, within the AADvance data to be passed between them.
Workbench. The settings include
pinging
communication settings and messages.
In Modbus communications, sending the
module locking screw
diagnostic Query Data command over a link
The AADvance latch mechanism seen on and by receiving a reply ensuring that the
the front panel of each module and link is healthy and the controller is able to
operated by a broad, flat-blade screwdriver. communicate with the master. No process
Uses a cam action to lock to the processor data is transferred or modified. In the case
base unit or I/O base unit. of slave devices that will not support pinging
then the Standby command will default to
N Inactive state, but no error will be returned.
NFPA 85 portable equipment
The Boiler and Combustion Systems
Enclosed equipment that is moved while in
Hazards Code. Applies to certain boilers,
operation or which can easily be moved
stokers, fuel systems, and steam generators.
from one place to another while connected
The purpose of this code is to contribute to
to the supply. Examples are programming
operating safety and to prevent uncontrolled
and debugging tools and test equipment.
fires, explosions and implosions.
process safety time (PST)
NFPA 86
For equipment under control this
A standard for Ovens and Furnaces.
represents the period of time a dangerous
Provides the requirements for the
condition can exist without the protection
prevention of fire and explosion hazards in
of a safety instrumented system before a
associated with heat processing of materials
hazardous event occurs.
in ovens, furnaces and related equipment.
processor base unit
O
A backplane assembly which holds all of the
on-line processor modules in an AADvance
The state of a controller that is executing controller. Part number 9100. See also
the application software. 'processor module'.

11-6 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Glossary of Terms

processor module RS-232-C, RS-422, RS-485


The application execution engine of the Standard interfaces introduced by the
AADvance controller, housed in a self- Electronic Industries Alliance covering the
contained and standardized physical form electrical connection between data
factor. communication equipment. RS-232-C is the
most commonly used interface; RS-422 and
producer
RS-485 allow for higher transmission rates
A controller producing a tag to one or more over increased distances.
consumers, at the request of the consumers.
RTC
program enable key
Real-time clock.
A security device that protects the
RTU
application from unauthorized access and
change, in the form factor of a 9-way 'D' Remote terminal unit. The Modbus protocol
type plug. Part number 9906. Supplied with supported by the AADvance controller for
the processor base unit. See also 'key Modbus communications over serial links,
connector'. with the ability to multi-drop to multiple
slave devices.
project
A collection of configurations and the
S
definition of the linking between them. See safe state
'configuration'.
A state which enables the execution of a
protocol process demand. Usually entered after the
detection of a fault condition; it makes sure
A set of rules that is used by devices (such
the effect of the fault is to enable rather
as AADvance controllers, serial devices and
than disable a process demand.
engineering workstations) to communicate
with each other. The rules encompass safety accuracy
electrical parameters, data representation,
The accuracy of an analogue signal within
signalling, authentication, and error
which the signal is guaranteed to be free of
detection. Examples include Modbus, TCP
dangerous faults. If the signal drifts outside
and IP.
of this range, it is declared faulty.
PST
safety-critical state
Process Safety Time
A faulted state which prevents the
R execution of a process demand.
real sensor
A class of analogue variable stored in a A device or combination of devices that
floating, single-precision 32-bit format. measure a process condition. Examples are
transmitters, transducers, process switches
redundancy
and position switches.
The use of two or more devices, each
sequential function chart
carrying out the same function, to improve
reliability or availability. An IEC 61131 language that divides the
process cycle into a number of well-defined
resolution
steps separated by transitions. See 'limited
The smallest interval measurable by an variability language'.
instrument; the level of detail which may be
represented. For example, 12 bits can
distinguish between 4096 values.

