You are on page 1of 6

Arc Flash Analysis: Investigation, Simulation and

Sensitive Parameter Exploration


Saeed Mohajeryami, Mahmoodreza Arefi, Zia Salami, IEEE senior member
Energy Production and Infrastructure Center (EPIC)
Electrical and Computer Engineering Department
University of North Carolina at Charlotte
Charlotte, NC, USA
Email: {smohajer, marefi, zsalami}@uncc.edu

Abstract—This paper conducts an investigation on the sen- Lee, who is widely considered the pioneer of electrical
sitivity of incident energy to critical arc flash parameters. In arc flash, in his seminal work [1], quantified the potential
order to perform such task, the authors explore the causes of burn hazards and educated personnel about the safety im-
arc flash by presenting the underlying concepts associated with
short-circuit fault analysis, and use these concepts to model and plications. Two more notable works following [1], which
simulate arc flash scenarios by employing IEEE 1584 standard. provided significant conclusions involving arcing faults were
An electrical system representative of a small industrial plant [3] and [4]. The authors in [3] determined the incident energy
is modeled and simulated using ETAP software. Then, arc flash at various distances from an arcing fault, which was the
analyses are performed on the system and the effect of incident first discussion on the directional effect of an arc within an
energy on various parameters is presented and discussed. The
results of this work could inform field personnel of the concepts enclosure. Also, in [4], the authors defined incident energy in
and sensitive parameters associated with arc flash analyses with regards to the fault duty and explored the variables required to
the intention of allowing them to quickly and safely recognize obtain this measurable value. It is from this work that much
methods for incident energy mitigation. of the 2000 Edition of the National Fire Protection Agency
Index Terms—Arc flash; sensitivity analysis; incident energy (NFPA) entitled ”Standard for Electrical Safety Requirements
reduction, fault clearing time, ETAP
for Employee Workplaces,” which is considered as one of the
primary governing industry standards for arc flash safety, was
I. I NTRODUCTION
developed. These papers, also, provided the foundation for
Electrical workers are exposed to arc flash hazards that re- further research that resulted in the development of another
quire equipment be de-energized during maintenance periods. primary governing industry standard IEEE Standard 1584-
This contributes to a significant loss of system functionality 2002, entitled ”IEEE Guide for Performing Arc-Flash Hazard
resulting in costly outages. Industry standards and health and Calculations” [5]. This standard, which is employed in this
safety regulations require the implementation of arc flash paper, focuses on calculation methods for determining arc fault
analyses on electrical equipment; however, the standards are currents, arc flash hazard marking, arc in enclosures and arc
often equivocal in terminology and difficult to determine when in open air, and provides for selection of personal protective
to appropriately apply. Arc flash analyses require the use of equipment.
various parameters combined in complex calculations. These In general, arc-flash studies could be classified into four
exhaustive procedures make it nearly impossible to perform groups: understanding of arc-flash hazards [6], [7], arc-flash
an accurate arc flash assessment in the field. Qualified field calculations [8], personnel and equipment protection [9], [10]
personnel need to understand the contributing factors of an arc and reduction of incident energy [11], [12].
flash and available retrofit methods for reducing the associated According to these categories, a major concern is how
incident energy. to decrease the amount of incident energy and bring it to
An arc flash is a rapid release of energy due to an arcing an acceptable level. Therefore, it is crucial to study the
