Enumerate all major equipments, tanks and vessels in Raw/Sanitary/fire water distribution facilities in utilities.
Give its service, rating and capacity.
D-1020: Hydro-pneumatic Drum, sanitary water surge drum to even-out fluctuations in pressure due to varying
demand
Capacity: 1,981mm x 4,877 mm
Enumerate all major equipments, tanks and vessels in Boiler water treatment plant and distribution facilities in
utilities. Give its service, rating and capacity
P-1005 A/B/C/D/E/F
Service: BFW pumps to SG-1/2/3/4/5
Capacity: 69 m3/h, Diff. Head: 539,496 mm
P-1005 G/H
Service: BFW pump to GODU/PFCC/CCR/SRU/NHT-2/LPG-2
Capacity: 104 m3/h, Pressure: 5854 kPa
P-1005 I/J/K
Service: BFW pumps to SG-6/7/8
Capacity: 114.5 m3/h, Pressure:5072 kPa
P-1007 A/B
Service: BFW pump to PWF/Hydrogen Unit
Capacity: 44.26 m3/h, Diff. Head– 225,552 mm
P-1068 A/B
Service: BFW pump to MEROX
Capacity: 74.91 m3/h, Diff. Head – 83,820 mm
E-1005
Service: SG-1001/2/3 BFW heater
Capacity: Surface area: 93.84 m2
E-1012A/B
Service: SG-1004/5 BFW heater
Capacity: Surface area: 16m2
E-1013
Service: SG-1006/7 BFW heater
Capacity: Surface area: 83.23 m2
E-1040
Service: SG-1008 BFW heater
Capacity: Surface area: 95m2
E-1080
Service: treated water heater
Capacity: Surface area: 327.114 m2
P-1012
Service: Phosphate injection pump
Capacity: P-1012 A/B/C:0.136 m3/h, P-1012D/E: 1.54 m3/h, P-1012F/G/H/I: 0.002 m3/h
P-1081A/B
Service: Nexguard injection pump
P-1023A/B/C
Service: Eliminox injection pump
P-1024A/B
Service: Triact/Neutralizing Amine injection pump
C-1001A/B
Service: Instrument Air for Utilities area
Capacity: 610 SM3/Hr, Discharge Pressure: 689 KPa (g)
D-1011
Service: C-1001A/B Instrument Air receiver
Capacity: 4.3M3
D-1034
Service: C-1001A/B Instrument Air receiver
Capacity: 5M3
Dr-1001
Service: Instrument Air Drier
Capacity: 127 SM3/Hr
Dr-1005
Service: Instrument Air Drier
Capacity: 365 SM3/Hr
Fil-1003
Service: Instrument Air filter
Capacity: 610 SM3/Hr
C-1006A/B
Service: Instrument Air for process area
Capacity: 4579 SM3/Hr, Discharge Pressure: 862 KPa (g)
D-1025
Service: Instrument Air Receiver
Capacity: 6.6 M3
D-1033
Service: Instrument Air Receiver
Capacity: 26 M3
D-1035
Service: Instrument Air Receiver
Capacity: 2222 M3
Dr-1007
Service: Instrument Air Drier
Capacity: 882 SM3/Hr
Dr-1009
Service: Instrument Air Drier
Capacity: 2222 SM3/Hr
Dr-1010
Service: Instrument Air Drier
Capacity:
Fil-1002
Service: Instrument Air filter
Capacity: 2866 SM3/Hr
C-1003
Service: Plant Air Compressor
Capacity: 2544 SM3/Hr, Discharge Pressure: 862 KPa (g)
C-1005A/B
Service: Plant Air Compressor
Capacity: 2290 SM3/Hr, Discharge Pressure: 551 KPa (g)
D-1032
Service: Plant Air Receiver
Capacity: 4.2 M3
SG-1001/2/3
Service: Steam Generator (Combustion Engineering Fixed with Tangential type burners)
Capacity: Max Continuous Rating (45,300 Kg/Hr); Design Pressure (5171 KPa (g))
Auxiliary: Air Preheater, Forced Draft Fan (steam driven), Induced Draft Fan
SG-1004/5
Service: Steam Generator (Mitsubishi built boiler with frontal fired single burner box)
Capacity: Max Continuous Rating (61,155 Kg/Hr); Design Pressure (5171 KPa (g))
Auxiliary: Forced Draft Fan (steam driven), Economizer
SG-1006/7/8
Service: Steam Generator (Mitsubishi built boiler with frontal fired upper and lower box)
