Professional Documents
Culture Documents
1
Product Presentation Agenda
2
Evolution of the Control Valve
Energy Valve
ePIV
Time
3
PI Valves
2-way valve that supplies a specific flow for each value of the
control signal –
Pressure
PI Valve
Flow
ePIV Operation
Air Flow
Temp. Control
Water Flow
Agenda
6
Coil Degradation
Coils Heat Transfer Degrades over time
• Damaged Coils
• Air Side Fouling
• Water Side fouling
Key
Terms:
Power Saturation Point
• Point beyond which coil cannot yield additional heat
transfer regardless of increased flow.
Waste Zone
• Range beyond the “Power Saturation Point”.
8
Waste Zone
Very little if any waste zone exists with a designed coil
efficiency at or near maximum efficiency.
9
Waste Zone
As a coil ages or becomes fouled or damaged the coil efficiency drops
Power Saturation
Point
10
Waste Zone
Coil efficiency continues to degrade overtime
Power Saturation
Point
The Coil reaches the Power Saturation Point long before the maximum
flow is reached
11
Power & Delta T
Achieving the ideal amount of heat transfer in a coil
is critical for overall system efficiency.
Power Saturation
Point
12
Agenda
13
What is the Belimo Energy Valve™?
BACnet
Actuator
Flow Sensor
Temperature Sensors
Valve (for supply & return water)
14
What is the Belimo Energy™ Valve?
Actuator
• Integrated Windows
Operating system
• BACnet
• Communicates to SL Module
on the flow sensor
15
Supported Networks
• Network Communication
• BACnet MS/TP
• BACnet IP
• TCP/IP
• MP-bus
16
What is the Belimo Energy Valve™?
• 2 way Characterized ball
valve Valve Body
• 2 ½ - 6”
• 127-713GPM
• ANSI 125
17
What is the Belimo Energy Valve™?
Flow Sensor
• No moving parts or
openings to clog or jam
• No maintenance
• Accuracy +/- 2%
18
What is the Belimo Energy Valve™?
Temp.
Sensors
• Resistance
Temperature Detectors
(RTD’s)
• Remote sensor is
Installed in provided
thermo well on opposite
side of coil
US-Patent: 2009/0009115
Control of sensor less and
brushless DC-Motor.
US-Patent: 6,352,106 B1
(by Optimum Energy under
US-Patent: 1999/30780 and exclusive license agreement)
1999/09138 High efficiency pumping and
Control valve with modified distribution system
characteristic CCV. incorporating a self-balancing,
modulating control valve.
20
Energy Valve Product Range
i.e. EV250S-127+ARBX24-65
21
Template
Energy Valve Operation
Strategies
• Flow + ∆T Manager
• Flow
• Position + ∆T Manager
• Position
22
Delta T Manager™
DDC Controlling Flow to
achieve DDC flow setpoint
100
90 Delta T Flow SP 20
Delta T Manager
Flow Setpoint (%)
80 18
takes over
16
70
Actual Delta T 14 SP (min)
60
12
50
10
Delta T (°F)
40
30 DDC Flow SP 8
20 6
10 4
0
Time
23
Delta T Manager™
Limiting flow to maintain ∆T setpoint
100
90 Delta T Flow SP 20
Flow Setpoint (%)
80
18
70 16
Actual Delta T (°F)
60 14
SP (min)
50 Delta T 12
Manager
Delta T (°F)
40 10
Active
30 DDC Flow SP 8
20 6
10 4
0
Time
24
Delta T Manager™
DDC flow lower
than ∆T Manager
100
90 Delta T Flow SP 20
Flow Setpoint (%)
80
18
70 16
Actual Delta T (°F)
60 14
SP (min)
50 Delta T 12
Manager
Delta T (°F)
40 10
DDC Flow SP Active
30 8
DDC is the
20 6
control signal
10 again 4
0
Time
25
Delta T Manager™ Power & Delta T
Waste Zone
Waste Zone
26
Delta T Manager
Actual Case Study from MIT
New right‐sized
Coil @14F T
27
Agenda
28
Web View:
Web-Based Parameterization Tools
• Real Time Data
• Real Time Configuration
29
Web View:
Live Trending
Trending
Examples
30
Parameterization Tools
Hand Held Device (ZTH-2 US)
• Quick Programming
• Quick Reconfiguration
• Fast Commissioning
• Local Display
31
Data Analysis Tool
Energy Valve
• Data Logging and
Storage
• Up to 13 Months of Data
• Export to .csv file format
Excel Tool
• Import .csv in to Excel
Tool
• Power Curves
• Charts, Graphs,
Trending
32
Energy Valve Settings Ordering Tool
• Customer Options
• Same as Web-view
• Defaults pre-set
• Generates PDF
33
Agenda
34
Energy Valve Strategy – Continuous
Commissioning
35
End Users Targets
• Hydronic Systems
• Owner-Occupied
• Sophisticated Owners
• Green Buildings
• Campuses
• District Cooling/Heating
Other Targets
• Consulting Engineers
• Performance Contractors
• Controls Contractors
• OEMS
36
End Users Benefits
37
End Users Benefits cont.
38
Consulting Engineer Benefits
• Strategic advantage for engineering firms in competitive bids.
39
Performance Contractor Benefits
40
Controls Contractor Benefits
• Strategic advantage for firms in competitive
bids.
• Improved commissioning/Continuous
Commissioning.
41
OEM/Other Partners Benefits
• Private label opportunities for select partners
• Integrated flow meter and temp sensor reduce cost and simplify installation
42
Why buy the Belimo Energy Valve™
Hydronic System Knowledge
• Flow, Energy Consumption, Delta T, Performance
Commissioning / Diagnostics
• Continuous Commissioning / Benchmarking
Coil
• ΔT Managing for peak coil efficiency
• Optimization in retro-fit applications
• Allows for predictive maintenance
Pump
• Reduced pumping energy from maximum coil ΔT’s achieved
Chiller Plant
• Improved efficiency from lower flow resulting in higher ΔT
• Released chilled water plant chiller capacity
43
Belimo Energy Valve™
44
Thank You !!
Questions?
Knowledge is Power
Belimo Energy Valve ™
45