Project Title: CHURCH AT YISHUN STREET 22

Date 19-Apr-17
Ref No. WKH-DEC2016-1641-R1
No. of Pages 3
Subject: GREEN MARK CALCULATIONS FOR EXISTING NON-RESIDENTIAL BUILDING

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
74% Part 74% Part 74% Part 74% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 1-1 FDC1000KXZE1
VRF Inverter
Stage FCU 1-1/1 to 1/2 FD140KXE6F/1 100.0 74.2 28.0 18.0 3.6 4.1 0.85
/ R410a
Multi purpose hall FCU 1-1/4 TO 1/8 FD140KXE6F/1

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
76% Part 76% Part 76% Part 76% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 1-2 FDC735KXZE1 VRF
74.0 56.2 19.9 13.1 3.7 4.3 0.82 Inverter /
Multi purpose hall FCU 1-2/1 TO 2/5 FDT140KXE6F/1
R410a
Specification of Outdoor Condensing Unit
Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
74% Part 74% Part 74% Part 74% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 1-3 FDC615KXZE1
PRAYING AREA 1-3 FCU 1-3/1 FDT112KXE6F/1 VRF Inverter
62.0 45.8 16.2 10.5 3.8 4.4 0.80
PRAYING AREA 1-4 FCU 1-3/2 FDT71KXE6F/1 / R410a
PRAYING AREA 1-5/6/7 & 1-11/2
FCU 1-3/3 TO 3/8 FDT71KXE6F/1

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
72% Part 72% Part 72% Part 72% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 2-1 FDC670KXZE1
VRF Inverter
PRAYING AREA 2-1/2/3 FCU 2-1/1 TO 1/6 FDT90KXE6F/1 67.0 48.5 17.9 11.1 3.7 4.4 0.81
/ R410a
PRAYING AREA 2-4 FCU 2-1/7 FDT140KXE6F/1

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
76% Full 76% Full 76% Full 76% Full
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 2-2 FDC670KXZE1
PRAYING HALL FCU 2-2/1 TO 2-2/3 FDUM90KE6F/B
VRF Inverter
PRAYER AREA 2-8 & 2-7 FCU 2-2/4 TO 2-2/5 FDT112KXE6F/1 67.0 50.7 17.9 12.0 3.7 4.2 0.83
/ R410a
PRAYER AREA 2-6 FCU 2-2/6 FDT90KXE6F/1
PRAYER AREA 2-5 FCU 2-2/7 FDK28KXE6F/1

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
80% Full 80% Full 80% Full 80% Full
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 2-3 FDC670KXZE1
OFFICE 1 FCU 2-3/1 FDK28KXE6F/1
OFFICE 2/3/4 FCU 2-3/2 TO 3/4 FDK45KXE6F/1
OFFICE 5 FCU 2-3/5 FDK71KXE6F/1 VRF Inverter
67.0 53.4 17.9 12.8 3.7 4.2 0.84
ADMIN FCU 2-3/6 & 7 FDT56KXE6F/1 / R410a
PRAYING AREA 2-9 FCU 2-3/8 FDT90KXE6F/1
MEETING ROOM FCU 2-3/9 FDT71KXE6F/1
DINING FCU 2-3/10 FDT140KXE6F/1

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
75% Part 75% Part 75% Part 75% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 3-1 FDC850KXZE1
VRF Inverter
CONGREGATION FCU 3-1/1 TO 1/6 FDUM140KE6F/B 85.0 63.7 24.9 15.4 3.4 4.1 0.85
/ R410a
PRAYING AREA 4 FCU 3-1/7 FDK28KXE6F/1
Specification of Outdoor Condensing Unit
Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
73% Full 73% Full 73% Full 73% Full
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 3-2 FDC850KXZE1 VRF Inverter
85.0 63.7 24.9 14.8 3.4 4.3 0.82
CONGREGATION FCU 3-2/1 TO FCU 3-2/6 FDUM140KE6F/B / R410a

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
73% Full 73% Full 73% Full 73% Full
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 3-3 FDC850KXZE1 VRF Inverter
85.0 62.4 24.9 14.8 3.4 4.2 0.83
CONGREGATION FCU 3-3/1 TO FCU 3-3/6 FDUM140KE6F/B / R410a

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
90% Part 90% Part 90% Part 90% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 3-4 FDC900KXZE1
PRAYING AREA 3-2 & 3-3 FCU 3-4/5 &4/6 FDK28KXE6F/1
PRAYING AREA 3-5 FCU 3-4/7 FDK45KXE6F/1
PRAYING AREA 3-6 / VRF Inverter
FCU 3-4/8 TO 4/10 FDT71KXE6F/1 90.0 81.1 28.0 22.8 3.2 3.6 0.99
MEETING ROOM / R410a
BEDROOM 1 TO 4 FCU 3-4/11 &4/14 FDK45KXE6F/1
SACRISTRY FCU 3-4/16 FDE112KXE6F/1
PRAYING AREA 3-1 FCU 3-4/1 & 3-4/2 FDUM140KE6F/B