fault caused by a short-circuit between two energized conduc- relationship between incident energy and system parameters.
tors. The electrical arc that occurs between these energized Although several researches have been carried out to conduct
conductors is, with exception to the laser, the hottest known such study, these works fail to address the incident energy’s
substance on earth. The arc can reach temperatures up to and sensitivity to adjusted parameters.
beyond 20,000 K, which is approximately four times as hot as This paper; therefore, attempts to determine the sensitivity
the sun’s surface [1] . During an arc flash, injuries might hap- of incident energy to critical arc flash parameters. In order to
pen from inhaled gases, blinding light, flying shrapnel, shock perform such task, the authors explore the causes of arc flash
waves and thermal radiation [2]. Besides, the arc flash could by presenting the underlying concepts associated with short-
cause severe damages to equipment by releasing substantial circuit fault analysis, and use these concepts to model and
amount of undesirable energy. Consequently, it is critical to simulate an arc flash scenario, representative of the potential
study this phenomenon to avoid the aforementioned problems. danger in a power plant.
The organization of this paper is as follows. Section II Converting from normalized energy provides the following
presents a model for calculation of arcing current and incident t 610x
energy. Then, in section III, an electrical system representative E = 4.184Cf En ( )( ) (4)
0.2 Dx
of a small industrial plant is modeled and simulated using Where:
ETAP software. Afterwards, in section IV, several sensitive E is the incident energy (J/cm2 );
arc flash parameters are defined, modeled and examined, and Cf is the calculation factor of 1.0 for voltages above 1kV
the results are provided. Section V closes the paper by drawing and is 1.5 for voltages at or below 1 kV;
conclusions. t is the arcing time (seconds);
x is the distance exponent;
II. E MPRICALLY DERIVED MODEL FOR ARCING CURRENT D is the distance from the possible arc point
AND INCIDENT ENERGY CALCULATIONS to the person (mm).
In IEEE’s 1584-2002 standard, an empirically derived III. I MPLEMENTATION
model for determining arcing current and incident energy is
A. Modeling
introduced. According to the standard, the model is intended
for applications where faults will escalate to three-phase [8]. To account for various industry configurations, a system that
In order to calculate the incident energy released by arc include a wide range of characteristics is modeled in ETAP
flash, it is necessary to compute three-phase arcing current. software. The system is supplied by the utility through a 23 kV
For system with voltages under 1000 V, (1) is used to calculate transmission system. The maximum and minimum available
the arcing current. short-circuit current supplied by the utility is defined as 12.5
kA and 7.4 kA, respectively, with an X/R ratio of 6.2 and 5.33,
log(Ia ) = K + 0.662 log(Ibf ) + 0.0966V + 0.000526G respectively. The system is fed through a delta-wye 250 MVA
(1)
+0.5588V (log(Ibf )) − 0.00304(log(Ibf )) step-down transformer supplying a 4.16 kV switchgear. The
switchgear bus (SWGR) feeds a 600 V Motor Control Center
Where: (MCC) through a delta-wye, 1000 kVA transformer, which
Ia is the arcing current (kA); in turn supplies a 208 V distribution power panel through a
K is -0.153 for open conurations (no enclosure) and delta-wye, 500 kVA transformer. The single-line diagram of
is -0.097 for box configurations (enclosed the system is shown in Fig.1.
equipment);
I bf is the bolted fault current for three-phase faults (kA);
V is the system voltage (kV);
G is the gap between conductors (mm).
However, for system with voltages of 1000 V and higher,
there is no distinction between open and box configurations
and (2) is used to calculate the arcing current.

