Professional Documents
Culture Documents
ANGLE CONNECTIONS
By W. H. Yang,1 M. D. Bowman,2 Member, ASCE, and
W. F. Chen,3 Honorary Member, ASCE
ABSTRACT: Seated-beam connections are occasionally used to attach a beam member to a column web or
flange, particularly during construction. This paper presents the results of an experimental program that was
designed to examine the flexural behavior of bolted, unstiffened seated angle connections. The sensitivity of
Downloaded from ascelibrary.org by MISSOURI, UNIV OF/COLUMBIA on 04/21/13. Copyright ASCE. For personal use only; all rights reserved.
several critical variables that influence the strength of the connection angle is reviewed. General descriptions of
the test procedures and observations are presented, followed by a detailed discussion of the test variables. The
test results are compared with corresponding theoretical predictions to asses the accuracy of various analytical
models. It was found that seat angle strength is significantly influenced by beam setback, angle thickness, and
the bolts that connect the angle to the flange of the supporting beam. Moreover, the strength of the seat angle
can be accurately predicted using a plastic hinge based analytical model that reflects the failure mode.
Test Setup
The test setup consisted of a test beam with end supports
and lateral braces, a braced test column, a loading frame, and
FIG. 2. Instrumentation and Dimensions
a longitudinal bracing system. A 2,743 mm (9 ft) long W460
⫻ 193 (W18 ⫻ 130) section of ASTM A36 steel was used for
the test beam. It was supported by a seat angle specimen at ducers were recorded with an OPUS 2.0 computerized data
the test end and a concrete block at the opposite end. A steel acquisition system. A detailed discussion of the test setup and
roller was used to simulate a simply supported end condition the instrumentation is provided by Yang (1997).
at the far end. The test beam was braced at the loading point The bearing stress distribution (or the reaction point) on the
and at the test end to provide lateral stability. The lateral braces seat angle is a key issue in computing the load-carrying ca-
were designed so that they would not carry any vertical load. pacity of seated beam connections. However, it is difficult to
The brace at the test end consisted of a pair of angles con- measure the bearing stress distribution directly. To overcome
nected to the column, but not attached to the beam web. This this difficulty, an indirect approach with two load cells was
prevented lateral movement of the beam without inhibiting utilized. One load cell was placed on top of the test beam at
vertical displacement. It should be noted that the test setup the loading point, while a second load cell was placed under-
utilized a seat angle only, and did not include a top connection neath the test beam at the far end. Using this arrangement, the
angle on the beam flange or web. The primary purpose for magnitude and location of the end reaction on the seat angle
this omission was so that the load and deformation response can be calculated using the following two equations of equi-
of the seat angle could be studied. The limited tests by Roeder librium (Fig. 2):
and Dailey (1989) clearly demonstrate that the top angle does Rangle = RLC #1 ⫺ RLC #2 (3a)
carry some load and contributes to the overall connection re-
sponse. Moreover, for applications when only a seat angle is RLC #1
utilized, such as during construction, it is important to under- x 0 = L ⫺ (L ⫺ a) (3b)
RLC #1 ⫺ RLC #2
stand the behavior of the seat angle alone.
A 1,524 mm (5 ft) long W360 ⫻ 463 (W14 ⫻ 311) section where Rangle = magnitude of end reaction on the seat angle;
of ASTM A36 steel was used for the test column. The vertical RLC#1, RLC#2 = load cell output at the loading point and far end,
leg of the test angles was attached to the web of the column respectively; and x 0 , L, and a = dimensions noted in Fig. 2.
with two 25 mm (1 in.) diameter A325 bolts. The bolts were LVDTs #1, #2, and #3 monitored the vertical deflection of
inserted into 27 mm (1 1/16 in.) diameter holes and tightened the test beam at the far end, loading point, and test end, re-
by the turn-of-nut procedure using an impact wrench. The sur- spectively. Because LVDT #3 was very close to the seat angle,
face of the test angles were coated with a whitewash to ob- and because the deformation of the test beam was negligible,
serve the onset of yielding. Flaking of the whitewash can be the reading of LVDT #3 represented the vertical movement of
used to infer locations where large strains occur. the seat angle that was in contact with the bottom flange of
The loading frame consisted of an W-section cross beam the test beam.
and two laced columns that were made with channel sections.
