You are on page 1of 16

Balancing & Flow

Measurement Valves

watts.com
Table of Contents
General Information................................................................................................................................. 2 – 3

Series CSM-61 –– Flow Measurement Valves for Low to Medium Flow Rate HVAC Units......................... 4 – 5

Series CSM-81-F –– Flow Measurement Valves for Medium to High Flow Rate HVAC Units........................... 7

Series CSM-91 –– Flow Measurement Valves for Medium to High Flow Rate HVAC Units........................ 8 – 9

Series TDV –– Triple Duty Valves for Single, Double and Vertical In-Line Pump Applications.................. 10 – 11

CSM-91-IK –– Insulation kits for Series CSM-91 and TDV to Meet ASHRAE 90.1 Specifications................... 12

Series PG –– Pressure Differential Gauges..................................................................................................... 12

Watts product specifications in U.S. customary units and metric are approximate and are provided for reference only. For precise measurements, please contact
Watts Technical Service. Watts reserves the right to change or modify product design, construction, specifications, or materials without prior notice and without
incurring any obligation to make such changes and modifications on Watts products previously or subsequently sold. 1
General Information
Importance of a Balanced System
Heating, cooling and water distribution systems must be accurately adjusted and balanced to achieve optimum system performance.
Unbalanced systems can produce wide temperature variations among rooms and can raise building energy costs. The installation of
balancing valves in combination with pre-determined accurate pressure drop calculations provides indoor comfort and energy efficiency
to the end user.

Accurately balanced systems provide the following benefits:


•  A comfortable indoor climate
•  Desired flow distribution throughout the building
•  Substantial energy and cost savings
•  Trouble-free operation and ease of maintenance

Role of Balancing Valves


The role of the balancing valve is to control the gallon per minute (gpm) flow rate in each building main, riser and branch to deliver the
designed gpm flow in chilled and/or hot water applications. At each heat transfer coil the balancing valve is set to provide the precise
flow rate specified by the design engineer to provide indoor comfort and energy efficiency within a building.

Figure 1 shows a typical hydronic system and illustrates the locations where balancing valves are usually installed.

The example below describes how Watts balancing valves would be applied to a system like that shown in Figure 1.

In Figure 1, Riser B has 12 coils that each require a 2 gpm flow rate to meet design requirements. The total design flow rate is (12
coils x 2 gpm) or 24 gpm per riser. Balancing valves will be applied on the main supply line, the coil return, the branch return and the
riser return as follows:
•  A Series CSM-91 shall be applied on the main supply line to control the flow rate to 48 gpm. (2 risers per header at 24gpm per riser)
•  A Series CSM-81-F shall be applied on each riser return line to control the flow rate to 24 gpm (4 branches per riser at
6 gpm per branch).
•  A Series CSM-61 shall be applied on each branch return line to control the flow rate to 6 gpm (3 coils at 2 gpm per branch).
•  A Series CSM-61 shall be applied on each coil return line to control the flow rate through the coil to 2 gpm.

Each return riser flows into the return header sending 24 gpm to the boiler or chiller.
Figure 2 is a typical heat transfer coil used in chilled or hot water hydronic systems. This illustration shows the products commonly

Figure 1

2
installed on the coil including an air vent, test plugs, a balancing valve, ball valves, a strainer and a gauge. Installations will vary due to
specification preference.

Figure 2 Two-Way Heating and Cooling Coils

Watts Watts Watts


FV-4/Duovent Series TP Series TP
Air Vent Test Plug Test Plug Watts
TCV Watts B-6081 or FBVS-3C Ball Valve
CSM 61

Watts
Series TP Test Plug
and
Coil Series DPG1 Pressure Gauge
Watts
Series TP
Test Plug Watts
Watts
S777S or S777SI B-6081 or FBVS-3C Ball Valve
Strainer with Blow Down