log(Ia ) = 0.00402 + 0.983 log(Ibf ) (2)

For both voltage cases, it is required to calculate a second


arcing current that is equal to 85% of the first arc duration.
Variations in the arcing current and the required time for the
upstream overcurrent device to open, are accounted for by this
second arc duration. The incident energy is then calculated
using both arc durations; the higher energy of the two is used.
Once the arcing current is determined, the incident energy
could be found by (3).

log(En ) = K1 + K2 + 1.081log(Ia ) + 0.0011G (3)

Where:
En is the arcing current (kA);
K1 is -0.792 for open configurations (no enclosure) and
is -0.555 for box configurations (enclosed
equipment);
K2 is 0 for open configurations (no enclosure) and
is -0.113 for box configurations (enclosed
equipment);
G is the gap between conductors (mm). Fig. 1: Single line diagram of the test system
B. Simulation • The time (in seconds) required to clear the arcing current
The test system is modeled with system parameters accord- (t);
ing to IEEE 1584 and short-circuit simulation is performed • The available short-circuit current (in kA) provided by
for the maximum and minimum available short-circuit values the utility(isc).
from the utility. Using the bolted fault current (IBF) values, the To gain a consistent comparison of sensitivity, each param-
arcing current (IA) and incident energy (E) were determined. eter’s base value is adjusted by the same ratio: one-fourth,
The results are provided in Table I and II for maximum and one-half, twice, quadruple, and octuplet. In the following
minimum utility Short-Circuit Current, respectively. subsections the sensitivity of incident energy to four critical
It is worth mentioning that in the arc flash analysis, Up- arc flash parameters is examined and the results are provided.
stream Over Current Protection Devices (OCPD) that did not
clear the arcing current in less than two seconds (120 cycles) A. Incident energy vs. distance from energized equipment
were manually fixed to two seconds in accordance with IEEE
At each bus, the base distance from a worker to a live
1584.
part, 36 inches for the SWGR and 18 inches for all other
IV. R ESULTS AND DISCUSSIONS buses, is adjusted and simulated. With all other parameters
In this section, one at a time, incident energy parameters are held constant, the resulting incident energy for variations in
adjusted and an arc flash analysis is performed while holding the working distance at each bus is provided in Table III.
all other contributing factors constant. The parameter sensitiv- Moreover, for illustration purpose, the results at bus 7 and
ity is determined by comparing the resulting incident energy the SWGR are shown in Fig. 2.
values to those of the base case. By isolating incident energy As the distance from an exposed electrical part to a worker
parameters, it is possible to determine the most significant grew smaller, the incident energy drastically increased; as
factors in reducing the potential hazard of work performed the distance grew larger, the incident energy decreased. This
on energized electrical equipment. In this paper, the following showed an inverse relationship between incident energy and
four contributing arc flash parameters are investigated. distance. The incident energy at the varying distance parame-
ters for the entire system is shown in Table III.
• The distance (in inches) from an electrical component to
the worker performing work (D);
• The gap between conductors (in mm) of the electrical
equipment where an arc can occur (G);

TABLE I: SIMULATED SHORT-CIRCUIT BOLTED FAULT CURRENT,


ARCING CURRENT AND INCIDENT ENERGY FOR MAXIMUM
UTILITY SHORT-CIRCUIT CURRENT
Ibf Simulated IA Simulated E Simulated
Bus
(kA) (kA) (cal/cm2 )
SWGR 41.54 39.349 0.495
Bus 3 41.19 38.102 1.011
Bus 4 31.09 29.604 0.772
Bus 5 15.65 12.937 94.387
MCC 14.46 11.04 73.909
Bus 7 14.10 11.706 0.995
Bus 8 14.19 11.663 0.992
Bus 9 13.44 11.778 1.002
Bus 10 13.40 11.18 0.95
PWR PNL 6.10 3.19 18.83 Fig. 2: Incident energy vs. distance from energized equipment at bus 7 and
Bus 13 2.03 1.43 0.07 the SWGR

