I/We Certified that installation detailed below has been installed and tested by us and that to the best of our
knowledge and belief, it complies with Indian Electricity Rule 1956 as early as IS 732-1963 Code of practice for
Electrical Installation and ready for inspection.
1. Name and address of the owner : SOUTH CO., Malkangiri Electrical Division.
of the electrical installation
2. Location of the electrical installation : Goudaguda Village under Malkangiri Section.
3. Purpose of the installation : Rural Electrification under DDUGJY scheme.
4. Voltage and system of supply : 11 KV line 3 ph 3 Wire. & LT line 3Ph 5 wire by ABC
5. A)
Class of Control equipment
Apparatus Make H.P/ Voltage No. of Current insulation
K.V Phase & & type of
frequency cooling Type Rating Make
Type of wiring conductor size : 11 KV line 3 ph, 3 wire Over head line
Conductor size : 55 Sqmm AAAC
Total Load : 14KW(BPL-14 )
iii) Length of the line : H.T – 1.787KM (3 ph, 3W) & LT – 0.704 KM
iv) Average span length : Under 60 mtrs (HT) & under 40 mtr (LT)
v) Stage if clearance are maintained
as per relevant section of
I.E.R 1956 : YES As per IE rule
Cont… P/2
//2//
6. EARTHING
i) Type of earth Electrode : PIPE, SPIKE for 11KV & Coil for LT
ii) Size of Earth Wire : 50x6 GI Flat & 6 SWG GI wire
iii) No. of earth electrode provided : Pipe- 11 nos, Spike-31 nos & Coil- 9 nos
7. Testing Results
i) Insulation Resistance to the whole insulator
Between each Conductor : 168 M ohm
ii) Between each Conductor & earth : 188 M ohm
iii) Insulation resistance for each apparatus : 141 M ohm
each Conductor and earth
iv) Earth Resistance for the System of earthling : 2.5 Ohm
10. Names & Permit No. and grade of the : R.R. Swain – L/M. – A – 148 PU
Wireman/Electrician/Lineman engaged Saroj Kr. Barik – W/M-B – BBS/CTC-307
In the work C.K Das-W/M - M.V - JSP - 1469
P.K Pradhan – M.V – PU – 1505
Sibaram Barik – L/M – M.V – CTC/1083
11.
Date of completion and final checking of : 05.06.18
The work by the supervisor