Professional Documents
Culture Documents
DA N S K ST A ND A RD S
Kollegievej 6 DK-2920 Charlottenlund
Tel:+45 39 96 61 01
Fax:+45 39 96 81 02
dansk.standards@ds.dk
www.ds.dk
DS publication form
Publication Types are published in different forms, as, respectively,
• full text publication (publication is printed in its entirety)
• approval sheet (publication is delivered as copy with a printed DS-cover)
• electronically (this publication is provided on an electronic media)
DS-designation
All DS-publications’ designations begin with DS followed by one or more prefixes and a number, for example, DS
383, DS/EN 5414 etc. If after No., an A or Cor is indicated, it means either that it is an appendix or an approval sheet
to the main standard, or that it is introduced into the main standard. The DS-name is indicated on the front.
Consistency with other publications:
Compliance can be either be IDT, EQV, NEQ or MOD
• IDT: When the publication is identical to a given publication.
• EQV: When the publication is technically in compliance with a given publication, but the
presentation has changed.
• NEQ: When the publication, technically or in terms of presentation, is not in accordance with a
given standard, but prepared on the basis of this standard.
• MOD: T When the publication has been modified in relation to a given publication.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Table of contents
Page
0 Preface ....... .................................................... ........... ...................................................................................... .......... 6
0.1 Entry into force ........................................................................................................................ ...................... ......... 6
0.2 Transitional provisions ...................................................................................................... ............. ........... ............ 6
0.3 Requirements of the building regulations ..................................................................... ........................................... 6
0.3.1 Common requirements for water and drainage installations .................. ............ .......... ...... .................. ......... 6
0.3.2 Water installations ....................................................................................................... ............... ....................... 7
0.3.3 Hot water ............................................... ........................................................ ..................................................... 8
0.3.4 Flooding ................................................................................................. ........... .... .... ........... ............... ........ 8
0.3.5 Materials, components and execution ............................................................ ...................................................... 8
0 Preface
The present, revised 4th edition of DS 439, Standard for water installations, has been prepared by the standardization
committee DS/S-314, Water supply.
The revision aims to bring the standard into compliance with changes of a legal and technical nature, which have been
introduced in the building regulations 2008. The revision does not include an actual update of the technical material. The
few changes that have been introduced are - apart from adaptation relating to hidden joints and water quality by tapping
sites - either consequential changes or corrections of typographical errors. The distinction between requirements and
guidelines has lapsed.
For water installations, most of the technical requirements have not previously been stated in the Building Regulations, but
have been included in DS 439, standard for water installations, which the Building Regulations refer to.
A key innovation is that part of the overall requirements in DS 439 is written directly into the Building Regulations.
Compliance with the requirements of the Building Regulations is mandatory.
All references to standards, etc., refer to the last, dated version of the mentioned publication.
2. Durability
Water and drainage systems must be made out of materials and components that are sufficiently durable against the
impacts and influences they are exposed to.
3. Density
Water and drainage systems must be so dense that accidental infiltration or leakage is avoided.
4. Placement
The placement of water and drainage systems in relation to building components, for example foundations or attachment to
building components, must be such that no damage can occur to the system or building components.
5. Materials
Components and materials must be in accordance with functional requirements.
8. Rainwater systems
Rainwater systems, where rainwater from roofs is used for toilets and washing machines in homes and similar residential
buildings, must be designed in accordance with the Ministry of the Environment’s Executive Order on water quality and
monitoring of water supply systems § 4, paragraph 1 and 2
11.Maintenance
Water and drainage systems must be maintained as necessary, so that they are kept in a safe technical and hygienic
condition.
15. Backflow
To protect the water supply system against pollution that flows back into the drinking water installation, a
backflow-safeguard must be installed on the distribution pipe after the soil pipe’s insertion into the property and before
branching to another pipe.
19. Overflows
Water systems must be designed so that inconvenient overflow from hot water to cold water systems can not occur.
24. Scalding
Water systems must be designed, so that during the tapping of water there is no risk of scalding, and so that no surface
temperatures occur that can cause injuries to persons.
0.3.4 Flooding
25. Leaks
Water systems must be designed so that there are adequate safeguards against spillage or leakage of water that can
cause damage to buildings. It must be possible to identify leaks.
29. Replaceability
Installation components that are positioned so that they are not replaceable, must be of such quality that they can last as
long as the building component, on which they are located. In the standard’s text, there is a reference to the requirements
of the building regulations, specified by: Requirement number fx/15/.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
1. Introduction
1.1 General
This standard - Standard for water systems – provides a series of instructions on the proper execution of water
systems in accordance with the general requirements contained in the building regulations.
This standard describes the general, functional requirements and provides examples and instructions on how these
requirements can be met. Other execution methods that meet the functional requirements, are approved in each case by
the local authority.
Questions of interpretation are referred to the standardization committee DS/S-314, Water supply.
1.2 Scope
This standard applies to water systems connected to public water supplies (public or private water supply
plants) and small non-public water supply systems.
The Building Regulations’ and the standard’s general functional requirements also apply to the part of the rainwater system
that includes the pipe system supplying toilets and washing machines with rainwater from the tank or other container,
Rainwater systems can be performed as described in the Pipe Centre-instruction 003, Use of rainwater for toilet flushing
and washing machines in homes.
The standard also applies to both new installations and modifications and additions to existing systems.
Repair of pipes and minor modifications when replacing single sanitation elements, fixtures, appliances, containers etc.,
can be performed with equipment and according to methods that were allowed at the time the system was installed.
Water systems include systems in buildings and in soil within the site boundary.
The Building Act applies to the entire country except the Faeroe Islands and Greenland.
Water systems
Factory-made products included in or connected to water systems, must, with regards to the characteristics that affect the
quality of the drinking water (see Ministry of the Environment’s Executive Order on water quality and monitoring of water
supply systems) be approved by the Enterprise and Construction Authority by ETA-Denmark A/S (VA-approval), unless the
product is exempted according to the then-current provisions for the approval scheme, or bears the CE-mark that shows
that the products are consistent with a harmonized standard or covered by a European technical approval with the relevant
requirements for Denmark.
Factory-made products included in or connected to water systems, must, with regards to the mechanical/physical
characteristics, either be:
• equipped with a CE-mark that shows that the products are consistent with a harmonized standard, or are covered
by a European technical approval with the relevant requirements for Denmark
• or have completed a production inspection and testing under a special procedure called certification system 3
Construction Products Directive. Certification System 3 corresponds to the system of certification ii) of Annex III of the
Housing Ministry’s Executive Order on the entry into force of the EC-Directive regarding the mutual approximation of the
member states’ laws and administrative provisions relating to construction products, with the changes imposed by the
EC-Directive amending, among others, the EC-Directive regarding construction products.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Rainwater systems
Rainwater systems where rainwater from roofs is used for toilets and washing machines in homes and similar residential
buildings, must be installed in accordance with the Ministry of the Environment’s Executive Order on water quality and
monitoring of water supply systems § 4, paragraph 1 and 2
Other approvals
Some products are not covered by an approval scheme. An example of a product that is not covered by an approval
scheme but must be approved by the local building authorities, is kitchen disposal units, because the municipalities may
have prohibitions, restrictions or special taxes due to the wastewater treatment plants’ capacity and quality.
Products or grouped systems, which are separately manufactured for installation in a particular system, must be approved
by the local building authority.
For construction of limited complexity, such as carports, detached houses, agricultural buildings and light industrial and
warehouse construction, there will be no construction case processing of the technical provisions of BR 08. The technical
provisions deal with buildings’ design, structures, fire protection, indoor climate, energy consumption and installations. The
buildings still require building permits. When construction is completed, the documentation for the technical conditions is
submitted to the municipal council together with a statement, indicating that the building is constructed in accordance with
the purpose of the Building Act and the provisions of the Building Regulations. This material is archived in the construction
case.
A notification must be in writing and signed by the owner. The notification shall include a description of the
work that is to be performed and be accompanied by a drawing with scale and a description of the building and its
location on the lot. For isolated renovations and modifications that include installation work,
the notification must also include drawings that describe the new installations’ connection to existing installations.
For construction works, which must be reported according to the building regulations, the work can be commenced no later
than 2 weeks after normal mail delivery time from the day the notification is received, if the council has not responded.
Such works do not need to be reported as finished to the municipal council.
1.4.2.3 Construction works that can be performed without building permit or notification
Some construction work can take place without a building permit or notification and without authorization for use from the
municipal council. This applies to, for example:
• Renovation and other changes in some of the buildings specified in the Building Regulations, if no expansion of the area
occurs
• Construction work by open pools
• Satellite antennas with a maximum diameter of 1.0 m and type-approved roof antennas
• Construction work by camp cabins and allotment houses.
These construction works do not need to be reported as finished to the municipal council.
1.4.4 Exemption
As mentioned, water systems should be installed as specified under the Building Regulations.
The Building Regulations refer to DS 439, Standard for water systems, which provides examples of installation methods
that meet the functional requirements.
Other installation methods that meet the functional requirements, must in each case be approved by the local authority.
If circumstances make it necessary to perform the work in another way – where it cannot be documented that functional
requirements are met, a special permission is required, an exemption. Exemption is granted by the municipal council.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
1.4.5 Registration
When an exemption is granted, it is often done under certain conditions. The municipality has the right to impose special
conditions, for example, that the conditions must be rectified if it turns out that the system does not function as expected or
if subsequently problems are found with the solution that the exemption was granted for. In the case of conditions that lead
to a significant economic burden, the municipality should arrange for a registration. Registration of the conditions of this
nature is done according to the Building Act’s § 27.
1.4.6 Complaint
be submitted regarding the building authority’s decisions in water system cases, in accordance with the Building Act’s
provisions (§ § 23 and 24). Any complaint over the municipal council's decision must be made to the State Administration,
see law regarding regional state administration. Complaints can be submitted regarding legal issues. The deadline for
appeals is 4 weeks from the day the decision is announced.
1.4.7 Fines
The Building Act lists a number of conditions, which may result in a fine. Some of these conditions include:
• A fine is imposed on anyone who violates the provisions of the Building Regulations by failing to notify of construction
work, failing to submit a completion notification or failing to apply for an exemption.
• A fine is imposed on anyone who commences construction work, commissions a construction work or otherwise
implements measures without obtaining permission as prescribed by law or in accordance with the provisions contained in
the legislation, or performs construction work or other action that requires prior authorization, in another way than what is
permitted by the appropriate authority.
• A fine is imposed on anyone who disregards the conditions specified in a permit subject to legislation or the provisions
contained in the legislation.
• If a construction work is performed in an illegal way, responsibility lies with the person who ordered the work or the person
who performed it, both persons depending on the circumstances.
• A fine is imposed on anyone who, for use in construction, produces or sells building materials that according to applicable
building provisions, can not legally be used in the construction in question.
• Ministry of the Environment’s Executive Order regarding payment for water according to measured consumption, etc., at
the property level, No. 525 of June 14th, 1996.
• The Enterprise and Construction Authority’s Executive Order regarding inspection of water meters used for measuring
the consumption of hot and cold water, No. 1034 of 10.17.2006.
These laws and regulations state that on all properties that were connected to public water supplies no later than January
1st, 1999, water meters must be installed at the property level for measuring the consumption of cold water.
For new buildings, i.e. for properties built after 01.01.1999, or new installation of water systems in existing buildings, the
individual housing unit or commercial unit must be prepared for the installation of meters for measuring consumption of
both cold and hot water.
