Professional Documents
Culture Documents
DRY TRANSFORMER
20±2.5 % / 0.4 kV, 25 kVA
Measuring
Description Value
Unit
1 GENERAL
Measuring
1.1 Manufacturer Transformers
Factory Zajecar
Power
1.2 Type
transformer
2 RATED DATA
- primary winding kV 24
- primary winding Cu
- secondary winding Cu
2.8 Frequency Hz 50
With cable,
- primary connection (HV)
underside
With busses from
above or cables
from underside.
- secondary connection (LV)
Low voltage
connection is
vertical.
2.10 Losses (guaranteed)
- secondary winding / /
Rated power-frequency
2.15
withstand voltage, 50Hz, 1 min.
- primary winding kV 50
- secondary winding kV 3
o
2.16 Max. ambient temperature C 40
o
- primary winding C 100
o
- secondary winding C 100
2.23 Cooling AN
3 CONSTRUCTION DATA
3.1 Dimensions
- lenght mm 810
- width mm 520
- height mm 815
3.3 Equipment
- 4xPt100 senzors (three in 1. 135oC (warning
Visual
every secondary winding and signal for partial
display for
one on magnetic core) exclusion )
temperature
- electronic relay with 6xPTC 2. 145oC
monitoring
senzors for thermal protection (exclusion)
bi-directional (in
- wheels two directions
with angle 90o)
- Lifting eyelet YES