Professional Documents
Culture Documents
DUCT SYSTEM Typical plots of the resistance to flow versus the air-
flow rate establish the system curves for three differ-
A AIRFLOW ent and arbitrary fixed systems, (A, B and C), illus-
trated in Figure 5-1. For a fixed system, an increase
An HVAC air distribution system may consist simply or decrease in the system airflow rate volume will
of a fan with ductwork connected to either the inlet or increase or decrease the system resistance along the
discharge or to both. A more complicated system may given system curve only.
include a fan, ductwork, air control dampers, cooling
coils, heating coils, filters, diffusers, sound attenua- Refer to System Curve A on Figure 5-1. Assume a
tion, turning vanes, etc. The fan is the component or system design point at 100 percent volume and 100
"air pump" in the system which provides energy to percent resistance. If the airflow rate volume is in-
the airstream to overcome the resistance to flow of creased to 120 percent of design volume, the system
the other components. The discussion in this Section resistance will increase to 144 percent of the design
A and the accompanying tables and figures on fan resistance in accordance with the system equation.
and system curves were developed by the Air Moving A further increase in volume results in a correspond-
and Conditioning Association, Inc. and reprinted with ing increase in system pressure. A decrease in vol-
some minor editing with their permission. (AMCA ume flow to 50 percent of design airflow volume would
Publication 201--"Fans and Systems"). result in a decrease to 25 percent of the design re-
sistance.
Notice that on a percentage basis, the same relation-
1. Component Losses ships also hold for the System Curves B and C.
Each duct system has a combined set of pressure These relationships are characteristic of typical fixed
resistances to flow which are usually different from HVAC systems.
every other system and are dependent upon individ-
ual duct system components. 3. System Curve/Fan Curve
The amount of the total pressure drop or resistance Interaction
to flow for the individual duct system components can If the system curve, composed of the resistance to
be obtained from the component manufacturer. For flow of the system and the appropriate "System Effect
preliminary computations, some pressure data is Factors," (discussed later in this section) has been
available in Chapter 9. accurately determined, then it is assumed that the
fan selected will develop the necessary pressure to
meet the system requirements at the designed airflow
2. System Curves (cfm or l/s).
At a fixed volume air flow rate through a given air The point of intersection of the system curve and the
distribution system, a corresponding pressure loss or fan performance curve determines the actual airflow
resistance to this flow will exist. If the flow rate is volume. If the system resistance has been accurately
changed, the resulting pressure loss or resistance to determined and the fan properly selected, their per-
flow also will change. The relationship governing this formance curves will intersect at the design airflow.
change is given by the following system equation: (See Figure 5-2). The normalized System Curve A
Equation 5-1 from Figure 5-1 has been plotted with a normalized
fan performance curve. The 100 percent design air-
flow volume of the system curve was arbitrarily se-
lected to intersect at 60 percent of the free delivery
airflow volume of the fan.
The airflow rate volume through the system in a given
installation may vary from changes in the system re-
5.1
DUCT DESIGN FUNDAMENTALS
5.2
CHAPTER 5
sistance, usually from fan dampers, duct dampers, 3. Again note that the interaction of the installed duct
mixing boxes, terminal units, etc. Referring to Figure system curve and the fan curve from actual operating
5-2, the airflow volume rate may vary from 100 per- conditions determine the duct system airflow volume
cent design airflow (Point 1, Curve A), to approxi- rate.
mately 80 percent of the design airflow by increasing
the resistance to flow, thus changing the system 4. Fan Speed Change Effects
curve characteristic to Curve B. This results in fan
operation at Point 2 (the intersection of the fan curve A change in fan speed will alter the airflow volume
and the new System Curve B). Similarly, the airflow rate through a given system as shown by Equation
rate can be increased to approximately 120 percent 5-2:
of the design airflow volume by decreasing the resis- Equation 5-2
tance to flow, thus changing the system curve char-
acteristic to Curve C. This results in fan operation at
Point 3 (the intersection of the fan curve and the new
System Curve C). Where:
To review; when system losses have been estimated Airflow rate = cfm (l/s)
accurately, when the duct systems have been fabri- Fan Speed = rpm (rad/s)
cated and installed exactly as shown on the drawings Figure 5-4 illustrates the increase in system airflow
with specified components, then the design airflow when the fan speed is increased 10 percent. Any
volume can be expected as illustrated in Figure 5-3 change in fan speed creates a new fan curve. The
at Point 1. system operating point then moves along the system
However, when the duct systems have not been es- curve from Point 1 to Point 2. The 10 percent in-
timated accurately or installed as shown, a higher crease in airflow extracts a severe fan power
pressure loss causes the fan to operate at Point 2 of penalty. According to the fan laws, the fan power
Figure 5-3, and a lower system pressure loss at Point output must then increase 33 percent.
5.3
DUCT DESIGN FUNDAMENTALS
Where:
Fan Power = HP (kW or W) Frequently, the extra horsepower (Watts) is not avail-
Fan Speed = rpm (rad/s) able from the existing fan motor, and the motor power
wiring is too small to add a larger motor.