The obligation and right to implement the installation belongs to the public water supply. Installation is performed by the
landowner at his or her expense at a location approved by the public water supply. Meters are made available by the public
water supply and remain the public water supply’s property
Table 1.1 - Overview of current provisions for individual metering of water consumption in buildings
New construction Existing construction
1
Property level Cold water Is prepared > Yes, requirements for
properties built before
1.1.1999
2
Hot water Is prepared ) Optional Optional
1} The provision does not apply if installing meters in residential or commercial units.
2) The provision does not apply if installing meters in residential or commercial units for measuring the total consumption of
water and meters for the total consumption of heat for heating and hot water (i.e. water meters and heat energy meters).
Housing Unit
A housing unit includes a residential apartment with kitchen/kitchenette with running water and an independent drain. A
college dorm with rooms without kitchen/own kitchenette is not covered by the rules. If individual rooms or youth housing
are designed in such a way that the tenant can get housing grants, they are covered by the rules.
Commercial unit
Commercial units means adjacent areas, which have separate access to each commercial unit, regardless of whether the
land is parceled out according to the law regarding condominiums. Single-family houses with mixed residential and
commercial must be viewed as one unit, as long as both the residential and commercial parts are used. There is therefore
no requirement for separate metering for the commercial part in such buildings.
Preparation for measurement of cold water
Preparation for the installation of a water meter usually involves:
• installing the cold water system so that measurement can take place with one meter.
• equipping the installation with a fitting with shut-off valves that are placed so that the meter can easily be installed without
first having to move major structural components, cabinets, etc.
• having the future meter be easily readable, i.e. without first having to dismantle cabinets and fastened plates, etc.
It is still optional whether to establish measurement of water at unit level.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Water systems in buildings and on private land must be performed, maintained and repaired by an authorized installer, a
licensed water and sanitation professional or an approved competent company.
The municipality has, pursuant to the building regulations, the right to inspect installation work before it being covered.
The Authorization Scheme, based on the Authorization Act, is managed by the Danish Safety Technology Authority under
the Ministry of Business and Growth.
In connection with the Act, a series of provisions have been issued detailing the requirements for authorization.
1.5 Letter symbols and units
safety factor
water’s specific heat, 4,2 kJ/kg °C
inner pipe diameter (mm)
tapping’s energy requirement (kWh)
value calculated on the basis of mutual usage frequency for tapping points in homes
height to highest or farthest tapping point over the supply point (m)
roughness in pipe (mm)
pipe length (m)
sum of the lengths of plug line and distribution line to the highest and/or farthest tapping points (m)
fixtures sound level (db(A))
pressure (kPa)
the available pressure for pressure loss in the plug line and distribution line (kPa)
efficient water heater effect (kW)
lowest normally occurring water pressure in the supply point (kPa)
highest normally occurring water pressure in the supply point without additional front pressure shock (kPa)
pressure in distribution pipe at the height of the tapping (kPa)
tapping points power requirement (kW)
dimension-giving water flow for distribution pipe exclusively for randomly used tapping points (l/s)
dimension-giving water flow for distribution pipe exclusively for both randomly used tapping points and other used
tapping points (l/s)
projected water flow by tapping point (l/s)
mean water flow by each individual tapping point (l/s)
weighted mean water flow for several tapping points connected to the distribution pipe (l/s)
smallest water flow (l/s)
largest water flow from one or more flush valves (l/s)
the sum of water flows for systematically used tapping points connected to pipes (l/s)
water flow from the hot water system (l/s)
3
the water flow by which a water meter can work satisfactorily (m /h)
Reynold’s number (dimensionsless)
water temperature (°C)
cold water temperature (°C)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
1.6Definitions
The terms "before" and "after" indicate placement in the water’s flow direction.
Shut-off valve
Valve that can shut off an installation element or is a part of the pipe network.
Tapping valve
Valve that can tap an installation element or a shut off part of the pipe network.
System for the production of hot water
Consists of a heat exchanger and possibly a container part.
System with charging circuit
A system consisting of a container and an external heat exchanger.
Container (reservoir)
Container in which the heated water is stored (accumulated) for later use.
Fitting
Generic term for all types of valves and taps.
Load tapping
Sample tapping, where pressure and water flow measurements are made during sample tapping.
Mixed fitting
Two tapping valves for both hot and cold water, equipped with a shared drain.
Pipe bushing
Protective pipe through which the water pipe is installed. Used for installation through wall, floor separation, foundation and
the like.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
mur - wall
grundgrænse – site boundary
koblingsledning – coupling pipe
fordelingsledning – distribution pipe
koblingsledning – coupling pipe
koblingspunkt - coupling point
forsyningsledning – supply pipe
forsyningspunkt – supply point
stikledning – plug line
jordledning – ground pipe
vandinstallation – water system
fordelingsledning - distribution pipe
Figure 1.4 –Water pipe network
Coupling point
Transitional spot between distribution pipe and coupling pip, see figure 1.4.
Competent company
Approved competent company which, pursuant to the authorization provisions, is entitled to perform limited work by
water systems.
Counter valve
Counter valve that ensures that water can only flow in one direction.
Counter valve, controllable
Counter valve, that is designed or placed in such a way, that its function can be controlled.
Air gap
Clear height between the water outlet and the highest possible water table in the installation element or the tub, over
which the outlet is positioned.
Authority
Authority means the local municipal council.
Meter dimension
The meter's nominal diameter or pipe threads on screws.
Adequate temperature
The temperature, which the tapped water must have in order to ensure a projected function.
Adequate water volume
The volume of water that is sufficient to ensure a projected function by the tapping point.
Adequate water flow
The water flow it should be possible to tap from the tapping point to ensure a projected function.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Rainwater system
Systems where rainwater from roofs is collected and used for toilet flushing and washing machines in homes and
residential buildings.
Pipe interruptor
See open pipe interruptor.
Pipe dimension
Accurate inside pipe diameter after indication in catalogue or standard sheet. Used for dimensioning graphs
(nomograms).
Pipe size
Indication of pipes’ trade name, which usually only to a certain extent will be in accordance with the actual pipe
dimension.
Safety valve
Valve, which - at a pre-set pressure- can discharge excess air, water or steam volumes from containers and pipe
systems.
Flush valve
Mechanical self-closing valve for flushing.
Static pressure
See total pressure.
Plug line
Pipe connecting the supply pipe with the water system, see figure 1.4.
Adjustable counter valve
Counter valve, which also acts as a shut-off valve or tapping valve
Noise Groups
Groups that classify tapping valves according to properties in terms of sound.
Systematically used tapping points
A tapping point that is used within certain periods, or more tapping points used simultaneously.
Tapping points
The locations in the water system from which water can be tapped.
Tapping valve
Valve for opening/closing and adjusting the water flow by the tapping point
Backflow blocker
Generic term for devices, which ensure that water can only flow in one direction.
The total pressure
The total pressure is the sum of the static pressure and dynamic pressure. In a resting fluid the dynamic pressure is
equal to 0, so that the total pressure equals the static pressure.
Pressure Groups
Groups that classify tapping valves according to the pressure loss, which will occur when tapping the projected water
flow through the fully open valve. Classification is specified in the authorizations /6//7/.
Pressure loss
The energy loss (per volume unit ) that occurs when water flows in pipes, containers and fittings.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Drain Valve
Valve or tap for tapping or draining of an isolated portion of a pipe network or an installation element.
Replaceability
Replaceable pipes:
In soil
- Pipes that are accessible for repairs after excavation.
In buildings
- Pipes that are accessible for repairs after dismantling of cover plates or the like, which primarily aim to hide the
installation.
Non-replaceable pipes:
In soil
- Pipes that are inaccessible for repair, for example, during building construction.
In buildings
- Pipes that are inaccessible for repair, for example, in concrete, wood or brick structures.
Vacuum Valve
Backflow blocker in the form of a valve construction, which – for underpressure in the water system - opens to the
surrounding air, thereby eliminating a possible siphoning.
VA-approval
Enterprise and Construction Authority's type approval of the material in water systems.
Water for industrial use
Water from drinking water systems, which is treated in special plants, after which it no longer meets the
requirements for drinking water in the Ministry of the Environment’s regulations.
Water Treatment Plant
Plants for changing the water’s chemical and/or microbiological properties.
Water system
The part of a pipe network that is located in buildings and associated land, see figure 1.4.
Pipe network
Generic term for supply pipe, plug line and water system, see figure 1.4.
Water and sanitation professional
Authorized company that pursuant to the authorization provisions is entitled to perform work at water supply and
drainage systems.
Water pressure
The static pressure in a water pipe. Water pressure is measured as static pressure relative to atmospheric pressure.
Heat exchanger (water heater)
In a heat exchanger, heat is transferred between two independent power circuits, where the primary side indicates
the heat-emitting circuit and the secondary side indicates the heat receiving circuit.
Heating of water can occur in different types of heat exchangers:
- Cap containers
- Hot water containers with built-in heating coil
- Flow water heaters
- Plate heat exchangers.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Plumber
Authorized company that pursuant to the authorization provisions is entitled to perform work on gas, water and
drainage systems.
Open pipe interruptor
Backflow prevention in the form of a pipe fitting, to which inner air has permanent access.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Dimensioning
2.1 General
Water systems must be dimensioned and executed so as to achieve a satisfactory water supply at each tapping site, taking
into account the supply conditions and the system’s and the building’s use and water consumption /13/.
The dimensioning and execution takes into account that the water’s temperature and time in the water system should not
unacceptably affect the quality of drinking water.
Before any changes are made to existing installations, either an assessment, a calculation
or a load tapping must be performed, that demonstrates that the supply conditions at each tapping site in the property will
not be significantly impaired.
2.2 Conditions
2.2.1 Performance
Water systems are dimensioned so that the individual tapping points can receive a water flow and water quantity that is
satisfactory for the function of the tapping point.
2.2.2 Noise
Water systems are dimensioned and executed so as to avoid any annoying noise.
The Building Regulations sets limits for the noise level from the water system. Here it is necessary to take
into account the properties of the used fittings in terms of sound. The approvals will usually contain information about this,
mainly through a classification of fittings in three noise groups with corresponding limitations in scope:
Noise Group 1: Lap < 20 dB (A). Tapping valves can generally be used without limitations.
Noise Group 2: Lap <30 dB (A). Tapping valves can be used in buildings where water system, building construction
and plan solution are designed so that they ensure that noise does not occur, or where there is assurance that the pressure
in front of the tapping valve will not exceed 300 kPa.
Noise Group 3: Lap > 30 dB (A). Tapping valves can generally be used in installations where there is assurance that the
pressure in front if the tapping valve will not exceed the value corresponding to the Lap level of 30 dB (A).
The noise is measured according to a method specified in DS/EN ISO 3822-1, Acoustics - Laboratory tests on noise emission
from appliances and equipment used in water supply installations - Part 1: Method of measurement.
2.2.3 Water pressure
The water installation is dimensioned for the lowest normal pressure pln in the supply pipe.
If the lowest normal pressure is not large enough to ensure an adequate water supply, the pressure booster system is
installed.
The lowest normal pressure in the supply pipe pln means the lowest pressure that occurs with a probability of 0.99 in a
period with high consumption, see figure V 2.2.3.
The maximum pressure in the supply line means the highest pressure pmax, which occurs in the supply pipe, see Figure V
2.2.3.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
The probability that the pressure at least has the size p i en forsyningsledning in a supply pipe in a period with a large
consumption of water.
Pressure p
0,99 1,0
Figure V 2.2.3 –Pressure in supply pipe
The water supply will normally be able to provide information on pressure conditions in the supply line by specifying the
lowest and highest water pressure at that location.
