Proyecto 0052 – EGE HAINA – Barahona 1

Doc. nr. Hoja 1


Smoke Detector Data Sheet
0052-0907-1101 de 5

SMOKE DETECTOR DATA SHEET

0 13/Dec/2017 Issue for Construction


DS RP RP

B 02/Aug/2017 Preliminar

A 31/Jul/2017 Preliminar

Rev. Fecha Descripcion Diseño Reviso Aprobo


Proyecto 0052 – EGE HAINA – Barahona 1

Doc. nr. Hoja 2


Smoke Detector Data Sheet
0052-0907-1101 de 5

1. INTRODUCTION 3
Purpose 3
Scope 3
Project Description 3

2. PROJECT DOCUMENTS 4

3. DATA SHEET 5
Proyecto 0052 – EGE HAINA – Barahona 1

Doc. nr. Hoja 3


Smoke Detector Data Sheet
0052-0907-1101 de 5

1. INTRODUCTION

Purpose

The purpose of this document is to define the features of the Smoke Detector for
the project “Barahona 1 Repowering Project”.

Scope

This report defines main features of the Smoke Detector for the project “Barahona
1 Repowering Project”.

Project Description

The Owner, Empresa Generadora de Electricidad Haina S.A. (EGE Haina), is one
of the main electricity generating companies in the Dominican Republic.
The Owner intends to install and operate a new 55 MW steam turbine generator
(Barahona 1 Repowering Project). The proposed new steam turbine will be located
in the city of Barahona on the southwestern coast-line of the Dominican Republic
and will be built adjacent to an existing steam turbine generator currently in
operation since 2002 and generating 45 MW net.
Proyecto 0052 – EGE HAINA – Barahona 1

Doc. nr. Hoja 4


Smoke Detector Data Sheet
0052-0907-1101 de 5

2. PROJECT DOCUMENTS
0052-1132-0001 Filosofia de sistema contraincendio – Fire Fighting
System Design Report.
0052-0907-2001 Fire & Gas System Design Report - Especificacion
Tecnica Deteccion Y Alarma Contra Incendio
185417.70.0200 “Barahona 1 - EPC Specification”;
0052-0765-0011 STG Building Fire Fifhting System - Layout of Hose
stations, Extinguishers, alarm pushbuttons, fire
detectors - Level 0,00
0052-0765-0012 STG Building Fire Fifhting System - Layout of Hose
stations, Extinguishers, alarm pushbuttons, fire
detectors - Mezzanine Levels 2,95 - 3,50
0052-0765-0013 STG Building Fire Fifhting System - Layout of Hose
stations, Extinguishers, alarm pushbuttons, fire
detectors - Levels 7,55 - 8,90
0052-0765-0021 STG Building Fire Fifhting System - Layout of
Automatic Wet Pipe Sprinklers System - Level 0,00 -
Plan, Sections and Details
0052-0765-0022 STG Building Fire Fifhting System - Layout of
Automatic Wet Pipe Sprinklers System - Mezzanine
Levels 2,95 - 3,50, Sections and Details
0052-0765-0023 STG Building Fire Fifhting System - Layout of
Automatic Wet Pipe Sprinklers System - Mezzanine
Levels Levels 7,55 - 8,90 Sections and Details
Proyecto 0052 – EGE HAINA – Barahona 1

Doc. nr. Hoja 5


Smoke Detector Data Sheet
0052-0907-1101 de 5

3. DATA SHEET
DATASHEET

SMOKE DETECTOR

1 Tag Number Element SD-01….


2 Service SMOKE DETECTOR
3 Reference Layout No. 0052-0765-0011; 0052-0765-0012; 0052-0765-0013
GENERAL
4 Area Classification -
5 Amb. Temperature Min. Max. 15°C 37,5°C
6 Location (indoor / outdoor) Indoor
7 Type Photoelectric (Optical Smoke Detector)
8 Power Supply Power Consumption 10-30 V DC by MFR
9 Integrated/Remote Measuring Accurancy Integrated with Transmitter High Sensitivity
10 SENSOR ELEMENT Mounting Bracket and Support YES
11 Elec Connection Material - by MFR
12 Elec Protection Mechanical Protection - IP65
13 Code Certification (NOTE 1)
14 Ambient Temperature
15 Temperature °C Min Nor Max. 15°C - 37,5°C
16 Pressure Mpa Min Nor Max. - - -
17 Component Quantity - -
OPERATION DATA
18 Range Set Point - -
19 L Alarm LL Alarm - -
20 H Alarm HH Alarm - -
21 Relative Humidity Min. 30% Max. 100%
22 Type Smoke Detector
23 Function Smoke Indication
24 Mechanical Protection IP65
25 Display No
26 Alarm Diagnostic YES YES
27 Power Supply Led Test 10 - 30 V dc Yes
ELECTRONIC
28 Output Signal Contact rating by MFR 3A - 30 V dc
TRANSMITTER
29 Contact action on alarm OPEN
30 Reset automatic / manual AUTOMATIC
31 Current output (optional) -
32 Housing Material by MFR
33 SIL Level -
34 Electrical Connection Mounting 1/2" NPT Yes (NOTE 2)
35 Manufacturer Model
36 PURCHASE
37
38 NOTES :
39 1) The equipment shall be "UL-listed" or "FM-approved"
40 2) Smoke detector are located on the ceiling and in the false foor (installation in accordance with NFPA 72)
41
42
43
44
45
46
47
48
49
50
51
52
53
54
55