located in Duhok /Kurdistan-Iraq
Plan Details
Livingroom: 33 m² Bathroom: 7 m²
Bedroom: 15 m² Bathroom: 4 m²
Bedroom: 17 m² Kitchen: 18 m²
Bedroom: 13 m² Hall: 14 m²
Porch: 9 m²
Page 2 of 11
1-ROOF CONSTRUCTION
𝐐 = 𝐔 ∗ 𝐀 ∗ (𝐂𝐋𝐓𝐃)𝐜𝐨𝐫𝐫𝐞𝐜𝐭𝐢𝐨𝐧
U=0.71 -- From Table @152.4mm h.w concrete with25.4 insulation with suspended ceiling
K=1
(CLTD)correction = 40.2
𝑸 = 𝟒𝟐𝟓𝟐. 𝟕𝟓𝟖 𝑾
Page 3 of 11
2-WALLS
A- not partition wall ( exposure wall)
Q = U ∗ A ∗ (CLTD)correction
I) NORTH WALL
(CLTD)correction = [12 + 0.5] ∗ 1 + (25.5 − 22) + (46 − 29.4)
(CLTD)correction = 32.6
𝑸 = 𝟒𝟒𝟗𝟕. 𝟎𝟑𝟗𝟔 𝑾
(CLTD)correction = 41.1
𝑸 = 𝟒𝟗𝟐𝟎. 𝟒𝟓𝟗𝟏𝟐 𝑾
Page 4 of 11
IV) West WALL
(CLTD)correction = [27 + 0] ∗ 1 + (25.5 − 22) + (46 − 29.4)
(CLTD)correction = 47.1
𝑸 = 𝟓𝟔𝟑𝟖. 𝟕𝟕𝟒𝟑𝟐 𝑾
3-GLASSES
A- Conduction
𝐐 = 𝐔 ∗ 𝐀 ∗ 𝐂𝐋𝐓𝐃
CLTD=8 From Table
U=1
4 windows 1.5*1.5
Q = 1 ∗ (1.5 ∗ 1.5) ∗ 8
𝑸𝟏 = 𝟏𝟖 ∗ 𝟒 = 𝟕𝟐 𝑾
3 windows 1.5*1.1
Q = 1 ∗ (1.5 ∗ 1.1) ∗ 8
𝑸𝟐 = 𝟏𝟑. 𝟐 ∗ 𝟑 = 𝟑𝟗. 𝟔 𝑾
3 windows 1.5*0.5
Q = 1 ∗ (1.5 ∗ 0.5) ∗ 8
𝑸𝟑 = 𝟔 ∗ 𝟑 = 𝟏𝟖 𝑾
QTotal = Q1 + Q2 + Q3
Page 5 of 11
B-Solar:
Q = A ∗ SC ∗ SHFG ∗ CLF
SC=0.92From Table @ 10mm Clear
SHFG From Table
CLF From Table
I) NORTH GLASSES
𝑸 = 𝟕𝟔𝟐. 𝟎𝟏𝟗𝟒𝟒 𝑾
II) EAST GLASSES
𝑸 = 𝟏𝟕𝟐𝟒. 𝟒𝟒𝟖 𝑾
III) SOUTH GLASSES
𝑸 = 𝟑𝟔𝟔𝟗. 𝟖𝟔𝟏𝟔 𝑾
Page 6 of 11
4-LIGHTS:
𝑄 = 𝑁𝑂. 𝑂𝐹𝐿𝐼𝐺𝐻𝑇𝑆 ∗ 𝑊𝐴𝑇𝑇𝐴𝐺𝐸 ∗ 𝐶𝐿𝐹
No.of light=15
𝑄 = 15 ∗ 40 ∗ 0.93
𝑸 = 𝟓𝟓𝟖 𝑾