2.2.4 Water flows
Water installation is dimensioned on the basis of the projected water flow at each tapping point. The indicated water flows
in Table V 2.2.4 can be considered adequate.
Table V 2.2.4 – Projected water flows at the most frequently occurring tapping points
Tapping point projected water flow q, (l/s)
2.3.2 Distribution pipe for a room in residential buildings and similar buildings
if it is likely that only one person uses the room, the dimension-giving water flow qd can be set to the largest projected water
flow qf of the tapping points in the room. If it is likely that several people in the room use the installation simultaneously, then
the dimension-giving water flow qd is determined based on an estimate of which tapping points can be expected to be used
simultaneously.
2.3.3 Distribution pipes for several rooms in residential buildings and similar buildings
Assuming that all the tapping points are used randomly, the dimension-giving water flow is calculated by using the
following formula:
where
qd is the dimension-giving water flower for distribution pipes exclusively with randomly used tapping points.
qm is the weighted mean water flow for several tapping points connected to the distribution pipe.
Σqf is the sum of the projected water flows qf according to table V 2.2.4
A and 0 are the constants that depend on the desired safety against overloads.
For water systems in residential buildings and similar buildings where the tapping points are used briefly and randomly as
in residential buildings, A can be set equal to 3.1, 0 = 0.015 and qm = 0.1 l/s.
The dimension-giving water flow qd for distribution pipes with largest qf less than or equal to 0.3 l/s,
then becomes (see table V 2.3.3):
qd = 0,2 + 0,015 (Σqf - 0,2) + 0,12 VΣqf - 0,2 l/s
The probability that the actual water flow exceeds qdr, is approximately 0.001 in this example.
If there are systematically used tapping points in an installation, then the largest water flow qsyst is calculated as the sum of
the projected water flows from these tapping points.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Table V 2.3.3 – Dimension-giving water flow qd for different projected water flows Σqf
sum of projected water dimension-giving sum of projected water dimension-giving
flows water flow flows water flow
Σqf (l/s) qd(l/s) Σqf (l/s) qd(l/s)
0,1 0,1 12 0,79
0,2 0,2 13 0,82
0,3 0,25 14 0,85
0,4 0,26 15 0,88
0,5 0,27 16 0,91
0,6 0,28 17 0,95
0,7 0,29 18 0,97
0,8 0,30 19 0,98
0,9 0,31 20 1,03
1,0 0,32 22 1,04
1,2 0,34 24 1,14
1,4 0,35 26 1,20
1,6 0,36 28 1,25
1,8 0,38 30 1,31
2,0 0,39 35 1,42
2,5 0,41 40 1,55
3,0 0,45 50 1,80
3,5 0,47 60 2,02
4,0 0,49 70 2,25
4,5 0,52 80 2,47
5,0 0,53 90 2,68
6,0 0,58 100 2,90
7,0 0,62 110 3,11
8,0 0,65 120 3,31
9,0 0,69 130 3,51
10,0 0,72 140 3,72
11,0 0,76 150 3,92
The dimension-giving water flow used in an installation that includes both randomly as well as systematically used tapping
points, is calculated as: qd = qd + qsyst l/s
If there are flush valves for toilets and urinals in an installation, then the largest water flow qsky} is calculated as:
qsky} = 1.5 +(n-1) 0,2 l/s for toilets
qsky} =0.4 + (n-1) 0,1 l/s for urinals
where n indicates the number of flush valves on the pipe.
The dimension-giving water flow used in an installation that includes both flush valves and randomly and systematically
used tapping points, is calculated as:
qd = qd + qsyst + qsky} l/s
If there are hoses in an installation, according to the requirements of the building regulations, the dimension-giving water
flow for pipes that only supply hoses {regardless of the quantity), is 0.33 l/s.
The dimension-giving water flow used in an installation that supplies both hoses and other tapping points, is calculated as:
qd = 0,33 + {qd - 0,2) + qsyst + qsky} l/s
Annex A specifies an indicative calculation method for qd based on measured average water flows from the individual
tapping points and for qf values greater than 0.3 l/s.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
The calculation method in the Annex is used, when an installation type has measured or estimated values for water flows,
usage frequency and consumption.
qtl dimension-giving water flow l/s
H 56 S I000
Σqf sum of projected water flows l/s
Figure V 2.3.3 – Dimension-giving water flow qd as a function of the sum of projected water flows qf
For the pressure loss calculation, the installation can be divided into the following sections:
1. Pressure loss in connection to the supply pipe. For pressure loss in tapping or T-indentation, see Table V 2.3.4 a, since
the dynamic pressure can be read in nomograms for pressure loss.
3. Pressure loss in single resistances. The pressure loss can be calculated as the resistance number for the single
resistance multiplied by the dynamic pressure.
The resistance number for the most frequently occurring single resistances is shown in table V 2.3.4 a, and the dynamic
pressure can be read in, for example, nomograms for pressure loss.
Pressure loss in single resistances excl. tapping valves, mixed fittings and larger single resistances such as water heaters,
etc. can, if you do not complete an accurate calculation, be set at 25 percent of the resistance in the straight pipe stretches.
4. Pressure loss in tapping valves and mixed fittings. The pressure loss is indicated by the classification of pressure groups
in Table V 2.3.4 b and approval /6//7/.
5. Pressure loss in coupling pipes. Pressure loss can be calculated as specified in item 3, as the part of the available
pressure that is not used up in accordance with items 1-5, as much as possible is used up in the coupling pipe to the
tapping point. By varying the coupling pipe’s dimension at each tapping point, it is usually possible to approximate the
projected water flow at each tapping point regardless of location.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Table V 2.3.4 b - Placement of tapping valves and mixed fittings in pressure groups
Pressure group kPa pressure loss Apm for fully open valve for the projected
water flow qf
kPa
50 Apn<50
150 50 < Ap< 150
300 150 < Apm <, 300
where
Åp0 - 100 kPa, when using tapping valves in pressure group 50 kPa
150 kPa, when using tapping valves in pressure group 150 kPa
220 kPa, when using tapping valves in pressure group 300 kPa.
If installations with larger ingle resistances, e.g., certain flow water heaters, are to be dimensioned through a simplified
calculation, one can use the simplified method when the available pressure loss is calculated like this:
Pdisp/L=Pla-10H- Åpo-Ape/L
where Ape is the pressure loss in kPa in the large single resistances for the dimension-giving water flow. The pressure
losses can be stated in the approval or obtained by contacting the manufacturer.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
32 40 50
0,5 1,6 8 35
1,0 6 20 60
2,0 15 45 100
3,0 20 65 100
4,0 30 80 100
5,0 40 95 100
15 20 25 32 40 50
0,5 0 0,2 1,0 9,1 34 58
1,0 0,1 0,3 3,0 19,5 37 96
2,0 0,1 1,0 7,5 34 65 100
3,0 0,2 2,5 12,1 48 78 100
4,0 0,2 3,0 16,2 59 100 100
5,0 0,4 4,0 22,5 71 100 100
To avoid wastage of water, the hot water system should be designed so that the hot water, at a water flow of 0.2 l/s,
reaches the tapping points easily without delay after the tapping has begun. This will often cause the plant to be installed
with circulation or heating pipes.
In cases where the delay and wastage of water is not particularly significant, specifically by tapping points, which are rarely
used – e.g., guest toilets, cleaning rooms and tapping points in basements - and by tapping points where a large amount of
mixed water is tapped - such as bathtubs and sinks for washing clothes - circulation or heating pipes can be omitted in
order to save energy.
For frequently used tapping points – e.g. in kitchens and family bathrooms - where distance conditions are such that a
reasonably short waiting time only can be achieved through circulation or heating pipes, one should strive to take into
account the energy consumption, for example, through good pipe insulation and timer controls, which restrict the
circulation to the actual times of use.
Installations that have both rarely used tapping points and good opportunities to obtain reasonably short waiting times, are
usually found in single-family houses. The requirement for an appropriate waiting time should not necessarily be achieved
through a requirement for circulation or heating pipes in all new single-family houses. In cases of exceedance, there should
be an energy-saving calculation, or other ways should be considered, whereby the standard’s overall functional
requirements can be met.
To achieve the best possible transfer of heat from the heating surfaces to the water, the heating surfaces must be designed
so that the coatings on these are kept at as low a level as possible. The heating surfaces must be accessible for cleaning.
Where the heating medium is hot water, flow and return temperature is specified at 80/60°C or 90/70°C. Other values, such
as 70/40°C or 60/30°C can be used in low temperature systems.
Corrections
If the effective container performance and effective volume is not determined by measurement, various corrections must
be performed.
Container volume
The container’s geometric volume will be larger than its effective volume, i.e.:
V = fY * Ve(f
where fY is a factor {greater than 1), which depends on the container’s geometry, the size of the heating surface and the
sensor’s location.
In systems with separate heat exchanger or containers that are supplied from own boiler and with baffle plate by cold
water connection, the effective volume for a rapid discharge close to the container’s physical volume is typically approx. 80
to 90%. For storage over several hours, which is typical, you can expect a mixing layer of approx. 15 cm of the container’s
height. For containers with built-in heating surface, you measure from the lowest point of the heat exchanger to the hot
water outlet.
For district heating supply containers with built-in spiral where the dimensioned flow temperature typically
is 60 or 65°C, the concept of effective volume is not used directly. In the dimensioning rules mentioned in 2.5.2.1.4 b
for this case, the container’s geometric volume measured from the bottom edge of the spiral is used.
Container power
When determining the necessary container power, you must take into account:
a. Deposits
If the effective container performance Peff is applicable to clean heating surfaces, there will be a reduction of the power
caused by deposits, i.e.:
Po = fp * Peff
where the factor fp will depend on water’s chemical properties, on maintenance and cleaning, on heating surface’s
temperature, and on whether an electrolysis system has been installed. The reduction can be set to 15-30%,
i.e.:
1.5 < fp < 1,30
Large values of fp, for example, can be found in certain types of gas water heaters and electric water heaters. A coating will
usually only affect the effective volume to a very small degree.
b. Circulation Loss
Depending on system size and isolation, the circulation loss can be set to 0.1 to 0.2 kW per apartment.
c. Electrolysis system
If electrolysis processing is used, the container should be of such a size that the water’s retention in the container will be at
least 20 minutes at the maximum hourly consumption. There are systems that do not require container volume.
For dimensioning temperatures for water heaters in residential buildings, you can select an approach temperature (cold
water) of 10°C and an outlet temperature (hot water) of 55°C.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Table V-2.5.1 Tappings and tapping programs for hot water tapping points in permanent housing (individual
tapping point
data for tapping unit bath tub shower kitchen sink bathroom
sink
smallest mixed water flow Pb,min l/s 0,21 0,14 0,10 0,056
adequate temperature (mixed Tb °C 40 40 45 40
water)
projected hot water volume vb I 125 42 15 10
(mixed water)
tapping time for one tapping s 600 300 150 180
Tappi tapping point’s power requirement 14.7
ngs TK =10°C kW 26,3 17,6 16.8 7,0
from TK = 5 °C kW 30,6 20,6 8,2
one tapping point’s energy requirement
tappi T =10°C kWh 4,36 1/47 0,61 0,35
K
ng TK = 5 °C kWh 5,09 1,71 0,70 0,41
point
Tappi number of tappings 2 4 2 4
ng
tapping interval = time between start of two min 30 20 20 20
progr
tappings
am
tapping period = time between repeated h 12 12 3 6
tappings
apartments, single-family homes and the like)
The table is used in the dimensioning of water heaters that supply individual tapping points, and as a basis for tapping
programs for water heaters that supply multiple tapping points in a permanent residence.
