Air System Name CU 6-1 to 6-6 Number of zones 1 Equipment Class TERM Floor Area 328.5 m² Air System Type SPLT-FC Location Singapore, Singapore
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Hourly Analysis Program v4.90 Page 1 of 4
Zone Sizing Summary for CU 6-1 to 6-6 Project Name: 23 Tuas Rd 08/22/2016 Prepared by: 04:32PM
Air System Information
Air System Name CU 6-1 to 6-6 Number of zones 1 Equipment Class TERM Floor Area 328.5 m² Air System Type SPLT-FC Location Singapore, Singapore
Sizing Calculation Information
Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates Sizing Data Calculated Space L/s Sizing Individual peak space loads
Zone Sizing Data
Maximum Maximum Zone
Cooling Design Minimum Heating Floor Sensible Airflow Airflow Time of Load Area Zone Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²) Zone 1 30.1 1924 1924 Jul 1600 0.0 328.5 5.86
Terminal Unit Sizing Data - Cooling
Total Sens Coil Coil Water Time
Coil Coil Entering Leaving Flow of Load Load DB / WB DB / WB @ 5.6 °K Peak Zone Name (kW) (kW) (°C) (°C) (L/s) Load Zone 1 43.6 34.4 25.8 / 17.5 11.0 / 10.3 - Jul 1400
Terminal Unit Sizing Data - Heating, Fan, Ventilation
Heating Htg Coil
Heating Coil Water Fan OA Vent Coil Ent/Lvg Flow Design Fan Fan Design Load DB @11.1 °K Airflow Motor Motor Airflow Zone Name (kW) (°C) (L/s) (L/s) (BHP) (kW) (L/s) Zone 1 0.0 -18.3 / -18.3 0.00 1924 0.000 0.000 197
Space Loads and Airflows
Cooling Time Air Heating Floor
Zone Name / Sensible of Flow Load Area Space Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²) Zone 1 FCU 6-1 TO 6-6 1 30.1 Jul 1600 1924 0.0 328.5 5.86
Hourly Analysis Program v4.90 Page 2 of 4
Air System Design Load Summary for CU 6-1 to 6-6 Project Name: 23 Tuas Rd 08/22/2016 Prepared by: 04:32PM
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1400 HEATING DATA AT DES HTG COOLING OA DB / WB 32.6 °C / 26.1 °C HEATING OA DB / WB 22.8 °C / 16.1 °C Sensible Latent Sensible Latent ZONE LOADS Details (W) (W) Details (W) (W) Window & Skylight Solar Loads 0 m² 0 - 0 m² - - Wall Transmission 0 m² 0 - 0 m² 0 - Roof Transmission 0 m² 0 - 0 m² 0 - Window Transmission 0 m² 0 - 0 m² 0 - Skylight Transmission 0 m² 0 - 0 m² 0 - Door Loads 0 m² 0 - 0 m² 0 - Floor Transmission 0 m² 0 - 0 m² 0 - Partitions 212 m² 4460 - 212 m² 0 - Ceiling 329 m² 6914 - 329 m² 0 - Overhead Lighting 8213 W 7097 - 0 0 - Task Lighting 0W 0 - 0 0 - Electric Equipment 4928 W 4390 - 0 0 - People 32 1837 2547 0 0 0 Infiltration - 0 0 - 0 0 Miscellaneous - 0 0 - 0 0 Safety Factor 20% / 20% 4939 509 0% 0 0 >> Total Zone Loads - 29637 3057 - 0 0 Zone Conditioning - 32593 3057 - 0 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 - 0 0 - Plenum Lighting Load 0% 0 - 0 0 - Exhaust Fan Load 0 L/s 0 - 0 L/s 0 - Ventilation Load 197 L/s 1788 6177 197 L/s -396 0 Ventilation Fan Load 0 L/s 0 - 0 L/s 0 - Space Fan Coil Fans - 0 - - 0 - Duct Heat Gain / Loss 0% 0 - 0% 0 - >> Total System Loads - 34381 9234 - -396 0 Terminal Unit Cooling - 34381 9245 - -396 0 Terminal Unit Heating - 0 - - 0 - >> Total Conditioning - 34381 9245 - -396 0 Key: Positive values are clg loads Positive values are htg loads Negative values are htg loads Negative values are clg loads
Hourly Analysis Program v4.90 Page 3 of 4
Hourly Air System Design Day Loads for CU 6-1 to 6-6 Project Name: 23 Tuas Rd 08/22/2016 Prepared by: 04:32PM