3
Series CSM-61
Flow Measurement Valves
Sizes: 1⁄2" – 3" (15 – 80mm)
Series CSM-61 Flow Measurement Valves are designed for ap-
plication on low or medium flow rate HVAC units. Their
compact size allows for easy installation and use in crowded
piping compartments. The CSM-61’s ball-type design, extended
throttling range, and large indicator plate, make for highly
accurate flow measurement, even in very low flow ranges. Soldered
The CSM-61’s positive memory feature is easy to see, access,
and operate, facilitating system balancing and flow measurement.
These valves are also bi-directional, so there is no chance of
installing the valve in the incorrect flow direction.
Series CSM-61 valves provide positive shutoff, eliminating the
need for a separate service valve. The solder style CSM’s may Threaded
be installed without disassembly, saving costly installation time.
These valves are also provided with blowout proof stems. Use,
misuse, corrosion, or wear will not allow the stem to “blowout,"
releasing pressurized hot or chilled water. Installations
Fan Coil Unit
Features Series CSM-61
• Accurate flow measurement
Fan
• Easy to use memory Coil
Unit
• Bi-directional flow
• Positive shutoff
• Safe “blowout" proof design
• Available with threaded and soldered end connections
• Integral drain port
Pump, Riser, and Branches
Specifications
A flow measurement valve shall be installed on each hot/chilled
Series CSM-61

Series CSM-61

Series CSM-61
Series CSM-61

water unit or as otherwise shown on plans. The valve shall be of


the bi-directional, blow-out resistant, tight shutoff, ball design,
with position indicator, memory device, checked metering ports
with drip caps and integral drain ports opposite the metering
ports type. The valve shall be a Watts Regulator Company Series
CSM-61.

Applications
• Fan coil units
• Water source heat pumps
• Reheat coils
• Panel coils
• Small branch lines
• Unit heaters
• Unit ventilators
• Finned radiation
• Small domestic hot water lines
• Convectors
• Small pumps

4
Materials of Construction Pressure-Temperature
Housing/Body Bronze Pattern Size Working Temp Max. Working Pres.
°F °C psi bar
Packing Material 1⁄2" – 2" (15 – 50mm) Viton® Solder 1⁄2" – 1" (15 – 25mm) 200* 93 100 7
21⁄2" – 3" (65 – 80mm) Neoprene
250 ** 121 200 14
Pressure Taps ⁄ " Brass SAE 45° Flare
14
11⁄4" – 2" (32 – 50mm) 200* 93 90 6
Seats 
1⁄2" – 1", 3" (15 – 25, 80mm) 250 ** 121 175 12
Carbon/Glass filled PTFE Thread 1⁄2" – 3" (15 – 80mm) 250 121 300 21
11⁄4" – 2" (32–50mm) Virgin PTFE. *Note 1: Solder used in joints: 50-50 Tin Lead (ASTM B32 Alloy Grade 50A)
Drain Plug Brass **Note 2: Solder used in joints: 95-5 Tin Antimony

Dimensions-Weights

A R

Model Size (DN) Dimensions (approx.) Weight


A C D R
in. mm in. mm in. mm in. mm in. mm lbs. kgs.
CSM-61-M1-S 1⁄2 15 211⁄16 68 15⁄8 41 1⁄2 13 13⁄4 45 1.0 0.45
CSM-61-M1-S 3⁄4 20 31⁄8 79 111⁄16 43 9⁄16 15 17⁄8 47 1.3 0.59
CSM-61-M1-S 1 25 313⁄16 97 17⁄8 47 13⁄16 20 21⁄16 52 1.8 0.82
CSM-61-M2-S 11⁄4 32 49⁄16 116 17⁄8 47 11⁄8 29 23⁄16 56 1.5 0.68
CSM-61-M2-S 11⁄2 40 47⁄8 123 2 50 15⁄16 33 25⁄16 59 1.9 0.86
CSM-61-M2-S 2 50 6 153 29⁄16 66 19⁄16 40 25⁄8 67 3.4 1.54
CSM-61-M1-T 1⁄2 15 23⁄8 60 15⁄8 41 1⁄2 13 13⁄4 45 1.0 0.45
CSM-61-M1-T 3⁄4 20 25⁄8 67 111⁄16 43 9⁄16 15 17⁄8 47 1.3 0.59
CSM-61-M1-T 1 25 31⁄8 80 17⁄8 47 13⁄16 20 21⁄16 52 1.9 0.86
CSM-61-M1-T 11⁄4 32 33⁄4 94 17⁄8 47 1 25 23⁄16 56 1.9 0.86
CSM-61-M1-T 11⁄2 40 315⁄16 100 2 50 11⁄16 27 25⁄16 59 2.3 1.04
CSM-61-M1-T 2 50 41⁄2 114 2 ⁄16 66 15⁄16 33
9 29⁄16 66 4.0 1.81
CSM-61-M1-T 21⁄2 65 61⁄2 165 41⁄8 104 23⁄16 55 31⁄8 80 13.0 5.90
CSM-61-M1-T 3 80 613⁄16 173 43⁄8 112 27⁄8 73 35⁄8 92 17.0 7.71
Suffix: S = Solder Ends, T = Threaded Ends