If it is demonstrated that a specified tapping fixture with specified equipment (e.g. a shower) functions satisfactorily for a
service that is less than the table's entries, then the water heater's performance can be determined accordingly, while
maintaining the tapping program. It is assumed that the water heater is always installed in connection with the equipment in
question.
The baths are expected to take place with the tappings indicated in table V 2.5.1.
Tapping for kitchen sink is not expected to take place at the same time as tapping for bath tub.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
These baths are expected to take place with the tappings and tapping intervals indicated in the tapping program in Table V
2.5.1.
Tapping for the kitchen sink is expected to take place simultaneously with the tapping to the shower with the tapping
program specified in Table V 2.5.1.
If the water heater only supplies the tapping points in the same room, a tapping program is set up taking into account the
room's use. Normally it can be assumed that tapping only takes place by one place at a time.
For systems for a single-family house or a single apartment, the required power will usually respond to tapping from the
kitchen sink and shower simultaneously. From formula (2.5.3) or table V 2.5.1 you get the required power:
With an addition for coatings of 15-30% the necessary power becomes 37 -42 kW.
2,5.2.1.2 b Dimensioning of hot water containers that supply all the tapping points in a single-family house
The tapping programs listed in 2.5.2.1.2 are used. The corresponding PE-curves are shown in Figure V 2.5.2. It
is assumed that the hot water heater supplies all the tapping points in a permanent residence and that it is a family home.
For residential dorms, for example, for one or two residents and in cottages, a different tapping program is set up, but the
value of individual tappings should be assumed to be as shown in Table V 2.5.1.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Figure V 2.5.2 – Dimensioning chart (P-E-curves) for water heaters that supply all hot water tapping points in a
permanent home for one family
For containers connected to boilers, both boiler power as well as the heat exchanger’s power must be in accordance with
Figure V 2.5.2. No deposit addition needs to be added to the boiler power here. The following should be complied with:
The flow of water in the boiler/container circuit corresponds to the power in Figure V 2.5.2 and a difference in the flow and
return flow temperatures of no more than 15°C.
The dimensioning difference between the mean boiler temperature in this situation and T mhi should not exceed 22°C. This
temperature difference is dimensioned for a lower value corresponding to a suitable supplement for coatings. Note: If the
system is designed so that the whole boiler’s power is added to the container, both water flow and heat exchanger are
dimensioned according to the boiler power.
The power can be determined by testing according to Institute of Technology, Heating and Installation Engineering, 1985:
Testing of water heaters, test bench and test methods.
For best utilization of the new dimensioning method, the selected hot water container should in principle be based on
measured values for the test methods that have formed the basis for the simulations, see Testing of water heaters, test
bench and test methods, DTI, Heating and installation engineering, 1985.
Normal apartment
A normal apartment is assumed to have 3.5 residents and bathroom with bath tub or shower that are considered identical
with a computational energy requirement of 4.36 kWh. Kitchen sink not included. Wash basin and bidet are only included in
apartments with 2 bathrooms.
The number of normal apartments is calculated based on the true number of apartments, number of occupants per
apartment and number of bathrooms and power per tapping. The number of the building’s normal apartments exists as the
building's energy requirements per day, divided by a normal apartment's energy consumption per day.
where
The calculation of the numerator in the formula is as follows: The apartments are divided into groups so that the apartments
within a group are the same in terms of number of residents and number of hot water units (i.e. number of bathrooms). For
each group, the product of n, p, v and E is calculated, and finally the sum of the products of the respective groups is
calculated.
Table V 2.5.3 – The smallest number of residents included per apartment. Thus a normal apartment has 4 rooms
and 3,5 residents
number of rooms 1 1V2 2 2V2 3 31/2 4 41/2 5 51/2 6 61/2 7
number of residents 2,0 2,0 2,0 2,3 2,7 3,1 3,5 3,9 4,3 4,6 5,0 5,4 5,6
Hot water units and energy requirements
For the calculation of hot water units that is included in v in the above-mentioned formula for calculation of the number of
normal apartments, there is a differentiation between apartments with one or two bathrooms. Where there is one
bathroom, only 1 hot water unit is assumed, which can be a bathtub or shower, and as previously mentioned, both are
expected to have an energy requirement of 4.36 kWh.
If there are 2 bathrooms, several hot water units and their energy requirements are included, such as the ones found in
Table 2.5.4.
It is noted that in both cases kitchen sinks are not included because the energy requirement for the kitchen sink is included
in the bathtub’s/shower's energy requirement.
No hot water units are included that do not occur in construction. Energy requirements for each hot water unit are also
listed in Table V 2.5.4.
Instead of calculating the numerator in formula (2.5.4), which is an expression of the building's energy requirements per
day for hot water, one can measure the energy consumption. It can be done in the case of a building that is to be
renovated, but for new buildings it will often be possible to find an existing building, which is very similar to the planned
building, and therefore this one can be measured instead.
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Table V 2.5.4- Hot water units and their energy requirements for use when performing calculations using formula
(2.5.4)
homes with one bathroom homes with two bathrooms
hot water unit energy hot water unit energy requirement kWh
requirement kWh
bathroom 1 bathroom 2
bath tub or shower (v — 1) 4,36 bath tub or (v=1) 4,36 (v=1) 2,18 or 1,70
shower
Table V 2.5.6 - Dimensioning powers and computational daily consumption for flow water heaters
tapping programs and powers
number of normal apartments 1 2 4 8 11 16 22 32 44 64 88 128
daily energy consumption 17,4 29.8 52,4 94,4 124,8 174,2 232,4 328,4 441,6 627,8 849,2 1 215,0
(kWh) – per apartment [kWh] 17,4 14.9 13,1 11,8 11,3 10,9 10,6 10,3 10,0 9,8 9,7 9,5
duration of tapping program [h] 3,7 4,3 4,9 5,5 5,7 5,9 6,1 6,3 6,4 6,6 6,7 6,8
max. power: 10 min. [kW] 26.5 35,7 48,7 67,9 79,9 97,6 116,5 144,8 175,7 222,8 274,8 355,3
max. power: 1 min. [kW] - per 37.6 46,6 60,0 80,3 93,0 112,0 132,0 162,0 195,0 244,0 299,0 383,0
apartment [kW] 37,6 23,3 15,0 10,0 8,5 7,0 6,0 5,1 4,4 3,8 3,4 3,0
2.5.2.1.4 b Dimensioning of hot water containers with built-in spiral for district heating
Dimensioning of containers with built-in spiral is based on a large number of computer simulations, of which the
results are depicted in Figure V 2.5.7. The diagram is based on the following conditions:
• An average cooling on the district heating side can be achieved, which with approximation, is equal to the
dimensioning cooling.
• In practical operation with hot water temperature 50-55°C and for moderate circulation pipe losses, primary
return temperatures can be achieved in the area around 40°C on average.
• The container volume is the container’s actual volume measured from the bottom edge of the heat
exchanger to the outlet nozzle.
• The effective power is incl. 0,15 kW circulation loss per apartment.
• The container power is defined as the effective power, which implies that there should be a deposit
supplement.
The power is further defined as the continuous performance at 10/45°C on the domestic water side. The
primary side's temperature is based on 60°C flow temperature and 40°C return flow temperature.
PV-curves for hot water containers with built-in spiral for district heating
Container [l/apt.]
Figure V 2.5.7 – Dimensioning diagram for hot water containers with built-in spiral.
The diagram shows the correlation between the power required per normal apartment, effective container
volume per normal apartment and the number of normal apartments
The power can be determined by testing according to Technological Institute, Heating and Installation Engineering,
1985: Testing of water heaters, test bench and test methods.
2.5.2.1.4 c Dimensioning of systems with charging circuit or containers with built-in heat exchanger supplied from
boilers
Systems with charging circuit, i.e. with external heat exchanger can be dimensioned by using the chart in Figure V
2.5.8. Dimensioning is performed for heating of domestic water at 55-45°C. Loss through circulation of hot water is
not included.
When using the diagram, the following conditions apply:
The container’s volume is the actual volume of the container for containers with built-in exchanger measured from
the bottom edge of the exchanger. An addition to the container’s height of 15 cm is recommended for the sake of
the separation layer’s thickness and the heating pipe.
The dimensioning diagram includes charging circuit systems where circulation is not flowing through the hot water
container and where the hot water container is top-filled and all systems are supplied from boilers where it is a
condition that the power, corresponding to Figure V 2.5.8, can be transferred to the container.
PV-curves for charging circuit systems or containers with built-in exchanger supplied from boilers
£
é
L
U
2 4 60 8 10 120
0 0 Container 0 0
[l/apt.]
Figure V 2.5.8 – Dimensioning diagram for systems with charging circuit (container with external heat
exchanger) or for systems supplied from boilers with internal or external heat exchanger
The diagram shows the correlation between the power required per normal apartment, effective container volume
per normal apartment and the number of normal apartments.
DS 439:2009
3 Resource consumption
3.1 General
The water Installation is installed taking into account sufficiently low resource consumption.
Emphasis should be given to reducing both water consumption and energy and material consumption.
The requirement applies to both the execution of the installation as well as its operation and maintenance.
System with fire hydrants and sprinkler systems are installed with their own separate pipe network without meter.
From systems without meters, water can only be taken in cases of fire, except for the consumption needed for testing
the system and possible renewal of the water.
Where meters are not required in connection with the execution of the installation, the installation is installed so that
meters may subsequently be installed without major changes to the installation, possibly by insertion of a fitting.
Meters that were in operation on August 1st, 1998, can still be used even though they are not type approved and
verified. Meters that have been taken down, which are reinstalled, must be calibrated and re-verified at an accredited
laboratory.
43 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Meter size is usually selected based on size of pressure loss over water meter by the dimension-giving water flow.
The biggest pressure loss in the meter should normally not exceed 0.4 bar (40 kPa) by the dimension-giving water
flow. This ensures that the flow volume is less than the flow volume at which the meter can briefly work satisfactorily
without being damaged.
For impeller meters, which are the most common type, the meter size can be selected using the curve sheet in figure
V 3.2.1, The curve sheet is indicative, as there may be deviations from brand to brand. The curve sheet is not
applicable to dry-running impeller meters, Woltman meters, etc.
It is noted that according to 4.4.1 a non-return valve is required immediately before or in the meter. When positioning
the meter, one should expect a small increase in pressure loss in the meter.
The final meter size is determined for all types of meters of the public water supply. The water meter is the public
water supply’s property.
20 30
flow in m3/h
flow in l/s
The installation is designed so that the meter can be removed from the installation, for example, by flexible pipe
stretches or for installation of expansion piece.
Placement of meter in buildings or in measuring well is agreed upon with the public water supply.
44 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Meter location with free distances required for reading the meter is shown in Figure V 3.2.2.
Necessary lengths for expansion when removing the meter are shown in Figure V 3.2.3.
The meter is installed so that the flow conditions in the pipes do not impair measurement accuracy.
For meters with dimensions of 50 mm or more, there must be a length of pipe before the meter of at least 10 x the
meter dimension. On this length of pipe, it will be possible to place valves, that in a fully open position do not give rise
to turbulence, e.g. free-flow valves. Pipe length between meter and valves should be at least 2 x meter dimension.
