Siemens BS240XL Installation Guide

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
2/13
guide

Siemens BS240XL Installation Guide

1. Installation

1.1 Room Layout

Picture 1: Site Layout for Shelter.

To every indoor site we try to follow the layout that is shown above. RBS cabinet must be
installed left of the door and close to the wall. The margins we must leave are shown in the
next diagram. To the back, about 150mm and to the left close to the wall. In front it must
have 750mm margin.

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
3/13
guide

Picture 2: BTS margins

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
4/13
guide

1.2 Cabinet mounting


We mount the cabinet to the floor using the earthquake kit.

Back side of cabinet

Front side of the cabinet

Special screw for mounting


on cement floor. Comes with
cabinet.

Screw for mounting on wooden surfaces.


Picture 3: Earthquake kit 8mm diameter, 80mm length. It is similar to
that we use for RBS Ericsson.

· Fix the back side earthquake kit on the floor.


· Push the cabinet so as to insert the feet into the kit. Perhaps you should move the
220VAC socket and the light switch before install the cabinet.
· Mount the last two parts at the front side feet.
· Put a metal plate to mount the top of the cabinet
· If the installation is inside a shelter, move the electric sockets.

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
5/13
guide

Picture 4: Installing earthquake kit

Metal plate to stabilize


the top of the cabinet.

Picture 5: Angle behind BTS.

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
6/13
guide

Picture 6: There are 2 angles at the back of the cabinet to mount them on the wall.

Picture 7,8: At the left picture is a wrong installation. At the right the sockets have been moved
to the correct positions.

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
7/13
guide

1.3 DC Feeding
BS240 takes DC voltage -48VDC from 2 cables 35mm2. The fuse is 50A.

Grounding cable 16mm2.


Terminates to main
grounding bar.(label is 1010
for first BTS, 1020 for
second)

DC power cables
2x35mm2.
Terminate to DC
power supply unit
(Sunlight).

Picture 9: DC cables

Connect DC
cables at position
3 of sunlight with
a fuse 50A (63 if
50A is not
available). Label
is 3110 for the
first cabinet. For
the second it is
3120.

Link PDU cables


must terminate at
high priority rail, at
position 6, 7 with
breakers 2x20A.
Labels must be
3010, 3011.

Picture 10: Sunlight breakers

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
8/13
guide

1.4 2Mbits Line


The cable that we use for ABIS has 4x4 wires and a grounding wire. Each quadruplet of
wires has three wires with the same color (white-purple- azure) and differs only to one wire
(blue or brown or orange or green). ABIS must be connected on top of the RBS to the
position it is shown below. The cover around the cable is the grounding and it is connected
only to one point, to the RL cabinet. The label of the cable must be 7111.

Picture 11: ABIS connector

Table 1: Configuration of the pins of terminal ABIS connector. To the pins 5, 6, 11, 12,
17, 18, 23, 24 that are the groundings we connect nothing. We ground Abis cable only to
RL cabinet.

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
9/13
guide

We connect each wire of the cable according to the table below. The pins with the (G) are groundings connected to cabinet’s main grounding.
We don’t connect anything to these pins.

Pins 1 3 5 (G) 7 9 11(G) 13 15 17(G) 19 21 23(G)


Wire Blue Purple Brown Purple Orange Purple Green Purple
Colors
Krone 8 (RX D) 6 (RX C) 4 (RX B) 2 (RX A)
Position
Pins 2 4 6 (G) 8 10 12(G) 14 16 18(G) 20 22 24(G)
Wire White Azure White Azure White Azure White Azure
Colors
Krone 7 (TX D) 5 (TX C) 3 (TX B) 1 (TX A)
position
4st quadruplet 3nd quadruplet 2rd quadruplet 1th quadruplet

