TEST REPORT FOR

SEL MOTOR PROTECTION SEL 710


RELAY-SEL 710
DATE: 21.06.2018

Project : SINGARENI THERMAL POWER PLANT, TELANGANA

Client : M/s STEAG ENEGY SERVICES PVT LTD

End Client : M/S SINGARENI

Panel Ref : PA FAN,PANELNO:04

Relay Make & Model : SEL-710

Serial No : 3140070050

CT & VT Ratio : 250/194A

1. Phase Over Current TOC – [ 51P] Non Directional Current (I) – 4XFLA A : TD- 0s ,FLA:0.776

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 3.104 3.104 0 0.031

Y-N 3.104 3.104 0 0.041

B-N 3.104 3.104 0 0.038

2. [51N ] Current (I) – 5A : Time Delay- 0 s

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 5 5 0 0.015

Y-N 5 5 0 0.019

B-N 5 5 0 0.024

3. JAM Current (I) – 2.5XFLA A ,Time Delay- 5 s FLA:0.776

PROTECTION ENGG M/S STEAG ENERGY SERVICE LTD

JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 1.94 1.94 5 4.98

Y-N 1.94 1.94 5 5.02

B-N 1.94 1.94 5 4.97

4. DIFFERENTIAL PROTECTION Current (I) – 0.1 A ,Time Delay- 0 s

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 0.1 0.1 0 0.025

Y-N 0.1 0.1 0 0.028

B-N 0.1 0.1 0 0.032

5. CURRENT IMBALANCE Current (I) – 10%A ,Time Delay- 5 s

Phase Set Current (A) Inj. Current(A) Actual Tripping Trip Time(s)
Time (s)
R-N 0.698 0.698 5 4.91

Y-N 0.698 0.698 5 5.04

B-N 0.698 0.698 5 5.07

6. UNDER VOLTAGE Voltage (I) – 0.5xVnm ,Time Delay- 2 s

Phase Sett Voltage (v) Inj. Voltage(v) Actual Tripping Trip Time(s)
Time (s)
PROTECTION ENGG M/S STEAG ENERGY SERVICE LTD

JAYAMKONDAN V MR.JEYAKUMAR
TEST REPORT FOR
SEL MOTOR PROTECTION SEL 710
RELAY-SEL 710
DATE: 21.06.2018

R-N 32 32 2 1.989

Y-N 32 32 2 2.02

B-N 32 32 2 2.01

7. THERMAL OVER LOAD

Phase Inj. Current(A) Trip Time(s)

R,Y,B 0.8 770

R,Y,B 0.9 430

R,Y,B 1.0 290

Check List:

1. LED Functions has been checked and found ok.


2. Relay operations has been found satisfied and fit for service.

PROTECTION ENGG M/S STEAG ENERGY SERVICE LTD

JAYAMKONDAN V MR.JEYAKUMAR