You are on page 1of 4

Issued by Switchgear Contracts Division LARSEN & TOUBRO LIMITED Powai Works, Bombay 400 072.

July-September 1994

Prospect/Retrospect − beyond a certain cross section,


adding to the cross section of the
conductor does not increase
ampacity of the busbar at all.

Higher Ampacity Of different profiles of conductors of
same cross section give different
ampacity under the same

Busbars −
conditions.
any profile, other than rectangle,
poses difficulty in manufacturing,
assembly and maintenance.
In the initial days, Power Control limits on the busbars in − if the busbar thickness is
Centres (PCCs) were connected to switchboards. It was also realised increased, its current carrying
the transformers and through that for paper bonded insulators, the capacity doesn't increase
feeders of the PCCs, various Motor insulating properties deteriorate proportionately. So, choosing a
Control Centres were being fed. This rapidly at higher temperature, conductor of rectangular cross
led to duplication of feeders, resulting in arcing fault in the busbar section, with minimum thickness,
extensive cabling and higher costs. zone. which is adequate for required
In LV switchgear, most of the power mechanical strength provides the
transformers used to be 1000kVA or When low temperature rise and best alternative.
1600kVA. Thus, the maximum higher current ratings were − above 1600A rating, ventilating
currents were of the order of specified, switchboard louvers help in increasing
2000-2500A. manufacturers started: ampacity of busbars.
When PMCCs were introduced, − Increasing the cross section of Inductive reactance of the busbars
larger transformers were connected busbar conductors results in higher temperature rise.
directly to the Motor Control Centres − trying with different geometry of
through ACB incomers. Last decade conductors for busbars. Even the conduction losses in
has seen the transformer rating switchboards have a cumulative
going up (upto 2500kVA) and Simultaneous study of different effect. They result in higher busbar
thereby the current rating of the variables under stipulated conditions temperature, burdening the air-
busbars also increasing. For a revealed that: conditioning system. It also means
medium size industrial plant, loss of power for which the user has
busbars of 3500A current rating − ampacity of busbars is governed to pay. Thus, effective steps taken to
have become a normal requirement. by: reduce these conduction losses will
• material of busbars not only save the user's money but it
Earlier specifications used to specify (aluminium/copper) will also make the system eco-
ambient temperature as 40 deg. C. friendly!
Later, it was also realised that the • cross section of busbars
tropical conditions in our country • profile of the conductors In this issue of L&T Current Trends,
may lead to an ambient of 45 deg.C. • spacing between the we bring you the analysis of this
or even higher at a few places. conductors of same phase inductive effect on the ampacity of
• total busbar zone volume busbars and a probable solution to
This awareness on the part of achieve higher ampacity of the
customers brought temperature rise • type of ventilation
busbar.
Feature

Interleaved busbar system for a.c. applications


An effective solution for achieving higher ratings

- U. V. Raut & S. R. Shetye


Switchgear Design & Product Development Department

Temperature rise (TR) is an To understand this, take the case The ratio of a.c. to d.c. watt loss is
important consideration for busbar of a flat shaped conductor known as Rac/Rdc ratio. (Hereafter
installations. As far as required assumed to be comprising several termed as 'ratio'). This indicates
ampacity of busbar system is smaller conductors of equal area in effective resistance (Rac) offered
below 1600 A, it can be parallel, carrying total current of 10 by a configuration in relation to the
conveniently achieved by using A as shown in figure 2 on page 4. actual resistance (Rdc). Ideal
one or more conductors of suitable In the case of uniform distribution, (minimum) value of this ratio is
size and shape. The problem lies watt loss works out to 20 W. For 1 i.e. Rac = Rdc.
in designing an a.c. busbar system non uniform distribution, element-
for higher ampacities. Test results wise currents differ not only in What is interleaving?
show that increasing cross section
beyond certain limits in a For increasing busbar system
conventional manner (say by ampacity, conventionally one tends
adding a conductor or increasing to add a conductor or a group of
the thickness) gives marginal conductors adjacent to existing
increasing in the ampacity. The conductors / groups and ends up
reason is skin and proximity effects placing all conductors / groups
or in other words, inductive effects together. (Refer to table 1,
due to a.c. currents. configuration 2) This results in
widely non uniform current
Direct current distribution over a distribution due to skin effect and
cross section depends only on the proximity effect. Proximity effect is
resistance and hence current dependent on the distance
density is uniform irrespective of between conductors. Hence, this
shape, size and arrangement of problem can be overcome by
conductors. However, a.c. arranging individual conductors in
distribution is controlled more by specific geometries. Interleaving is
inductive effects than by one such arrangement. (Refer to
resistance. Effect of current in the configuration 5).
conductor itself is known as skin
effect. This causes the current to Interleaving means arranging
concentrate in the outer parts. conductors groups in the alternate
Effect of current in the adjacent fashion (R Y B R Y B). In the
conductor is known as proximity configuration 5, two groups of
effect. Inductive effects result in three conductors each per phase
non uniform current distribution have been arranged in this fashion.
over a cross section (i.e. inefficient One can go even beyond this and
use of conducting material); make three groups of two
consequently making busbars to conductors each to increase the
run at a higher temperature. rating further.