Example 5-1 (U.S.) This fact is often startling to the system designer who
A 10 HP fan runs at 500 rpm. finds the system short of air. Only 10 percent more air
is needed, but the selected motor horsepower is not
Calculate the HP at 550 rpm. capable of a 33 percent increase in load. The in-
creased power requirements are the result of in-
Solution creased work done. The greater volume flow rate of
Using Equation 5-3: air moved by the fan against the resulting higher sys-
tem resistance to the flow, causes increased work to
be done. In the same system, the fan power in-
creases as the cube of the speed ratio, and fan effi-
ciency remains the same at all points on the same
system curve. (See HVAC Fan Equations in Chapter
Example 5-1 (Metric) 14.)
A 75 kW fan runs at 50 rad/s.
Increasing the fan speed also may create problems
Calculate the fan power at 55 rad/s. for the fan by putting it and possibly the ductwork into
5.4
CHAPTER 5
a higher pressure classification. Be sure to review when selecting fans from manufacturers' catalogs or
the fan rating table for pressure class limits or contact curves (fan airflow volume is constant).
the fan manufacturer to determine if the fan speed Equation 5-4
may be increased safely.
5.5
DUCT DESIGN FUNDAMENTALS
tors" may compensate for resistance losses that how it works, it will be necessary to add a "System
were overlooked and the actual system will deliver Effect Factor" to the calculated system pressure
design flow (Point 1, Figure 5-3). Occasionally, how- losses to determine the actual system curve. The
ever, the estimated system resistance, including the System Effect Factor for any given configuration is
"Safety Factors," is in excess of the actual installed dependent on the airflow velocity at that point.
system conditions. Since the fan has been selected In the example illustrated on Figure 5-6, the point of
for design conditions (Point 1), it will deliver more air intersection between the fan performance curve and
(Point 3) because the actual system resistance at the the actual system curve is Point 4. The actual airflow
design flow rate is less than design (Point 4). volume will, therefore, be deficient by the difference
This result may not necessarily be an advantage be- from 1 to 4. To achieve the design airflow volume, a
cause the fan will usually be operating at a less effi- System Effect Factor equal to the pressure difference
cient point on the performance curve and may require between Points 1 and 2 should have been added to
more horsepower than at design flow. Under these the calculated system pressure losses and the fan
conditions, it may be necessary to reduce the fan selected to operate at Point 2. Note, that because
speed or to adjust a damper to increase the actual the System Effect is velocity related, the difference
system resistance (Curve C) to the original design represented between Points 1 and 2 is greater than
characteristic (Curve A). the difference between Points 3 and 4.
Chapter 6--"Fan-Duct Connection Pressure
Losses" contains the necessary data, charts and ta-
bles needed to determine the System Effect Factors
OTHER FACTORS required by duct connections to HVAC system fans.
AFFECTING DUCT SYSTEM The System Effect Factor is given in inches of water
gauge (Pascals) and may be added to the total sys-
PRESSURES tem pressure losses as shown on Figure 5-6. How-
ever, System Effect can not be measured in the field
1. System Effect when the system is being tested and balanced. It can
only be calculated using the data in Chapter 6.
A "derating" of the HVAC system fan, called "System Therefore the HVAC system designer should derate
Effect" must be taken into account by the system the HVAC system supply fan by deducting the Sys-
designer if a realistic estimate of fan/system perfor- tem Effect Factor from the fan rated capacity (in. w.g.
mance is to be made. It must be appreciated that the or Pa).
System Effect Factors given in Chapter 6 of this man-
The velocity figure used in entering the chart will be
ual are intended as guidelines and are, in general,
either the inlet or the outlet velocity of the fan. This
approximations. Some have been obtained from re-
will be dependent on whether the configuration in
search studies, others have been published previ-
question is related to the fan inlet or the outlet. Most
ously by individual fan manufacturers, and many rep-
catalog ratings include outlet velocity figures, but for
resent the consensus of engineers with considerable
centrifugal fans, it may be necessary to calculate the
experience in the application of fans.
inlet velocity. The necessary inlet dimensions usually
Fans of different types and even fans of the same are included in the fan catalog.
type, but supplied by different manufacturers, will not
necessarily react with the system in exactly the same
way. It will be necessary, therefore, to apply judge-
2. Wind Effect
ment based on actual experience in applying the Sys- With few exceptions, building intakes and exhausts
tem Effect Factors. cannot be located or oriented for a prevailing wind to
Figure 5-6 illustrates deficient fan/system perfor- assure HVAC system operation. Wind can assist or
mance resulting from undesirable flow conditions. It hinder supply air and exhaust air fans depending on
is assumed that the system pressure losses have their position on the building, but even in locations
been accurately determined (Point 1, Curve A) and a with a predominant wind direction, the ventilating sys-
suitable fan selected for operation at that point. How- tem must perform adequately for all other directions.
ever, no allowance has been made for the effect of Airflow through a wall opening results from positive
the system connections on the fan's performance. To or negative external and internal pressures. Such dif-
compensate for this "System Effect" and to explain ferential pressures may exceed 0.5 in. w.g. (125 Pa)
5.6
CHAPTER 5
during high winds. Supply and exhaust systems, and Where system stability is essential, the supply air and
openings, dampers, louvers, doors, and windows exhaust air systems must be designed for higher
make the building flow conditions too complex for [pressures about 3 to 4 in. w.g. (750 to 1000 Pa)] to
most calculation. The opening and closing of doors minimize unacceptable variations in flow rate. To con-
and windows by building occupants add further com- serve energy, the system pressure selected should
plications. be consistent with system needs.