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
64% Part 64% Part 64% Part 64% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 4-1 FDC735KXZE1 VRF Inverter
74.0 47.0 19.9 10.2 3.7 4.6 0.76
LOFT FCU 4-1/1/1 TO 1/5 FDUM140KE6F/B / R410a

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
64% Part 64% Part 64% Part 64% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
CU 4-2 FDC800KXZE1
VRF Inverter
FCU 4-2/1 TO 2/4 FDUM140KE6F/B 80.0 51.5 21.9 11.3 3.6 4.6 0.77
LOFT / R410a
FCU 4-2/5 TO 2/6 FDUM112KE6F/B

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
78% Part 78% Part 78% Part 78% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
FCU 4-3 FDC560KXZE1 VRF Inverter
56.0 43.6 16.3 8.2 3.4 5.3 0.67
PRAYING AREA 4-1/2/3 FCU 4-31 TO 3/6 FDT90KXE6F/1 / R410a

Specification of Outdoor Condensing Unit


Area Served Designation Offered Model
Total Cooling Capacity Power Input (kW) COP kW/RT
73% Part 73% Part 73% Part 73% Part
Systems /
Full Load Full Load Full Load Load
Refrigerant
Installed (Based on Installed (Based on Installed (Based on (Based on
Capacity CU Load Capacity CU Load Capacity CU Load CU Load
Profile) Profile) Profile) Profile)
FCU 4-4 FDC500KXZE1 VRF Inverter
50.0 36.5 14.0 8.8 3.6 4.1 0.85
UPPER PART OF CONGREGATION
FCU 4-4/1 & 4/1 FDU224KXZE1 / R410a

Total: 1,042.0 778.3 292.7 183.8

Indoor temp : 27/19 Deg C DB/WB. Outdoor temp : 35 Deg C DB

*Above calculation for reference only. Condensing units capacity at part load are to be confirmed by Consultant.

Step B-3 Determine the overall expected operating efficiency of the systems

The expected operating efficiency of the overall air-conditioning system serving the building is :

A) Efficiency at Part Load (kW/Tons)

Total Required Overall operating Greenmark


Total Power Input (kw) Total Required Overall
Cooling (kw) efficiency for the system Points
@Part Load Cooling (RT) Green Mark
@Part Load (KW/RT) Scored

183.8 778.3 221.3 0.831 GoldPlus 28.7


GREEN MARK CALCULATIONS FOR EXISTING NON-RESIDENTIAL BUILDING

Air-Conditioned Buildings
Prescribed system efficiency of air-conditioning system to be as follows:
(ii) For Buildings uding Air Cooled Chilled-Water Plant or Unitary Air-Conditioners:

Peak Building Cooling Load (RT)


< 500 ≥500
Green Mark Rating
Minimum Design System Efficiency (1) DSE
(kW/RT)
Certified 1.10 1.00
Gold 1.00
GoldPlus 0.85 Not applicable (2)
Platinum 0.78

Important Notes:
(1) The efficiency of the overall air-conditioning system shall meet its design system efficiency as well as the corresponding minimum DSE stipulated for the respective
air-conditioning system and Green Mark rating during the building operating hours specified below:-

Office Buildings: Hotels:


Monday to Friday: 9am to 6pm Monday to Sunday: 24 Hours

Retail Malls: Industrial & Other Building Types:


Monday to Sunday: 10am to 9pm To be determined based on operating hours

Note (2) For building with peak building cooling load of more than 500RT, the use ofair-cooled central chilled-water plant or other unitary air-conditioners are not
applicable for Gold and higher ratings. In general, the system efficiency of the air-cooled chilled-water plant and unitary air-conditioners are to be comparable with the
stipulated efficiency for water-cooled central chilled-water plant. Buildings that are designed with air-cooled systems and for higher Green Mark rating will be assessed
on a case by case basis.

Green Mark Points

For Peak building cooling load ≥500 RT

14 points for meeting the prescribed air-conditioning system efficiency of 0.85kW/RT.

0.35 points for every percentage improvement in the air-conditioning system efficiency over the baseline.

Points scored = 0.35 x (% improvement) (Up to 20 points)

For Peak building cooling load <500 RT

14 Points for meeting the prescribed air-conditioning system efficiency of 1.1 kW/RT.

0.2 points for every percentage improvement in the air-conditioning system efficiency over the baseline.

Points scored = 0.2 x (% improvement) (Up to 20 points)


% improvement = 24.48%

Therefore points scored = 28.7 (Total of 20 points MAX for green mark)