WIND LOAD COMPUTATIONS

MAIN WIND FORCE RESISTING SYSTEM (Table 207B.2-1)

COMPONENTS AND CLADDING (Table 207E.4-1)

Structure: MUNICIPAL BUILDING

STEP 1: Risk Category of Building or Other Structure

➢ Occupancy Category: I - Essential Facilities (Table 103.1)

STEP 2: Basic Wind Speed, V:

Province: Batangas

V = 270 kph (Figure 207.5-1C):

STEP 3: Wind Load Parameters

a. Wind directionality factor, Kd (Section 207A.6)

Kd = 0.85 (Table 207A.6-1)

b. Exposure Category:

Surface Roughness B: Urban and suburban areas, wooded areas, or other terrain

with numerous closely spaced obstructions having the size of single-family

dwellings or larger.

Exposure: B (Section 207A.7)


Plan Elevation

c. Topographic Factor, Kzt (Section 207A.8)

Kzt = 1.0 (Table 207A.8-1)

d. Gust Effect Factor,G

Rigid Building

Gf = 0.85 (Section 207A.9)

*The gust-effect factor for a rigid building or other structure in permitted to be

taken a 0.85.

e. Enclosure Classification (Section 207A.10)

Ao – total area of openings in a wall that receives positive external pressure

Ag – total gross area of that wall in which Ao is identified

Ao > 0.8Ag

Ag = (16) (30) = 480 m2 Ao = m2

154.7𝑚2
Percentage Open = 480𝑚2
= 0.32

therefore, Enclosed Building


f. Internal Pressure Coefficient (Section 207A.11)

GCpi = ±0.18 (Table 207A.11-1)

STEP 4 and 5: Velocity Pressure Exposure Coefficient, Kz and Velocity Pressure, qz

Table. Velocity Pressure Exposure Coefficient and Velocity Pressure for MWFRS
MWFRS

HEIGHT (m) Kz
q z.
(Table 207E.3-1)
(Equation 207B.3-1)
or
kPa
Kz = 2.01 (z/zg)2/α

4 0.57 1.671
8 0.62 1.817
12 0.76 2.227

Mean roof
0.83 2.461
h1 = 17

18 0.85 2.491

Table. Velocity Pressure Exposure Coefficient and Velocity Pressure for C&C
C&C

HEIGHT (m) Kz
q z.
(Table 207E.3-1)
(Equation 207B.3-1)
or
kPa
Kz = 2.01 (z/zg)2/α

4 0.70 2.052
8 0.70 2.052
12 0.76 2.227

Mean roof
0.83 2.461
h1 = 17

18 0.85 2.491
zg = 365.76, α = 7 (Table 201A.9-1)
qz = 0.613 Kz Kzt Kd V2 (N/m2) (Equation 207B.3-1)

STEP 6: External Pressure Coefficient, Cp or CN for MWFRS

STEP 6: External Pressure Coefficient, GCp for C&C

Hip Roof

L = 24m h/L = 0.708

B = 21m Roof Angle = 14.03624°

h = 17m

L/B = 1.4286

where:

L = horizontal dimension of a building measured parallel to the wind direction

B = horizontal dimension of a building measured normal to wind direction

h = mean roof height of a building

For Main Wind Force Resisting System

Table. External Pressure Coefficient for MWFRS


MWFRS

SURFACE
SURFACE CASE L/B or h/L Cp
TYPE
Windward All +0.8
Walls Leeward 1.4286 -0.43333
Side All -0.7

0.708 -0.672
Roofs Windward
0.708 -0.18
(Normal to
Ridge) Leeward 0.708 -0.3866

0 to h 0.708 -0.9
Side1
h to 2h 0.708 -0.5
Roofs
(Parallel to 0 to h 0.708 -0.9
Ridge) Side2 h to 2h 0.708 -0.5
>2h 0.708 -0.3

Table. External Pressure Coefficient for MWFRS


MWFRS

DESIGN
PRESSURE (p)
SURFACE
SURFACE Z (m) q Cp
TYPE
+GCpi -GCpi

Windward 4 1.671 +0.8 -0.218 2.490


8 1.817 +0.8 -0.119 2.59
12 2.227 +0.8 0.160 2.868
Walls 0.28
16 2.403 +0.8 2.988
Leeward 0 to 16 2.462 -0.43333 -2.260 0.448
Side 0 to 16 2.462 -0.7 -2.819 -0.111

2.462 -0.672 -2.760 -0.052


Roofs Windward -1.731
2.462 -0.18 0.977
(Normal to
Ridge) Leeward 2.462 -0.3866 -2.163 0.545

0 to 17.25 2.462 -0.9 -3.57 -0.862


Roofs Side1 -2.585
17.25 to 34.5 2.462 -0.5 0.123
(Parallel to 0 to 17.25 2.462 -0.9 -3.57 -0.862
Ridge) Side2 17.27 to 34.5 2.462 -0.5 -2.585 0.123
>34.5 2.462 -0.3 -2.093 0.616

p = qGfCp – qi (GCpi) (Equation 207B.4-2)

For Components and Cladding

A = 0.10(30) = 3 m2; GOVERN A = 0.04(30) = 1.2 m2

A = 0.4(17.25) = 6.9m2 A = 0.9m

Table. Wall Design Pressures for Components and Cladding

C&C

ZONE 4 AND 5 ZONE 4 ZONE 5


COMPONENT A (m2) (+GCpi) (-GCpi) (-GCpi)
(Figure 207E.4-1) (Figure 207E.4-1) (Figure 207E.4-1)

Walls 3 +0.91 -1.02 -1.24

Table. Controlling Design Pressure for Wall Components


C&C

DESIGN PRESSURE (kPa)


COMPONENT
Zone 4 Zone 5
Positive Negative Positive Negative

Wall 0.886 -3.865 0.886 -4.407

p = qh[GCp – GCpi] (Equation 207E.4-1)

Table. Roof External Pressure Coefficient

C&C

ZONE 1 AND 2 ZONE 1 ZONE 2


A
COMPONENT (+GCpi) (-GCpi) (-GCpi)
(m2)
(Figure 207E.4-2B) (Figure 207E.4-2B) (Figure 207E.4-2B)

Roof 3 +0.41 -0.86 -1.47

Overhang: Zone 1 = -3.17 ; Zone 2 = -2.2

Table. Roof Design Pressures

C&C

COMPONENT DESIGN PRESSURE (kPa)


Zone 1 Zone 2
Positive Negative Positive Negative

Roof 2.364 -3.471 2.364 -4.973

Overhang: Zone 1 = -9.159 ; Zone 2 = -6.771

p = qh[GCp – GCpi] (Equation 207E.4-1)