You are on page 1of 2

7 Fuel

1) Fuel Gas
Basically process off-gas from the CDW Unit will be utilized.
The balance of the fuel gas requirement will be imported from the existing Dumai
Refinery.

Property and Battery Limit Condition

Process Off-Gas (*1) Imported


Property
100N EOR 150N SOR NP (*3) LPG
Sp. Gravity (Air = 1.00) 0.414 0.418 0.6696 1.8
Molecular Weight 11.98 12.12 - 52.4
NHV, kcal/Nm3 7086 7132 8164 25500
HHV, kcal/Nm3 7884 7945 8164 ―
Composition (mole%)
H2O 0.42 0.41 ― ―
H2S 0.02 0.02 3000 ppm ―
CO ― ― ― ―
CO2 ― ― ― ―
N2 ― ― ― ―
H2 72.74 71.35 53.90
C1 10.84 10.90 22.08 0.35
C2= ― ― 1.26 ―
C2 1.68 1.66 10.65 ―
C3= ― ― 0.80 ―
C3 5.13 6.39 5.71 40.99
C4= - - 0.80 0.05
iC4 3.27 4.67 3.41 30.45
nC4 2.84 4.29 0.41 26.48
C5+ 3.04 0.31 1.68
C5= ― ―
iC5 0.51
nC5 0.25
C6+ 0.22
Total 100.0 100.0 100.0 100.0
Battery Limit Condition
Temperature, oC
Normal 38 45
Mechanical Design 95 80
Pressure, kg/ ㎠ (g)
Min/Nor/Max 2.0/3.5/3.5 2.6/3.0/3.5
Mechanical Design 5.6 5.3
Note) 1. Basically, process off-gas from the CDW unit will be utilized.
2. The balance of the fuel gas requirement will be supplied from LPG Vaporizer.
3. Pertamina UP-2 New Plant (HDC)