Figure V 3.2.2 - Meter location in building with the Figure V 3.2.3 – Meter location with indication of
free distances that are necessary for reading and necessary lengths for expansion and for
replacing meter dismantling of meter. Schematically set up
Water installations, from which tapping happens automatically, should be installed so that the tapping is managed by
the need for flushing.
Automatic flushing of urinals can be performed, on condition that the water volume per urinal is limited (normally
max. 20 l per hour), and that the system is automatically disconnected outside of the usage time. Flushing can, for
example, be managed by photo cells or switches.
The water supplied from the waterworks, is primarily meant for domestic purposes, personal hygiene, wash and
cleaning etc.
45 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Permission to use water for special technical systems that use water to a larger extent, and which don’t require water
of a high hygienic quality, can be given on condition that water-saving measures be implemented for, for example,
recycling of water.
Permission can be given to use water for cooling, if the cooling system is equipped with a cooling tower or the like,
and the water consumption is limited to priming water that serves as after-fill for the evaporation that occurs during
the operation of the cooling system.
3.3.2.1 Rainwater systems for use of rainwater for toilet flushing and washing machines
Rainwater systems are designed according to a number of overall requirement specifications. Please refer to /8/.
In Pipe Center instruction 003, use of rainwater for toilet flushing and washing machines in homes, there is a detailed
guideline on design and installation of rainwater systems.
Water wastage caused by repair and maintenance work is limited to a reasonable degree.
Installation elements are positioned so that they can easily be repaired and maintained.
Shut off valves and drain valves should be installed to such an extent that water spillage, when emptying in
connection with repair and maintenance work, is limited.
Hot water containers should be shut off, but in such a way that the water’s expansion is not impeded,
Fittings, such as safety and non-return valves, which require regular repair and maintenance, are positioned so that
water wastage is limited.
For hot water containers with a water content of more than 300 I, the safety valve should be placed over the top of the
hot water container, and the non-return valve is placed between 2 shut-off valves.
For hot water containers with a water content of 300 l or less, the non-return valve and shut-off valves can together
be replaced by an adjustable non-return valve.
3.3.6 Preventing misuse
.By tapping points where the risk of unnecessary water consumption is high, the installation is installed so that water
consumption for use is limited.
Limiting water consumption relates to showers, etc., in bathrooms, in schools, swimming pools, businesses,
campgrounds, marinas, etc.
The water flow at the individual showers is limited to the size needed for proper function. With appropriately designed
tapping points, this can often be achieved.
46 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Water consumption by showers in public pools and the like is limited by an automatic reduction of tapping time at each
tapping point. Central operation of several showers should only take place where there is assurance that all showers are
used simultaneously. Setting the desired temperature is done easily and quickly, for example, by means of thermostatically
controlled mixed fittings.
Water systems must be made out of materials, etc., that, taking into account the installation method and use of resources,
have sufficient durability /2/.
The aim is that as much of the installation as possible be designed as replaceable, with regard to maintenance,
repair and changes to the use of the building.
Installation components that are positioned in such a way that they are not replaceable, must be of such quality that they
can last as long as the building or the part of the building where they are located. See also BYG-ERFA Sheet No. 05 04 10,
Corrosion in water systems - threaded joints of galvanized steel, and BYG-ERFA Sheet No. 05 06 27, Domestic Water
Installations - piping materials..
Materials and assemblies must be selected while taking into account the current water quality and installation method.
Assemblies should not be used in non-replaceable installations in buildings. Built-in fixtures can be used if delivered with
assemblies for pipe connections and a leakage protection box, which ensures that any leakage can be discovered on the
fixture or through an empty pipe.
The use of built-in fixtures assumes that the function of the fixture and its components for ensuring density and notification
of leakage, is documented in accordance with accepted test methods. Table V 3.4.1 provides examples of suitable pipe
materials with regard to corrosion problems in different water qualities, uses and replaceability. The mentioned overview of
limiting water qualities does not take into account that these materials can give off too much metal in relation to the drinking
water requirements.
Table V 3.4.1 b indicates some types of water, which cause special corrosion problems.
Copper and galvanized steel can be used in the same pipe system, provided that all parts of steel are placed before parts
of copper in the flow direction.
The installation is performed so that the risk of water containing copper flowing back into the pipes and containers made
out of steel, etc., is minimal. Transitional pieces can be built in, like for example, ion traps in the form of so-called ’pig tails’,
which prevents natural circulation of water. The transitional piece may be made out of a suitable plastic material. See also
BYG-ERFA Sheet No. 94 10 21. Large parts of brass and gunmetal may give off copper in quantities that are harmful to the
galvanized steel pipes, and therefore it is recommended to also build in ion traps in the transition from galvanized steel
pipes to bigger parts of brass and gunmetal, e.g. distribution pipes.
Copper must be able to expand freely, so that temperature fluctuations do not result in corrosion fatigue.
Temperature fluctuations will occur in, for example, hot water pipes without circulation or with time-limited circulation.
The system must be dimensioned and executed so that the materials are not destroyed by turbulence corrosion. For
copper pipes, the speed must not exceed the values specified in Table V 3.4.1 c.
For regulation of any circulation pipes, it should be ensured that the circulation is efficient and uniform. In a regulated
circulation system of galvanized steel with electrolytic protection, the speed should be at least 0.05 to 0.1 m/s.
Since impurities in pipes, etc., result in an increased risk of corrosion, there should be, before use of new construction and
after repairs have been performed on an installation, an effective flushing of the installation so that all impurities are
removed.
Out of consideration for corrosion risks, the period from the first water filling until use, should be as short as possible.
Flushing the installation is carried out at regular intervals (approximately 1 time per month), until the installation is used.
Electrolysis systems are put into operation at the same time as the installation and adjusted according to the water
consumption.
47 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Valves, pipe fittings, fixtures, meters, water meters, containers etc., in the pipe system, are installed with water-affected
parts made out of material that has sufficient corrosion resistance. Valves etc., made out of dezincification-resistant brass
or gunmetal, is considered to have adequate corrosion resistance. Where water has a low chloride content compared to
the transient roughness, regular brass can be used. Replaceable tapping and mixing valves of ordinary brass may be used.
Table V 3.4.1 d provides examples of suitable combinations of materials in systems for hot water production and
subsequent pipe installations, taking into account water quality.
Table V 3.4.1 e provides indicative examples of collection methods for replaceable water pipes in buildings and
for water pipes in the ground. Please also refer to BYG-ERFA Sheet No. 07 05 01, Galvanized water pipes - corrosion and
corrosion in new systems.
48 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Table V 3.4.1 a - Examples of suitable pipe materials for water pipes, taking into account corrosion problems in
various water qualities, uses and replaceability
1
use
material water quality in ground inside building
49 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
alkalinity (HCO-3 > 300 mg/l Galvanized steel should not be used
aggressive carbon dioxide > 2 mg/l Galvanized steel should not be used
-2
Cl" + 2SO Galvanized steel should not be used
------------- ~> 1 measured in mmol/l
HCO3
pH < 7 and hydrogene content is less than sulphate copper can pit
content measured in mol/l
HCO:
-------2-<1
SOj-
alkalinity (HC03) > 240 mg/l After being idle for 12 hours, copper release in the tubes
may exceed 2 mg/l
high chloride content in relation to the transient brass can dezincify
roughness Dezincification-resistant alloys can be used
-
Cl > 150 mg/l increased corrosion risk for stainless steel
high conductivity (> 100 mS/m) magnesium anode can be used but corrodes quickly.
Risk of odors and hydrogen development
low conductivity (< 30 mS/m) magnesium anode in untreated steel container can only
be used for specially suitable structures or through
insertion of multiple anodes
very low conductivity (< approx. 10 mS/m) electrolysers and enameled containers with anode can
not be used
1) Information on water quality can be obtained from the waterworks.
2) Corresponds to the transient roughness from calcium having to be above 0.5 mmol/l {2.8° dH German roughness
degrees).
50 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Table V 3.4.1 c – Maximum speeds in water pipes made out of copper with regard to
corrosion
1
water pipe installation area highest justifiable speed in m/s
2
cold water hot water
<25 °C <70°C
pipe with continuous flow replaceable and non-replaceable 2,0 0,5
e.g. circulation pipe distribution pipes
pipe with total flow > 6 hours replaceable and non-replaceable 2,0 1,3
per day distribution pipes and coupling pipes
pipe with total flow > 6 hours replaceable distribution pipe and no limits
per day coupling pipe
1) In extremely adverse conditions, turbulence corrosion can occur, e.g. due to corrosive water, poor
geometry at branches, valves, solder joints, etc., air pockets in pipes, relatively long duration of flow.
2) At higher temperatures, the speeds should be reduced by at least 25 per cent.
51 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Table V 3.4.1 d - Examples of suitable materials for systems for hot water production with
regard to water quality
1 2
system for hot water production requirements for subsequent pipe installation
water quality
2
heating surface containr galvaniz galvanized coppe stainless plastic
ed steel steel +r steel
electrolysis
3 4
cap container or steel + conductivity +) 0 +) + +
container with magnesium anode > 30 mS/m
inserted heating steel + electrolysis conductivity + + 0 0 0
surface made out of > 10 mS/m
copper, enamelled 3 5 5
steel pipe or stainless steel, enamelled with conductivity +) - +) +) +
steel anode > 10 mS/m
3 5 5
steel, plastic-coated no special +) - +) +) +
1
requirements )
copper-lined steel pH > 7,5 - - + + +
stainless steel no special + 0 + + +
6
requirements )
flow water heaters copper pH > 7,5 - - + + +
7 7
stainless steel no special
6
+) +) + + +
requirements )
Legend:
+ The combination is right.
- The combination can not be used.
0 The combination can be created, but is normally not required.
1) Plastic coatings are assumed to be impermeable.
2) If heating takes place with electric heating coil or heating coil, one should take into account the corrosion conditions that
are temperature-dependent. Materials must at least be as reported in Table V 3.4.1 a.
3) If the container is equipped with copper heating surface, galvanized steel pipes can subsequently not be used.
4) Maintenance of the anode is very important.
5) The risk of galvanic corrosion at spigots. The risk may be minimized by using non-conductive transitional piece, e.g.
plastic transitional piece that is approved for hot water.
6) Material and construction is adapted to water quality. Steel quality similar to AISI 316 or better.
7) If heat exchanger is copper brazed, galvanized steel pipes can subsequently not be used.
52 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Table V 3.4.1 e - Indicative examples of assembly methods for pipes and fittings for replaceable
water pipes in buildings and water pipes in soil
material assembly method
pipe fitting hard soft mech
solde solder anical rubber
threaded assembly
1 1
ring ing asse ring
flange assembly
mbly assem
bly
lead cast
bonding
welding
cast iron cast iron - - - - - jb - jb
2
galvanized steel galvanized soft castings - - - - - - jb b -
stainless steel stainless steel - - - - jb - - - -
3
copper copper or copper alloy ib jb jb ) - jb - - jb -
PVC plastic or metal - - - jb jb jb - ib -
PEL plastic or metal - - - - jb - - - -
PEM jb - jb - - - -
PEH jb - - - jb -
PEX metal - - - - - - - -
Legend:
b: Usable in building
j: Usable in soil
53 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Pressure booster systems are designed to take into account both the size of the pressure increase as well as the time
during which the pressure increase occurs.
Pressure booster systems are controlled automatically and designed so that the pressure only increases during periods
when supply pressure is too low to ensure an adequate supply.
Pressure booster systems should have a high degree of efficiency in the entire operating range. The pressure should only
be increased in the part of the installation that needs it.
Water systems, in which pressure increases are performed, are installed for a sufficiently low pressure loss in the
installation.
