DISCRIMINATION REPORT ON ELECTRICAL SERVICE

FOR WIPRO CMBT BLOCK-II.

PROJECT : WIPRO CMBT BLOCK-II,


COIMBATORE.

CLIENTS : WIPRO TECHNOLOGIES.

ARCHITECTS : C.R NARAYANA RAO, ARCHITECTS AND ENGINEERS

CONSULTANTS : SRIPEKSHA CONSULTANCY SERVICES

SUBJECT : Discrimination report for Electrical Service BLOCK-II.


Page 2/30

Discrimination report

Wipro Coimbatore

Information

Name : Anish G
First name :
Company : Schneider Electric India Pvt Ltd
Customer : Sripeksha Engineering Consultancy
Services Pvt Ltd

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 3/30

01.MSB-2 & SMSB-A

t(s) NW20H1-Micrologic 5.0 A-2000A


NW08H1-Micrologic 2.0 A-800A
NSX630N-Micrologic 2.3-630A

1000

100

10

0.1 NW08H1-Micrologic 2.0 A-800A : Total discrimination


NSX630N-Micrologic 2.3-630A : Total discrimination

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: Total Discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 4/30

Settings

Range Masterpact Masterpact Compact


Circuit-breaker NW20H1 NW08H1 NSX630N
Trip unit/curve Micrologic 5.0 A Micrologic 2.0 A Micrologic 2.3
Rating 2000.00 800.00 630.00
Long-time
Io 630.00
Ir 1.00 2000.0A 1.00 800.0A 1.00 630.0A
tr 24.0 24.0s 24.0 24.0s 16.0 16.0s
Short-time
Im/Isd 10.00 20000.0A 10.00 8000.0A 10.00 6300.0A
I�t (delay) OFF
tm/tsd 0.40 0.40s
Instantaneous
Ii OFF 6900.0A
Discrimination
Limit Upstream device Total discrimination Total discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 5/30

APFCR Panel-1&2

t(s) NSX400N-Micrologic 2.3-400A


NSX250N-TM-D-200A

1000

100

10

0.1

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: No Discrimination. To achieve Total Discrimination incomer to be changed to


NSX630N, 630A Micrologic 2.3, MCCB. Upstream MCCB to be changed acoordingly.

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 6/30

Settings

Range Compact Compact


Circuit-breaker NSX400N NSX250N
Trip unit/curve Micrologic 2.3 TM-D
Rating 400.00 200.00
Long-time
Io 320.00
Ir 1.00 320.0A 1.00 200.0A
tr 16.0 16.0s 15.0 15.0s
Short-time
Im/Isd 8.00 2560.0A
I�t (delay)
tm/tsd
Instantaneous
Ii 4800.0A 10.00 2000.0A
Discrimination
Limit Upstream device

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 7/30

UPS Input Panel

t(s) NSX630F-Micrologic 2.3-630A


NSX400F-Micrologic 2.3-400A
NSX160F-TM-D-160A

1000

100

10

0.1 NSX160F-TM-D-160A : Total discrimination

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: Discrimination Limit-6.9kA. To achieve Total Discrimination incomer to be changed to


NS800N, Micrologic 2, 800A MCCB. Upsteam MCCB to be changed accordingly.

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 8/30

Settings

Range Compact Compact Compact


Circuit-breaker NSX630F NSX400F NSX160F
Trip unit/curve Micrologic 2.3 Micrologic 2.3 TM-D
Rating 630.00 400.00 160.00
Long-time
Io 630.00 400.00
Ir 1.00 630.0A 1.00 400.0A 1.00 160.0A
tr 16.0 16.0s 16.0 16.0s 15.0 15.0s
Short-time
Im/Isd 8.00 5040.0A 8.00 3200.0A
I�t (delay)
tm/tsd
Instantaneous
Ii 6900.0A 4800.0A 1250.0A
Discrimination
Limit Upstream device Total discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 9/30

UPS OP Panel

t(s) NSX630F-Micrologic 2.3-630A


NSX400F-Micrologic 2.3-400A

1000

100

10

0.1

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: No Discrimination. Total Discrimination cannot be achieved as the incomer is lesser
than outgoing, since UPS are operated in parallel.

