PRE-FAT RT02 33kV Transformer 1
F650 Feeder Protection

00
Project Number: Rev.:
100061-ND-CP07-RE

This document contains the following:

Vendor Vendor
Descnption Pages
No. Document number Rev.
F650 0 Inspection test 6

00 27103/2017 First Issue GE VMLB RCAV


Rev. ddlmm/yyyy Description Created Checked Approved
Project Name: Sondu (Therdibuoro)· Homa Bay (Ndhiwa)·
Awendo Electrification Proiect


GE Customer: Republic of Kenya· Ministry of Energy

PO number:
Digital Energy
Commissioning Nr:

Switchgear Identification: T02+RT02 33KV TRANSFORMER 1

F650 Feeder Protection


RElAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1Ht6E
Settings Reference: Serlal Nr.: 82.896.101
Functions Tested: SlP·SlG Type: Multifunctional Protection

Comments:

INSPECTION TEST

1. VISUAL INSPECTION
• Ok

,. USO/ETHERNET PORT COMMUNICATION


• OK

3. CONFIGURATION FILE UPLOAD


• OK. Ndhiwa_BCU_TRAF033kV.650

4. POWER SUPPLY
• 107.SVdc

5. CONTACT INPUTS
• Verified

6. CONTACT OUTPUTS
• Verified

7. LOGIC
• Verified

8. VOLTAGE AND CURRENT INPUTS METERING TESTS


• Venf1ed

9. PROTECTION AND FUNCTIONAL TESTS


• Ve rifted

tl_ /!cf/I-
»:>

->
Switchgear Identification: T02+RT02 33KV TRANSFORMER 1
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.101
Functions Tested: 51P-51G Type : Multifunctional Protection

SUMMARY OF WIRED CONTACT OUTPUTS


Contact
Description State Tested
ID

F3 CB Open NO OK

F4 CB Close NO OK

F5 CB INI FAIL RT01 NO OK

G3 CB TC1 NO OK

G4 CB TC2 NO OK

H3 Open DS NO OK

H4 Close DS NO OK

H6 POS REPT DS & CB in NO OK

H7 POS REPT DS & CBout NO OK

2
Switchgear Identification: T02+RT02 33KV TRANSFORMER 1
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.101
Functions Tested: 51P-51G Type : Multifunctional Protection

SUMMARY OF WIRED CONTACT INPUTS


Contact ID Description Tested Remarks

F_CC2 (F2) AVR intern Fail OK

F_CC3 (F3) TC1 FAIL OK

F_CC4 (F4) TC2 FAIL OK


F_CC5 (F5)
Intlock Overd sw OK
F_CC6 (F6)
DC supply PROT2 OK
F_CC7 (F7)
DC suply T3 Fail OK
F_CC11 (F11)
V meter FAIL OK

F_CC12 (F12) V BCPU FAIL OK

F_CC13 (F13) V AVR FAIL OK

F_CC14 (F14) Heating FAIL OK

G_CC3 (G3) CB OPEN OK

G_CC4 (G4) CB CLOSE OK

G_CC6 (G6) CB SF6 AL OK

G_CC7 (G7) CB SF6 Block OK

G_CC9 (G9) CB CLS LOCK DRIV OK

G_CC10 (G10) CB MOT PROT TRP OK

G_CC11 (G11) CB Excesiv RUN OK

G_CC12 (G12) CB HEAT FAIL OK

G_CC13 (G13) CB In Remote OK

G_CC14 (G14) CB In Local OK

H_CC1 (H01) DS Mot Prot TRP OK

H_CC2 (H02) DS In Remote OK

H_CC3 (H03) DS In Local OK

3
Switchgear Identification: T02+RT02 33KV TRANSFORMER 1
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.101
Functions Tested: 51P-51G Type : Multifunctional Protection

H_CC4 (H04) DS Closed OK

H_CC5 (H05) DS Open OK

H_CC6 (H06) DS MCB Heat FA OK

H_CC9 (H09) 33kV CBF STG2 OK

J_CC3 (J03) CBF INI RT01 OK

J_CC7 (J07) CBF STG2 RT01 OK

J_CC10 (J10) V TRF BUS FAIL OK

4
Switchgear Identification: T02+RT02 33KV TRANSFORMER 1
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.101
Functions Tested: 51P-51G Type : Multifunctional Protection

UNBALANCED SYSTEM TO IDENTIFY PHASES (Read values on Primary values)

Phase VOLTAGE INJECTION ACTUAL VALUE CURRENT INJECTION ACTUAL VALUE

V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle

A 20 V 0º 5.996KV 0.0º 1A 0º 0.498KA 359.669º

B 40 V -120º 11.973KV 119.699º 2A -120º 0.998KA 119.496º

C 60 V -240º 17.972KV 239.422º 3A 120º 1.498KA 239.308º

CURRENT INJECTION (G) ACTUAL VALUE

I Mag I Angle I Mag I Angle

1A 0.499KA

BALANCED V&I SYSTEM (Read values on Primary values)

Phase VOLTAGE INJECTION ACTUAL VALUE CURRENT INJECTION ACTUAL VALUE

V Mag V Angle V Mag V Angle I Mag I Angle I Mag I Angle

A 63,5 V 0º 19.037KV 0.0º 1A 0º 0.498KA 359.485º

B 63,5 V -120º 19.010KV 119.527º 1A -120º 0.499KA 119.216º

C 63,5 V -240º 19.008KV 239.218º 1A 120º 0.499KA 238.779º

5
Switchgear Identification: T02+RT02 33KV TRANSFORMER 1
RELAY DATA
Manufacturer : GE Digital Energy Model Nr.: F650MMBF1G1HI6E
Settings Reference: Serial Nr.: 82.896.101
Functions Tested: 51P-51G Type : Multifunctional Protection

51P – PHASE TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

A 1.5A 0º 0.96A 1.256s OK


IEC CURVE A
B 1.5A -120º 0.96A TDM:0.13 0.96A 1.261s OK 17/3/17
(1.23s)
C 1.5A 120º 0.96A 1.259s OK

CONTACT
OUTPUTS F05, G03, G04 OK 17/3/17
ACTIVATED

LED LED 1 OK 17/3/17

51G– GROUND TIME OVERCURRENT-


CURRENT INJECTION SETTING VALUE TESTED VALUE CONCLUSION

I Mag I Angle PKP TIME PKP TIME RESULT DATE


(OK/NOT OK)

G 0.17A 0º NO PKP - OK
0.17A 0.6s 17/3/17
G 0.18A 0º 0.18A 635.7ms OK

CONTACT
OUTPUTS F05, G03, G04 OK 17/3/17
ACTIVATED
LED LED 2 OK 17/3/17

REMARKS:

GE Digital Energy Customer


INSPECTORS Representative
Representative

NAME EDER LAFRAGUA

SIGNATURE

DATE 23/3/2017