Mechanical HVAC systems are affected by wind con- Where building balance and minimum infiltration are
ditions. A low-pressure wall exhaust fan, 0.05 to 0.1 important, consider the following:
in w.g. (12 to 25 Pa) can suffer a drastic reduction in a) Fan system design with pressure adequate to
capacity. Flow can be reversed by wind pressures on minimize wind effects.
windward walls, or its rate can be increased sub-
stantially when subjected to negative pressures on b) Controls to regulate flow rate or pressure or
the lee and other sides, Clarke (1967) when meas- both.
uring HVAC Systems operating at 1 to 1.5 in. [w.g. c) Separate supply and exhaust systems to serve
(250 to 375 Pa), found flow rate changes of 25 per- each building area requiring control or balance.
cent for wind blowing into intakes on an L-shaped d) Doors (possibly self-closing) or double-door air
building compared to the reverse condition. Such locks to non-controlled adjacent areas, partic-
changes in flow rate can cause noise at the supply ularly outside doors.
outlets and drafts in the space served.
e) Sealing windows and other leakage sources
For mechanical systems, the wind can be thought of and closing natural vent openings.
as producing a pressure in series with a system fan,
either assisting or opposing it (Houlihan 1965).
5.7
DUCT DESIGN FUNDAMENTALS
3. Stack Effect
When the outside air is colder than the inside air, an
upward movement of air often occurs within building
shafts, such as stairwells, elevator shafts, dumbwai-
ter shafts, mechanical shafts, or mail chutes. This
phenomenon, referred to as normal stack effect, is
caused by the air in the building being warmer and
less dense than the outside air. "Normal stack effect"
is greater when outside temperatures are low and
when buildings are taller. However, "normal stack ef-
fect" can exist even in a one story building.
When the outside air is warmer than the building air,
a downward airflow frequently exists in shafts. This
downward airflow is called "reverse stack effect." At
standard atmospheric pressure, the pressure differ-
ence due to either normal or reverse stack effect is
Figure 5-7 PRESSURE DIFFERENCE DUE TO
expressed as:
NORMAL STACK EFFECT (2)
Equation 5-5
5.8
CHAPTER 5
If the leakage paths are uniform with height, the neu- changes in a duct system with the total pressure and
tral plane is near the mid-height of the building. How- static pressure grade lines in reference to the atmos-
ever, when the leakage paths are not uniform, the pheric pressure datum line.
location of the neutral plane can vary considerably,
At any cross-section, the total pressure (TP) is the
as in the case of vented shafts. McGuire and Tamura sum of the static pressure (SP) and the velocity pres-
(1975) provide methods for calculating the location of
sure (Vp).
the neutral plane for some vented conditions.
Equation 5-6
TP = SP + Vp
3. Reducers
When duct cross-sectional areas are reduced, such
as at converging sections B (abrupt) and F (gradual),
both the velocity and velocity pressure increase in
the direction of airflow and the absolute value of both
the total pressure and static pressure decreases. The
pressure losses are due to changes in direction or
velocity of the air and occur at transitions, elbows,
and duct obstructions, such as dampers, etc. Dy-
namic losses can be expressed as a loss coefficient
(the constant which produces the dynamic pressure
losses when multiplied by the velocity pressure) or by
Figure 5-9 PRESSURE DIFFERENCE DUE TO the equivalent length of straight duct which has the
STACK EFFECT (2) same loss magnitude.
5.9
DUCT DESIGN FUNDAMENTALS
5.10
CHAPTER 5
5.11
DUCT DESIGN FUNDAMENTALS
as a supply air duct with atmospheric pressure push- by a constant is the same as multiplying or dividing
ing the air to the lower pressure area created by the the equivalent round size by the same constant.
fan suction. Thus, if the circular equivalent of an 80 in. x 26 in.
(2030 mm x 660 mm) duct is required, it will be twice
that of a 40 in. x 13 in. (1015 mm x 330 mm) that has
D STRAIGHT
LOSSES
DUCT
a circular equivalent of 24 inches (610 mm) diameter
or 2 x 24 = 48 inches (1220 mm) diameter.
Rectangular ducts should not be sized directly from
actual duct cross-sectional areas. Instead, Tables
14-2 and 14-3 must be used, or the resulting rectan-
1. Duct Friction Losses gular duct sizes will be smaller creating greater duct
velocities for a given airflow.
Pressure drop in a straight duct section is caused by
surface friction, and varies with the velocity, the duct
size and length, and the interior surface roughness,.
Friction loss is most readily determined from Air Duct
Friction Charts (Figures 14-1 and 14-2) in Chapter 14.