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 10/30

Settings

Range Compact Compact


Circuit-breaker NSX630F NSX400F
Trip unit/curve Micrologic 2.3 Micrologic 2.3
Rating 630.00 400.00
Long-time
Io 630.00 400.00
Ir 1.00 630.0A 1.00 400.0A
tr 16.0 16.0s 16.0 16.0s
Short-time
Im/Isd 8.00 5040.0A 8.00 3200.0A
I�t (delay)
tm/tsd
Instantaneous
Ii 6900.0A 4800.0A
Discrimination
Limit Upstream device

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 11/30

MSB MSR SA & SB

t(s) NSX400F-Micrologic 2.3-400A


NSX160B-TM-D-160A

1000

100

10

0.1

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: Total Discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 12/30

Settings

Range Compact Compact


Circuit-breaker NSX400F NSX160B
Trip unit/curve Micrologic 2.3 TM-D
Rating 400.00 160.00
Long-time
Io 400.00
Ir 1.00 400.0A 1.00 160.0A
tr 16.0 16.0s 15.0 15.0s
Short-time
Im/Isd 8.00 3200.0A
I�t (delay)
tm/tsd
Instantaneous
Ii 4800.0A 1250.0A
Discrimination
Limit Upstream device

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 13/30

NTC SMSB SB

t(s) NSX100B-Micrologic 2.2-100A


NSX100B-TM-D-63A

1000

100

10

0.1

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: No Discrimination. To achieve Total Discrimination incomer MCCB to be changed to


NSX250B, Micrologic 2.2 set at 160A.

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 14/30

Settings

Range Compact Compact


Circuit-breaker NSX100B NSX100B
Trip unit/curve Micrologic 2.2 TM-D
Rating 100.00 63.00
Long-time
Io 100.00
Ir 1.00 100.0A 1.00 63.0A
tr 16.0 16.0s 15.0 15.0s
Short-time
Im/Isd 8.00 800.0A
I�t (delay)
tm/tsd
Instantaneous
Ii 1500.0A 500.0A
Discrimination
Limit Upstream device

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 15/30

Fire Mode Panel

t(s) NSX630F-Micrologic 2.3-630A


NSX160F-TM-D-125A
NSX100F-TM-D-80A

1000

100

10

0.1 NSX160F-TM-D-125A : Total discrimination


NSX100F-TM-D-80A : Total discrimination

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: Total Discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 16/30

Settings

Range Compact Compact Compact


Circuit-breaker NSX630F NSX160F NSX100F
Trip unit/curve Micrologic 2.3 TM-D TM-D
Rating 630.00 125.00 80.00
Long-time
Io 630.00
Ir 1.00 630.0A 1.00 125.0A 1.00 80.0A
tr 16.0 16.0s 15.0 15.0s 15.0 15.0s
Short-time
Im/Isd 8.00 5040.0A
I�t (delay)
tm/tsd
Instantaneous
Ii 6900.0A 1250.0A 640.0A
Discrimination
Limit Upstream device Total discrimination Total discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 17/30

MCR PAC Panel

t(s) NSX160B-TM-D-125A
NSX100B-TM-D-100A

1000

100

10

0.1

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: No Discrimination. To achieve Total Discrimination outgoing 100A MCCB to be


changed t0 63A, D Curve Acti9 MCBs since the CL is 35kW.

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 18/30

Settings

Range Compact Compact


Circuit-breaker NSX160B NSX100B
Trip unit/curve TM-D TM-D
Rating 125.00 100.00
Long-time
Io
Ir 1.00 125.0A 1.00 100.0A
tr 15.0 15.0s 15.0 15.0s
Short-time
Im/Isd
I�t (delay)
tm/tsd
Instantaneous
Ii 1250.0A 800.0A
Discrimination
Limit Upstream device

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 19/30

MSR PAC Panel

t(s) NSX160B-TM-D-160A
NSX160B-TM-D-125A

1000

100

10

0.1

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: No Discrimination. Discrimination Limit can be enhanced to 2kA by changing the
outgoing MCCB to NSX100B, 100A, TMD MCCB as the CL is 50kW.