5-PEOPLE :
I) Sensible heat
𝑄𝑠 = 5 ∗ 75 ∗ (0.97)
𝑸𝒔 = 𝟑𝟔𝟑. 𝟕𝟓 𝑾
II) Latent heat
𝑄𝑙 = 5 ∗ 75
𝑸𝒍 = 𝟑𝟕𝟓 𝑾
Page 7 of 11
6-APPLIANCE:
I) Sensible heat
𝑄𝑠 = 10 ∗ 550 ∗ (0.73)
𝑸𝒔 = 𝟒𝟎𝟏𝟓 𝑾
II) Latent heat
𝑄𝑠 = 10 ∗ 100
𝑸𝒔 = 𝟏𝟎𝟎𝟎 𝑾
Page 8 of 11
7-VENTILATION
L/S/PERSON
𝐋/𝐬
𝑽̇𝒇 = 𝑵𝑶. 𝑶𝑭𝑷𝑬𝑹𝑺𝑶𝑵 ∗
𝑷𝑬𝑹𝑺𝑶𝑵
ṁ𝒇 = 𝑽̇ ∗ 𝝆
No.of Person=5
L/s/Person =3.5 from Table 6.1
Ρ=1.2 Kg/m3
Cp=1.022 Kj/Kg*C
𝑳 𝒎𝟑
𝑽̇𝒇 = 𝟓 ∗ 𝟑. 𝟓 = 𝟏𝟕. 𝟓 = 𝟎. 𝟎𝟏𝟕𝟓
𝑺 𝒔
𝒌𝒈
ṁ𝒇 = 𝟎. 𝟎𝟏𝟕𝟓 ∗ 𝟏. 𝟐 = 𝟎. 𝟎𝟐𝟏
𝒔
1) Sensible heat
𝑄𝑠 = ṁ𝒇 ∗ 𝐶𝑃𝑚 ∗ ∆𝑇
𝑸𝒔 = 𝟎. 𝟓𝟏𝟓𝟏 𝑲𝑾 = 𝟓𝟏𝟓. 𝟏𝑾
2) Latent heat
𝑄𝑙 = ṁ𝒇 ∗ ℎ𝑓𝑔 ∗ ∆𝑊
Hfg=2500 kj/kg
w2=0.011 from psychrometric chart
w1=0.0087 from psychrometric chart
𝑸𝒍 = 𝟎. 𝟏𝟐𝟏 𝑲𝑾 = 𝟏𝟐𝟏 𝑾
3) Total
𝑄𝑡 = 𝑄𝑠 + 𝑄𝑙
𝑄𝑡 = 515.1 + 121
𝑸𝒕 = 𝟔𝟑𝟔. 𝟏 𝑾
Page 9 of 11
8-INFILTRATION
ACH (AIR CHANGE PER HOUR)
ṁ𝒇 = 𝑽̇ ∗ 𝝆
Volume=Area*L=149*3
Ρ=1.2 Kg/m3
Cp=1.022 Kj/Kg*C
𝟏𝟒𝟗 ∗ 𝟑 𝐦𝟑
𝑽̇𝒇 = 𝟎. 𝟔𝟗 ∗ ( ) = 𝟎. 𝟎𝟖𝟓𝟕 = 𝟖𝟓. 𝟕 𝐋/𝐬
𝟑𝟔𝟎𝟎 𝐬
I) Sensible heat
Qs = ṁ𝐟 ∗ CPm ∗ ∆T
Qs = 𝟎. 𝟏𝟎𝟑 ∗ 1.022 ∗ (46 − 22)
𝑸𝒔 = 𝟐. 𝟓𝟐𝟐 𝑲𝑾 = 𝟐𝟓𝟐𝟐𝑾
II) Latent heat
Ql = ṁ𝐟 ∗ hfg ∗ ∆W
Ql = 𝟎. 𝟏𝟎𝟑 ∗ 2500 ∗ (0.011 − 0.0087)
𝑸𝒍 = 𝟎. 𝟓𝟗𝟐𝟐 𝑲𝑾 = 𝟓𝟗𝟐. 𝟐 𝑾
III) Total
Qt = Qs + Ql
Qt = 2522 + 592.2
𝑸𝒕 = 𝟑𝟏𝟏𝟒. 𝟐 𝑾
Page 10 of 11
Results Table
add 8%
Total Total Total heat gain
Q sensible Q latent for factor
ITEM heat heat gain Refrigeration
(W) (W) of safity
gain (W) (KW) Tons (RT)
(R.T)
Page 11 of 11