Capacity: Max Continuous Rating (68,200 Kg/Hr); Design Pressure (5171 KPa (g))
Auxiliary: Forced Draft Fan, Economizer
D-1001
Service: SG-1001/2/3 continuous B/D flash drum
Capacity: 11,959 Kg/Hr; Design Pressure: 1,206 KPa (g); Design Temperature: 277°C
D-1050
Service: SG-1004/5 continuous B/D flash drum
Capacity: 11,959 Kg/Hr; Design Pressure: 1,206 KPa (g); Design Temperature: 277°C
D-1040
Service: SG-1006/7/8 continuous B/D flash drum
Capacity: Design Pressure: 1172 KPa (g); Design Temperature: 246°C
E-1008
Service: SG-1001, SG-1002 & SG-1003 Continuous Blowdown/condensate exchanger
Capacity: Surface Area (34.96 m2)
E-1026
Service: Continuous Blowdown/condensate exchanger
Capacity: Surface Area (27 m2)
E-1008
Service: SG-1006/7/8 Continuous Blowdown/Tg-1004/5 cold condensate exchanger
Capacity: Duty (1800MJ/h), Surface Area (17.9 m2)
D-1007
Service: Condensate Storage Drum
Capacity: 3048 mm x 2438 mm
P-1008 A/B
Service: Desuperheater Pumps for MPS
Capacity: 12.5 m3/h; Pressure: 1131 KPa (g)
P-1062A/B
Service: Desuperheater Pumps for Sg-1004/5/6/7/8 SH steam and Process station
Capacity: 8.172 m3/h, pressure: 5318 KPa (g)
P-1009
Service: Spare F.O. pump
Capacity: 22 m3/h; Pressure: 1103 KPa (g)
P-1010A/B
Service: F.O. pump to Process units
Capacity: 21 m3/h; Pressure: 827 KPa (g)
P-1010C/D
Service: F.O. pump to Sg-1001/2/3/4/5
Capacity: 21 m3/h; Pressure: 1158 KPa (g)
P-1010E/F
Service: F.O. pump to Sg-1006/7/8
Capacity: 20 m3/h; Pressure: 1245 KPa (g)
Vessels
D-1008/9
Service: F.O. Drum for Boilers and Process Units
Capacity: 317,974 Liters
D-1021A
Service: F.G. Knock out Drum
Capacity: Pressure: 517 KPa (g)
D-1021B
Service: F.G. Knock out Drum
Capacity: Pressure: 518KPa (g)
E-1006
Service: Sg-1001/2/3/4/5 F.O. heater
Capacity: Heating Surface Area: 107 m2
E-1007
Service: Process units F.O. heater
Capacity: Heating Surface Area: 107 m2
E-1010
Service: Sg-1006/7/8 F.O. heater
Capacity: Heating Surface Area: 268 m2
Draw a sketch of the Following indicating flow path and label equipment:
33.1 Fuel oil facilities (include receive and transfer lines from process area to utilities)
33.2 Boilers pilot gas/fuel oil/ fuel gas distribution
Tk-702, Tk-703
Service: 25° Baume Caustic Storage tank
Capacity: 158,987 Liters
Tk-704
Service: Odorous Spent Caustic Storage tank
Capacity: 1,033,415 Liters
Tk-2901
Service: Non- Odorous Spent Caustic Storage tank
Capacity: Liters
P-1019
Service: Circulation pump
Capacity: 54 m3/h
P-1020A/B
Service: Fresh Caustic Transfer Pump
Capacity: 11 m3/h
TG-1001/2/3/4/5
Service: Turbine driven power generator
Capacity: TG-1001/2: 5000kw, Worthington Turbine: 3600RPM, 1 Curtis 16 rateau, 3000kw straight condensing
Generator: 2 poles, 60 Hz, 3 phase, 4160V, 3600RPM
TG-1003: 5360kw, Elliot Turbine: 5630RPM, 8 rateau, 4300kw straight condensing,
Generator: 4 poles, 60 Hz, 3 phase, 4160V, 1800RPM
TG-1004/5: 7000kw, Elliot Turbine: 6272RPM, 8 stages, 5000kw straight condensing,
Generator: 4 poles, 60 Hz, 3 phase, 4160V, 1800RPM
E-1001/2/3(22,730kg/hr)/4/5
Service: TG-1/2/3/4/5 exhaust surface condenser
D-1003/4/5/44/45
Service: TG-1/2/3/4/5 condensate receiver
Draw a sketch of the Following indicating flow path and label equipment:
43.1 TG’s automatic gland seal and leak off system
43.2 TG’s Lube oil system.