Lecture 3rd

Approximate Methods of
Distribution System Analysis (2)
Course Teacher:
Dr. Muhammad Mohsin Aman
Course Code:
EE-524
Course Title:
Electrical Power Distribution System Engineering -1
Venue:
Department of Electrical Engineering , NED University Karachi.
1

3rd Lecture’s Outline

Dr. Muhammad Mohsin Aman 1


8/18/2016

3rd Lecture’s Outline


� Distribution System Load Models
�Uniformly Distributed Loads
�Lumped Load models
� Load Models
� Uniformly Distributed Load Model
� Lumped Load Model
� Lumping Loads in Geometric Configurations
� Rectangular Configuration
� Triangular Configuration
3

Distribution of Loads

Dr. Muhammad Mohsin Aman 2


8/18/2016

Distribution of Loads
Two load models can be assumed for voltage drop calculations:
• Uniformly Distributed Loads
• Lumped Load models

Uniformly Distributed Loads


• Many times it can be assumed that loads are uniformly distributed along a line
where the line can be a three-phase, two-phase, or single-phase feeder or lateral.
This is certainly the case on single-phase laterals where the same rating
transformers are spaced uniformly over the length of the lateral.
• When the loads are uniformly distributed, it is not necessary to model each load
in order to determine the total voltage drop from the source end to the last load.
• Figure 3.6 shows a generalized line with n uniformly distributed loads.

Dr. Muhammad Mohsin Aman 3


8/18/2016

Uniformly Distributed Loads


Voltage Drop
• Figure 3.6 shows n uniformly spaced loads dx miles apart. The loads are all equal
and will be treated as constant current loads with a value of di. The total current
into the feeder is IT.
• It is desired to determine the total voltage drop from the source node (S) to the
last node n.

Uniformly Distributed Loads


Voltage Drop (cont..)
Let

Dr. Muhammad Mohsin Aman 4


8/18/2016

Uniformly Distributed Loads


Voltage Drop (cont..)
Let

Uniformly Distributed Loads


Voltage Drop (cont..)
Let

10

Dr. Muhammad Mohsin Aman 5


8/18/2016

Uniformly Distributed Loads


Voltage Drop (cont..)
Let

11

Uniformly Distributed Loads


Voltage Drop (cont..)
Let

12

Dr. Muhammad Mohsin Aman 6


8/18/2016

Uniformly Distributed Loads


Voltage Drop (cont..)
Equation 3.16 gives the general equation for computing the total voltage drop from the
source to the last node n for a line of length l. In the limiting case where n goes to
infinity, the final equation becomes:

In Equation 3.17, Z represents the total impedance from the source to the end of the
line. The voltage drop is the total from the source to the end of the line.

13

Uniformly Distributed Loads


Voltage Drop (cont..)
• The equation 3.17 can be interpreted in two ways.
1. The first is to recognize that the total line distributed load can be lumped at the
midpoint of the lateral as shown in Figure 3.7.

14

Dr. Muhammad Mohsin Aman 7


8/18/2016

Uniformly Distributed Loads


Voltage Drop (cont..)
2. A second interpretation of Equation 3.17 is to lump one-half of the total line load
(current) at the end of the line (node n). This model is shown in Figure 3.8.

Figures 3.7 and 3.8 give two different models that can be used to calculate the
total voltage drop from the source to the end of a line with uniformly distributed
loads.
15

Uniformly Distributed Loads


Power Loss
Of equal importance in the analysis of a distribution feeder is the power loss. If the
model of Figure 3.7 is used to compute the total three-phase power loss down the line,
the result is

When the model of Figure 3.8 is used to compute the total three-phase power loss, the
result is

It is obvious that the two models give different results for power loss. The question is,
which one is correct? The answer is neither one.
16

Dr. Muhammad Mohsin Aman 8


8/18/2016

Uniformly Distributed Loads


Power Loss (cont…)
• To derive the correct model for power loss, reference is made to Figure 3.6 and
the definitions for the parameters in that figure. The total three-phase power loss
down the line will be the sum of the power losses in each short segment of the
line.
• For example, the three-phase power loss in the first segment is

17

Uniformly Distributed Loads


Power Loss (cont…)

18

Dr. Muhammad Mohsin Aman 9


8/18/2016

Uniformly Distributed Loads


Power Loss (cont…)

Where R = r ⋅ l, the total resistance per phase of the line segment, Equation 3.25 gives
the total three-phase power loss for a discrete number of nodes and line segments.