They are based on standard air with a density of
0.075 lb/cu. ft. (1.204 kg/m3) flowing through average
clean round galvanized metal ducts with beaded slip
E DYNAMIC
LOSSES
couplings on 48 inch (1220 mm) centers, equivalent
to an absolute roughness of 0.0003 feet (0.09 mm). Wherever turbulent flow is present, brought about by
The previous duct friction loss charts were based on sudden changes in the direction or magnitude of the
30 inch (760 mm) joints and an absolute roughness velocity of the air flowing, a greater loss in total pres-
of 0.0005 (0.15 mm), and most computer software sure takes place than would occur in a steady flow
programs and duct calculators still contain these through a similar length of straight duct having a uni-
older values. The SMACNA Duct Design Calculators form cross-section. The amount of this loss in excess
(both U.S. and Metric) contain the newer data. of straight-duct friction is termed dynamic loss. Al-
In HVAC work, the values from the friction loss charts though dynamic losses may be assumed to be
and the SMACNA Duct Design Calculators may be caused by changes in area actually occupied by the
used without correction for temperatures between airflow, they are divided into two general classes for
50°F to 140°F (10 Cto 60 C) and up to 2000 feet convenience: (1) those caused by changes in direc-
(600m) altitude. Figure 14-5 and Tables 14-26 and tion of the duct and (2) those caused by changes in
14-32 may be used where air density is a significant crosssectional area of the duct.
factor, such as at higher altitudes or where high tem-
perature air is being handled to correct for tempera- 1. Duct Fitting Loss Coefficients
ture and/or altitude. The actual air volume (cfm or
I/s) is used to find the duct friction loss using Figures The dynamic loss coefficient "C" is dimensionless
14-1 and 14-2. This loss is multiplied by the correction and represents the number of velocity heads lost at
the duct transition or bend (in terms of velocity pres-
factor(s) to obtain the adjusted duct friction loss.
sure). Values of the dynamic loss coefficient for el-
bows and other duct elements have been determined
2. Circular Equivalents by laboratory testing, and can be found in the tables
HVAC duct systems usually are sized first as round in Chapter 14. It should be noted, however, that ab-
ducts. Then, if rectangular ducts are desired, duct solutely reliable dynamic loss coefficients are not
sizes are selected to provide flow rates equivalent to available for all duct elements, and the information
those of the round ducts originally selected. Tables available for pressure losses due to area changes is
14-2 and 14-3 in Chapter 14 give the circular equiva- generally restricted to symmetrical area changes.
lents of rectangular ducts for equal friction and airflow Tables 14-6 and 14-7, which show the relationship of
rates for aspect ratios not greater than 11.7:1. Note velocity to velocity pressure for standard air, can be
that the mean velocity in a rectangular duct will be used to find the dynamic pressure loss for any duct
less than the velocity for its circular equivalent. Mul- element whose dynamic loss coefficient "C" is
tiplying or dividing the length of each side of a duct known.
5.12
CHAPTER 5
Where:
Using Equation 5-10:
V = Velocity (fpm) - -. N
Q = Airflow (cfm)
A = Cross-sectional Area (sq. ft.)
Using Equation 5-8:
Equation 5-9 (Metric) TP = C x Vp = 0.40 x 0.275
TP = 0.11 in. w.g.
(Elbow pressure loss)
Where:
Example 5-2 (Metric)
V = Velocity (m/s)
Q = Airflow (m3/s), 1000 I/s = 1 m3/s An elbow in a 600 mm x 500 mm duct conveying
A = Cross-sectional Area (m2) 3500 I/s has a loss coefficient (C) of 0.40. Find the
elbow pressure loss.
(or)
Solution
Using Equation 5-9:
Where: (3500 I/s = 3.5 m3/s), (600 mm = 0.6 m),
V = Velocity (m/s) (500 mm= 0.5 m)
Q = Airflow (l/s)
A = Area (mm2)
In fittings, such as junctions, where different areas
are involved, letters with and without subscripts are
used to denote the area at which the mean velocity
is to be calculated, such as "A" for inlet area, "Ac"
for upstream or "common" duct area, "Ab" for branch V = 11.67 m/s
duct area, "As" for downstream or "system" duct Using Equation 5-10:
area, "Ao" for orifice area, etc.
Vp = 0.602 x (11.67)2 = 81.99 Pa (Use 82)
Velocity pressure (Vp) may be calculated from Equa-
tion 5-10 or obtained from Tables 14-6 and 14-7 in Using Equation 5-8:
Chapter 14. TP = C x Vp = 0.40 x 82
TP = 32.8 Pa
Equation 5-10 (U.S.)
2. Pressure Losses in Elbows
Dynamic-loss coefficients for elbows (see Table 14-
Equation 5-10 (Metric) 10) are nearly independent of the air velocity and are
affected by the roughness of the duct walls only in
5.13
DUCT DESIGN FUNDAMENTALS
the case of the bends. In tables used in other texts, cient when the R/W ratio is equal to 1.0 or higher (see
the dynamic losses often are grouped with the friction Table 14-10, figure F). However, most installations do
losses to facilitate design calculations by determining not have ample room for this configuration and
bend losses in terms of additional equivalent lengths smaller R/W ratios are required The use of splitter
of straight duct or inches of water. However, the elbow vanes drops the fitting loss coefficient values of these
loss coefficients in Table 14-10 are used with the duct low R/W ratio radius elbows to a minimal amount.
velocity pressure to calculate the "total pressure" The splitter vane spacing may be calculated as
loss of each fitting. The additional duct friction loss (if shown in Figure 5-12.
any) of the elbow is included in the calculations for
the adjacent straight duct sections (by measuring to
Example 5-3 (U.S.)
the centerline of each fitting).