The frame was braced to prevent out-of-plane displacement Variables and Material Properties
using angles. A vertical force was applied to the top of the test
beam via a 535-kN (120-kilo pound) capacity hydraulic jack The major test variables in the experimental study were
attached to the cross beam of the load frame. beam attack, angle thickness, angle length, beam-to-angle at-
A longitudinal bracing system was originally designed to tachment bolts, and level of bolt tightness. To examine these
provide horizontal constraint at the far end of the test beam. variables a number of different test cases were evaluated with
However, pilot tests indicated that a 25 mm (1 in.) horizontal various combinations of the test variables. A total of 77 seat
movement of the test beam in a longitudinal direction could angle specimens with 42 different cases were tested.
be developed for the unrestrained beam. Hence, significant Beam setback is used herein to indicate the distance from
compressive force could be engendered in the test beam due the face of the column web to the end of the test beam at the
to restraint at the far end. Therefore, for most of the tests, the beginning of the test. The following six different beam setback
restraint at the far end of the test beam was released, and the values were used: 12.7, 19.0, 25.4, 31.8, 38.1, and 44.5 mm
longitudinal bracing system was only used to hold instrumen- (1/2, 3/4, 1, 1 1/4, 1 1/2, and 1 3/4 in.).
tation and to prevent excessive horizontal displacement when All of the test angles had equal horizontal and vertical leg
collapse occurred. sizes. Five different angle thicknesses and two different angle
sizes were examined: 9.5 and 12.7 mm (3/8 and 1/2 in.) thick-
Instrumentation nesses were used for angles with 127 mm (5 in.) long legs;
whereas 15.9, 19.0, and 25.4 mm (5/8, 3/4, and 1 in.) thick-
The instrumentation used in the experimental program in- nesses were used with 152-mm (6-in.) leg sizes. Also, three
cluded two load cells and four LVDTs. The location for the different angle widths were used: 152, 203, and 267 mm (6,
instrumentation is shown in Fig. 2. Test data from these trans- 8, and 10 1/2 in.). Tension tests were conducted per ASTM A
JOURNAL OF STRUCTURAL ENGINEERING / NOVEMBER 1999 / 1225
strength of the seat angle with no bolts used to attach the seat ing starts at the first hinge location (‘‘b’’ in Fig. 3). As a result,
angle to the beam flange. Although this condition is not rec- a noticeable decrease in stiffness of the connection is observed.
ommended for conventional practice, it was studied, neverthe- The degradation of stiffness continues until the peak load point
less, to provide a comparison with the strength of seat angles is reached and a failure mechanism is formed. After the peak
that are attached to the beam flange. For this condition, the load point, the connection can deform continuously without
mechanism of friction and gravity alone was used to attach significant loss of strength until the end of the test. The bolt-
the beam flange to the seat angle. tightened test was always terminated due to excessive defor-
mation, and no collapse of the test beam occurred during load-
TEST RESULTS AND OBSERVATIONS
Test Procedures
The loading rate of the hydraulic jack was adjusted manu-
ally using a pressure regulator to control the output pressure
of the pump. The load was applied continuously from the in-
itial loading state until failure. The data acquisition system was
programmed to record test data at 1.5-s intervals. The initial
elastic loading rate was about 4.5–9.0 kN/s (1–2 kip/s). When
the load-deflection curve began to deviate from linear behav-
ior, the loading rate was gradually reduced to displacement
control to collect additional data. The test was terminated
when one of the following four conditions occurred:
1. Peak load point passed and the load started to drop while
the vertical displacement, as inferred from LVDT #3, still
increased.
2. Excessive vertical or horizontal displacement of the test
beam observed, i.e., the readings of LVDTs #3 or #4
surpassed 25 mm (1.0 in.).
3. Collapse of the test beam.
4. The reading of Load Cell #1 reached the maximum ca-
pacity of the hydraulic jack.
General Observations
Based on their general behavioral trend, the tests fall into
two broad categories: (1) Bolt-tightened (39 tests) and (2) no-
bolt cases (38 tests). Bolt-tightened indicates that two bolts
were used with nuts tightened to attach the horizontal leg of FIG. 3. Typical Load-Deflection Curves: (a) Load versus Verti-
the seat angle to the beam flange, whereas the no-bolt case cal Displacement; (b) Load versus Horizontal Displacement
indicates that no bolts were used to secure the angle to the
beam. Twenty-four of the 39 bolt-tightened tests produced an
angle failure strength that ranged from 197 to 498 kN (44.3
to 112.0 kips); 15 specimens did not fail when the capacity of
the loading actuator (516 kN) was reached. Thirty-four of the
no-bolt tests produced an angle failure strength range of 72–
443 kN (16.2–99.6 kips); four specimens did not fail when
the capacity of the loading actuator was reached.