Table 2: Connections on BTS

Krone 1a 1b 2a 2b 3a 3b 4a 4b 5a 5b 6a 6b 7a 7b 8a 8b
pin
BTS pin 20 22 19 21 14 16 13 15 8 10 7 9 2 4 1 3
Wire White Azure Green Purple White Azure Orange Purple White Azure Brown Purple White Azure Blue Purple
Color
Mode TX+ TX- RX+ RX- TX+ TX- RX+ RX- TX+ TX- RX+ RX- TX+ TX- RX+ RX-
PCM ID PCM 1 PCM 2 PCM 3 PCM 4

Table 3: Connections on Krone

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
10/13
guide

1.5 External Alarms


Inside every Siemens cabinet there is a termination point for 12 alarms. This point lies in
front of the cabinet, up-right. These positions are for special sensors of the cabinet but we
can use them for external alarms. But from these 12 positions only 7 are available to connect
external alarm cables. The label for the cable from BTS to RL cabinet is 6113.

Picture 12: Alarm module

Table 4: Operation of each pin at alarm module

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
11/13
guide

We will make the connections as described below. The alarm cable that transfers the alarms
from ADF to cabinet must be marked 6113.

Alarm Definition at Siemens BS240XL with Sunlight and MPB


BTS ENVBTSE Alarm Declaration Position
pins Number on Krone
13-14 ENVBTSE 2 MPB Door Open 5
11-12 ENVBTSE 3 MPB Temperature too High 2
9-10 ENVBTSE 4 PSU Battery Discharge 14
7-8 ENVBTSE 5 MPB Aviation Light Failure 9
5-6 ENVBTSE 6 PSU Mains Failure 11
3-4 ENVBTSE 7 PSU Rectifer non Urgent 16
1-2 ENVBTSE 8 PSU DC Voltage < 47V 12

Table 5: Alarm connections with Sunlight

Alarm Definition at Siemens BS240XL with Antrice and MPB


BTS ENVBTSE Alarm Declaration Position
pins Number on Krone
13-14 ENVBTSE 2 MPB Door Open 5
11-12 ENVBTSE 3 MPB Temperature too High 2
9-10 ENVBTSE 4 MPB Fire Detected 7
7-8 ENVBTSE 5 MPB Aviation Light Failure 9
5-6 ENVBTSE 6 PSU Mains Failure 11
3-4 ENVBTSE 7 PSU Rectifier non Urgent 12
1-2 ENVBTSE 8 PSU DC Voltage < 47V 14

Table 6: Alarm Connections with Antrice

Alarm Definition at Siemens BS240XL with Antrice and Single Sensors


BTS ENVBTSE Alarm Declaration Position
pins Number on Krone
13-14 ENVBTSE 2 Door Open 5
11-12 ENVBTSE 3 Temperature too High 2
9-10 ENVBTSE 4 Fire Detected 7
7-8 ENVBTSE 5 PSU Mains Failure 11
5-6 ENVBTSE 6 PSU Rectifier Urgent 13
3-4 ENVBTSE 7 PSU Rectifier non Urgent 12
1-2 ENVBTSE 8 PSU DC Voltage < 47V 14

Table 7: Alarm Connections with Antrice

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
12/13
guide

1.6 Jumpers
Jumpers are female straight - male angle, 1.5m long They come with the cabinet. Installer
must cut the plastic insulation at the point where it touched RBS (see photo). Also pay
attention to second jumper of DUAMCO 3 because it obstructs HALCA connector to
connect on BTS.

This jumper must be put


here because of Local
Management port.

Picture 13: Jumper installation at BTS.

Date: 13-02-2006 Version: 05


Siemens BS240XL Installation
13/13
guide

Contents

Siemens BS240XL Installation Guide......................................................................................... 2


1. Installation ...................................................................................................................... 2
1.1 Room Layout .......................................................................................................... 2
1.2 Cabinet mounting .................................................................................................... 4
1.3 DC Feeding ............................................................................................................. 7
1.4 2Mbits Line............................................................................................................. 8
1.5 External Alarms .................................................................................................... 10
1.6 Jumpers ................................................................................................................. 12

Date: 13-02-2006 Version: 05

You might also like