A 48 in. (H) x 24 in. (W) smooth radius elbow has a
Data now available for losses in compound bends,
throat radius of 6 in. Find the radius of each of two
where two or more elbows are close together, do not
splitter vanes and the fitting loss coefficient.
warrant refinement of design calculations beyond use
of the sum of the losses for the individual elbows. Solution:
Actually, the losses may be somewhat more or less Using Figure 5-12 and Table 14-10, figure G:
than for two bends. Loss coefficients for some nor-
mally used double elbow configurations may be ob-
tained from Table 14-10.
From Table 14-10. Figure G for two splitter
Loss coefficients for some elbows with angle bends vanes, CR = 0.585
other than 90° may be computed from the table in
Note 1 on page 14-19. Loss coefficients for elbows
discharging air directly into a large space are higher
than those given for elbows within duct systems (see
Table 14-16 figure E).
A. SPLITTER VANES
Smooth radius rectangular duct elbows (with radius c) From the fitting loss coefficient table for two
throat and heel) have a reasonably low loss coeffi- splitter vanes (opposite R/W = 0.25), C = 0.04
5.14
CHAPTER 5
Example 5-3 (Metric) of the distortion created by some turning vane rails
(runners). But, multiple, single thickness turning vane
A 1200 mm (H) x 600 mm (W) smooth radius elbow
sections with vanes 36 inches (914 mm) long or less
has a throat radius of 150 mm. Find the radius of
can be installed in large elbows instead of using dou-
each of two splitter vanes and the fitting loss coeffi-
ble thickness vanes.
cient.
5.15
DUCT DESIGN FUNDAMENTALS
5.16
CHAPTER 5
b) Single, Every Other Vane Missing that are not tangent to the airflow direction can cause
From Figure 5-13, C = 0.46 a high pressure loss. This "non-tangent to the airflow
TP = C x Vp = 0.46 x 71.6 problem" also happens in normal 90° elbows with
TP = 32.94 Pa careless workmanship. A proper installation in a
Loss for 6 elbows = 1976 Pa change-of-size elbow is shown in Figure 5-15 where
c) Double, Standard Spacing the vanes have been installed so that they are tangent
The loss coefficient for the 50 mm double thick- to the airflow.
ness vane is 0.50 (10 m/s).
TP = C x Vp = 0.50 x 71.6
TP = 35.8 Pa 3. Pressure Losses in Divided-
Loss for 6 elbows = 214.8 Pa
Flow Fittings
The difference in losses of the three different turning
vanes in the same elbows becomes very important A. STRAIGHT-THROUGH SECTIONS
to the energy conscious HVAC system designer who
only has 2.0 in w.g.(500 Pa) system static pressure Whenever air is diverted to a branch, there will be a
to work with. The a) single thickness vane elbows velocity reduction in the straight-through section im-
used 0.414 in. w.g. (98.82 Pa) or 20.7 percent of the mediately following the branch. If no friction or dy-
available pressure. The b) elbows, with half of the namic losses occurred at the junction, there would be
turning vanes missing, consumed 0.828 in. w.g. no loss in total pressure and the change in velocity
(1976 Pa) or 41.4 percent of the system pressure. pressure would be completely converted into a regain
The c) double thickness vane elbows used 0.90 in. (rise) in static pressure.
w.g. (214.8 Pa) or 45.0 percent. It has been found by tests that the regain coefficient
Another turning vane problem occurs when a rectan- across a takeoff can be as high as 0.90 for well
gular duct mitred elbow changes size from inlet to designed and constructed round ducts with no re-
outlet. Until research data is available, the pressure ducing section immediately after the takeoff.
loss calculations should be based on the higher ve- Under less ideal conditions, such as in rectangular
locity pressure of the smaller size. The use of double ducts with a high aspect ratio or takeoffs closely fol-
thickness vanes is not recommended because they lowing an upstream disturbance, the regain coeffi-
usually cannot be moved in many vane rails or run- cient can be as low as 0.50. A static pressure regain
ners so that they are tangent to the airflow. However, of 0.75 normally is used. Static regain (or loss) is
the critical and rather common problem is that turning included in the duct fitting loss coefficient tables which
vanes are put into the vane rails as they are for a have changes in cross-sectional areas of the main
normal 90° elbow, as shown in Figure 5-14. Vanes duct.
5.17
DUCT DESIGN FUNDAMENTALS
5.18
CHAPTER 5
5.19
DUCT DESIGN FUNDAMENTALS
charge in blow-through units. They also may be used H). When fans are tested and rated, discharge duct-
in branch ducts to dissipate excess static pressure in work is attached. However, this "free discharge" in-
low resistance runs. stallation has been used as an industry "standard"
Commonly used "shop" fabricated butterfly damper for roof mounted exhaust fans for many years. Ex-
loss coefficients in Table 14-18 are based on a con- ample 5-5 using Table 14-16 G indicates why margin-
stant velocity. Use of these coefficients will be found ally sized exhaust systems have suffered through the
in the duct design examples in Chapters 7 and 8. years.
However, AMCA tests have shown that there can be
a dramatic increase in the pressure drop of small Example 5-5 (U.S.)
dampers as compared to large dampers of the same A small vent set has an outlet velocity of 1790 fpm at
design (see Figure 5-22).