As a condition for dimensioning, a low pressure loss in the conduction system is expected (such as an average pressure
loss per m of pipe of 2-4 kPa/m).
Fixtures are used in low pressure group.
Execution of the hot water installation is for the purpose of reducing energy consumption, for example, by:
- Reducing heat loss to surroundings
- Reducing energy losses when tapping water with too low a temperature
- Reducing energy consumption during possible pump circulation
- Using water-saving design of fixtures
- Automatically controlling hot water temperature
- Using electric heating cables where this leads to less energy consumption than, for example, circulation.
54 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
For adequate hot water temperatures in terms of functionality and comfort, see 4.6.4.
For recommended hot water temperatures in terms of the risk of germs and bacteria growth, see 2.5.1.
Water Heaters are insulated according to DS 452, Code of practice for thermal insulation of technical installations;
55 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
4.1 Conditions
4.2.1 The quality of the added water
Water that is added to drinking water installations, is assumed, in physical, chemical and bacteriological terms, to meet the
requirements that the Ministry of the Environment sets for drinking water /14/.
Rainwater systems with water from certain roof areas, may be used for toilets and washing machines in homes and
residential buildings. With regard to the requirement specifications for these systems, please see /8/. Rainwater systems
are installed according to the Technology Institute’s Pipe Center-instruction 003, Use of rainwater for toilet flushing and
washing machines in homes.
A water installation that is connected to a regular water supply (public or private municipal waterworks) must not
simultaneously be associated with other water extraction plants such as emergency supply plants, rainwater systems and
single facilities.
Water from water supply systems, which are subject to regulatory supervision, is assumed to be satisfactory.
For emergency supply established between two water extraction systems, in the event that one or the other water supply
fails, the connection is established in such a way that the two systems can not directly be connected with each other.
Systems for changing the water’s chemical or bacteriological quality may only be placed in the water installation after being
authorized by the authority, and only if the treated water is used solely for technical purposes, or the system
meets the requirements of the building regulations. Refer to / 6/ and Orientation from the EPA No. 6, 2004.
Installations for water for industrial use or installations that for other reasons result in the requirements for drinking water
quality not being met, are marked in such a way so as to avoid misuse /21/.
Systems only used for heating of water, aluminum and magnesium anodes, electrolytic plants and certain unrefined
mechanical filters are deemed only to affect water quality to a lesser extent during proper operation.
Pipes to treated water are marked with special color or according to DS 134, Colors, and distinguishing letters on pipes for
use on drawings and pipe systems. Tapping fixtures and apparatus are marked "Not Drinking Water '
Water for washing machines and dishwashers - also for ordinary households - are regarded as water for technical
use when the treated water is used exclusively for these devices.
Hot water systems are installed so that the hot water, at a water flow of 0.2 l/s, reaches frequently used tapping points
easily without delay. If an adequate waiting time for the hot water of a maximum of 10 seconds is used, the following table
can work as a guideline for the length of a copper pipe, which has been completely emptied for water that remained still in
the copper pipe.
56 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
where
r is the waiting time in seconds
dl is the pipe’s inner diameter in mm
L is the pipe’s length in meters
Use of these guidelines will limit the concentration of copper in the intake of drinking water projected as the weekly
average.
waiting time approximate length of copper pipe that is emptied in r seconds in the dimensions
(outer diameter x thickness in mm):
sec. 10x0,8 12x1,0 15x1,0 18x1,0 22x1,0 28x1,2
1 3,6 m 2,5 m 1,5 m 1,0 m 0,6 m 0,4 m
2 7,2 m 5,1 m 3,0 m 2,0 m 1,3 m 0,8 m
3 11 m 7,6 m 4,5 m 3,0 m 1,9 m 1,2 m
4 14 m 10 m 6,0 m 4,0 m 2,5 m 1,6 m
5 18 m 13 m 7,5 m 5,0 m 3,2 m 1,9 m
6 22 m 15 m 9,0 m 6,0 m 3,8 m 2,3 m
7 25 m 18 m 10 m 7,0 m 4,5 m 2,7 m
8 29 m 20 m 12 m 8,0 m 5,1 m 3,1 m
9 33 m 23 m 14 m 9,0 m 5,7 m 3,5 m
10 36 m 25 m 15 m 10,0 m 6,4 m 3,9 m
Waiting time for "emptying" of copper pipes, dependent on pipe diameter and pipe length
If the stretch of pipe consists of partial sections with different diameters, the waiting time is calculated as the sum of waiting
times for each stretch of pipe, and all waiting times are calculated for 0.2 l/s, regardless of whether one part of the stretch
of pipe might be a distribution pipe that is dimensioned for a higher flow.
4.3 Damages
4.3.1 Ruptures
Water systems must be designed in such a way that there is no risk of ruptures /9/. Water systems must be designed so as
to avoid damaging pressure and pressure shocks /9/.
Water systems are made out of materials and components that can withstand the highest pressure that can occur in the
system, but at least 1000 kPa.
For systems that are in an unblockable connection with the atmosphere, the pressure is set individually. This applies to, for
example, containers where there is no shut-off option after the container.
Heating of water must take place so that no harmful pressure arises.
Heating of water must take place in such a way that the water temperature usually does not exceed 95°C.
For water heaters, safety valves are installed and dimensioned so that the pressure can not exceed the pressure, which
the container and the system is intended for. The safety valves’ function must be easily controlled by manual control of a
weight or spring-loaded arm or the like.
57 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Safety valves are installed and placed so that the risk of calcificaton, dirt, etc., that hinders proper function, is small. Safety
valves are normally placed on the cold water inlet near the water heater, and so that there are no shut-off valves, control
valves or other constrictions between the water heater and the safety valve.
Safety valve may be omitted for containers that are in an un-blockable connection with the atmosphere through a pipe
connection with necessary opening.
For non-pressure-resistant flow water heaters and containers, shut off valves, control valves or other constrictions must not
be placed on the outlet pipe.
For water heaters, where the water temperature can exceed 100°C, protection is established according to specific rules
established by the Danish Working Environment Authority.
Outlets from safety valves are installed and placed so that the blow-capability is not reduced, and so that drainage of
excess water can take place visibly and hazard-free.
The outlet pipe from the safety valve must not be blocked. Normally, the outlet pipe should have at least the same
dimension as the safety valve’s open end. It must not be installed directly on the drain pipe, but instead, for example, end
up freely and visibly over the floor drain’s water table or freely and visibly over funnel or other installation element with a
corresponding water trap.
The pressure booster system is installed so that the pressure can not exceed the test pressure.
The pressure booster system is equipped with automatic shutoff, which is triggered at a pressure that is less
than or equal to the test pressure, and at a pressure on the suction side of less than 100 kPa.
The pressure booster system is equipped with easy to read pressure gauges.
If using positive displacement pumps (e.g. piston pumps), the authority may require special measures, such as safety
valves to ensure against impermissible pressures.
Water systems are installed so as to avoid generating explosive gases.
In water systems with electrolysis systems, overtreatment of water can cause a development of hydrogen sulphide and
hydrogen (H2). The electrolytic treatment of the water must be controlled by the water consumption, if overtreatment is to
be avoided.
4.3.2 Scalding
Water systems must be installed so that the collection of water does not result in a risk of scalding, and so that
no surface temperatures occur that can cause damage to persons /24/.
Outlets from safety valves are installed so that the outflowing hot water does not pose a risk of scalding.
The requirements are deemed to have been met in housing, etc., if one of the following conditions is met:
- Installations for the production of hot water are installed so that the hot water temperature does not exceed 65°C
- Cold water is mixed in centrally so that the temperature does not exceed 65°C
- The mixture is controlled automatically
- At the individual tapping points for personal hygiene, mixing fixtures have been installed that are designed so that the
temperature of the tapped water can not exceed 65°C.
By shower seats and the like, in kindergartens and some personal care departments, mixing at the tapping points should
ensure that the temperature of the tapped water can not exceed 38°C.
Surface temperatures that can cause harm to people, are deemed not to be able to occur if the pipes and containers etc.,
are insulated in accordance with DS 452, Code of practice for thermal insulation of technical installations.
The surface temperature on any uninsulated parts of the water system should not exceed 65°C in apartments, etc., and
90°C in boiler rooms, container rooms etc.
The surface temperature of the controls on tapping fixtures should not exceed 40°C.
58 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
You can disregard the requirement for maximum surface temperatures on coupling pipes in the same room as the tapping
fixture.
Outlets that lead to installation elements that are intended for personal hygiene, are installed so that there is no risk of
scalding.
Measures to protect against back-flow of treated water is adjusted according to the treated water’s health
hazard and the nature and use of the installations.
Installations for drinking water shall be designed so that water that is tapped at a tapping point, and treated water, can not
flow back to the drinking water installation /16/.
Please also refer to DS/EN 1717, Protection against pollution of drinking water in water systems and general
requirements for backflow protection.
For new systems and substantial modifications to existing installations, in order to protect water supply system against
pollution from failing backflow prevention from installation elements, water heaters, water treatment plants, rainwater
systems, etc., an appropriately approved /6//7/ backflow prevention must be installed on the distribution pipes after the
ground pipe’s insertion into the property and before branching to another pipe /15/. Refer to DS/EN
1717, Protection against pollution of drinking water in water systems and general requirements for backflow protection.
In ordinary homes, a non-return valve can be used, if necessary, installed in the property's water meter.
In installations with rainwater systems, a special backflow prevention is used, especially approved for this purpose, in
accordance with Pipe Center-instruction 003, Use of rainwater for toilet flushing and washing machines in homes.
In other installations, backflow prevention is used that has been adapted according to the treated water’s health hazard
and the nature and use of the installation.
Methods for protection against backflow are shown in Figure 4.4.1 V a and V 4.4.1 b. DS/EN 1717, Protection against
pollution of drinking water in water systems and general requirements for backflow protection, extensively describes
methods for ensuring the quality of drinking water and establishes minimum requirements for product standards for
backflow prevention.
Rainwater systems that are installed as indicated in the Technology Institute’s Pipe Center-instruction 003, Use of
rainwater for toilet flushing and washing machines in homes, are deemed to have met the requirements.
1. Air gap. A clear height of at least 20 mm between the tapping valve’s outlet and the highest possible water level in the
installation element {sink, bathtub, etc..), which the tapping valve is positioned over. If the installation element is equipped
with overflow, and if this can safely carry off the greatest amount of added water, the distance may be measured to this
point. If there is overflow by the bidet, sink and kitchen sink, these are deemed not to have sufficient capacity, and the
height is therefore measured over the installation element’s upper edge.
For particularly hazardous installations such as tubs containing toxic or corrosive substances, the free height is increased
to at least 50 mm. At these particularly hazardous installations, the air gap can not be replaced by non-return valves and/or
vacuum valves.
2. Non-return valve. For installations with a particular risk, such as in laboratories and softening plants, the non-return
valve is designed or placed in such a way that its function can be controlled. This can be done by placing the non-return
valve after a shut-off valve and a drain valve. This way, unwanted backflow can be discovered. Please also refer to DS/EN
1717, Protection against pollution of drinking water in water systems and general requirements for backflow protection.
3. Vacuum Valve. The vacuum valve can be positioned either so that it usually is under pressure (high pressure vacuum
valve), or so that it is only under pressure when opening a tapping valve (low pressure vacuum valve).
59 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Vacuum valves are placed directly on the inlet pipe in a T-piece, whose height above the top edge of the installation
element (possibly the overflow according to the same criteria as specified under air gap) is at least 300 mm.