Document: 553631 11-7


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

SFF synchronous
Safe Failure Fraction. Given by (the sum of A data communications term describing a
the rate of safe failures plus the rate of serial transmission protocol. A pre-arranged
detected dangerous failures) divided by (the number of bits are expected to be sent
sum of the rate of safe failures plus the rate across a line per second. To synchronise the
of detected and undetected dangerous sending and receiving machines, a clocking
failures). signal is sent by the transmitting computer.
There are no start or stop bits.
SIF
Safety Instrumented Function. A form of
T
process control that performs specified TA
functions to achieve or maintain a safe state
See 'termination assembly'.
of a process when unacceptable or
dangerous process conditions are detected. target
SIL An attribute of a 'configuration' which
describes characteristics of the AADvance
Safety Integrity Level. One of four possible
controller on which the configuration will
discrete levels, defined in IEC 61508 and IEC
run. Includes characteristics such as the
61511, for specifying the safety integrity
memory model and the sizes of variable
requirements of the safety functions to be
types for the controller.
allocated to a safety-related system. SIL4 has
the highest level of safety integrity; SIL1 has TCP
the lowest.
The whole of an installation (of which the Transmission control protocol. One of the
AADvance system forms a part) must meet core protocols of the Internet Protocol
these requirements in order to achieve an suite. It provides reliable, ordered delivery
overall SIL rating. of a stream of bytes from a program on one
computer to another program on another
SNCP computer. Common applications include the
World Wide Web, e-mail and file transfer
SNCP (Safety Network Control Protocol) is
and, for an AADvance controller, Modbus
the Safety Protocol that allows elements of
communications over Ethernet.
an AADvance System to exchange data.
SNCP is a SIL 3 certified protocol which termination assembly
provides a safety layer for the Ethernet
network making it a "Black Channel". A printed circuit board which connects field
wiring to an input or output module. The
SNTP circuit includes fuses for field circuits. The
board carries screw terminals to connect
Simple Network Time Protocol. Used for
field wiring to the controller, and the whole
synchronizing the clocks of computer
assembly clips onto the 9300 I/O base unit.
systems over packet-switched, variable-
latency data networks. TMR
structured text Triple modular redundant. A fault tolerant
arrangement in which three systems carry
A high level IEC 61131-3 language with
out a process and their result is processed
syntax similar to Pascal. Used mainly to
by a voting system to produce a single
implement complex procedures that cannot
output.
be expressed easily with graphical languages.
TÜV certification
Independent third party certification against
a defined range of international standards
including IEC 61508.

11-8 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:
Glossary of Terms

U
U
Rack unit. A unit of measure used to
describe the height of equipment intended
for mounting in a standard rack. Equivalent
to 44.45mm (1-¾ inches).
V
validation
In quality assurance, confirmation that the
product does what the user requires.
verification
In quality assurance, confirmation that the
product conforms to the specifications.
voting system
A redundant system (m out of n) which
requires at least m of the n channels to be in
agreement before the system can take
action.
W
withstand voltage

The maximum voltage level that can be


applied between circuits or components
without causing a breakdown.

Document: 553631 11-9


(ICSTT-RM447J_EN_P) Issue: 09:
Additional Resources
For more information about the AADvance system refer to the associated Rockwell
Automation technical manuals shown in this document map.

Publication Purpose and Scope


553630 Safety Manual This technical manual defines how to safely apply AADvance
controllers for a Safety Instrumented Function. It sets out
standards (which are mandatory) and makes recommendations to
ensure that installations meet their required safety integrity level.
553631 Solutions This technical manual describes the features, performance and
Handbook functionality of the AADvance controller and systems. It sets out
some guidelines on how to specify a system to meet your
application requirements.
553632 System Build This technical manual describes how to assemble a system, switch
Manual on and validate the operation of your system.
553633 Configuration This manual defines how to configure an AADvance controller
Guide using the AADvance Workbench to meet your system and
application requirements.
553634 Troubleshooting This technical manual describes how to maintain, troubleshoot
and Maintenance and repair an AADvance Controller.
Manual
553701 OPC Portal This manual describes how to install, configure and use the OPC
Server User Manual Server for an AADvance Controller.

Document: 553631 12-1


(ICSTT-RM447J_EN_P) Issue: 09:
Solutions Handbook (AADvance Controller)

553847 PFH avg and This document contains the PFHavg and PFDavg Data for the
PFDavg Data AADvance Controller. It includes examples on how to calculate
the final figures for different controller configurations. The data
supports the recommendations in the AADvance Safety Manual
Doc No: 553630.

Regional Offices
Rockwell Automation Oil and Gas Resources are available in Regional Offices worldwide.

Rockwell Automation Rockwell Automation Rockwell Automation


4325 West Sam Houston Hall Road Millenium House
Parkway North, Suite Maldon Campus 1
100 Essex Aberdeen Science & Tech
Houston CM9 4LA Park
Texas 77043-1219 England, UK Balgownie Road, Bridge
USA of Don
Scotland, UK
Tel: +1 713 353 2400 Tel: +44 1621 854444 +44-1224-227-780
Fax: +1 713 353 2401 Fax: +44 1621 851531

Rockwell Automation. Abu Dhabi: Dubai:


No. 2 Corporation Road 903, Bin Hamoodah Building Silvertech Middle East
#04-01 to 03 9th Floor FZCO
Corporation Place Khalifa Street PO Box 17910
Singapore 618494 Abu Dhabi, Jebel Ali Free Zone
UAE Dubai,
UAE
Tel: +65 6622-4888 971-2-627-6763 +9714 883 7070
Fax: +65 6622-4884

Internet: http://www.rockwellautomation.com/icstriplex
Technical support: icstsupport@ra.rockwell.com
Sales enquiries: sales@icstriplex.com

12-2 Document: 553631


(ICSTT-RM447J_EN_P) Issue: 09:

You might also like