TABLE II: SIMULATED SHORT-CIRCUIT BOLTED FAULT CURRENT, TABLE III: SIMULATED BUS INCIDENT ENERGY VALUES AT
ARCING CURRENT AND INCIDENT ENERGY FOR MINIMUM VARYING DISTANCES FROM ELECTRICAL EQUIPMENT
UTILITY SHORT-CIRCUIT CURRENT
Ibf Simulated IA Simulated E Simulated Incident Energy (cal/cm2 )
Bus 1 1
(kA) (kA) (cal/cm2 ) Bus ID 4
Base 2
Base Base 2 Base 4 Base 8 Base
SWGR 29.627 28.229 0.348 SWGR 1.9 1.0 0.5 0.3 0.1 0.1
Bus 3 28.976 27.619 0.714 Bus 3 16.2 4.0 1.0 0.3 0.1 0.0
Bus 4 24.13 23.072 0.589 Bus 4 12.3 3.1 0.8 0.2 0.0 0.0
Bus 5 15.304 12.664 92.234 Bus 5 1510.2 377.5 94.4 23.6 5.9 1.5
MCC 14.166 10.833 72.409 MCC 718.9 230.5 73.9 23.7 7.6 2.4
Bus 7 13.817 11.483 0.975 Bus 7 15.9 4.0 1.0 0.2 0.1 0.0
Bus 8 13.767 11.443 0.971 Bus 8 15.9 4.0 1.0 0.2 0.1 0.0
Bus 9 13.905 11.552 0.981 Bus 9 16.0 4.0 1.0 0.3 0.1 0.0
Bus 10 12.564 10.483 0.93 Bus 10 15.2 3.8 1.0 0.2 0.1 0.0
PWR PNL 5.966 3.157 18.79 PWR PNL 183.1 58.7 18.8 6.0 1.9 0.6
Bus 13 2.057 1.45 0.07 Bus 13 1.1 0.3 0.067 0.3 0.0 0.0
B. Incident energy vs. gap between conductor width Furthermore, it is determined that for bus voltage levels
above 1 kV the incident energy has a direct relationship to
The base case gap width between phase conductors is
the gap width; nevertheless, for voltages below 1 kV the
102 mm at the SWGR bus, 25 mm at the MCC bus, 15
incident energy has an inverse relationship to the gap width.
mm at the PWR PNL bus and 13 mm at all other buses.
The exception to this is the 208 V Bus 13, whose incident
These values are adjusted by the particular ratios and the
energy has a direct relationship to the gap width despite its
resultant incident energy at each bus is presented in Table
voltage level below 1 kV.
IV. Besides, for illustration purpose, the results at bus 7 and
the SWGR are shown in Fig. 3. Fig. 3 shows the variance C. Incident energy vs. fault clearing time
in incident energy at the SWGR and Bus 7 by increasing the
gap between conductors; however, it is very unlikely that a The upstream Fault Clearing Time (FCT) of OCPD for each
conductor gap’s value would range between 200 800 mm bus is adjusted from the base case. The type of Protective
(2*Base G, 4*Base G and 8*Base G for base gap of 102 mm Devices (PD) and FCT base values for all buses are listed in
at the SWGR). Additionally, it should be noted that several of Table V.
the ranges tested are outside of those recommended by IEEE The incident energy at each bus for the varying FCT ratios
1584 ”Equipment and Voltage Class Factors” [8], implying is shown in Table VI.
that IEEE 1584’s empirical model can no longer be used to Moreover, for illustration purpose, the effect on incident
accurately determine arc flash results. energy by varying the FCT at Bus 5, the MCC bus and the
The relationship of incident energy and the gap between PWR PNL bus’ upstream OCPD is shown in Fig.4.
conductors is not consistent for all buses. As a matter of As the time increases for each PD to clear its bus’ arcing
fact, for the SWGR bus, Bus 3, Bus 4 and Bus 13, the fault, the incident energy increases showing a direct relation-
incident energy has a direct relationship with the gap width; ship. To accurately model the incident energy’s sensitivity to
as the gap increased or decreased, the incident energy reacts time, the FCT is was not fixed to two seconds for the base case,
similarly. However, for all other buses, the incident energy has as this would not have shown time’s effect on incident energy
an inverse relationship with the gap width; as the gap increased for arcing faults lasting longer than 120 cycles. From Table V,
or decreased, the incident energy reacts inversely. it is understood that Bus 4, Bus 5 and the MCC bus showed
a lack of coordination in the system as their upstream OCPDs
did not clear the arcing fault, but instead the PD of one, two
and three buses away cleared the fault, respectively. Bus 4 had
a hazard category of 0; thus, its coordination was not critical;
however, Bus 5, the MCC bus and the PWR PNL bus, each

TABLE V: TYPE OF PD AND FCT BASE VALUES FOR ALL BUSES


Bus Type Protecting device FCT Base Value
SWGR Fuse 1 0.01 seconds
Bus 3 Fuse 3 0.01 seconds
Bus 4 Fuse 1 0.01 seconds
Bus 5 Fuse 1 2.12 seconds
MCC Fuse 1 4.39 seconds
Bus 7 CB 7 0.023 seconds
Bus 8 CB 8 0.023 seconds
Bus 9 CB 9 0.023 seconds
Bus 10 CB 10 0.023 seconds
PWR PNL CB 10 38.066 seconds
Fig. 3: Incident energy vs. gap between conductor width at SWGR and bus 7 Bus 13 CB 13 0.01 seconds