For additional information, request literature ES-CSM-61. 5


Series CSM-81-F
Flow Measurement Valves
Sizes: 21⁄2" – 8" (65 – 200mm)
Series CSM-81-F Flow Measurement Valves are designed for
application on medium to high volume flow rate HVAC units. The
CSM-81-F’s lubricated plug design, extended throttling range
and large indicator plate provide accurate flow measurement and
long service life.
CSM-81-F’s unique cylindrical plug design provides full flow with
minimal pressure drops and low operating torque. Large wrench
flats on the external plug surface make setting or closing the valve
simple.
Series CSM-81-F valves feature easily accessible checked me-
tering ports with drip caps to facilitate system balancing and flow
measurement. These valves also provide positive shutoff,
eliminating the need for a separate service valve.
Applications
Features
• Fan coil units
• Accurate flow measurement
• Water source heat pumps
• Flanged end connections
• Reheat coils
• Positive shutoff
• Panel coils
• Checked metering ports
• Branch lines
• Low torque
• Pumps
• Face to face dimensions to ANSI B16.10

Specifications
A flow measurement valve shall be installed on each hot/chilled Typical Installations
water unit or as otherwise shown on the plans. The valve shall be Fan Coil Unit
Series CSM-81-F
of flanged end connections, provide positive shutoff, low torque
cylindrical plug design, with position indicator plate and checked Fan
metering ports. The valve shall be a Watts Regulator Company Coil
Unit
Series CSM-81-F.

Pump, Riser, and Branches Series CSM-81-F


Series CSM-81-F

Series CSM-81-F

Series CSM-81-F

6
Pressure-Temperature Materials of Construction
Maximum Working Temperature: 250˚F (121˚C) Body ASTM-A-126 Class B semi-steel
Maximum Working Pressure: 175psi (12 bar) Plug ASTM-A-126 Class B semi-steel
Stem Seal PTFE
Pressure Taps Brass 1⁄4" SAE 45° Flare

Dimensions-Weights

Flange hole di­men­sions


G conform to ANSI B16.1
F
Class 125.
C

E
D

Model Size (DN) Dimensions (approx.) Weight


A C D E F G
in.
mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs.
CSM-81-F 21⁄2 65 71⁄2 191 51⁄8 130 315⁄16 99 7 178 ⁄ 17
11 16 21⁄2 64 29.5 13.38
CSM-81-F 3 80 8 203 51⁄16 137 43⁄16 106 71⁄2 191 ⁄ 19
34 21⁄2 64 39.0 17.69
CSM-81-F 4 100 9 229 61⁄2 165 415⁄16 124 9 229 15⁄16 24 21⁄2 64 61.5 27.89
CSM-81-F 5 125 101⁄2 267 73⁄4 197 6 153 10 254 1 25 35⁄8 92 88.0 39.91
CSM-81-F 6 150 101⁄2 267 73⁄4 197 6 153 11 279 1 25 35⁄8 92 100.0 45.35
CSM-81-F 8 200 111⁄2 292 93⁄16 233 61⁄2 165 131⁄2 343 11⁄8 28 35⁄8 92 172.0 78.00
Suffix: F = Flanged Ends.

