Configuration Guide for

ZXDU68 S/W201 V5.0


Configuration Guide

 Alarms Configuration

 Battery Configuration

 IP Configuration

© ZTE Corporation. All rights reserved.


Alarms Configuration

1. Alarms Planning

2. Hardware Connection

3. Alarms Configuration

© ZTE Corporation. All rights reserved.


Alarms Planning
ZTE Power Existing Dry Contacts' No.
Claro's Requirements CLARO Hardware Interface
Alarms Suggested
LLVD1 Alarm
BLVD Alarm Bajo Voltaje
DC Failure Pin1~Pin3 of X16 on
ALARMA 1 A5
(Falla DC) Batt.Volt.Low SIB
(COLOR VERDE)
DC Volt.Low
SMR Fan Fault
SMR Out.V.H.O.
SMR Out.C.H.
SMR Out.Fuse
PFC Out.V.H.
PFC Out.V.L.
Critical fail of Rectificador Mayor
SMR EEPROM Pin4~Pin6 of X15 on
rectifier ALARMA 2 A4
SIB
(Rectificador Mayor) (COLOR CAFE)
SMR In.Comm F.

SMR Start Abr.


SMR In.Fuse
SMR Input Off

SMR Out.V.L.

Puerta Abierta
Door Alarm Pin4~Pin6 of X16 on
Door Alarm ALARMA 3 A6
(Rectificador Menor) SIB
(COLOR NARANJA)
Falla A/C
AC Failure
AC Power Off ALARMA 4 A3 Pin1~Pin3 of X15 on
(Falla AC)
(COLOR AZUL) SIB

© ZTE Corporation. All rights reserved.


Alarms Configuration

1. Alarms Planning

2. Hardware Connection

3. Alarms Configuration

© ZTE Corporation. All rights reserved.


Hardware Connection
A1 as example

© ZTE Corporation. All rights reserved.


Hardware Connection
A1 as example

Hardware Description:
COM1 is short with NC1 when alarm disappear;
COM1 is short with NO1 when alarm generate.

Notes: To use COM1/NC1 or COM1/NO1 is base on the main


equipment. Normally, we use COM1/NO1

© ZTE Corporation. All rights reserved.


Alarms Configuration

1. Alarms Planning

2. Hardware Connection

3. Alarms Configuration

© ZTE Corporation. All rights reserved.


Alarms Configuration
LLVD1 alarm as example

Notes:
1. To config all the other alarms base on Alarms Planning one by one;
2. To change alarms which are config Dry Contact A3~A6 on default into other Dry Contacts
(A1 or A2) or No(No is suggested) ;
3. The alarms which are mask on default no need to change
© ZTE Corporation. All rights reserved.
Configuration Guide

 Alarms Configuration

 Battery Configuration

 IP Configuration

© ZTE Corporation. All rights reserved.


Battery Configuration
To config Battery Cap.-3# as example

Notes:
1. To config all the other battery cap. one by one;
2. To config the battery cap. 0000AH if there is no battery to connect.

© ZTE Corporation. All rights reserved.


Configuration Guide

 Alarms Configuration

 Battery Configuration

 IP Configuration

© ZTE Corporation. All rights reserved.


IP Configuration

Notes:
1. To config Local IP Mode to Static;
2. To config Local IP, Mask and Gateway supplied by Claro.

© ZTE Corporation. All rights reserved.


Cableado de Alarmas en SIU ZTE

© ZTE Corporation. All rights reserved.


Cableado de Alarmas en Flexi

© ZTE Corporation. All rights reserved.