TABLE IV: SIMULATED BUS INCIDENT ENERGY VALUES AT TABLE VI: SIMULATED BUS INCIDENT ENERGY VALUES AT
VARYING GAP BETWEEN CONDUCTOR WIDTHS VARIOUS UPSTREAM OCPD FCTS

Incident Energy (cal/cm2 ) Incident Energy (cal/cm2 )


1 1 1 1
Bus ID 4
Base 2
Base Base 2 Base 4 Base 8 Base Bus ID 4
Base 2
Base Base 2 Base 4 Base 8 Base
SWGR 0.4 0.4 0.5 0.6 1.1 3.0 SWGR 0.1 0.2 0.5 1.0 2.0 4.0
Bus 3 1.0 1.0 1.0 1.0 1.1 1.3 Bus 3 0.3 0.5 1.0 2.0 4.0 8.1
Bus 4 0.8 0.8 0.8 0.8 0.9 1.0 Bus 4 0.2 0.4 0.8 1.5 3.1 6.2
Bus 5 99.4 97.4 94.4 88.2 77.1 58.8 Bus 5 25.0 50.0 83.6 200.1 400.2 800.4
MCC 81.2 78.4 73.9 65.3 51.0 31.2 MCC 40.6 79.7 133.8 324.5 648.9 1297.8
Bus 7 1.0 1.0 1.0 0.9 0.8 0.6 Bus 7 0.3 0.5 1.0 1.9 3.9 7.8
Bus 8 1.0 1.0 1.0 0.9 0.8 0.6 Bus 8 0.3 0.5 1.0 1.9 3.9 7.8
Bus 9 1.1 1.0 1.0 0.9 0.8 0.6 Bus 9 0.3 0.5 1.0 2.0 3.9 7.8
Bus 10 1.0 1.0 1.0 0.9 0.8 0.6 Bus 10 0.2 0.5 1.0 1.9 3.7 7.4
PWR PNL 19.3 19.1 18.8 18.2 17.1 15.1 PWR PNL 89.6 235.0 300.6 716.6 1433.6 2866.2
Bus 13 0.065 0.066 0.067 0.073 0.074 0.076 Bus 13 0.0 0.0 0.067 0.1 0.2 0.4
Fig. 4: Incident Energy vs. FCT at Bus 5, the MCC and the PWR PN

