REPORT (BUSDUCT)
The observations and the suggestions described document wise as these suggestions shall include in
those relevant documents.
1. Enclosure material
Normally busduct enclosure come with steel or aluminum enclosure. In here due to high
salinity in air it shall use Aluminum enclosure to avoid corrosion issues.
2. Conductor insulation
Conductor insulation shall be extruded epoxy compound material other than manually
insulated cupper bars
Doc No 02. Material requisition for low-voltage switch board and bus duct
It shall mention about the installation trainings for the contractor. Also supplier shall
provide the onsite installation and testing supervision
Doc No 03. Extent of supply for low-voltage switch board and bus duct
1. Conductor material
It shall mentioned as high purity copper with (99.9% Cu) Tin plated on surface for better
conductivity
Busbar shall be sandwich type with shall no spaces for trapping air throughout the length.
Also such compact design will not allow to develop fire throughout the busduct if fire occurred
Insulation grade of the conductors shall be in higher grade (Ex Class F insulation)
4. Flexible Conductors
It shall introduce flexible conductors for all flange ends as if there any vibration develop
at one end it will not progress through the busduct.
Refer to the discussions had regarding the document reviews we can suggest above mentioned
observations and recommendations. If you need more detail or the provided clarifications are not
sufficient please do contact us or further clarifications
Prepared by
Surendra Bandara
B.Se. Eng. AMIE (SL)
+94773524898