For additional information, request literature ES-CSM-81. 7


Series CSM-91
Flow Measurement/Balancing
Valves
Sizes 21⁄2" – 12" (65 – 300mm)
Series CSM-91 Flow Measurement/Balancing Valves are
designed for application on medium or large flow rate HVAC
systems, pump packages, and cooling towers. They feature
a multi-turn adjustment range for maximum control, pressure Angle Pattern
differential readout ports on both sides of the valve to allow for
easier installation and positive shutoff for servicing equipment. In
addition, these valves also incorporate a micrometer type hand-
wheel adjustment, visually readable settings and a tamper-proof
memory stop.
The CSM-91’s field-convertible design allows the valve to be
changed from the factory-standard straight pattern to an optional Straight Pat­tern
angle pattern with standard tools and no additional parts. This al-
lows the valve to be used as a replacement for angles or elbows, Applications
and will not affect the valve’s accuracy.
Maximum flow requires a one-foot pressure drop across the • Hot/Chilled water coils
valve to obtain an accurate meter reading with the valve set point • Cooling tower & chiller connections
from 50% to 100% open for greatest accuracy. • Primary & secondary connections
The valve should be installed with flow in the direction of the arrow
on the valve body, and installed at least five pipe diameters down-
stream from any fitting, and at least ten pipe diameters down- Typical Installations
stream from any pump. Two pipe diameters downstream from the
CSM-91 should be free of any fittings. When installed, easy and
unobstructed access to the valve handwheel and metering ports Hot/Chilled Water Coil
for adjustment should be provided. Mounting of the valve in piping = CSM-91
must prevent sediment buildup in metering ports.

Features
Fan
• Multi-turn adjustment Coil
• Interchangeable metering and drain ports on both sides Unit
of valve
• Positive shutoff
• Tamper-proof memory stop Cooling Tower & Chiller Con­nec­tions
• Micrometer type handwheel adjustment - visually readable
from a distance
• Field convertible for straight or angle pattern
Cooling Cooling
• Grooved end connections with optional flange adapters Tower Tower

Specifications
A flow measurement valve shall be installed as shown on plans.
Each valve shall have two 1⁄4" (6mm) NPT brass metering ports
with Nordel® check valves and gasketted caps located on both
sides of valve seat. Two additional 1⁄4" (6mm) NPT connections
with brass plugs are to be provided on the opposite side of the
Con­dens­ers Pump
metering ports for use as drain connections. Drain connections
and metering ports are to be interchangeable for measurement
flexibility when valves are installed in tight locations. The valve Primary & Secondary Con­nec­tions­
body shall be ductile iron with industrial standard grooved ends. Primary Mains
Valve stem and plug disc shall be bronze with ergonomically
designed handwheel with multi-turn handwheel adjustments.
Secondary
Sizes 21⁄2" and 3" (65 and 80mm) - five turns, 4" – 6" Pump Circuit
(100 – 150mm) - six turns, 8" and 10" (200 and 250mm) - twelve
turns, and 12" (300mm) - fourteen turns. Flange adapters shall
be supplied to prevent rotation. The valve shall be a Watts Regu- Fan
Coil
lator Company Series CSM-91. Unit

Pump
8
Pressure-Temperature Materials of Construction
Grooved Ends Only Body Ductile Iron ASTM A536 GR65-45-12
Maximum Working Pressure: 375psi (26.25 bar) Disc Bronze ASTM B584 C-84400
Maximum Temperature: 230°F (110°C) Seat 21⁄2" – 6" (65 – 150mm) Engineered Resin
8" – 12" (200 – 300mm) EPDM
Flange Stem 21⁄2" – 6" (65 – 150mm) Brass ASTM B-16,
Maximum Working Pressure: 8" – 12" (200 – 300mm) Stainless Steel
Class 125: 175psi (12 bar) O-ring Buna-N
Maximum Temperature: 230°F (110°C) Memory Lock Brass ASTM B-16
Meter Ports NPT Brass Body with Schrader Valve
Drain Tappings (2) 1/4" Brass plug
Note: Series CSM-91 valves are shipped with grooved ends stan­dard. For com­
pan­ion flang­es, please specify size when or­der­ing. In­su­la­tion blocks are also
or­dered sep­a­rate­ly from valve. Please spec­i­fy size when or­der­ing.