had hazard categories greater than 4 implying that no work Fig. 5: Time-current characteristic curve of bus 5 and mcc protective devices
should be performed on them while energized. Each of these
three buses had FCTs greater than 120 cycles allowing them
to be fixed at two seconds. By performing this, the PWL PNL
bus’ hazard category is reduced to 3; Bus 5 and the MCC bus’
hazard categories remains greater than 4. The coordination of
these two bus’ PDs is shown in Fig. 5. The arcing current at
Bus 5 and the MCC bus, without the FCT fixed to two seconds,
was 11.0 kA and 9.38 kA, respectively which is shown in Fig.
6. These current values are 85% of the arcing current of their
corresponding buses and are used because of their increase on
the incident energy. The Time- Current Characteristics (TCC)
curve shows that for both of the arcing currents, approximately
9.38 kA and 11.0 kA, the system is not coordinated. For the
MCC bus’ arcing current, its protective device CB6, does not
fully open. As a result, the arcing current is not cleared and
travels upstream to the next PD. At this PD, Fuse 4, it is
apparent that there is no selectivity in coordination; Fuse 4
is equipped to handle the current from Bus 5 and the MCC Fig. 6: Selectively coordinated time-current characteristic curve of bus 5 and
MCC protective devices
bus, yet the lack of coordination shows Fuse 1 is set to clear
the faults before Fuse 4 has a chance; thus, removing current
from all downstream system devices.
D. Incident energy vs. available short circuit currents
A new thermal magnetic Circuit Breaker (CB) is used in
place of CB6. This PD has a much smaller continuous current With the coordination parameters set back to that of the base
as well as instantaneous current rating. As a result, the amount case, the maximum available short-circuit current provided by
of time required to clear the 9.38 kA arcing current on the the utility is adjusted from the base case of 12.5 kA, by the
MCC bus is reduced from 4.39 seconds by Fuse 1, to 0.021 defined ratios, and its effect on incident energy is shown in
seconds by the newly inserted CB’s instantaneous trip region, Table VII.
shown in Fig. IV. This FCT provides an incident energy that The available short-circuit current has a direct relationship
is highest for the initial arcing current, not 85% of the arcing to the incident energy. The increase of available short-circuit
current; thus, increasing the fault current at the PD from current provides a greater short-circuit current value on the
9.38 kA to 11.04 kA. The resulting incident energy reduces primary side of transformer 1 (XFMR1), which in turn pro-
the hazard category from greater than 4, to 0. Adjusting the vides greater short-circuit values throughout the system. This
Bussmann fuse settings of Fuse 4 from 600E to 150E ensures increase in short-circuit current increases the arcing current
the system is selectively coordinated. The 11.0 kA arcing which increases the FCT of PDs. As shown in Fig. 4 and
current at Bus 5 is cleared by its upstream OCPD, Fuse 4, presented in Table VI, the increase in FCT is directly propor-
in 0.349 seconds, as opposed to Fuse 1’s clearing time of tional to incident energy and thus, incident energy increases.
2.12 seconds. By appropriately coordinating the system, the Although incident energy is affected by available short-circuit
incident energy is reduced, lowering the hazard category at current, it typically is not a subject of consideration when
Bus 5 to level 3. attempting to mitigate the hazards of an arc flash. The cus-
TABLE VII: SIMULATED BUS INCIDENT ENERGY VALUES AT
VARIOUS UTILITY AVAILABLE SHORT-CIRCUIT CURRENTS to combine their findings and address some potential concerns.
Preparing a single standard that covers all scenarios and
Incident Energy (cal/cm2 ) avoids confusion should be the vanguard of technical research
Bus ID 1
Base 1
Base Base 2 Base 4 Base 8 Base regarding arc flash analyses.
4 2
SWGR 0.2 0.3 0.5 0.7 0.9 1.0 There is still much debate to the over/under conservativeness
Bus 3 0.3 0.6 1.0 1.4 1.7 1.9 of IEEE’s 1584 Std. due to its empirical data. The empirical
Bus 4 0.3 0.5 0.8 1.0 1.1 1.2
Bus 5 85.6 91.3 94.4 96.0 96.8 97.3 model covers only the range of system characteristics tested
MCC 67.8 71.8 73.9 75.0 75.6 75.9 in IEEE’s laboratories, requiring the use of other standards
Bus 7 0.9 1.0 1.0 1.0 1.0 1.0 for characteristics outside the tested ranges. A deeper analysis
Bus 8 0.9 1.0 1.0 1.0 1.0 1.0
Bus 9 0.9 1.0 1.0 1.0 1.0 1.0 of the underlying arc flash properties for a wider range of
Bus 10 0.9 0.9 1.0 1.0 1.0 1.0 conditions may prove in the development of not only a more
PWR PNL 18.7 18.8 18.8 18.9 18.9 18.9 accurate empirical method, but also a more accurate theoretical
Bus 13 0.1 0.1 0.067 0.1 0.1 0.1
method.
Another area of concern arises over the current method