Lower installation height is only permitted in grouped fixtures with special approval.
Instead of vacuum valves at each installation element, a shared vacuum valve can be placed for each rising distribution
pipe. However, it is a condition that the branching of the rising distribution pipe is placed at a height of at least 300 mm
above the installation element’s upper edge.
4. Open pipe interruptor. An open pipe interruptor that is designed according to the ejector principle, is positioned at a
height of at least 20 mm above the installation element’s upper edge. Open pipe interruptors in connection with flush valves
with toilets or bedpan washers, are always placed at least 300 mm above the bowl's rim.
3
fire extinguishing system ) water-filled hoses
60 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
non-pressure-resistant plants for hot hot water container with more than 10 l
1
water production volume
shut-off valve
non-return valve
non-return valve, controllable
non-return valve, adjustable
safety valve
tapping valve
vacuum valve
1) Shut-off valve and non-return valve can be replaced by an adjustable non-return valve.
2) For all pressure-resistant flow water heaters, the examples shown here assume that the heated water volume is less
than 10 l. If the volume is greater than 10 l, a shut-off valve, a non-return valve and a safety valve must always be placed on
the inlet pipe.
3) Are installed according to the rules indicated in:
- The Building Regulations
- The Danish Institute for Fire and Security Technology’s fire-technical guideline no. 16
- DS/EN 671-1 Hose reels with semi-rigid hoses
61 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
pollution degree nature of pollution or risk examples of premises/ method to ensure proper
tapping points and water function
treatment plants, where risk
of pollution can occur
1 highly concentrated toxins chemical industries,
or particularly dangerous laboratories
viruses and bacteria
62 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Water that is allowed to remain in water installations for a shorter or longer period of time, will change the quality. This
could be due to bacterial growth or discoloration.
The removal must be done right at the branching from the part of the installation that is in use. Parts of a water installation,
which for more than a year is expected to be unused, must be shut off and drained. This does not apply to fire fighting
installations.
Emptying of a temporarily unused installation can be done in such a way that there is no risk of contamination of the
installation.
Since the water in the fire extinguishing system only is renewed occasionally, a non-return valve is placed right where the
extinguishing system branches off from the normally used pipe system.
The non-return valve’s closing mechanisms are made out of metal or other material that is resistant to extremely high
pressures on the closing mechanism. The non-return valve may not be an adjustable non-return valve.
Draining should be done so that it can be established that the installation is completely empty.
Pipe systems that are unused for shorter periods than approx. 1/2-1 year, like for example in summer cottages, do not
need to be emptied with regard to pollution hazards. See also 4.5.8 on protection against frost.
Pipelines, containers, etc., for drinking water, which may come into contact with liquid or gaseous substances that
may be under higher pressure than the water supply pressure, are designed in such a manner or made of such materials
that the risk of penetration of foreign matter into the water installation through corrosion, etc., can be disregarded.
Drainage devices are installed and positioned so that polluting organisms and substances can not penetrate into the water
installation.
Pipes made of polyethylene (PE) are not sufficiently impermeable to certain hydrocarbons and can therefore not be used
as ground pipes at gas stations, garages, etc., where the leachable and percolating oil and gas can diffuse through the
pipe wall.
For distances between pipes, please refer to DS 475, Standard for the establishment of pipe systems in soil.
Filling of water in hot water installations (central heating plants, maximum temperature 120°C) and low pressure steam
plants (Max. 120°C and max. pressure 1 bar) will normally be allowed when it is done through an adjustable non-return
valve.
Emptying to seepage well, or the like, may be permitted where there is no risk of groundwater, rising drainage water and
percolating surface water, etc., penetrating into the water installation, or if the water installation is designed so that it can be
shut off after being emptied. Emptying mechanisms must be designed so that emptying is easy to do, and takes a
sufficiently short time.
In heat exchangers (e.g. in water heaters), where pipes or containers with drinking water may come into contact with
harmful media, such as sewage, and water to which harmful substances have been added (such as antifreeze agents,
corrosion-inhibiting agents, etc.), measures are taken that can notify if due to corrosion, risks arise of harmful substances
penetrating into the drinking water.
For hot water containers, where the water pressure is greater than the pressure in the heating medium, special measures
are usually not required.
63 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Where the pressure in the heating medium can become greater than the water pressure, e.g. through district heating,
special measures can be implemented in terms of the quality of material and possibility for inspection and cleaning. Cap
containers made of steel without special corrosion protection may not be used in district heating plants.
In cap containers where the heat medium pressure is greater than the water pressure, a corrosion protection alone through
the use of a magnesium anode, is not considered sufficiently safe, since protection is dependent on anode replacement.
By contrast, a magnesium anode is considered to provide adequate protection in a cap container made of steel, if the heat
medium pressure is less than the water pressure as in normal central heating plants.
Where, exceptionally, the cooling of galvanic baths or the like is allowed through direct use of water that passes through
the cooling pipes in the bath, there can be no shut-off valves on the cooling water pipe after the bath, and it must
end up freely visible above the floor drain or the like.
4.4.6 Aids
If aids are used when installing water systems, such as cooling/lubricating agents and fluxes that can
cause damage to pipe installations, or which impair water quality, the aids are flushable with water and easy to remove,
and removal must be done before use.
Coolants/lubricants and fluxes are subject to the approval scheme for each product.
4.5.1 Foundation
Water systems must be installed so that, when excavating for their installation, or during any subsequent repair or in the
permanent state, no damage occurs to the property's foundation, and the systems must be positioned in relation to the
property’s foundation so that, when excavating for the pipes along the length of the property or intersecting the property,
this does not result in a deterioration of the foundations support capacity or damage occurs as a result of deposits.
Pipes are installed so that the pipes are supported throughout their length. For pipes with sleeve joints, one must
avoid that the sleeve carries the pipe. If the soil bottom is not sufficiently sustainable, a special foundation must be made.
For changes in direction and branching. the pipe must be secured against displacement, if necessary through back-casts.
Please also refer to DS/EN 1997-1 and DS/EN 1997-2, Eurocode 7: Geotechnical design and DS 430, Code of Practice for
the laying of underground flexible pipelines of plastics, and DS 475, Code of Practice for trenching for underground pipes
and cables
4.5.2 Penetrations
Water systems must be installed so that they do not give rise to fire and dispersal of smoke between fire compartments or
between fire cells /1.
When water systems are installed in or across building components, for which there are fire safety requirements,
the overall construction must be performed so that the required fire-technical separation is maintained.
Pipe penetrations in building components are performed so that the building components’ properties are not unacceptably
impaired.
This requirement relates to, for example, building components’ strength and protection against moisture and sound.
Pipe penetrations that are likely to be exposed to moisture, for example, in bathrooms, are made moisture-proof.
4.5.3 Brackets
Securing water installations to building components is performed in such a way that no damage occurs to building
components and installation parts.
64 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
The requirement relates to the attachment of pipes, fittings and installation elements to building components, see Table V
4.5.3 a and b.
Attachment of pipes etc., to building components, may only be done to building components that can absorb the clamping
forces.
Table V 4.5.3 a – Largest distance between pipe clamps to horizontal distribution pipes
pipe size largest distance between pipe clamps on pipe made of:
mm steel m copper m PVC, PEH, PEM m PEL, PEX m
<20 2,5 1,25 0,7 0,3
25 2,5 2,5 0,9 0,4
32 2,5 2,5 1,0 0,4
40 ~~' 3,0 2,5 1,1 0,5
50 3,0 2,5 1,2 0,5
65 4,0 2,5 1,4 0,6
75 4,0 3,0 1,5 0,6
90 5,0 3,0 1,6 0,7
100 5,0 3,0 1,7 0,7
Table V 4.5.3 b - Largest distance between pipe clamps to vertical distribution pipes
pipe size largest distance between pipe clamps on pipe made of:
mm steel m copper m PVC, PEH, PEM m PEL, PEX m
<20 2,5 1,25 0,8 0,5
25 2,5 2,5 1,0 0,6
32 2,5 2,5 1,3 0,8
40 3,0 2,5 1,6 1,0
50 3,0 2,5 2,0 1,3
65 4,0 2,5 2,5 1,6
75 4,0 3,0 3,0 1,9
90 5,0 3,0 3,6 2,2
100 5,0 3,0 4,0 2,7
4.5.5 Pressure-shock
Water systems are installed so that pressure shocks etc., do not damage any building components, installation parts or the
environment.
Pressure shocks can cause pipes to break etc., and this might cause harm to the environment.
4.5.6 Flooding
Water systems must be installed so that there are adequate safeguards against spillage or leakage of water that can cause
damage to buildings /25/.
Tapping points may only be installed where there is a complete drainage installation with sufficient capacity, or where the
water can be discharged in another way or collected appropriately /26/.
65 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Devices with automatic water filling, that are set up in rooms without a floor drain, must have mounted or built-in adequate
protection against accidental water leakage and must be placed so that any leakage of water can be discovered /27/.
Washing machines and dishwashers for household use, which are CE-marked according to DS/EN 61770, Electric
appliances connected to the water mains - Avoidance of backsiphonage and failure of hose-sets, which are sold in
Denmark, can be placed in a room with no floor drains if they are placed on a waterproof surface that is constructed so that
outflow or leakage of water can be discovered.
Washing machines and dishwashers for household use, which are CE-marked according to DS/EN 61770, Electric
appliances connected to the water mains - Avoidance of backsiphonage and failure of hose-sets, which are sold in
Denmark, with special protection and special design to ensure that leakage of water is prevented, can be installed in rooms
without floor drains and waterproof surface.
Washing machines or dishwashers without protection against flooding, can only be set up in rooms with floor drains.
4.5.7 Condensate
Water systems must be installed so that no harmful condensation occurs.
In buildings, water systems that carry cold water, must be insulated against condensation.
insulation of visible coupling pipes against condensation can usually be omitted in the same room as the tapping point.
Insulation can be performed according to DS 452, Code of practice for thermal insulation of technical installations.
Risk of frost damage can normally be avoided when the following rules are observed:
a. Pipes in soil are installed at a depth of at least 1.2 m to the top of the pipe. Pipes for sprinkler systems and other
fire extinguishing systems, however, should be installed at a depth of at least 1.4 m, as there is usually no water movement
in these pipes and the risk of frost damage is therefore higher than for normal pipes. Pipes should not be inserted into
buildings through or right by light boxes or basement stairways, but must be kept at a distance of at least
1.0 m.
b. If pipes for temporary use (construction use, allotments, garden irrigation, etc..) are placed at a non-frost-free
depth, the system must be installed so that it can be shut off and tapped off.
c. Pipes in unheated rooms should not be placed on outer walls and away from doors, windows or other
openings to the outside.
d. Pipes that may occasionally be exposed to frost for short periods should be insulated. Pipes that may be exposed to frost
for extended periods should be equipped with heating alternatives, such as electric heating cables that are put
into operation during periods of frost.
e. Installations in buildings that are periodically unused, and where there is no assurance that the building is kept
heated, should be installed so that they can be emptied.
When determining the lifetime, one must take into account the building's function and design, as well as the way the
installation is integrated in the building.
Installation parts that require inspection and maintenance or have a shorter lifetime than the building, must be replaceable.
66 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Installation parts, where the risk of leakage is particularly high or can not be assessed with certainty, must be performed so
that any leaks are discovered immediately.
In evaluating the lifetime of the installation and the risk of leaks, the following is taken into account:
- The materials’ resistance. Copper pipes for cold and hot water and PEX pipes and stainless steel pipes for cold
water, are considered suitable materials.
