Sub: Proposal for Supply and Installation of Garbage Walk in Cold Room at Terminal – 1
of Nedumbassery Airport.

We thank you for the valuable enquiry /the courtesy extended to our executive during the
discussions. Please find here with our offer , as enumerated below for your kind perusal .
For your easy evaluation we have segregated the proposal as below;

• Basis of Design & Technical specifications


• Exclusions
• Bill of quantity & Price schedule
• Commercial Terms and Conditions

In case of any clarifications, please feel free to get in touch with us.
Thanking and assuring you of our best attention and service at all times.

Yours Faithfully

For RINAC INDIA LTD

GOPI KIRAN
8594078857.

Regd Off: #5, Saraswathi Niwas, Main Channel Road, Saraswathipuram, Ulsoor, Bangalore 560008
Tel: 91-80- 25542998, 41132929/ 98, Fax : 25511750 mail. rilco@rinac.com www.rinac.com

Offer Reference : CS/2485/17-18


39/5568-G,II Floor , JAS Arcade , Thaundayil Road , Panampilly Nagar , Kochi – 682 036
Tele fax:0484-2326165 ; www.rinac.com

TECHNICAL PROPOSAL FOR GARBAGE WALK IN CHILLER


This proposal would include supply and installation of 1 Chiller .Wall, ceiling & floor are to
be constructed using Pre-fabricated PUF insulated panels. Freon-based split type refrigeration
systems would be provided for refrigerating rooms. Any civil & structural works including
finished floor, secondary roofing etc. shall be in the scope of customer / other agencies.

General Specifications

Room enclosures for the above mentioned rooms are proposed to be constructed using
modular panels of sandwich type. Panels are manufactured with CFC-free blowing agent.
Wall & ceiling are proposed to be constructed using Pre-Fabricated Rigid Polyurethane Foam
(RPUF) insulated panels. Panels shall be laminated with PCGI sheet outside and SS 304
Sheet inside for non exposed walls and ceiling and SS 304 Sheet on both sides for exposed
walls as per Specification / Layout. The PCGI lamination color shall be RAL 9002 (off
white). The wall to wall & ceiling to ceiling shall have profiled edges and the joinery shall be
with tongue-and-groove arrangement. Chiller room shall be provided with 80 mm thick
panels as mentioned in the BOQ. The wall to ceiling joinery shall be held using flashing from
inside & outside. All the resulting panel joinery shall be applied with silicon sealant.
The floor shall be constructed using PUF slabs with polythene sheet as vapor barrier. Floor
insulation has not been considered for ante rooms. PCC / other tiles in ante room shall be in
the scope of customer.

The doors for chiller room shall be Face-mounted – Step - swing type with thickness &
lamination same as wall panels. The door frame (and leaf in case of freezer rooms) shall be
provided with heaters for avoiding condensation as a resultant of moist air touching the cold
surface. The door shall be provided with locks from outside. The door shall be provided with
internal safety release mechanism so that people when accidentally locked inside can come
out even when the door is locked from outside. An electrical safety buzzer switch shall also
be provided with illumination near the door, so that the trapped person can call for a help.
Doors are provided with strip curtain to minimize infiltration . Chiller door is provided with
view port and SS Kick Plate. Doors shall have Fermod make Locks and Hinges.

The refrigeration system shall be split type of suitable capacity with Air Cooled Condensing
Units located outside the rooms and the Evaporator Units located inside the rooms with
interconnecting copper piping & cabling works. The condensing unit shall house suitable
capacity Hermetic Hermetic compressor, condenser coil with fans & interconnecting piping
with necessary valves fittings & accessories. Electrical starter panel for the full unit shall be
mounted inside the condensing unit. Necessary power will be terminated by client at each
condensing unit.

Regd Off: #5, Saraswathi Niwas, Main Channel Road, Saraswathipuram, Ulsoor, Bangalore 560008
Tel: 91-80- 25542998, 41132929/ 98, Fax : 25511750 mail. rilco@rinac.com www.rinac.com

Offer Reference : CS/2485/17-18


39/5568-G,II Floor , JAS Arcade , Thaundayil Road , Panampilly Nagar , Kochi – 682 036
Tele fax:0484-2326165 ; www.rinac.com

The evaporator cabin shall be constructed using SS casing. All the refrigerant tubes shall be
with copper construction & Al fins. The evaporator shall be provided with suitable fin
spacing to allow sufficient frost build up to enable longer operation hrs between defrost.
Defrost shall be settable time-based auto-off cycle type for chiller .

