CENTURION LABORATORIES

VALIDATION DOCKET
AIR HANDLING UNIT Page of

E.1 TROUBLE SHOOTING & PREVENTING MAINTENANCE SHCEDULE

E.1.1 Problem, Cause & Remedy for AHU system

Sr.
Problem Causes Remedy
No.
1 AHU system is not Insufficient Voltage Check connection for any
starting. loose joints
Main SFU has tripped / not Switch on switch or put a
switched on. new fuse.
2 Air flow of AHU Filters choked Clean the filters as per
system seems to be filter cleaning.
reduced. Cooling coil choked. Clean coil as per coil
cleaning procedure.
Motor appears to rotate Rewind the motor or
slowly. replace bearing of motor.
Motor rotating in reversed Reverse phase connection
direction. at Motor terminal.
3 Cooling is less in AC Less air flow in room. Check the points as per
area. Sr. no.2
Low thermostat setting. Set the thermostat at set
point.
Compressor is not starting. Check contactor &
electrical accessories.
Refer to AC mechanic.
4 Temperature control in Low gas in AC system Refer to AC mechanic.
AC areas.
Resistance to outdoor Clear the obstruction if
condensing unit. any.
Fresh air damper is open Reset the damper as per
more than the set point. set point.
5 Manometer is showing Zero setting is disturbed. Set the Zero setting.
either low reading or
Air leakage from Door & Seal the leakages.
disturbed reading.
windows.
Reduced air flow in room. Check the points as per
Sr. no.2.
Fresh air damper setting Reset the damper as per
disturbed. set point.