0.25 in. w.g. static pressure. Calculate the capacity
Attention is called to the large loss coefficients of a loss of the "free discharge" roof mounted fan. (0 -
fan "free discharge," i.e. no ductwork on the dis- 30, A1,/A = 1.5).
charge side of the fan (Table 14-16, Figures G and
5.20
CHAPTER 5
5.21
DUCT DESIGN FUNDAMENTALS
pressure in the main supply duct leaving the fan. DUCT AIR
What would be the pressure loss of the fitting found
in Table 14-18, Figure L if the beam duct height ratio F LEAKAGE
(L/H) was 2 (with and without single thickness turning
vanes)? The amount of duct leakage in an HVAC system may
be determined in advance by the system designer
using data extracted from the SMACNA "HVAC Duct
Solution: Construction Standards-Metal and Flexible" and the
From Table 14-7, Vp - 62 Pa for 10 m s. SMACNA "HVAC Air Duct Leakage Test Manual".
From Table 14-18, Figure L,
C = 0.77 for single thickness turning vanes Leakage in all unsealed ducts varies considerably
C = 9.24 without turning vanes with the fabricating machinery used, the methods of
assembly, and the workmanship. For sealed ducts, a
With Turning Vanes: wide variety of sealing methods and products exists.
Fitting loss = C x V, - 0.77 x 62= 477Pa Each has a relatively short shelf life and no docu-
Without Turning Vanes: mented research has identified the in-service aging
Fitting loss = C x Vp = 9.24 x 62 573 Pa characteristics of sealant applications. Many sealants
One can see that the 477 Pa pressure loss of the contain volatile solvents that evaporate and introduce
fitting with turning vanes is but 8 percent of the initial shrinkage and curing factors. Surface cleanliness and
625 Pa in the duct system. The 573 Pa pressure loss sealant application in relation to air pressure direction
are other variables. With the exception of pressure-
of the fitting without turning vanes theoretically de-
sensitive adhesive tapes, no standard tests exist to
stroys the system airflow by wiping out 92 percent
evaluate performance and grade sealing products. A
of the 625 Pa total system pressure! Actually, the
variety of sealed and unsealed duct leakage tests
operating point of the system fan curve interchange
have confirmed that longitudinal seam, transverse
moves up and to the left on the fan curve, substan-
tially reducing the system airflow (see Figure 5-23). joint, and assembled duct leakage can be repre-
sented by:
5.23
DUCT DESIGN FUNDAMENTALS
Equation 5-12 (U.S.) designer should independently account for air leak-
CL = F/P065 age in casings and frames of equipment in the duct
Equation 5-12 (Metric) system. Casings or volume-controlling air terminal
C, = 720 F/P 65 units may leak 2 to 5% of their maximum flow. The
effects of such leakage should be anticipated, if al-
where: lowed, and the ductwork should not be expected to
C, = Leakage class at 1 in.w.g. (250 Pa) static compensate for equipment leakage. Allowable leak-
pressure-cfm/100 sq. ft. (I/s per m2) age should be controlled consistent with airflow tol-
F = Leakage rate-cfm/100 sq. ft. (I/s per m2) erances at the air terminals. A leakage class of 3 is
duct surface attainable for all duct systems by careful selection of
P = Static Pressure-in.w.g. (Pa) joints and sealing methods and by good workman-
ship.
Table 5-2 is a summary of the leakage class attain- Where zero leakage is required, designers should
able for good duct construction and sealing practices. understand that contractors may have difficulty meet-
Connections of ducts to grilles, diffusers, and regis- ing their requirements. Zero leakage is not a practical
ters are not represented in the test data. The HVAC objective except in critical situations such as nuclear
system designer is responsible for assigning accept- safety-related applications. One (1) percent leakage
able leakage rates. Although leakage as a percentage also is difficult or impossible to attain in larger sys-
of fan airflow rate is an important evaluation criterion tems. The shaded area in Table 5-3 predicts that one
(see Table 5-3), designers should first become famil- (1) percent leakage in duct systems is only attainable
iar with the leakage rates from selected construction up to 2 in.w.g. (500 Pa) static pressure, which elimi-
detail. This knowledge allows the designer to analyze nates all higher pressure systems, and all larger sys-
both first cost and life cycle cost of a duct system so tems where the system airflow per square foot of duct
the owner may benefit. In performing an analysis, the surface is low.
5.24
CHAPTER 5
Additional discussions of leakage analysis may be ameter duct from A to F has 800 square feet of
found in the SMACNA "HVAC Air Duct Leakage Test duct surface.
Manual." Leakage = 10.6/100 x 800 = 85 cfm
Example 5-7 (U.S.) b) The average pressure from F to J and P is 1.5
Using a typical duct system shown in Figure 7-2 of in.w.g. [(2 + 1)/2]. From Table 5-2, the leakage
Chapter 7, find the total leakage of the supply duct- class for a 2 in.w.g. duct class round metal duct
work in both cfm and percentage of airflow. is "12". Using Figure 5-24(A), the leakage factor
would be 15.5 cfm/100 sq. ft. The total calcu-
Solution lated duct surface is 900 square feet.
a) The average pressure from A to F is 2.5 in.w.g. Leakage = 15.5/100 x 900 = 140 cfm (F to J
[(3 + 2)/2]. From Table 5-2, the leakage class and P).
for a 3 in.w.g. duct class round metal duct is Leakage for similar ducts (F to W and X
"6". Using Figure 5-24(A), the leakage factor branches) would be the same, so the total
would be 10.6 cfm/100 sq. ft. The 34 inch di- would be 140 + 140 = 280 cfm of leakage.