19

Uniformly Distributed Loads


Power Loss (cont…)
For a truly uniformly distributed load, the number of nodes goes to infinity. When that
limiting case is taken in Equation 3.25, the final equation for computing the total three-
phase power loss down the line is given by:

20

Dr. Muhammad Mohsin Aman 10


8/18/2016

Uniformly Distributed Loads


Power Loss (cont…)
A circuit model for Equation 3.26 is given in Figure 3.9. From a comparison of
Figures 3.7 and 3.8, used for voltage drop calculations, to Figure 3.9, used for power
loss calculations, it is obvious that the same model cannot be used for both voltage
drop and power loss calculations.

21

The Exact Lumped Load Model

22

Dr. Muhammad Mohsin Aman 11


8/18/2016

Distribution of Loads
In the previous lecture, we have seen two load models can be assumed for
voltage drop calculations:
• Uniformly Distributed Loads
• Lumped Load models

23

Voltage Drop Model for Uniformly Distributed Loads


For voltage drop mode, the total voltage drop from the source to the last node n for a
line of length is given by:

�1 �
Vdrop total � Re � � Z � I T �
�2 �
In Equation, Z represents the total impedance from the source to the end of the line.
The voltage drop is the total from the source to the end of the line.

24

Dr. Muhammad Mohsin Aman 12


8/18/2016

Voltage Drop Model for Uniformly Distributed Loads


• The equation 3.17 can be
interpreted in two ways.
1. The first is to recognize that the
total line distributed load can be
lumped at the midpoint of the lateral
as shown in Figure.
2. A second interpretation of
Equation 3.17 is to lump one-half of
the total line load (current) at the end
of the line (node n). This model is
shown in Figure 3.8.

25

Power Loss Model for Uniformly Distributed Loads


• For a truly uniformly distributed load, the number of nodes goes to infinity. When
that limiting case is taken in Equation 3.25, the final equation for computing the total
three-phase power loss down the line is given by:

• A circuit model for Equation 3.26 is given in Figure 3.9. From a comparison of
Figures 3.7 and 3.8, used for voltage drop calculations, to Figure 3.9, used for power
loss calculations, it is obvious that the same model cannot be used for both voltage
drop and power loss calculations.

26

Dr. Muhammad Mohsin Aman 13


8/18/2016

The Exact Lumped Load Model


�In the previous sections lumped load models were developed.
�It was shown that the same models cannot be used for the computation of
the total power loss down the line.
�What is needed is one model that will work for both voltage drop and
power loss calculations.
�Figure 3.10 shows the general configuration of the exact model that will
give correct results for voltage drop and power loss.

27

The Exact Lumped Load Model


�In Figure 3.10 a portion (Ix) of the total line current (IT) will be modeled kl
miles from the source end, and the remaining current (cIT) will be modeled at
the end of the line. The values of k and c need to be derived.

�In Figure 3.10 the total voltage drop down the line is given by:

28

Dr. Muhammad Mohsin Aman 14


8/18/2016

The Exact Lumped Load Model

�where
• Z = total line impedance in ohms
• k = factor of the total line length where the first part of the load current is
modeled
• c = factor of the total current to place at the end of the line such that
IT = Ix +c⋅IT

29

The Exact Lumped Load Model


�It has shown that the total voltage drop down the line is given by:

�Set Equation 3.17 equal to Equation 3.27:

�Equation 3.29 shows that the terms inside the brackets on both sides of the
equal sign need to be set equal, that is

�Simplify Equation 3.30 by dividing both side of the equation by ZIT:

30

Dr. Muhammad Mohsin Aman 15


8/18/2016

The Exact Lumped Load Model


�Solve Equation 3.31 for k:

�The same procedure can be followed for the power loss model. The total
three-phase power loss in Figure 3.10 is given by:

�The model for the power loss of Figure 3.9 gives the total three-phase
power loss as:

31

The Exact Lumped Load Model


�Equate the terms inside the brackets of Equations 3.33 and 3.34 and
simplify:

�Put the value of k from Eqn. 3.35.