magnitude but also in phase angle Table 1 gives ratios for various
Figure 1 gives current distribution configurations of three phase
(Note that arithmetic addition is
pattern over round conductors in busbar systems with wide and
11.2 A). Watt loss in this case is
various configurations where each moderate/close interphase
30.8 W. As watt loss is more,
dot represents a unit quantity of spacings. One can note the
steady state temperature will be
current. difference between the ratios for
higher for the same value of
current; or for the same steady wide spacings and close spacings
Why does non uniform distribution for configurations 2, 3 & 4.
state temperature, it will have lower
result into higher losses and Effective resistance (relative) is
apmacity.
thereby high temperature? given in the last column.
2 L&T Current Trends, July-September 1994
Discussion on Table 1 aluminium. This is because for evident from ratios for wide
copper, inductive effects distort spacings at which interphase
(1) Effect of increase in busbar current more due to lower proximity effects are negligible.
cross-section in a conventional resistance. This reflects in the However, for close spacings,
manner: Configuration 2 is having effective resistance (Rac) which is configurations 3 and 4 are
double the cross-section as that of not lower in the same proportion marginally better than configuration
configuration 1. However, effective as that of Rdc. Considering the 2. These sections are also not
resistance for middle phase is fact that heating is proportional to desirable as processing on
more and so is the heat produced the square of the current, rating machines, making joints etc. is
at same current. Thus, increasing with copper would be only 19% difficult.

• RESISTANCE VALUES ARE RELATIVE WITH THE BASE VALUE OF 9 SQ. IN. ALUMINIUM AS 1

Table 1

the cross-section has not given more. Thus, for large cross- (4) Interleaved System
any benefits. Configuration 2 will sections, changing the material (configuration 5):
carry more current only because from aluminium to copper gives For same cross sectional area,
more number of flats are available marginal increase in the ampacity interleaved configuration 5 enjoys
for dissipating the heat. at a very high cost. much better rations than
configurations 2, 3 & 4. This is
(3) Use of Tubes/Channel section due to substantial improvement in
(2) Effect of changing the material (configurations 3 & 4): These are current distribution as proximity
from aluminium to copper: For often suggested for busbar effects tend to cancel each other.
configuration 2, copper is having systems as they are ideal shapes
higher ratio as compared to that of to counter skin effect. This is Comparing this with configuration

L&T Current Trends, July-September 1994 3


2, effective resistance for middle Results of TR test (ii) Figure 3 gives instantaneous
phase is less than half. Therefore, (at the instant of 105 kA peak
ampacity would be more by A test was carried out on a 2.5 current in the R phase) values of
around 35 to 40% for aluminium metre long busduct (IP54) with short circuit current and force for
and 40 to 45% for copper or in configurations 2 & 5 with configurations 2 & 5. For the
other words, the losses will be less aluminium at 3150 A. Average rise interleaved arrangement, forces
in the same proportion. for configuration 2 was 66°C and due to short circuit current are
that for configuration 5 was 36°C. much lower. This enables redesign
One can also note that for and reconsideration of the busbar
interleaved system, ratios for all Other advantages of interleaved support system. Also, it can
phases are uniform; while for other system enable the existing support system
configurations, ratios for middle to withstand much higher fault
phase are much higher. Thus, (i) It offers lower and balanced levels.
ampacity is limited by TR on this impedance. This becomes
phase even though outer phases important for long busducts where Disadvantages of the interleaved
run cooler. voltage drop is critical. system
(i) Phases see each other at
greater number of places. This
may increase size of busbar
chamber.
ISO 9001 for L&T's Switchgear
(ii) Putting equalizers between
and groups is difficult. However
equalizers are not required if each
Petrol Pumps load is tapped from both packets.

(iii) For busduct applications, phase


cross-over chamber may become
The switchgear and petrol pump - design, manufacture, marketing- essential to facilitate passing all
related operations of Larsen & installation and servicing of bars (of a phase) through CTs.
Toubro Limited have been awarded switchgear and controlgear pro-
ISO 9001 certificate by BVQI, ducts; switchboards; and petrol Conclusion
London - one of the leading metering and dispensing units. The
accreditation agencies in the product range covered includes Considering all pros and cons,
world - following comprehensive about 550 catalogued and price- optimum solution for reducing loss
audit of quality systems at the listed standard products, motor and of energy and achieving high
Company's factories at Powai, power control centres and various ampacity busbar system would be
Madh and Ahmednagar as well as types of petrol pumps with mechani- interleaving. As interleaved system
its marketing offices. cal and electronics register. L&T needs less material and use of
holds a leadership position in India aluminium is possible for very high
The ISO 9001 certification covers for these products. ratings, this system is better suited
for Indian conditions.

Edited, printed and published by Cerena de Souza for Larsen & Toubro Limited. Published from L&T House, Ballard Estate,
Bombay 400 001 and printed at Vakil & Sons Ltd., 18 Ballard Estate, Bombay 400 001. Associate Editor : Luis S. R. Vas.

You might also like