tomer usually cannot change the amount of available current of analyzing single-phase arcing faults. The IEEE 1584 Std.
that the utility provides; however, it is possible to reduce the treats single-phase faults as three-phase faults as it states
available current through current limiting devices that increase this is a conservative approach, assuming single-phase faults
the system impedance. For each parameter analyzed, only the eventually escalate to three-phase. Further research into single-
maximum available short-circuit current is used. It is inferred phase arcing faults may prove the over conservativeness of this
that because of the linear nature of the best-fit line, as well as assumption, or in specific circumstances, discredit it altogether.
the linearity of the multiplying parameter ratios, any effect a The economic concerns resulting from an arc flash incident are
parameter has on its relationship to incident energy at max- second only to those of personal safety. Continuous research of
imum available short-circuit current, it would similarly have this topic will provide greater system efficiency, reduce costs
on its relationship to incident energy at minimum available related to equipment failure and outages, and provide a safer
short-circuit current. working environment for field personnel.
ACKNOWLEDGMENT
V. C ONCLUSION AND RECOMMENDATION
The authors would like to thank Mr. Daniel R. Potton for
This paper investigated the underlying concepts of an arc his invaluable contributions to this work.
flash and presented an approach for performing the analysis on
a desired system using t the IEEE 1584 standard. To carry out R EFERENCES
such task, a system representative of an electrical plant was [1] R. H. Lee, ”The Other Electrical Hazard: Electrical Arc Blast Burns,”
modeled and simulated and the sensitivity of incident energy to IEEE Transactions on Industry Applications, vol. IA-18, no. 3, May/June
four critical arc flash parameters was determined. The results 1982, pp. 246-251.
[2] D. R. Doan, R. A. Sweigart, ”A Summary of Arc Flash Energy Calcula-
are provided as follows. tions,” IEEE Transactions on Industry Applications, vol. 39, no. 4, July
• An arc flash’s incident energy is most sensitive to the 2003, pp. 1200-1204.
[3] R. L. Doughty, et al., ”Testing Update on Protective Clothing and
amount of time required for a protective device to clear Equipment for Electric Arc Exposure,” IEEE conference on Petroleum
the arcing current during a fault. and Chemical Industry, 1997.
[4] R. L. Doughty, et al., ”Predicting Incident Energy to Better Manage
• The upstream OCPD’s FCT should be the primary the Electric Arc Hazard on 600 V Power Distribution Systems,” IEEE
retrofitting focus of an engineer trying to mitigate the conference on Petroleum and Chemical Industry, 1998.
hazard category of energized equipment. [5] C. Inshaw, R. A. Wilson, ”Arc Flash Hazard Analysis Mitigation,” IEEE
PES 58th Annual Conference for Protective Relay Engineers, 2005.
• By increasing the distance from equipment, incident [6] K. Lippert, et al., ”Understanding Arc Flash Hazards,” Record of the 2004
energy reduces. Annual Technical conference on Pulp and Paper Industry, July 2004
[7] R.A. Jones, et al., ”Staged Tests Increase Awareness of Arc-Flash Hazards
• For bus voltage levels above 1 kV the incident energy in Electrical Equipment,” Petroleum and Chemical Industry Conference,
has a direct relationship to the gap width. Record of 44th IEEE Annual Conference of Incorporated Industry Ap-
plications Society, Banff, Alta, 15-17 Sep. 1997.
• For voltages below 1 kV the incident energy has an [8] IEEE Std. 1584-2002, IEEE Guide for Performing Arc Flash Hazard
inverse relationship to the gap width. Calculations, New York, NY, 2002.
[9] A. Holliday, J. Kay, ”IR Sight Glasses Protect Against Arc-Flash Expo-
• As the time increases for each PD to clear fault arcing sure,” IEEE Industry Applications Magazine, Vol. 13, Issue 3, pp. 5968,
fault, the incident energy increases showing a direct May-June 2007.
relationship. [10] W. Lee, et al., ”Arc flash and Electrical Safety,” 66th Annual Conference
of Protective Relay Engineers, College Station, TX ,8-11 April 2013.
• By increasing utility available short-circuit current, inci- [11] M. D’Mello, et al., ”Arc Flash Energy ReductionCase Studies,” IEEE
dent energy increases. Transactions on Industry Applications, Vol.49 , Issue 3, pp. 11981204,
March 2013.
Arc flash analyses are in an adaptive stage requiring contin- [12] G. Gregory, K. Lippert, ”Applying Low-Voltage Circuit Breakers To
uous updating from research and laboratory experiments. The Limit Arc Flash Energy,” Record of 2007 Annual Pulp and Paper Industry
Technical Conference, Williamsburg, VA, 2007.
IEEE and NFPA are currently preparing an updated standard

You might also like