The bolt-tightened specimens were typically stronger and
deflected more than no-bolt specimens with comparable thick-
nesses and angle lengths. Fig. 3 illustrates typical load-deflec-
tion curves of seated connections from these two categories.
Both specimens consist of 127 ⫻ 127 ⫻ 12.7 angles (5 ⫻ 5
⫻ 1/2) that are 267 mm (10.5 in.) wide with a 19-mm (3/4-
in.) beam setback.
For a bolt-tightened seated connection, yielding—as in-
ferred by whitewash flaking—was observed to initiate near FIG. 4. Deformed Shape of Bolt-Tightened Specimens
42.1%.
Differences between bolted and no-bolt specimens are also
shown in Fig. 6. Significant differences in the strength for the
FIG. 5. Deformed Shape of No-Bolt Specimens
two cases are evident. However, a similar trend on the effect
of beam setback is apparent for both cases: An increase in
ing. At the end of the test, the yield region appears to have beam setback results in a decrease in strength. Only limited
extended completely through the compression zone of the ver- test results are shown in the upper right corner of the figure
tical leg, and yield lines had formed in both legs of the seat for the thicker bolt-tightened specimens and the 25-mm (1-in.)
angle. A view of the typical deformed shape of several bolt- no-bolt specimen.
tightened specimens is illustrated in Fig. 4. The AISC Connections Manual (Manual 1994) indicates
For a no-bolt seated connection, yielding initiates near the that 13 mm (1/2 in.) is a typical nominal setback. The setback
fillet in the center of the vertical leg, and then propagates along position could change somewhat during construction for a va-
the length of the angle. From the no-bolt load-deflection riety of reasons. One possibility is that some shifting could
curves shown in Fig. 3 (Case 16: NBL-T4-S3-1), it can be occur as the column is adjusted for final plumbness. The sen-
seen that no obvious linear portions are observed at the initial sitivity of the setback variable, as illustrated in Fig. 6, indicates
stages of loading. Vertical and horizontal displacements both that efforts should be taken during construction to ensure that
increase nonlinearly soon after the load is applied, and both excessive changes in the nominal setback do not occur.
displacements are about the same magnitude throughout the
loading process. The test often ends with the sudden collapse
of the test beam. The postpeak unloading portion of the load- Angle Thickness
deflection curves were only occasionally recorded due to the
Fig. 7 illustrates the relationship between average strength
rapid nature of the no-bolt failure modes. Only one yield line
and angle thickness. [Again, the results of 12.7 mm (1/2 in.)
forms in the no-bolt test, rather than two yield lines, as noted
thick angle specimens are scaled down by an angle length
for the bolt-tightened case. The yield line for the no-bolt test
factor of 8/10.5 for comparison purposes.] Because the eccen-
forms on the vertical leg of the angle that is bolted to the
tricity of the load is directly related to angle thickness (i.e.,
column web. Also, the width of the yield zone is much nar-
eccentricity = setback ⫺ thickness/2), there is a fundamental
rower than the yield zone developed in the bolt-tightened
difference between connections made with thin and thick an-
cases. The horizontal leg of the angle experiences no plastic
gles. For example, when the beam setback is bs = 19 mm (0.75
deformation. Fig. 5 shows typical deformed shapes of several
in.) and the connection is made with a 9.5 mm (3/8 in.) thick
no-bolt seated angles.
angle, then the load from the supported beam would be trans-
mitted to the angle vertical leg (which is bolted to the column
DISCUSSION OF TEST VARIABLES web), primarily through the bending action of the angle hori-
Beam Setback zontal leg, as illustrated in Fig. 8(a). In contrast, however, if
the connection is made with a 25 mm (1 in.) thick angle, then
Fig. 6 illustrates the relationship between average seat angle most of the load would be transmitted to the vertical leg
strength and beam setback. All of the angle test specimens in through direct bearing action, as shown in Fig. 8(b). In the
Fig. 6 are 203 mm (8 in.) wide, except the 12.7 mm (1/2 in.) latter case, the bending action of the horizontal leg of the angle
thick specimens, which are 267 mm (10.5 in.) wide. The angle would be a secondary effect.