�Solving Equation 3.36 for c results in:

32

Dr. Muhammad Mohsin Aman 16


8/18/2016

The Exact Lumped Load Model


�Substitute Equation 3.37 into Equation 3.32 and solve for k:

�The interpretation of Equations 3.37 and 3.38 is that


� one-third of the load should be placed at the end of the line,
� and two-thirds of the load placed one-fourth of the way from the source
end.
� Figure 3.11 gives the final exact lumped load model.

33

Lumping Loads in Geometric Configurations

34

Dr. Muhammad Mohsin Aman 17


8/18/2016

Lumping Loads in Geometric Configurations


�Many times feeder areas can be represented by geometric configurations
such as rectangles, triangles, and trapezoids.
�By assuming a constant load density in the configurations, approximate
calculations can be made for computing the voltage drop and total power
losses.
�The approximate calculations can aid in the determination of the maximum
load that can be served in a specified area at a given voltage level and
conductor size.

35

Lumping Loads in Geometric Configurations


�For all of the geographical areas to be evaluated, the following definitions
will apply:

� D = load density in kVA/mile2


� PF = assumed lagging power factor
� z = line impedance in Ω/mile
� l = length of the area
� w = width of the area
� kVLL = nominal line-to-linevoltage in kV
� It will also be assumed that the loads are modeled as constant current
loads.

36

Dr. Muhammad Mohsin Aman 18


8/18/2016

Lumping Loads in Geometric Configurations


1. Rectangle

37

Rectangle
�A rectangular area of length l and width w is to be served by a primary
main feeder. The feeder area is assumed to have a constant load density with
three phase laterals uniformly tapped off of the primary main.
�Figure 3.12 is a model for the rectangular area.

38

Dr. Muhammad Mohsin Aman 19


8/18/2016

Rectangle
�Figure 3.12 represents a rectangular area of constant load density being
served by a three-phase main running from node n to node m.
�It is desired to determine the total voltage drop and the total three-phase
power loss down the primary main from node n to node m.

39

Rectangle
�The total current entering the area is given by:

�An incremental segment is located x miles from node n.


�The incremental current serving the load in the incremental segment is
given by:

�The current in the incremental segment is given by:

�The voltage drop in the incremental segment is


40

Dr. Muhammad Mohsin Aman 20


8/18/2016

Rectangle
�The total voltage drop down the primary main feeder is

�Evaluating the integral and simplifying:

where Z = z ⋅ l
�Equation 3.43 gives the same result as that of Equation 3.17, which was
derived for loads uniformly distributed along a feeder.
�The only difference is the manner in which the total current (IT) is
determined.

41

Rectangle
�The bottom line is that the total load of a rectangular area can be modeled at
the centroid of the rectangle as shown in Figure 3.13.
�It must be understood that in Figure 3.13, with the load modeled at the
centroid, the voltage drop computed to the load point will represent the total
voltage drop from node n to node m.

42

Dr. Muhammad Mohsin Aman 21


8/18/2016

Rectangle
�A similar derivation can be done in order to determine the total three phase
power loss down the feeder main. The power loss in the incremental length is

�The total three-phase power loss down the primary main is

�Evaluating the integral and simplifying:

where R = r ⋅ l
43

Rectangle
�Equation 3.44 gives the same result as that of Equation 3.26. The only
difference, again, is the manner in which the total current IT is determined.
�The model for computing the total three-phase power loss of the primary
main feeder is shown in Figure 3.14. Once again, it must be understood that
the power loss computed using the model of Figure 3.14 represents the total
power loss from node n to node m.

44

Dr. Muhammad Mohsin Aman 22


8/18/2016

Problem
Lumping Loads in Rectangle Configurations

45

Problem
�It is proposed to serve a rectangular area of length 10,000 ft. and width of
6000 ft. The load density of the area is 2500 kVA/mile2 with a power factor of
0.9 lagging.
�The primary main feeder uses 336,400 26/7 ACSR on a pole configured as
shown in Figure 3.3. The impedance of the line was computed to be

46

Dr. Muhammad Mohsin Aman 23


8/18/2016

Problem
�The question at hand is what minimum standard nominal voltage level can
be used to serve this area without exceeding a voltage drop of 3% down the
primary main? The choices of nominal voltages are 4.16 kV and 12.47 kV.
Compute, also, the total three-phase power loss.
�The area to be served is shown in Figure 3.15.