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 20/30

Settings

Range Compact Compact


Circuit-breaker NSX160B NSX160B
Trip unit/curve TM-D TM-D
Rating 160.00 125.00
Long-time
Io
Ir 1.00 160.0A 1.00 125.0A
tr 15.0 15.0s 15.0 15.0s
Short-time
Im/Isd
I�t (delay)
tm/tsd
Instantaneous
Ii 1250.0A 1250.0A
Discrimination
Limit Upstream device

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 21/30

MSR-SB-1 & SA-1

t(s) NSX250B-TM-D-200A
C60H-D-32A

1000

100

10

0.1 C60H-D-32A : Total discrimination

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: Total Discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 22/30

Settings

Range Compact Multi9


Circuit-breaker NSX250B C60H
Trip unit/curve TM-D D
Rating 200.00 32.00
Long-time
Io
Ir 1.00 200.0A
tr 15.0 15.0s
Short-time
Im/Isd
I�t (delay)
tm/tsd
Instantaneous
Ii 10.00 2000.0A 384.0A
Discrimination
Limit Upstream device Total discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 23/30

MCR-SB-1 & MCR-SA-1

t(s) NSX100B-TM-D-100A
C60H-D-32A

1000

100

10

0.1 C60H-D-32A : 0.8kA

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: Discrimination Limit-0.8kA. To achieve Total Discrimination incomer MCCB to be


changed to NSX100B, Micrologic 2.2, 100A MCCB.

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 24/30

Settings

Range Compact Multi9


Circuit-breaker NSX100B C60H
Trip unit/curve TM-D D
Rating 100.00 32.00
Long-time
Io
Ir 1.00 100.0A
tr 15.0 15.0s
Short-time
Im/Isd
I�t (delay)
tm/tsd
Instantaneous
Ii 800.0A 384.0A
Discrimination
Limit Upstream device 0.8kA

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 25/30

Utility Panel-1

t(s) NSX250F-TM-D-200A
NSX100B-TM-D-63A

1000

100

10

0.1 NSX100B-TM-D-63A : Total discrimination

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: Total Discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 26/30

Settings

Range Compact Compact


Circuit-breaker NSX250F NSX100B
Trip unit/curve TM-D TM-D
Rating 200.00 63.00
Long-time
Io
Ir 1.00 200.0A 1.00 63.0A
tr 15.0 15.0s 15.0 15.0s
Short-time
Im/Isd
I�t (delay)
tm/tsd
Instantaneous
Ii 10.00 2000.0A 500.0A
Discrimination
Limit Upstream device Total discrimination

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 27/30

Lift Panel-4Nos

t(s) NSX100B-TM-D-100A

C60H-C-20A C60H-C-63A

1000

100

10

0.1 C60H-C-20A : 0.8kA


C60H-C-63A : 0.8kA

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: Discrimination limit-0.8kA. Discrimination Limit can be enhanced to 6kA for the 63A
Feeder and Total Discrimination for remaining feeders by changing the incomer MCCB to NSX100B,
Micrologic 2.2, 100A MCCB.

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 28/30

Settings

Range Compact Multi9 Multi9


Circuit-breaker NSX100B C60H C60H
Trip unit/curve TM-D C C
Rating 100.00 20.00 63.00
Long-time
Io
Ir 1.00 100.0A
tr 15.0 15.0s
Short-time
Im/Isd
I�t (delay)
tm/tsd
Instantaneous
Ii 800.0A 150.0A 472.5A
Discrimination
Limit Upstream device 0.8kA 0.8kA

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 29/30

Main ELDB Panel

t(s) NSX100B-TM-D-80A
NSX100B-TM-D-40A

1000

100

10

0.1 NSX100B-TM-D-40A : 0.63kA

0.01
1 10 100 1000 10000 I(A)

Discrimination Status: Discrimination Limit-0.63kA. To achieve Total Discrimination incomer MCCB to be


changed to NSX100B, Micrologic 2.2 100A, MCCB and outgoing to be changed to Acti9 MCB C Curve.

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.
Page 30/30

Settings

Range Compact Compact


Circuit-breaker NSX100B NSX100B
Trip unit/curve TM-D TM-D
Rating 80.00 40.00
Long-time
Io
Ir 1.00 80.0A 1.00 40.0A
tr 15.0 15.0s 15.0 15.0s
Short-time
Im/Isd
I�t (delay)
tm/tsd
Instantaneous
Ii 640.0A 500.0A
Discrimination
Limit Upstream device 0.63kA

Project: Wipro Coimbatore 05/10/2018 11:19:07 AM

The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the
products contained herein.
This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for
specific user applications.
It is the duty of any such user or integrator to perform the appropriate and complete risk analysis, evaluation and testing of the products
with respect to the relevant specific application or use thereof.
Neither Schneider Electric Industries SAS nor any of its affiliates or subsidiaries shall be responsible or liable for misuse of the
information contained herein.