The interconnecting copper piping shall be generously designed to minimize the pressure
drop in the system. The suction line shall be insulated with Nitryl rubber to avoid sweating. A
PVC/GI drain pipe with necessary U trap shall be provided to take out the condensate water
outside the cold rooms.

Internal Lighting of the rooms shall be provided with vapor proof fittings along with
necessary interconnecting cabling works & the light switch located conveniently near the
door.

The compressor on/off based on the load shall be controlled by a Micro processor based
temperature indicator-cum-controller which shall also control the defrost cycle, on/off of
fans, fault indications etc, thereby controlling the entire refrigeration system.

The Design shall be based on the following assumptions and inputs from your end :

Room: Garbage Walk in Chiller


Sl
Parameter Value
No
1 Ambient Temperature [in °C] 40 Deg C
Designed Room Temperature
2 4 Deg C
[± 2 °C]
3 Product to be stored Garbage
Product Incoming Temperature
4 30 Deg C
[°C]
Qty of Product stored per
5 300 Kg / day
Day/batch [in Kg]
6 Pull down time [Hrs] 12 Hrs
Specific heat [Cp] Above
7 4 kJ/Kg K
Freezing [kJ/Kg K]
8 External Room Size 2.15 X 2.40 X 2.70 m
9 Material of Insulation RPUF
10 Thickness of Insulation [mm] 80 mm
11 Wall Lamination In/Out SS/SS & SS/PCGI
12 Ceiling [In/Out] SS/PCGI
13 Serration on panel Yes
14 Type of floor insulation RPUF
Thickness of Floor insulation
15 80mm
[mm]
16 Flooring PCC/Tiles in Client Scope

Regd Off: #5, Saraswathi Niwas, Main Channel Road, Saraswathipuram, Ulsoor, Bangalore 560008
Tel: 91-80- 25542998, 41132929/ 98, Fax : 25511750 mail. rilco@rinac.com www.rinac.com

Offer Reference : CS/2485/17-18


39/5568-G,II Floor , JAS Arcade , Thaundayil Road , Panampilly Nagar , Kochi – 682 036
Tele fax:0484-2326165 ; www.rinac.com

17 Size of Door 900 x 2000 mm


Swing, Panel mounted – Step Type type, 80mm
18 Type of Door thick, SS finish with view port, SS Kick Plate
and strip curtain.
19 Type of refrigeration system Split Type
20 Type of Cooling DX Type
Capacity of Refrigeration
21 3 KW
system [KW ]
22 Type of Refrigerant R404a
23 Type of Compressor Hermetic
24 Type of Condenser Air-Cooled
25 Model of Condensing Unit sCAHP0403ZMH
26 No of Condensing Units 1 No.
27 Model of Evaporator unit SEUP03ZPMH
28 No of Evaporator Units 1 No.
29 Electrical Panel for Ref System Inbuilt in condensing unit
30 Type of evaporator units Forced Air Cooled
31 MOC for evaporator units SS Casing, Cu Tubes, Al Fins
Temperature / humidity
32 Micro Processer based
indicator-cum-controller
33 Lighting Inside the rooms Suitable for 50 Lux luminosity
34 Type of light fitting Vapour proof Twin
Interconnecting piping and
6 RMT considered. Additional distances shall be
35 wiring between the Cond units
charged on RMT basis @ 2020 / mtr
and Evap units
Power Supply
36 4.12 KW , 415 V, 50 Hz, 3 ph
( Connected load )

Regd Off: #5, Saraswathi Niwas, Main Channel Road, Saraswathipuram, Ulsoor, Bangalore 560008
Tel: 91-80- 25542998, 41132929/ 98, Fax : 25511750 mail. rilco@rinac.com www.rinac.com

Offer Reference : CS/2485/17-18


39/5568-G,II Floor , JAS Arcade , Thaundayil Road , Panampilly Nagar , Kochi – 682 036
Tele fax:0484-2326165 ; www.rinac.com

EXCLUSIONS

1. Safe unloading & storage of the panels, equipments & erection material.

2. Any civil & structural works, including floor finish inside ante rooms, secondary
roofing, etc.

3. Platform and weather protection for the condensing units and trays for piping and
cabling.

4. Incoming power factor corrected power to the main electrical panel

5. Condensate Drain connection to drain point. We have considered piping to the nearest
floor level.

6. Single phase 415 V, 50 Hz, 3 ph power supply for installation activity.

7. Adequate lighting arrangement for installation activities.

8. Provision of lights other than inside the rooms mentioned in the design.

9. Inter connecting piping & cabling has been calculated based on the assumption as
mentioned in the design. Additional distance will be charged on RMT basis .