47

Solution
�sa

48

Dr. Muhammad Mohsin Aman 24


8/18/2016

Solution
�sa

49

Solution
�It is clear that the nominal voltage of 4.16 kV will not meet the criteria of a
voltage drop less than 3.0%. For a nominal voltage of 12.47 kV, the total area
current is

50

Dr. Muhammad Mohsin Aman 25


8/18/2016

Solution

�The nominal voltage of 12.47 kV is more than adequate to serve this load. It
would be possible at this point to determine how much larger the area could be
and still satisfy the 3.0% voltage drop constraint.

51

Solution
�For the 12.47 kV selection, the total three-phase power loss down the
primary main is

52

Dr. Muhammad Mohsin Aman 26


8/18/2016

Lumping Loads in Geometric Configurations


2. Triangle

53

Triangle
�Figure 3.16 represents a triangular area of constant load density being
served by a three-phase main running from node n to node m.
�It is desired to determine the total voltage drop and the total three-phase
power loss down the primary main from node n to node m.

54

Dr. Muhammad Mohsin Aman 27


8/18/2016

Triangle
�The area of the triangle is

�The total current entering the area is given by:

�The current entering the incremental line segment is

where A1 = area of triangle up to the incremental line segment.

55

Triangle
�asasd

56

Dr. Muhammad Mohsin Aman 28


8/18/2016

Triangle
�asasd

57

Triangle
�Equation 3.53 shows that the total voltage drop from the vertex to the base
of the triangular area can be computed by modeling the total triangle load two-
thirds of the distance between the vertex and the base of the triangle.
�The model for the voltage drop calculation is shown in Figure 3.17.

58

Dr. Muhammad Mohsin Aman 29


8/18/2016

Triangle
�A similar derivation can be made for the power loss model. The power loss
in the incremental line segment is

59

Triangle
�The total three-phase power loss from node n to node m becomes:

�Evaluating the integral and simplifying:

�Equation 3.55 gives the total three-phase power loss down the primary main
from node n to node m.

60

Dr. Muhammad Mohsin Aman 30


8/18/2016

Triangle
�The model for the power loss is given in Figure 3.18.

61

Problem
Lumping Loads in Triangle Configurations

62

Dr. Muhammad Mohsin Aman 31


8/18/2016

Problem
�The triangular area shown in Figure 3.19 is to be served by a feeder of
nominal voltage 12.47 kV. The load density of the area is 3500
kVA/mile2 at a power factor of 0.9 lagging. The conductor on the
primary main is 336,400 26/7 ACSR, and the configuration of the pole is
that of Figure 3.3.
�The impedance of the line is
z=0.306+j0.6272 ohm/mile and the Kdrop
factor is 0.00035291% drop/kVA-mile
�Krise factor for the given conductor
is 0.00040331% rise/kvar-mile.

63

Problem
�Use the Kdrop factor from the line of Example 3.2 and determine the percent
voltage drop from node n to node m.

64

Dr. Muhammad Mohsin Aman 32


8/18/2016

Solution
�sads

65

Solution
�sads

66

Dr. Muhammad Mohsin Aman 33


8/18/2016

Solution
�Suppose now that a shunt capacitor bank is to be installed somewhere
along the primary main in order to limit the percent voltage drop to node
m to 3.0%. Two decisions must be made:
1. Three-phase rating of the capacitor bank
2. Location of the capacitor bank
�The total reactive power of the area was computed to be 2462.6 kvar.
That means that a capacitor bank rated up to 2462.6 can be used without
causing the feeder to go into a leading power factor condition. Since this
is assumed to be the peak load, a capacitor bank rated at 1800 kvar (three-
phase) will be used in order to prevent a leading power factor condition
for a smaller load. Depending upon the load curve during the day, this
bank may or may not have to be switched. 67

Solution
�dsad

68

Dr. Muhammad Mohsin Aman 34


8/18/2016

Solution
�The total three-phase power loss down the primary main before the
shunt capacitor is added is computed by lumping the total triangular load
at:

69

Dr. Muhammad Mohsin Aman 35


���������������������������������������������������������������������������
���������������������������������������������������������������������������������
�����������������������������������������������������