Measuring centers MC3x0 series
Network recorders – MC350 & MC350H
Multimeter – MC330
Energy meter – MC320
o Voltage and current auto range measurements up to 600 VL‐N, 12.5 A
o Active energy accuracy class 0.5S
o Up to four I/O modules (analogue output, pulse output, alarm output,
tariff input)
o 4 Energy counters with tariff clock or tariff input
o Internal recorder 8MB
o MODBUS, DNP3, M‐Bus or PROFIBUS DP‐V0
o Certified ship version
Technical Documentation
PROPERTIES
Various types of communication modules are available.
o Measurements of instantaneous values of more than 60 Serial RS485, M‐Bus or PROFIBUS can be used for
quantities (U, I, P, Q, S, PF, PA, f, φ, THD, MD …) connecting device in to the network, standard USB and
o Harmonics measurements up to 31st harmonic serial RS232 for connection of device to computer or
o Measurements of minimum and maximum values controller and service USB communication (not galvanic
o 8 MB flash memory for recorder separated) that can be used for a fast set‐up without need
o 4 Energy counters for auxiliary power supply.
o Accuracy class U, I, P … 0.5
Available combinations, supported functions and types can
o Active energy Class 0.5S be seen in options table.
o Frequency range from 16 Hz to 400 Hz
2 МС350/MC330/MC320 Measuring centers
Technical Documentation
Communication TECHNICAL DATA
Meter can be equipped with communication module. Measurement inputs
Different options are possible:
Serial RS485 VOLTAGE MEASUREMENTS:
Serial RS232 Measuring range 10 … 600 VLN
USB 2.0 (MC330, MC350, MC350H only) Nominal voltage(UN) 50 … 500 VLN
PROFIBUS + Service USB (MC330, MC350, MC350H Max. measured value (cont.) 600 VLN ; 1000 VLL
only) Overload 2 × UN; 10 s
M‐Bus (MC350, MC350H only) Consumption < 0.1 VA
Service USB (MC320, MC330 only) Input impedance 3.3 MΩ per phase
Relay output (MC330, MC350, MC350H only) 2 outputs
Basic accuracy under reference conditions
Analogue output (MC350, MC350H only) 2 outputs Accuracy is presented as an accuracy class according to EN
Tariff input 2 inputs 61557‐12 except when it is stated as an absolute value
Digital input (MC330, MC350, MC350H only) 2 inputs Measurand Accuracy class
MC350H/МС350/MC330/MC320 Measuring centers 3
Technical Documentation
SERIAL COMMUNICATION RS485 INPUT / OUTPUT modules
Connection type Network ELECTROMECHANICAL RELAY OUTPUT (MC330, MC350,
Insulation Protection class II MC350H)
3.5 kV AC TRMS 1 min Purpose alarm, pulse, general
Max. connection length 1000 m purpose digital output
Transfer mode Asynchronous Type Electromechanical Relay
Protocol MODBUS RTU / DNP3 switch
Transfer rate 2.4 kBaud to 115.2 kBaud Rated voltage AC 250 V AC
Max. switching current AC 1000 mA AC
PROFIBUS COMMUNICATION Rated voltage DC 250 V DC
Connection type Network Max. switching current DC 200 mA DC
(valid for resistive load)
Insulation Protection class II
2.5 kV AC TRMS 1 min Contact resistance ≤ 100 mΩ (100 mA, 24V)
Max. connection length As per PROFIBUS‐DP Pulse Max. No.4000 imp/hour
networks (if used as pulse output) Min. length 100 ms
Transfer mode DP‐V0 Insulation voltage
Transfer rate 9.6 kBaud to 12 MBaud Between coil and contact 4 kV AC TRMS
M‐BUS COMMUNICATION Between contacts 1 kV AC TRMS
Connection type Network
PULSE (DIGITAL) OUTPUT (SO)
Insulation Protection class II Purpose pulse, alarm, general purpose
2.5 kV AC TRMS 1 min digital output
Max. connection length 1000 m Type Optocoupler open collector
Transfer mode Asynchronous switch
Protocol M‐Bus Rated voltage 40 V AC/DC