10. Primary member for suspension of air cooling units, if required.

11. Any other items other than specified in our bill of quantities and scope of work.

*****************

Regd Off: #5, Saraswathi Niwas, Main Channel Road, Saraswathipuram, Ulsoor, Bangalore 560008
Tel: 91-80- 25542998, 41132929/ 98, Fax : 25511750 mail. rilco@rinac.com www.rinac.com

Offer Reference : CS/2485/17-18


39/5568-G,II Floor , JAS Arcade , Thaundayil Road , Panampilly Nagar , Kochi – 682 036
Tele fax:0484-2326165 ; www.rinac.com

BOQ AND PRICE SCHEDULE


Supply
Sl Supply - Installation
Part No / Description Qty UOM [INR] –
No Ref System [INR]
Panels
A Garbage Walk in Chiller - 2.15 x 2.40 x 2.70 Mtr
1 80 mm PUF panel - Wall SS/SS 5.91 Sqmt
2 80 mm PUF panel - Wall PCGI/SS 18.77 Sqmt
3 80 mm PUF panel - Ceiling PCGI/SS 5.16 Sqmt
80mm PUF slab with polythene sheet
4 5.16 Sqmt
for floor panel
5 Flashing with necessary Fastners 38.00 Rmt
900 x 2000mm SS panel door 80 mm
6 thk step type with SS Kick Plate & 1.00 Nos
View Glass 300x 300 mm
7 Strip curtain for Positive Temperature 1.00 Nos
8 Vapor proof light – twin 1.00 Nos 176,426 130,508 40,245
Air cooled condensing unit with
canopy of 3 KW capacity suitable for
9 +4 deg C room condition with 1.00 Nos
hermatic compressor suitable for Std
ambient condition (sCAHP0403ZMH)
Evaporator unit with SS casing of 3
kW ref capacity for positive
10 1.00 Nos
temperature with medium velocity fans
- EUP03ZPMH
Copper Piping and Power Cabling - 6
11 1.00 Nos
mtr

TOTAL
1 Supply Value Basic Ex-Works [INR] 306,934
2 Installation Value Basic [INR] 40,245
Total Basic ( Supply + Installation) 347,179

GST extra @ 18 % for supply of PUF Panels , Doors and Accessories


GST extra @ 18 % for supply of Refrigeration Systems, Freight and other levies etc. extra as
applicable.
IGST extra @ 9 % for Installation
CGST extra @ 9 % for Installation
Freight extra @ actual from RINAC Bangalore Works ( Rs 20,000/- approximate )

Any variation in taxes and duties including fresh levies during the execution of the order shall be to
the Purchaser’s account.

*****************

Regd Off: #5, Saraswathi Niwas, Main Channel Road, Saraswathipuram, Ulsoor, Bangalore 560008
Tel: 91-80- 25542998, 41132929/ 98, Fax : 25511750 mail. rilco@rinac.com www.rinac.com

Offer Reference : CS/2485/17-18


39/5568-G,II Floor , JAS Arcade , Thaundayil Road , Panampilly Nagar , Kochi – 682 036
Tele fax:0484-2326165 ; www.rinac.com

Commercial Terms & Conditions

1. Scope

The price offer made by RINAC is based on the technical specification furnished by the
Purchaser subject to the technical offer, bill of quantities and such other technical information
furnished by RINAC.

2. Drawings

In the event of an order, RINAC shall submit a detailed drawing for the approval of the
Purchaser and the approved drawings thereafter shall form the basis for execution.

3. Inspection

The price offer of RINAC is based on inspection and final testing at site after installation,
unless otherwise specified elsewhere by RINAC. The offer does not include factory testing /
inspection, any independent laboratory testing and such other inspection / testing of any kind.
The final testing shall however be based on mutually agreed parameters and methods.

4. Price basis

The price quoted by RINAC is based on all the input credits that are applicable as per the
laws of the land. All terminal duties, taxes and other Government levies, as applicable shall
be paid extra by the Purchaser to RINAC. In the event of any concessional taxes and duties
availed by the Purchaser through statutory forms or Government notifications, RINAC shall
agree for such deduction subject to applicability and reversal of input credit as may be
required.

5. Taxes & Duties

The price quoted by RINAC is based on current level of GST and other levies as applicable.
Should there be any statutory variation of taxes and duties, including fresh levies at the time
of execution, the same shall be charged extra and shall become payable by the Purchaser to
RINAC.

6. Lien on property

RINAC shall hold the lien on all the materials supplied to the Purchaser until the full payment
is made to RINAC as per the terms of the contract.