Stainless steel pipes for hot water are considered suitable with exterior protection, see table V 3.4.1 a.
- Techniques for performance of the work.
- Safety when inspecting the work.
- Extent of possible damage.
- Experiences with installation parts.
Pipes with assemblies that, with respect to density and resistance, can be considered equivalent to pipes without
assemblies, for example, factory-made installations, must be performed as non-replaceable. Density and resistance must
be documented and stated in the approval /6/ /7/.
There are several installation methods that can meet the above-mentioned standard requirements. Where risk of damage
is particularly high, hidden pipes, for example, can be put in empty pipes, which enables immediate discovery of leaks.
Non-visible assemblies can be placed in recesses or the like, for example as shown in Figure V 4.5.9, where leaks can be
discovered immediately and where inspection and repair can be performed easily.
Non-replaceable pipes made of copper in the sizes 12, 15, 18 and 22 mm, which are damaged after the installation has
been commissioned, can be repaired by using a solder assembly carried out according to specified guidelines, for
example, repair of non-replaceable copper pipes in water installations, DTI Work Instruction 9301, Danish Technological
Institute 1993.
67 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
4.5.11 Leakage-resistance
Prior to commissioning after new construction, modifications and major repairs, the installation must be tested for
leakage-resistance /3/.
Water systems must be leakage-resistant for the maximum occurring pressure, but at least 600 kPa, measured at the
installation’s lowest point.
Leakage-resistance can be tested with water pressure. The leakage-resistance test pressure must at least be the highest
occurring operating pressure.
In supply areas where it is likely that the supply pressure will be increased, the leakage-resistance test pressure should be
determined accordingly.
In special cases, the leakage-resistance test can be performed with air pressure, but no more than 50 kPa, and in
accordance with the Danish Working Environment Authority’s regulations.
4.6 Inconveniences
Pipe penetrations through walls and floor separations are usually performed with odor-proof packed bushings. Where this
does not give rise to inconveniences, such as basements, the penetrations can be performed non-odor-proof.
The Building Authority requires fire-technical separation between certain types of rooms and groups of rooms.
If the authorities do not place accessible shut-off valves on the plug line, shut-off valves will be placed on the ground pipe.
The main shut-off valve must be readily accessible and easy to operate. The location of the valve is marked in accordance
with the authority’s provisions.
Water systems are equipped with shut-off valves and drainage options to an extent that is determined while taking into
account the expected frequency and extent of the work and the installation's size and use.
Water systems in residential buildings are performed so that frequent repairs etc., in a home, can be performed without
inconvenience to other homes.
In multi-storey buildings, shut-off valves should also be placed on all vertical distribution pipes by the branching from the
horizontal main distribution lines.
68 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Water systems are performed so that inconvenient overflow from the hot water to the cold water installation can not occur
/19/.
Water systems are performed so that inadvertent heating of the cold water is avoided as much as possible.
Insulation can be performed according to DS 452, Code of practice for thermal insulation of technical installations.
Regarding the temperature of the heated water, in terms of germs and bacterial growth, see 2.5.1.
For sinks, which will mainly be used for washing of hands, e.g. in toilets in offices, medical clinics, etc.,
water temperatures achieved by mixing hot and cold water at tapping points down to about 30° C can be accepted.
Water systems are performed so that an accidental cooling of the hot water is avoided as much possible.
Pipes for hot water are insulated against heat loss according to DS 452, Code of practice for thermal insulation of technical
installations. Pipes for hot water should not be installed in particularly cold rooms (e.g., basements).
Insulation may be omitted on coupling pipes in the same room as the tapping point, if the wait is not too long. If the wait
becomes too long, circulation is performed in the hot water system.
Pipes are kept at a distance from the electricity meter frames that is consistent with the provisions of the
Common Regulations for connection of electrical installations and usage elements. Please also refer to DS 1102,
Installations in building - Calculation of installation spaces for pipelines
Pressure booster systems may not cause annoying pressure fluctuations or noise in the building or neighboring properties.
The building regulations specify requirements for max. permissible noise levels in certain rooms. The provisions indicate
the possibility that compliance with the requirements can be checked through measurement.
The requirement may be satisfied by selecting appropriate fixtures, etc., and through an appropriate dimensioning,
placement and execution.
Fast-closing and quickly closable fixtures can cause pressure shocks, thereby causing noise.
69 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Systems for cathodic protection or electrolysis are dimensioned and operated so as not to develop malodorous gases.
Current, anode sizes etc., are tailored to the properties of the water and the size of consumption, so that the release of
aluminum does not become too big.
70 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Installation parts (fittings, appliances, containers, etc.) must be labeled so that operating method and restrictions of use are
readily understandable.
For installations for hot water production, water treatment systems, pressure boosting systems and fixtures that require
monitoring and maintenance, the clear distance on the operation side must be at least 0.6 m.
The room where the water system is located, should be arranged so that it is possible to perform replacement or repair
of components and fittings. It should be easily accessible and access paths should be planned so that the necessary
replacements of components, etc., can be performed.
The operating Instruction must be prepared and detailed, taking into account the water installation’s design and size
according to DS 1021, Users manual regarding service components and equipments in building.
It should also be structured so that it is easily understandable and easy to use in the daily work. Tables, diagrams and
illustrations should be used to a great extent, which can give a clear overall picture of the functions, location of components
etc.
The operating instruction should contain a table of contents, address and telephone lists, general information about the
systems and a summary of agreements affecting the operating and maintenance work.
The operating instruction should also give a briefing on the structure of the systems and the operation as well as
information on the location of the components.
One should aim to offer easy access to the devices that are to be used to check the system's function and
proper operation.
71 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Annex A
(informative)
Determining the dimension-giving water flow qd in distribution pipes
The following calculation method may be used, when an installation type has measured or estimated values for water
flows, rates of use and consumption. The values can come from measurements on systems in use in buildings with similar
use.
The calculation of the dimension-giving water flow qd based on measured mean water flows from the individual tapping
points, as well as for the projected water flows greater than 0.3 l/s, can be done using the following formula:
qd = 2qm + 0{Σqf - 2qm) + A/qm* 0 /Σqf - 2qm l/s
where
qd is the dimension-giving water flow used exclusively for distribution pipes with randomly used tapping points.
qm is the weighted mean water flow for several tapping points connected to the distribution pipe.
q = G1 * qu + G2 * qi2 G+ ……+ Gn * qin/ΣGn l/s
G is a relative size that is calculated based on measured usage frequencies and tapping times at different tapping points. ql
are the mean water flows at each tapping point. G and ql are assigned to the same exposure period.
Σqf is the sum of the projected water flows qf according to Table V 2.2.4.
0 is the probability that it is the qm water stream that is tapped from any tapping point in a period of high consumption. The
value of o can be determined by measurement on installations in use. So far, 0 can be expected to be 0.015.
A is a safety factor that can be set to 3.1.
The mean water flow q1 and the number of tappings at each tapping point G can be determined through measurements on
installations in buildings in use.
Table VA.1 lists examples of measured G- and qt-values for tapping points on a distribution pipe in a building.
If there are no measurements, qm can be calculated from estimated values of the mean water flows q1 and the G-values for
each tapping point. If q1 = qf for the particular tapping point, the mean water flow qm usually stays on the safe side.
72 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
If an installation has systematically used tapping points, then the most probable water flow q syst is calculated as the sum of
projected water flows from these without reduction for simultaneity.
The dimension-giving water flow in an installation that includes both random and systematically used tapping points, is
calculated as:
q’d=qd + qsyst l/s
If an installation has flush valves for toilets or urinals, then the largest water flow is calculated as:
qskyl = 1.5 + (n-1) 0.2 l/s for toilets
qskyl = 0.4 + (n-1) 0.1 l/s for toilets
The dimension-giving water flow in an installation that includes both flush valves and randomly used tapping points, is
calculated as:
q’d=qd + qskyl l/s
if an installation has hose-reels, according to the requirements of the building regulations, then the dimension-giving water
flow for pipes that only supply hose-reels (regardless of the number), is 0.33 l/s.
The dimension-giving water flow in an installation that includes both hose-reels and other tapping points, is calculated as:
q'd= 0,33 + {qd-0,2) + qsyst + qskyl l/s
73 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
Annex B
(informative)
Associated codes of practice, standards, laws, regulations, circularies and
publications
74 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
DS/EN 1452-5 Plastics piping systems for water supply and for buried and above-ground drainage and sewerage under
pressure - Unplasticized poly(vinyl chloride) (PVC-U) - Part 5: Fitness for purpose of the system
DS/EN 1997-1 National Annex to Eurocode 7: Geotechnical design - Part 1: General rules
DS/EN 1997-2 National Annex to Eurocode 7: Geotechnical design - Part 2: Ground investigation and testing
DS/EN 12201-1 Plastics piping systems for water supply, and for drainage and sewerage under pressure - Polyethylene
(PE) - Part 1: General
DS/EN 12201-2 Plastics piping systems for water supply, and for drainage and sewerage under pressure - Polyethylene
(PE) - Part 2: Pipes
DS/EN 12201-3 Plastics piping systems for water supply, and for drainage and sewerage under pressure - Polyethylene
(PE) - Part 3: Fittings
DS/EN 12201-4 Plastics piping systems for water supply - Polyethylene (PE) - Part 4: Valves
DS/EN 12201-5 Plastics piping systems for water supply, and for drainage and sewerage under pressure - Polyethylene
(PE) - Part 5: Fitness for purpose of the system
DS/EN 12897 Water supply - Specification for indirectly heated unvented (closed) storage water heaters
DS/EN 15091 Sanitary tapware - Electronic opening and closing sanitary tapware
DS/EN 61770 Electric appliances connected to the water mains - Avoidance of backsiphonage and failure of hose-sets
DS/EN ISO 3822-1 Acoustics - Laboratory tests on noise emission from appliances and equipment used in water supply
installations - Part 1: Method of measurement - Amendment 1: Measurement uncertainty
DIN 4708-1
DIN 4708-2
DIN 4708-3
DBI Handbook, Fireproofing of buildings, published by DBI - Danish Institute of Fire and Security Technology
Fire Safety Guide No. 31, Fire sealing – Fire sealing of penetrations for installations, published by DBI - Danish Institute of
Fire and Security Technology
Fire Safety Guide No. 15 from the Danish Institute of Fire and Security Technology. Water-filled hose-reels
Environmental Project 970 2004 K. Nielsen, A. Andersen and E Fontenay, Metal release into drinking water part 2,
continuation of tests of materials for house installations, EPA 2004
Working Report No. 12 from the Environmental Protection Agency 2005, E Fontenay, A. Andersen and K. Nielsen,
Guideline on metallic materials for water installations, EPA 2005
Information from EPA, No. 6, 2004
SBI-instruction 165, Water systems, National Building Research Institute, 1990
Pipe Center-instruction 002, Resource saving water installations in houses, Technological Institute 1999
Pipe Center -instruction 003, Use of rainwater for toilet flushing and washing machines in houses, Technological Institute
2000
DTI work instruction 9301.1993. Repair of non-replaceable copper pipes in water installations
Dimensioning of water heaters, DTI, Taastrup, April 1990
Testing of water heaters, test bench and test methods, Technological Institute, Heat and installation engineering, 1985
Common Rules for the connection of electrical installations and usage elementss, Danish Energy 2007
75 (da)
Single user license: Tecnimont Civil Construction,Viale M.te Grappa 3 ,IT-20124 Milan
DS 439:2009
76 (da)