Dimensions-Weights

Spac­er Flange Dia.


C

C
Flange
Dia.

t
D
D
Spac­er F2 E
A F F1
A
Straight Pattern (Stan­dard) Angle Pattern (Con­vert­ible)
Straight Pattern
Size (DN) Dimensions (approx.) Flange Dia. Spacer Weight
A C D F 125#
in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs kgs
21⁄2 65 12 305 95⁄8 245 23⁄4 70 29⁄16 65 7 178 1 25 19 9
3 80 12 305 101⁄2 267 27⁄16 62 3 76 71⁄2 191 1 25 24 11
4 100 14 356 109⁄16 268 3 76 37⁄16 87 91⁄4 235 11⁄4 32 42 19
5 125 171⁄2 445 131⁄16 332 35⁄8 92 415⁄16 125 10 254 11⁄4 32 81 37
6 150 2011⁄16 525 133⁄4 349 47⁄16 113 57⁄8 149 11 279 2 51 120 54
8 200 283⁄16 716 245⁄8 625 511⁄16 144 77⁄8 200 131⁄2 343 21⁄4 57 310 141
10 250 30 762 261⁄2 673 69⁄16 167 915⁄32 241 16 406 21⁄4 57 460 209
12 300 38 ⁄16 964 287⁄16 722 75⁄8 194 125⁄8 321 19 483 21⁄4 57 870 395
1

Angle Pattern (Field Convertible*)


Size (DN) Dimensions (approx.) Flange Dia. Spacer Weight
A C D E F1 F2 125#
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs kgs
21⁄2 65 101⁄8 257 95⁄8 245 45⁄8 117 73⁄8 187 29⁄16 65 23⁄4 70 7 178 1 25 19 9
3 80 1013⁄16 275 101⁄2 267 37⁄8 98 83⁄8 213 3 76 27⁄16 62 71⁄2 191 1 25 24 11
4 100 125⁄8 321 109⁄16 268 43⁄8 111 95⁄8 244 37⁄16 87 3 76 91⁄4 235 11⁄4 32 42 19
5 125 155⁄8 397 131⁄16 332 51⁄2 140 12 305 415⁄16 125 35⁄8 92 10 254 11⁄4 32 81 37
6 150 189⁄16 471 133⁄4 349 65⁄8 168 141⁄8 359 57⁄8 149 47⁄16 113 11 279 2 51 120 54
8 200 245⁄16 618 245⁄8 625 93⁄16 233 1815⁄16 481 77⁄8 200 511⁄16 144 131⁄2 343 21⁄4 57 310 141
10 250 267⁄8 683 261⁄2 673 93⁄4 248 205⁄16 516 915⁄32 241 69⁄16 167 16 406 21⁄4 57 460 209
12 300 3111⁄16 805 287⁄16 722 14 356 241⁄16 611 125⁄8 321 75⁄8 194 19 483 21⁄4 57 870 395
*Note: Series CSM-91 valves are shipped as straight pattern from fac­to­ry. To convert to angle pattern  refer to instruction sheet shipped with valve.

For additional information, request literature ES-CSM-91. 9


Series TDV
Triple Duty Valves
Sizes: 21⁄2" – 12" (65 – 300mm)
Series TDV Triple Duty Valves are designed for use on single,
double, and vertical in-line pump applications. The TDV com-
bines the functions of a positive hand-tight shutoff valve, check
valve, and flow control valve into one versatile package, and
eliminates the need to utilize three separate valves on the pump
system. By using the Series TDV, fewer components and fewer
connections are required. Therefore, installation time is reduced,
less space is needed, and the potential for leaks is reduced: Angle Pattern
adding up to significant cost savings.
The field-convertible design allows the TDV to be changed from
the factory-standard, straight pattern to an optional angle pattern
by using standard tools, and no additional parts. This allows the
TDV to be used as a replacement for angles and elbows, and Straight Pattern
generates even greater savings on space and connections.
The TDV is also designed for easy field serviceability with bonnet
O-rings that can be replaced under pressure by backseating the Typical Installations
valve, and seats that can be changed without the use of special
tools. Base Mounted Single Suction Pump