Transfer rate 300Baud to 9600Baud Max. switching current 30 mA (RONmax = 8Ω)
Pulse length (if used programmable (2 … 1000 ms)
USB COMMUNICATION as pulse output)
Connection type Direct
TARIFF INPUT
Max. connection length 5 m
Rated voltage 230 V 20 % AC/DC
Insulation Protection class II 75 … 110 V AC/DC
3.5 kV AC TRMS 1 min Max. current < 0.6 mA
Insulation – Service USB Protection class I Frequency range 45 … 65 Hz
communication (see warning 2.2 kV AC TRMS 1 min ON voltage 40 ... 120 % of rated voltage
below) OFF voltage 0 ... 10 % of rated voltage
Transfer mode Asynchronous
4 MC350H/МС350/MC330/MC320 Measuring centers
Technical Documentation
ANALOGUE OUTPUT (MC350, MC350H) AUX POWER SUPPLY
Note! UNIVERSAL SUPPLY – FULL RANGE
Analogue output is available only in combination with High Nominal voltage AC range 48 … 276 V
range Universal power supply. Nominal frequency range 40 … 65 Hz
y0 in compliance with EN 60529
1 ENVIRONMENTAL CONDITIONS
ye
c or c 1 Ambient temperature usage group III
x0
1 Operating temperature ‐ 10 to +60 °C
xe Storage temperature ‐ 40 to +70 °C
95% r.h. non‐condensing
Maximum humidity
Bent characteristic
Altitude 2000 m
xb1 x xb EU DIRECTIVES
b – number of break point (1 to 5) Directive 2014/35/EU on low voltage.
Directive 2014/30/EU on electromagnetic compatibility.
yb yb 1 xe Directive on RoHS 2011/65/EU.
c or c 1
xb xb1 ye
TERMINALS
Connection Max. conductor cross‐sections
Voltage inputs (4) 2.5 mm2 with pin terminal
4 mm2 solid wire
Current inputs (3) Ø 6 mm; one conductor
with insulation
Power supply (2) 2.5 mm2; one conductor
Modules (3 each) 2.5 mm2; one conductor
MECHANICAL
Vibration withstand 0.7g, 3 … 100 Hz
Mounting Pannel mounting
Cutting for installation: 92+0,8 mm
acc. to DIN EN 50 022
Weight (max) 500 g
MC350H/МС350/MC330/MC320 Measuring centers 5
Technical Documentation
CONNECTION DIMENSIONAL DRAWING
System:
Voltage inputs can be connected either directly to low‐
voltage network or via a high‐voltage transformer to high‐
voltage network.
Current inputs can be connected either directly to low‐
voltage network or shall be connected to network via a
corresponding current transformer (with standard 1 A or 5
A outputs).
System/ connection with Terminal assignment
Single‐phase connection 1b (1W)
Three‐phase three‐wire connection with balanced load 3b (1W3) CONNECTION TERMINALS AND MARKINGS
Function Connection
IL1 CT1
AC current IL2 CT2
IL3 CT3
Measuring
UL1 2
input
UL2 5
AC voltage
UL3 8
N 11
Three‐phase three‐wire connection with unbalanced load 3u (2W3)
I/O − 1 15
Common
I/O 1, 2 16
(1, 2)
Inputs / I/O – 2 17
outputs I/O – 3 18
Common
I/O 3, 4 19
(3, 4)
I/O – 4 20
Three‐phase four wire connection with balanced load 4b (1W4) + / AC (L) 13
Auxiliary power supply
– / AC (N) 14
Rx / A / M+ 21
RS232/RS485
GND / C / NC 22
/M‐Bus
Tx / B / M‐ 23
3 – A
8 – B
Communication D‐SUB
PROFIBUS 6 – 5V
9pin
5 – GND
Three‐phase four wire connection with unbalanced load 4u (3W4) 4 – RTS
USB USB type B
Service USB Mini USB
6 MC350H/МС350/MC330/MC320 Measuring centers
Technical Documentation
COMPLIANCE WITH STANDARDS
Standard EN Description
Electrical safety in low voltage
distribution systems up to 1000 V a.c.
61557‐12 and 1500 V d.c. ‐ Equipment for testing,
measuring or monitoring of protective
measures
Safety requirements for electrical
61010‐1 equipment for measurement, control
and laboratory use
Electricity metering equipment (a.c.)
62053−21*
Particular requirements
Electricity metering equipment (a.c.)
