Professional Documents
Culture Documents
Q_box = Q_fw80
m_box * cp_b * (70-20) = m_fw80 * cp_w *(80-70)
m_fw80= 22619.048 kg/h 6.2830688 kg/s fresh water with temperature 80°
Q_fw80 = m_w100*cp_w*100+m_fw11*cp_w*11
Q_fw80 = (m_fw80-m_fw11)*cp_w*100 + m_fw11*cp_w*11
m_fw80*80 = m_fw80*100-m_fw11*100 + m_fw11*11
m_fw11= 5082.932 kg/h 1.4119256 kg/s mass flow fresh water 11°
Q_HW_washer = m_w110 * cp_w * (110-105) 105° own astimation -> at least 5° temperature difference
m_w105= 105216.69 kg/h 29.226859 kg/s
reference Temperature for all calculations: T_ref = 0°C
erature 80°
ure difference
Mass and Energy balance for the different components reference Temperature for
2. Mixing point
m_w105 = 29.226859 kg/s
m_w_return = 3.67 kg/s
Q1 = -Q2
m1 * cp_w * (T_f - T_i1) = - m2 * cp_w * (T_f - T_i2)
m_w105 * cp_w * (T_f - 105) = m_w_return *cp_w * (T_f - 90)
T_f = 103.32659 °C temperature after mixing point
t= 2h
m_w= 10000 kg/2h
m_w= 5000 kg/h
Q_gas = 1908.9 kJ/s 1720 kJ/s 1720-> number comes from "boiler efficiency excel
Q_gas = 6872040 kJ/h
m_gas= 123.984 kg/h mass flow natural gas need for boiler
m_gas= 0.03444 kg/s
1kg fuel / sec = 21.074 kg(FG)/s for 1kg fuel (natural gas) we get 21.047 kg flue gas /exhaust gas (FG) -> numbe
Q_losses= 235.535197 kW
m "boiler efficiency excel"
haust gas (FG) -> number comes from "boiler efficiency excel"
renewable energy sources - calculation
we have 2 options for using biogas: 1st is to use
1. Biogas 2nd is to use the biogas in a CHP-plant - we can
m_ww= 1.32859224 kg/s m³/s when density of (waste) water is 1g/cm³
CSB= 4.78 kg/m³
efficiency= 0.8 80% of produced metahne can be used for ener
production= 0.28 m³/kg_CSB 0.28m³ Methane can be produced per kg CSB
Hu = 10.1 kWh/m³
Electicity ? other option is to use the biogas for producing electricity and
Heat ?
2. Solar
the efficiency of solar panels depends on the sourounding temperature and the temperature of the liqid
for 11° sourounding temperature and 85° temperature of the solar panels about 50% efficiency can be achieved (we desed
efficiency: 0.5
Autor:
thik we should just calculate the remaining energy demand
available energy for use: 1919137.5 kWh/a AFTER!!! Heat recovery for this option
3. CHP (instead of gas boiler) With this calculation we did replace the "normal" gas boiler with a CHP plant -> the aim
information efficiency from the slides of the lecture "cogen", slide number 4
Autor:
efficiency_ele 35.3 %
replace by heat demand AFTER heat recovery?
efficiency_therm 50 %
Losses 14.7 %
n be supplied by biogas
boiler with a CHP plant -> the aim was to produce as much heat as we need for running the processes; the electric energy is going to be
heat recovery?
possible zu produce - multiplied by operation hours of the year we get the produced energy during the year
suggestions:
-) we produce biogas from waste water; with the biogas we can run a cogeneration /CHP (combined heat and power) to pro
is it possible to use the heat from CHP to heat the fresh water for the washer????
-) solar power we can use for preheating
-) waste heat (exhaust air) from the dryer has 70° - this can be used für pre heating the cleaning water (from 11° to 55°)
operating hours per yea 4500 h/a all processes are operating 4500h/a
E1= 1155015 kWh/a with using the operatin hours the energy demand can be calculated
E2= 1845301.5 kWh/a with using the operatin hours the energy demand can be calculated
fresh water energy de 1845301.5 kWh/a we do not take solar energy for heating the fresh water for the washer - s
solar ratio= 1.04 solar ratio (S kWh_solar/kWh_process; question to be answered: how lar
fresh water for cleanin 1155015 kWh/a we deside to use the solar energy for heating the general cleaning water
solar ratio= 1.66 solar ratio (S kWh_solar/kWh_process; question to be answered: how lar
with biogas produced from waste water we can run a CHP plant or replace some natural gas at the boiler
? electricity produced
? heat produced
using renewable sources to supply the remaining energy demand
ombined heat and power) to produce electricity and use the heat in our process
he fresh water for the washer - solara ratio is around 1 - this leads to high system costs for sesonal storage, we desided to use here a he
uestion to be answered: how large is the storage
ating the general cleaning water - no sesonal storage necessary, cheeper system costs
uestion to be answered: how large is the storage
as at the boiler
e, we desided to use here a heat recovery system from the processes
Pinch analyse
m m m cp m*cp T_in
air for dryer 1 m_air 1.77 1 1.77 11
cleaning water 2 m_cw 1.38890693 4.2 5.83340909 11
fresh water 3 m_washer 1.415 4.2 5.943 11
waste water A m_ww 1.33 4.2 5.586 80
humid air B m_HA 1.76890909 1 1.76890909 180
flue gas C m_FG 0.66217949 1.2 0.79461538 150
T Q_cold Q_hot
10 596.042
20 596.042 -39.730769
30 596.042 -39.730769
40 596.042 -39.730769
50 596.042 -39.730769
60 192.825 -39.730769
70 192.825 -39.730769
80 192.825 -81.495245
90 177 -179.44671
100 177 -179.44671
110 177 -179.44671
120 177 -179.44671
130 177 -179.44671
140 177 -179.44671
150 177 -179.44671
160 177 -53.067273
170 177 -53.067273
180 177 -53.067273
T_out Q (kW)
180 299.13
55 256.67
80 410.067
70 -55.86
70 -194.58
20 -103.3
Economic evaluation
Invest 10000 €
life time 8 years
Inflation Barwert
Erlössteigerung
Kostendegression
zirkelbezug
x= 0.80280373
x= 0.80280373 Zirkeltbezug unter Optionen -> Formel-> interative Kalkulationen erlauben
kulationen erlauben