5.25
DUCT DESIGN FUNDAMENTALS
c) The average pressure from J to M is 1 in.w.g. d) The total duct system leakage (not counting the
because the VAV boxes require 1 in.w.g. inlet flexible connections) is:
pressure. From Table 5-2, the leakage class will a) AF = 54 l/s
remain at "12", as it is based on 1 in.w.g. The
b) F/IO = 110 l/s
calculated duct surface for all four (4) branches
(M, S, W, and X) is 1320 square feet. c) IM/etc. = 135 l/s
Leakage = 12/100 x 1320 = 159 cfm Total = 299 I/s duct leakage
d) The total duct system leakage (not counting the Percent leakage = 299 x 100/10,000 Is
= 2.99%
flexible connections) is:
Although the duct systems in Figures 7-2 and 8-2 are
a) AF = 85 cfm similar, the metric unit dimensions are not conver-
b) FJ/P = 280 cfm sions from the U.S. unit dimensions, so the percent-
c) JM/etc. = 159 cfm age leakages from the two examples cannot be com-
pared.
Total = 524 cfm duct leakage
If a VAV system was built to a duct class of 3 in.w.g.
Percent leakage = 524 x 100/20,000 cfm (750 Pa) throughout and 1 in.w.g. (250 Pa) was re-
= 2.62% quired at the VAV boxes, the average pressure would
be 2 in.w.g. (500 Pa). From Table 5-2 and Figure 5-
24 the following is obtained:
Example 5-7 (Metric)
Round metal duct,
Using a typical duct system shown in Figure 8-2 of C, = 6 & F = 9 cfm/100 ft2 (0.5 l/sper m2)
Chapter 8, find the total leakage of the supply duct-
work in both l/s and percentage of airflow. Rectangular metal duct,
CL = 12 & F = 18 cfm/100 ft2 (0.95 l/sper m2)
5.26
CHAPTER 5
Solution
Equation 5-14 (Metric) a) Calculate the duct velocity using Equation 5-9:
y = 79.2
5.27
DUCT DESIGN FUNDAMENTALS
Example 5-8 (Metric) Insulating this duct reduces heat loss to 20 percent
of the uninsulated duct.
A 20 metre length of 600 mm by 900 mm uninsulated
sheet metal duct, freely suspended, conveys heated
air through a space maintained above freezing at Example 5-9 (Metric)
5°C. Based on heat loss calculations for the heated Same as Example 5-8, except the duct is insulated
zone, 8100 I/s of standard air at a supply air temper- externally with 50 mm thick fibrous glass with a den-
ature of 50°C is required. The duct is connected di- sity of 12 kg/m3. The insulation is wrapped with 0%
rectly to the heated zone. Determine the air temper- compression.
ature entering the duct and the duct heat loss.
Solution
All values, except U and P, remain the same as Ex-
Solution
ample 5-8. From Figure 14-7(a), U = 0.83 W/(m2°C)
a) Calculate the duct velocity using Equation 5-9: at 15 m/s. P = 3400 mm. Therefore:
y = 394
te = 50.20C
Select U = 4.16 W/m2 0C (from Figure 14-7). Q1,= 2300 W (2.3 kW)
Calculate P = 2 (600 + 900) = 3000 mm Insulating this duct reduces heat loss to 20 percent
y = 2.01 AVp/UPL of the uninsulated duct.
5.28
CHAPTER 5
Although the SMACNA Duct Design Committee has Figure 5-26 shows three unusual configuration 900
incorporated new fitting loss coefficient data for turn- elbows that were included in the above test project.
ing vanes into Table 14-10H in Chapter 14 after many Generally in all of the testing, the lowest value for a
years of testing, the balance of the fitting loss coeffi- fitting loss coefficient was obtained at the highest test
cient data in this section did not have a sufficient velocities, and the highest values were obtained at
range of testing to be totally reliable under all condi- velocities below 1200 fpm (6 m/s). However other in-
tions. However, the data is accurate within the re- accuracies enter in as the velocity pressure is being
search test parameters listed. reduced more rapidly because it is a function of the
square of the reduced velocity. Existing data for a
1. Other Elbow Configurations smooth radius 900 rectangular elbow (Table 14-10F
from Chapter 14) with R/W = 0.75 and 1.0 is com-
In addition to the various test projects on turning vane pared with that of Elbows A, B, and C in Figure 5-
elbows discussed earlier in Section E, other types of 26. Note that when the throat of the 90° mitered elbow
mitered rectangular duct elbows without turning (Figure 5-25) is changed from 90° to 450 (Elbow A)
vanes were tested. Loss coefficients were obtained or is made on a curved radius (Elbow B), the loss
for three sizes of 900 mitered elbows-12 x 12 inch coefficient values are cut by 50 to 70 percent. This
(300 x 300 mm), 22 x 8 inch (550 x 200 mm), could amount to a substantial savings of pressure
and 8 x 22 inch (200 x 550 mm). These are com- loss (i.e. energy).