62053−22*
Particular requirements
Electricity metering equipment (a.c.)
62053−23*
Particular requirements
Electricity metering equipment (a.c.)
62053−31*
Particular requirements
EMC requirements for electrical
equipment for measurement, control
61326‐1
and laboratory use Part 1: General
requirements
Degrees of protection provided by
60529
enclosures (IP code)
Tests for flammability of plastic
UL 94 materials for parts in devices and
appliances
Industrial communication networks –
IEC 61158
Fieldbus specifications (Type 3)
Communication system for and remote
13757
reading of meters
* ‐ Partial compliance
MC350H/МС350/MC330/MC320 Measuring centers 7
Technical Documentation
DATA FOR ORDERING EXAMPLE OF ORDERING
When ordering the meter, all required specifications shall The MC350 meter is connected to secondary phase voltage
be stated in compliance with the ordering code. Also up to 500 VL‐N and 5 A secondary current. There are no
additional information could be stated if needed. Most special requirements for energy accuracy. A universal
typical options are shown as an example. supply and two modules are built‐in the meter. The first
module is a relay output and the second one is a tariff input
(230 V AC). Meter has USB communication, it is calibrated
to frequency 50, 60 Hz, finish is standard.
Ordering code example:
MC350 S ARNG S U U M T A T
8 MC350H/МС350/MC330/MC320 Measuring centers
Technical Documentation
Communication
Accuracy Class
Power Supply
Input/Output
Input/Output
Connection
Calibration
Frequency
(COM1)
Current
Voltage
Energy
Finish
Input
Type
1&2
3&4
Aux
MC3x0x X X X X X X X X X
| | | | | | | | | T Through Hole Transformer *
| | | | | | | | | C Screw Terminal Connector
| | | | | | | | A Standard *
| | | | | | | | P IP54
| | | | | | | | H HVE (Tropical Seal)
| | | | | | | | S Ship Version (not supported with PROFIBUS)
| | | | | | | D 2x Digital input 230 V (MC330, MC350, MC350H only)
| | | | | | | E 2x Digital input 75 ... 110 V (MC330, MC350, MC350H only)
| | | | | | | F 2x Digital input 24 V DC (MC330, MC350, MC350H only)
| | | | | | | T 2x Tariff input 230 V
| | | | | | | Z 2x Tariff input 75 ... 110 V
| | | | | | | N Without *
(MC350, MC350H
| | | | | | | A 2x Analogue output
with aux. power supply type H only)
| | | | | | S 2x Pulse output
| | | | | | M 2x Relay output (MC330, MC350, MC350H only)
| | | | | | N Without *
| | | | | S RS232
| | | | | D RS485
(MC330, MC350, MC350H only;
| | | | | P PROFIBUS + Service USB
excludes Ship Version)
| | | | | L M‐Bus + Service USB (MC350, MC350H only)
| | | | | U USB
| | | | | N Without * (MC320, MC330 only)
| | | | | M Service USB (MC320, MC330 only)
| | | | U 20 ... 300 V DC, 48 ... 276 V AC ( Uni. power supply ‐ Full range) *
| | | | A 57.7 V AC
| | | | B 63.5 V AC
| | | | C 100 V AC
| | | | D 110 V AC
| | | | E 230 V AC
| | | | F 400 V AC
| | | | G 500 V AC
| | | | I 240 V AC
| | | | J 440 V AC
100 … 265 V DC, 85 ... 265 V AC
| | | | H (MC350, MC350H only)
(Uni. power supply ‐ High range)
| | | S 50, 60 Hz * Calibration frequency is valid only
| | | A 400 Hz for measuring inputs
| | | B 16.6 Hz and not for power supply!
| | | C 200 Hz
| | ARNG Autorange – 50 … 500 V *
| | 63V5 57.7 … 63.5 V (MC320, MC330 only)
| | 110V 100 … 110 V (MC320, MC330 only)
| | 240V 230 … 240 V (MC320, MC330 only)
| S Active cl.1 / Reactive cl.2 *
| H Active cl.0.5S / Reactive cl.2
MC320 Energy meter
MC330 Multimeter
MC350 Network recorder
MC350H Network recorder with individual harmonics measurements
* ‐ Default ordering value
MC350H/МС350/MC330/MC320 Measuring centers 9