7. Execution period
Regd Off: #5, Saraswathi Niwas, Main Channel Road, Saraswathipuram, Ulsoor, Bangalore 560008
Tel: 91-80- 25542998, 41132929/ 98, Fax : 25511750 mail. rilco@rinac.com www.rinac.com

Offer Reference : CS/2485/17-18


39/5568-G,II Floor , JAS Arcade , Thaundayil Road , Panampilly Nagar , Kochi – 682 036
Tele fax:0484-2326165 ; www.rinac.com

The time frame for supply and erection shall be considered from the date of technically and
commercially clear order. Further, the commitment on execution period shall be subject to
standard force majeure condition.

8. Force majeure condition

The Purchaser shall grant extension of execution period automatically without any damages
to RINAC in the event of force majeure condition which shall include but not restricted to
natural disasters like earth quakes, floods, hurricanes, riots, wars, war like situation, other
major social upheavals, Government restrictions, strikes, lock-outs and other acts of God
which does not fall under the normal control of RINAC.

9. Terms of payment

Unless otherwise specifically agreed by RINAC in writing,

All the supplies of RINAC shall be covered under the following terms of payment:

a. 50% of the basic contract value as advance along with the order
b. 50% of the basic contract value + 100% of taxes, duties, freight etc. against readiness
of material or documents through bank

The payment against erection shall be made as below:

a. 30% of the basic contract value as advance along with the order
b. 60% of the basic contract value + 100% of taxes and duties against pro-rata
completion of erection activity
c. 10% of the basic contract value against commissioning and handing over.

Any statutory deduction, if made, shall be supported through a TDS Certificate within 30
days of such deduction. No other deduction shall be made for any other reason whatsoever.

10. Bonus / Liquidated damages

Neither party shall be liable for any bonus / liquidated damages for supplies earlier or latter
than the contractual period, unless otherwise specifically agreed by RINAC.

11. RINAC shall not furnish any guarantees, indemnity bond or such other document unless
otherwise specifically agreed in writing.

Regd Off: #5, Saraswathi Niwas, Main Channel Road, Saraswathipuram, Ulsoor, Bangalore 560008
Tel: 91-80- 25542998, 41132929/ 98, Fax : 25511750 mail. rilco@rinac.com www.rinac.com

Offer Reference : CS/2485/17-18


39/5568-G,II Floor , JAS Arcade , Thaundayil Road , Panampilly Nagar , Kochi – 682 036
Tele fax:0484-2326165 ; www.rinac.com

12. Warranty

RINAC shall offer a standard warranty of 12 months from the date of commissioning or 15
months from the date of invoice whichever is earlier against manufacturing defects,
installation deficiencies and such other reasons attributable to RINAC. This warranty
however shall not cover in the event of damage caused by accident, abuse, mis use and used
for application different to those to which it is intended. Further, warranty shall remain
invalid in the event of the product / system attended by any persons or agencies not
authorized by RINAC. Any modification, alterations etc., if made, to the original equipment,
shall render the warranty invalid.

13. Validity

Unless otherwise specifically confirmed in writing by RINAC, the price offer shall remain
valid for acceptance by the Purchaser for a period of 30 days from the date of offer beyond
which it is subject to confirmation in writing by RINAC.

14. Dispute / resolution

In the unlikely event of any unresolved dispute, the same shall be settled in accordance with
the Indian Arbitration and Conciliation Act 1996 subject to all amendments till date.

15. Power & Water supply

Unless otherwise agreed by RINAC in writing, the power and water supply connections shall
be obtained by the Purchaser for both construction and for final testing.

16. Approval from statutory authorities

All approval from statutory authorities like Electricity Dept, Water & Sewerage Dept,
Pollution Control Board, Forest Dept. etc as may be required shall be obtained by the
Purchaser and RINAC shall render all assistance in terms of drawings, technical data etc.
which falls under their purview.

17. Variation in quantities

All variation in quantities, post award of the contract during drawing approval or at later
stage shall be suitably price corrected in accordance with the unit rates already available in
the contract or in the quotation submitted by RINAC. If there are any items required for
execution but not quoted, the same shall be price adjusted through a revised quote to be
furnished by RINAC.
* * * * * * *

Regd Off: #5, Saraswathi Niwas, Main Channel Road, Saraswathipuram, Ulsoor, Bangalore 560008
Tel: 91-80- 25542998, 41132929/ 98, Fax : 25511750 mail. rilco@rinac.com www.rinac.com

Offer Reference : CS/2485/17-18