Abstract: Internet of Thing becomes a advanced technology in transforming many areas of mod-ern age including power system.
Electricity is also a backbone of the country’s economy and it is important to get the reliable supply at all time. Using IoT technology,
the switching time and restoration of the system can be reduced and consequently the reliability can be improved. In this paper, how to
concern the IoT technology in power system is described. Moreover, the reliability improvement by IoT technology is also conducted
with the reliability indices analysis. According to the results, the amount of energy not supply, ENS and system average interruption
duration is reduced by the IoT technology. The reliability test system of RBTS bus 2 is used as the test system.
Keywords: I0T, Power system, Reliability improvement, Energy not supply, SAIDI, Smart Grid
1. INTRODUCTION
The Internet of Things (IoT) refers to the use of intelligently
connected devices and systems to leverage data gathered by
embedded sensors and actuators in machines and other
physical objects. IoT is expected to spread rapidly over the
coming years and this convergence will unleash a new
dimension of services that improve the quality of life of
consumers and productivity of enterprises, unlocking an
opportunity. For consumers, the IoT has the potential to
deliver solutions that dramatically improve energy efficiency,
security, health, education and many other aspects of daily
life. For enterprises, IoT can under-pin solutions that improve
decision-making and productivity in manufacturing, retail, Fig. 1 Block Diagram of RTU
agriculture and other sectors [1].
2. METHODOLOGY
.The major area where IoT deals with energy management Distribution system is responsible for transferring electrical
systems is the smart grid. IOT extends the benefits of smart energy to the end users. The outage in the distribution system
grid be-yond the automation, distribution and monitoring has a localized effect compared with generation and
being done by the utilities [2]. The task of the IoT in the field transmission sectors. However, analysis of the customer
of electrical energy includes failure statistics indicates that the distribution system has the
(1) Advanced Metering Infrastructure (AMI) greatest contribution to the unavailability of supply to a
customer.
(2) SCADA (Supervisory Control and Data
Acquisition) In this paper, to analyze the impact of protection system on
reliability, following reliability indices are used: system
(3) Smart Inverters average interruption frequency index (SAIFI), system average
interruption duration index (SAIDI), customer average
(4) Remote control operation of energy
interruption duration index (CAIDI), energy not supplied
consuming devices
index (ENS) and average energy not supplied index (AENS)
By using conventional switch gears in distribution systems, it The equations of reliability indices are equation (1)-(5) [4].
takes too much time to know fault locations and to disconnect
Reliability indices are typically computed by utilities at the
the faulted lines. By using Distribution Automation System
end of each year by using historical outage data recorded in
(DAS), the problem can be solved in short time. . Therefore,
distribution outage reports. This is important because utilities
it is necessary to use automated protections devices controlled
know how their systems are performing. However, it is less
by SCADA system to improve the reliability of the system.
useful when the specific impact of various design
And IOT technology is used in SCADA system.
improvement options wish to be quantified and compared. To
In SCADA system, Remote Telemetry Unit (RTU) is a device make such comparisons, a model must be developed which is
that collects and transmits the data to Mater Terminal Unit capable of predicting.
(MTU). RTUs are equipped with input chan-nels for sensing
or metering, output channels for control. A block diagram of total number of customer interrupti ons
SAIFI
RTU is shown in Fig.1. The working principle of each
total number of customer sserved
protection devices such as disconnector and circuit breaker
(CB) are monitored by programmable logic controller
(PLC)[3].
www.ijsea.com 130
International Journal of Science and Engineering Applications
Volume 7–Issue07, 130-132, 2018, ISSN:-2319–7560
λ N
i i
N
= i per/ year (1) Table 1 Feeder types and lengths
sum of customer interrupti on duration Feeder Length Feeder section
SAIDI
total number of customer Type (km) numbers
U N 1 0.6 2,6,10,14,17,21,28,30,34
i i
2 0.75 1,4,7,9,12,16,19,22,24,27,29,32
N
= i hr/year (2) ,35
U N
i i Table 2 Loading data
λ N Feeder Average Load Peak Load Numbers of
= i i hr/year (3)
customers
(MW) (MW)
ENS L U
a(i) i MWh/yr (4) 1 3.645 5.934 652
17 19 20 22 23 Lines
LP10 LP11 LP12 LP13 LP14 LP15
x F2
x
12 14
33kV
13 15 The λ is failure rate per year per kilometer for lines and failure
F1 LP8 LP9 rate per year for transformers. The r is repair time in hour.
x 4 The rp is replacement time by a spare in hour. The s is
1 7 10
3
switching time in hour.
2 5 6 8 1 9
www.ijsea.com 131
International Journal of Science and Engineering Applications
Volume 7–Issue07, 130-132, 2018, ISSN:-2319–7560
6. ACKNOWLEDGMENTS
We are deeply grateful to Ministry of Education, Myanmar for
giving a chance for motivating to submit the research papers.
7. REFERENCES
[1] GSM Association. (2014). Understanding the internet of
thing (IoT). https://www.gsma.com/iot/wp-
content/uploads/2014/08/cl_iot_wp_07_14.pdf
http://www.electricaltechnology.org/20 16/07/internet-of-
Fig.3 Comparison of ENS in two cases things-iot-and-its-applications-in-electrical-power-
industry.html
The comparison of energy not supply is shown in [3] Ohn Zin Lin and Hajime Miyauchi(2014). DG Potential
Fig.3 and the amount of ENS is compared in two cases for
in Myanmar and Proposed Method to Improve Distribution
four feeders. according to results, the amount of ENS is
reduced using IoT technology. For example, ENS is decreased System Reliability by DGs and SCADA Based Distribution
from 3.7042 MW to 0.5665 MW per year. Automation System. Paper presented at the international
conference of electrical engineering, 20145: HongKong
www.ijsea.com 132