pared with existing data from Table 14-10D in Chapter
14 in Figure 5-25. Note that the new data is reason-
ably consistent with older data being used. Test ve-
2. Taps at End of Ducts
locities ranged from 800 fpm (4 m/s) to 4400 fpm (22 Many new duct systems are installed without supply
m/s) in 200 fpm (1 m/s) increments. outlets in place until the tenant space is leased and
5.29
DUCT DESIGN FUNDAMENTALS
a floor plan submitted. If the last outlet in a duct is somewhat proportional to the change in loss coeffi-
not at the very end, does the "cushion head" affect cient values. As this configuration also is essentially
the loss coefficient? To answer this common ques- an elbow, compare the values with Tables 14-10D and
tion, tests were made of 10 and 12 inch (250 and 300 14-14Q in Chapter 14.
mm) diameter ducts with 14 x 6 and 22 x 8 inch
(350 x 150 and 550 x 200 mm) taps located 1, 6,
and 12 inches (25, 150 and 300 mm) from the capped 3. Future Test Results
end of each round duct and tap.
SMACNA unilaterally has additional research projects
The results were plotted and the fitting loss coeffi- underway along with joint research projects with ASH-
cients are shown in Figure 5-27 The surprise was RAE. Between editions of this manual, Technical Bul-
that the distance from the tap to the end of the duct letins will be issued to allow SMACNA Contractors
only changed the values by a small amount; but the access to the latest in HVAC system design infor-
velocity ratio between the tap and the main duct was mation resulting from these projects.
5.30
CHAPTER 5
5.31
FAN-DUCT CONNECTION
PRESSURE LOSSES
Most of the text material and accompanying tables and figures in this section were developed by the Air Moving
and Conditioning Association, Inc. and reprinted with their permission (AMCA Publication 201-"Fans and
Systems").
System Effect Curves were discussed in Chapter 5, available, assume that the tests were made with only
but the basics will be repeated as they relate to fan an outlet duct.
(equipment) connections. Figure 6-1 shows a series AMCA Standard 210 specifies an outlet duct that is
of 24 System Effect Curves. By entering the chart at not greater than 105 percent nor less than 95 of the
the appropriate air velocity (on the abcissa), it is pos- fan outlet area. It also requires that the included angle
sible to read across from any curve (to the ordinate) of the transition elements should not be greater than
to find the "System Effect Factor" for a particular 15° for converging elements nor greater than 70 for
configuration. System Effect Curve "letter designa- diverging elements.
tions" (such as R, S, T, etc.) may be obtained from
Tables 6-1 through 6-4 and Figures 6-9, 6-11, 6-12 Figure 6-2 shows the changes in velocity profiles at
and 6-17 in this section. The System Effect Factor is various distances from the fan outlet. For 100 percent
given in inches of water gauge (in. w.g.) or Pascals recovery, the duct, including the transition, should ex-
(Pa) and it must be added to the total system pres- tend at least two and one half equivalent duct diam-
sure losses or subtracted from the fan performance eters and will need to be as long as six equivalent
pressure rating. duct diameters at outlet velocities of 6,000 fpm (30
m/s) and higher. If it is not possible to use a full length
The velocity rate used in entering the chart will be outlet duct, a System Effect Factor must be added to
either the inlet or the outlet velocity of the fan, depen- the system resistance losses.
dent on whether the configuration in question is re-
lated to the fan inlet or the outlet. Most catalog ratings To determine the applicable System Effect Factor, cal-
include outlet velocity figures, but for centrifugal fans, culate the average velocity in the outlet duct and enter
it may be necessary to calculate the inlet velocity the System Effect Curves (Figure 6-1) at this velocity.
(see Figures 6-20 and 6-21). The necessary dimen- Select the appropriate System Effect Curve from Ta-
sioned drawings are usually included in the fan cat- ble 6-1. The ratio of blast area to outlet area is not
alog. usually included in fan catalog data and it will be
necessary to obtain this from the fan manufacturer.
If more than one configuration is included in a sys-
tem, the System Effect Factor for each must be de- NOTE: The system Effect Factor includes only
termined separately and the total of these System the effect of the system configuration on the
Effects must be added to the total system pressure fan's performance. Any additional friction
losses or subtracted from the fan pressure rating. losses due to additional ductwork should be
added to the calculated system pressure loss.
Also, System Effect cannot be field measured
... only calculated.
FAN OUTLET
CONDITIONS 2. Outlet Diffusers or Evases
The process which takes place in the outlet duct is
1. Outlet Ducts often referred to as "static regain." The relatively high
velocity airstream leaving the blast area of the fan
Fans intended primarily for use with duct systems are gradually expands to fill the duct. The kinetic energy
usually tested with an outlet duct in place. The sys- (velocity pressure) decreases and the potential en-
tem designer should examine catalog ratings care- ergy (static pressure) increases.
fully for statements defining whether the published In many systems, it may be feasible to use an outlet
ratings are based on tests made with outlet ducts, duct which is considerably larger than the fan outlet.
inlet ducts, both or no ducts. If information is not In these cases, the static pressure available to over-
6.1