Features
• Reduced field installation and material cost
• Eliminates requirement of three valves on pump discharge
• Soft seat to ensure tight shutoff
• Spring closure design, non-slam silent check valve feature
• Valve Cv designed to ASHRAE flow recommendations for
quiet system operation
• Grooved end connections with optional flange adapters

Specifications
A triple duty valve shall be installed on the discharge side of
Base Mounted Double Suction Pump
each pump as indicated on the plans. The valve body shall be
ductile iron with grooved ends and anti-rotation lugs on the inlet
and outlet of the body. The valve shall have two 1⁄4" (6mm) NPT
connections on each side of the valve seat. Two connections to
have brass pressure metering ports with check valve and gasket-
ted caps. Two other connections to be supplied with brass drain
plugs. Metering ports are to be inter-changeable with brass drain
plugs. The valve disc shall be bronze plug type with engineered
resin seat 21⁄2" – 6" (65 – 150mm) and EPDM for
8" – 12" (200 – 300mm).
Valve stem shall be stainless steel with wrench flats. Flange
adapters, where necessary, shall be Class 125) ductile iron
flanges with anti-rotation lugs and EPDM gaskets. Valve shall be
a Watts Regulator Company Series TDV.
Vertical In-line Pump
Applications
• Single, double and vertical in-line pumps

10
Pressure-Temperature Materials of Con­struc­tion
Body Ductile Iron ASTM A536 GR65-45-12
Grooved Ends Only
Disc Bronze ASTM B584 C-84400
Maximum Working Pressure: 375psi (26.25 bar)
Seat 21⁄2" – 6" (65 – 150mm) Engineered Resin
Maximum Temperature: 230°F (110°C) 8" – 12" (200 – 300mm) EPDM
Flange Stem Stainless Steel ASTM S582 Type 416
Maximum Working Pressure: Spring Stainless Steel ASTM S302
Class 125: 175psi (12 bar) O-ring Buna-N
Maximum Temperature: 230°F (110°C) Meter Ports NPT Brass Body with cap
Drain Tappings (2) 1/4" Brass plug
Note: Series TDV valves are shipped with grooved ends stan­dard. For com­pan­ion
flang­es, please specify size and class rating when or­der­ing. In­su­la­tion blocks are
also ordered separately from valve. Please spec­i­fy size when or­der­ing.

Dimensions-Weights A
F2 E

Flange C Flange
C Dia. Dia.

D D
Spacer
A F
Spacer F1
Straight Pattern (Stan­dard) Angle Pattern (Con­vert­ible)
Straight Pattern
Size (DN) Dimensions (approx.) Flange dia. Spacer Weight
A C D F 125#
in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs. kgs
21⁄2 65 12 305 7 178 23⁄4 70 29⁄16 65 7 178 1 25 19 9
3 80 12 305 713⁄16 198 27⁄16 61 3 76 71⁄2 191 1 25 24 11
4 100 14 356 8 203 3 76 37⁄16 87 91⁄4 235 11⁄4 32 42 19
5 125 171⁄2 445 101⁄8 257 35⁄8 92 415⁄16 125 10 254 11⁄4 32 81 37
6 150 2011⁄16 526 103⁄8 264 47⁄16 113 57⁄8 149 11 279 2 50 120 54
8 200 283⁄16 716 2213⁄16 579 511⁄16 144 77⁄8 200 131⁄2 343 21⁄4 57 310 141
10 250 30 762 285⁄8 727 69⁄16 167 915⁄32 240 16 406 21⁄4 57 460 209
12 300 381⁄16 967 325/8 829 75⁄8 194 125⁄8 321 19 483 21⁄4 57 870 395

Angle Pattern (Field Convertible*)


