You are on page 1of 2

CERT

EN ISO 9001
no. 16 100 0254
STANDARD FEATURES
Introduction
The AICOOL FD Evaporator Unit is special engineered to match latest requirements in medium commercial and light
industrial application. These series offer a generous a wide range of cooling capacity from 30 up to 750 MBH.

Using high quality components with international standard ISO, CE, GS, TUV, UL etc., FD series ensure a reliable heavy

CHILLED WATER duty better efficiency unit in it's class. Compactness, easy access for installation and maintenance, heavy gauge generous
material are the based characters of the its superior design.

The FD series are designed simple construction form. The compact design of the units optimize space for shipment and

INDOOR UNIT require only minimal installation space. Multiple Fan of bigger airflow capacity give the flexibility in capacity requirement.

Performance The cooling capacity is rated according to ARI standard, using Water (Inlet Temp 6.7 C and
Outlet Temp 12.2 oC).
o

Easy Maintenance The service-oriented design concept provides easy access to the Air Filter, by removing the filter
side plate.
30.000 Btu/hr ... Cabinet The cabinet is made of heavy gauge galvanized steel, powder coating finished, providing
optimum corrosion resistance.
750.000 Btu/hr Blower Direct driven Centrifugal Fan up to 4,000 CFM for single Fan and can be combine for dual Fan,
more efficient (no slip, no adjustment pulley and Belt, less of moving part as bearing), more quite
and reduce of pulsation. Provide sufficient external static pressure at minimal energy
consumption.
Coils Air standard Evaporator coils for air conditioning have a generous 12 FPI, large enough to
prevent from dust blocking of the Fins, are made of plain tube seamless copper tube with 3/8”
diameter, arranged in staggered pattern mechanically expanded into aluminum fins and leakage
tested by 35 bars.
All Evaporator coils are designed with such large face area, to prevent from carry over of
condensation water into the air duct system.
Drain Pan Full area Drain pan are Larger drain pan double skinned insulated of 10 mm thick PE Foam with
3
0.12 gr/mm density.
Air Filter High performance filter media about durable thermal bonded filters (100% polyester), free of
silicon, can be cleaned by beating or washing.

OPTIONAL FEATURES
® Higher grade air filter up to H15 class (Hepa filter) ® Two/Three Way valve motorized for chilled water control
® Higher external static pressure ® Starter Control panel for operating system
® Epoxy coated aluminum fins or copper fins. ® Variable Speed Drive
® Double skinned with up to 50 mm PE insulation. ® Aluminum grille and plenum

FD
Water, Glycol
ADE IN
M
BEST
PERFORMANCE

N
I

DO I
NES

Every Cooling Solution... We Have It AICOOL reserves the right to change in specifications without prior notice
SPECIFICATION DATA
CHILLED WATER INDOOR UNIT
Model FD / __ / CW Unit 032 042 052 062 077 102 127 152 202 252 302 352 402 452 502 602 752