Size (DN) Dimensions (approx.) Flange dia. Spacer Weight
A C D E F1 F2 125#
in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm in. mm lbs kgs
21⁄2 65 115⁄8 295 73⁄8 187 23⁄4 70 45⁄8 117 29⁄16 64 7 178 7 178 1 25 19 9
3 80 1111⁄16 297 83⁄8 213 27⁄16 61 37⁄8 98 3 76 713⁄16 199 71⁄2 191 1 25 24 11
4 100 123⁄8 314 95⁄8 245 3 76 43⁄8 111 37⁄16 87 8 200 91⁄4 235 11⁄4 32 42 19
5 125 155⁄8 397 12 305 35⁄8 92 51⁄2 140 415⁄16 124 101⁄8 253 10 150 11⁄4 32 81 37
6 150 17 432 141⁄8 359 47⁄16 111 65⁄8 168 57⁄8 149 103⁄8 264 11 279 2 50 120 54
8 200 32 813 1815⁄16 481 511⁄16 145 93⁄16 234 77⁄8 200 2213⁄16 580 131⁄2 343 21⁄4 57 310 141
10 250 387⁄8 975 205⁄16 516 69⁄16 161 93⁄4 248 915⁄32 240 285⁄8 727 16 406 21⁄4 57 460 209
12 300 465⁄8 1184 241⁄16 612 75⁄8 194 14 356 125⁄8 321 325/8 825 201⁄2 521 21⁄4 57 870 395
*Note: Series TDV valves are shipped as straight pattern from fac­to­ry. To convert to angle pattern  refer to instruction sheet shipped with valve.

For additional information, request literature ES-TDV. 11


Series CSM-91-IK
Insulation Kits
Sizes: 21⁄2" – 4" (65 – 100mm)
Series CSM-91-IK Insulation Kits are available in sizes
21⁄2" – 6" (65 – 150mm) to suit Watts Series CSM-91 balancing
valves and Series TDV triple duty valves. The outside shell is a
preformed, removable PVC jacket with a flame spread rating of
50 or less. These systems provide sufficient mineral fiberglass
insulation to meet ASHRAE 90.1 specifications in operating con-
ditions with maximum fluid design operating temperature range
of 141°F – 200°F (61˚C – 93˚C) and mean rating temperature of
125°F (52˚ C). For additional information, request literature ES-CSM-91-INS.

Series PG
Pressure Differential Gauges
Series PG Pressure Differential Gauges are designed for use
with all Watts flow measurement valves and flow measurement
orifices. This Series may also be used to check differential pres-
sures across other system components including pumps, strain-
ers, coils, etc. All readout kits feature overrange protection and
are equipped with hoses, carrying case and instructions.

Features
• Portable
• For use with Watts flow measurement valves & orifices Models PG-2 – PG-6
• Overrange protection
• Equipped with hoses, carrying case and instructions

PG-2 – PG-6 PG-8


Max. Pressure 300psi (20.7 bar) 500psi (34.5 bar)
Max. Temp. 235°F (113°C) 235°F (113°C)
Accuracy ± 3% ± 5%
Carrying Case Yes Yes
Shutoff Valves No No
Kits contain case, differential meter, two lengths of hose with gauge fittings, air
venting features and instructions.

Model PG-8

Ranges:
PG-2 0 – 16 ft. (0 – 4876 kg/m2) water
PG-3 0 – 35 ft. (0 – 10668 kg/m2) water
PG-4 0 – 100 in. (0 – 2540 kg/m2) water
PG-5 0 – 200 in. (0 – 5080 kg/m2) water
PG-6 0 – 50 in. (0 – 1270 kg/m2) water
PG-8 0 – 135 in. (0 – 3429 kg/m2) water

For additional information, request literature ES-PG-2-6 or ES-PG-8.

Nordel® is a registered trademark of Dupont Dow Elastomers.


Viton® is a registered trademark of Dupont Dow Elastomers.

12
For Technical and Ordering Assistance, please call us at 978-688-1811.
To locate your nearest Watts representative, please click on our
find a sales rep locator on watts.com.

Represented by:

A Watts Water Technologies Company USA: No. Andover, MA • Tel. (978) 688-1811 • Fax: (978) 794-1848 • www.watts.com
Canada: Burlington, ON • Tel. (905) 332-4090 • Fax: (905) 332-7068 • www.wattscanada.ca

F-CBFM 1023 © 2011 Watts