Application Chilled Water


Btu/h 30,000 40,000 50,000 60,000 75,000 100,000 125,000 150,000 200,000 250,000 300,000 350,000 400,000 450,000 500,000 600,000 750,000
Total Cooling Capacity kW 8.8 11.7 14.6 17.6 22.0 29.3 36.6 43.9 58.6 73.2 87.9 102.5 117.2 131.8 146.5 175.7 219.7
TR 2.5 3.3 4.2 5.0 6.3 8.3 10.4 12.5 16.7 20.8 25.0 29.2 33.3 37.5 41.7 50.0 62.5
Btu/h 18,000 24,000 30,500 37,200 44,700 60,500 75,000 90,300 125,800 156,250 156,300 217,350 248,800 268,650 306,000 361,200 459,000
Sensible Cooling Capacity kW 5.3 7.0 8.9 10.9 13.1 17.7 22.0 26.4 36.8 45.8 45.8 63.7 72.9 78.7 89.6 105.8 134.4
TR 1.5 2.0 2.5 3.1 3.7 5.0 6.3 7.5 10.5 13.0 13.0 18.1 20.7 22.4 25.5 30.1 38.3
Chilled Water Flow m3/hr 1.5 2.0 2.0 2.5 3.8 5.0 5.3 7.6 10.2 12.7 12.6 14.8 16.8 18.9 21.0 30.2 31.5
Power Supply V/Ph/Hz 380 - 420 / 3 / 50
Inlet in 1 1 1 1 1 1 1/2 1 1/2 1 1/2 2 2 2 2 2 1/2 2 1/2 2 1/2 3 3
Pipe size
Outlet in 1 1 1 1 1 1 1/2 1 1/2 1 1/2 2 2 2 2 2 1/2 2 1/2 2 1/2 3 3
Type Finned & Tubes Coil (Aluminum Fins on Inner Grooved Copper Tubes)
Cooling
Rows 2 3 2 3 3 4 4 3 4 4 4 4 4 4 5 6 6
Coil
Fin Spacing fpi 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12 12
Type / Drive Forward Curved Centrifugal Fan / Direct Driven Forward Curved Centrifugal Fan / Belt Driven
Quantity 1 1 1 1 1 1 1 1 1 2 2 1 1 1 1 1 1
3
Evaporator m /hr 1,800 1,800 3,200 3,200 3,550 4,800 6,000 8,600 11,000 12,000 13,800 17,850 21,500 24,800 28,000 34,000 40,000
Air Flow
Fan cfm 1,059 1,059 1,882 1,882 2,088 2,824 3,529 5,059 6,471 7,059 8,118 10,500 12,647 14,588 16,471 20,000 23,529
Pa 150 150 185 185 275 275 275 300 300 300 400 300 400 400 400 350 400
External Static Pressure
in Wg 0.6 0.6 0.74 0.74 1.1 1.1 1.1 1.2 1.2 1.2 1.6 1.2 1.6 1.6 1.6 1.4 1.6
Type Squirrel Cage Induction

Evaporator Power Supply V/Ph/Hz 380 - 420 / 3 / 50


Motor Rated Load Ampere A 1.0 1.0 1.3 1.3 1.6 2.3 3.1 4.9 7.1 2 x 3.1 2 x 3.8 5.8 9.1 9.1 9.1 11.6 11.6
Rated Input Power W 250 250 370 370 550 800 1,100 1,800 3,000 2 x 1,100 2 x 1,500 4,000 5,500 5,500 5,500 7,500 7,500
Noise Level dB 56 56 60 60 64 67 67 68 68 68 68 70 70 70 70 70 70
Weight kg 67 70 88 92 116 146 180 181 254 302 349 389 437 463 509 580 683

DIMENSIONAL DATA
FD 032 - FD 302 FD 352 - FD 752 Model FD 032-042 052-062 077 102 127 152 202 252 302 352 402 452 502 602 752

A mm 900 1,350 1,400 1,400 1,700 1,700 2,000 2,200 2,200 2,400 2,400 2,400 2,400 2,400 2,400
B mm 700 730 830 950 1,030 1,030 1,030 1,065 1,065 1,996 2,094 2,094 2,158 2,158 2,310
C mm 510 510 590 635 730 730 840 840 950 1,230 1,230 1,380 1,380 1,780 1,780
D1 mm 286 313 345 338 398 398 479 398 435 629 698 698 775 775 874
D2 mm 298 321 340 378 460 460 520 460 491 629 698 698 775 775 874
E1 mm 370 370 440 495 570 570 670 670 770 1,020 1,020 1,170 1,170 1,570 1,570
E2 mm 800 1,250 1,300 1,300 1,600 1,600 1,900 2,100 2,100 2,300 2,300 2,300 2,300 2,300 2,300
F mm 1,030 1,480 1,530 1,530 1,830 1,830 2,130 2,330 2,330 2,352 2,352 2,352 2,352 2,352 2,352
G mm 1,100 1,550 1,600 1,600 1,900 1,900 2,200 2,400 2,400 2,400 2,400 2,400 2,400 2,400 2,400
H mm 440 465 540 660 740 740 740 755 755 1,948 2,046 2,046 2,110 2,110 2,263

FD/JUN09-R4
* Nominal Cooling Capacity Conditions : Air Inlet Condition 26.7°C / 51% RH and Chilled Water In Temp 6.7°C, Chilled Water Out Temp 12.2°C
We improve our products continuously, therefore we reserve the right to make modifications without prior notice.

You might also like