Bolt Tightness
FIG. 7. Effect of Angle Thickness on Connection Strength
ASTM A325 high-strength bolts were used to connect the
seat angle specimens to the web of the test column and to the
bottom flange of the supported beam. The bolts connecting the
seat angle to the column web were fully tightened using turn-
of-nut tightening per the Research Council on Structural Con-
nections specification (‘‘Specification’’ 1988). The tightness of
the bolts connecting the test beam to the seat angle was a test
parameter in the experiments. The following three different
tightness levels were studied: (1) Turn-of-nut fully tightened;
(2) snug tight; and (3) finger tight.
Fig. 9 compares the load-deflection curves of seated con-
nections tightened using the three different methods. From this
comparison it can be noted that the ultimate load-carrying ca-
pacities of the seated connections are not very sensitive to the
bolt tightness. A snug tight connection has almost the same
load-carrying capacity as a fully tightened one; a finger tight
connection can reach 95% of the strength of a fully tightened
connection. Because further tightening of the bolts from the
snug tight condition to the fully tight condition does not im-
prove the performance of the connection significantly, then it
is appropriate to suggest that the snug tight condition for the
two beam-to-angle attaching bolts should be permissible.
However, it should be noted that if the seat is used as part of
FIG. 8. Illustration of Connections with Thick and Thin An-
gles: (a) Thin Angle; (b) Thick Angle the final connection and the bolt holes are oversized, the bolts
must be fully tightened.
The slenderness of a thin angle vertical leg under compres-
sion is much larger than that for a thick angle. While the load- Beam End Restraint
carrying capacity of seated connections with thick angles is a Two duplicate tests were conducted to study the effect of
largely a problem of material strength, the effect of stability the restraint at the far end of the test beam provided by a
could play a role in the performance of seated connections longitudinal brace. Fig. 10 compares the load-deflection curves
with thin angles, particularly for the no-bolt cases. As a result, of the two duplicate bracing tests. For the bolt-tightened spec-
seated connection strength increases very rapidly with an in- imens shown in Fig. 10(a), the flexible longitudinal brace sig-
crease in the angle thickness. Consequently, the ultimate ca- nificantly increases the connection stiffness, but not the
pacities of some of the seated connection test specimens made strength. The brace also changes the deformed shape of the
with 19 mm (3/4 in.) and 25 mm (1 in.) thick angles could seat angles by causing the plastic hinge location to shift up-
not be reached due to the limited capacity of the loading ward along the vertical leg, as illustrated in Fig. 11. For the
system. no-bolt specimens, however, the longitudinal brace can in-
Beam-to-Angle Attachment Bolts
The effect of the beam-to-angle attachment bolts on the per-
formance of unstiffened seated connections can be observed
in the load versus displacement curves shown in Fig. 3. Two
general observations can be made.
First, the load-carrying capacity can be increased by at least
125% if the beam-to-angle attachment bolts are installed and
tightened. This increase in load-carrying capacity is primarily
accomplished by changing the failure mode from a single-
hinge mechanism (which is statically determinate) for the no-
bolt case to a double-hinge mechanism (which is statically
indeterminate), for the bolt-tightened case. The change in the
failure mechanism is evident when comparing the deformed
shapes of bolt-tightened cases (Fig. 4) with those of no-bolt
cases (Fig. 5). Additionally, the effect of stability is more pre- FIG. 9. Effect of Bolt Tightness on Connection Strength
ACKNOWLEDGMENTS
The research reported herein is based in part on work sponsored by
the Department of Labor, Occupational Safety and Health Administration,
which is greatly acknowledged.
APPENDIX. REFERENCES
Garrett, J. H., and Brockenbrough, R. L. (1986). ‘‘Design load for seated-
beam in LRFD.’’ Engrg. J., 23(2), 84–88.
Manual of steel construction, allowable stress design. (1989). 9th Ed.,
American Institute of Steel Construction, Chicago.
Manual of steel construction, load and resistance factor design. (1994).
2nd Ed., Vol. II, American Institute of Steel Construction, Chicago.
FIG. 13. Effect of Beam Setback for Bolted and Unbolted Seat Roeder, C. W., and Dailey, R. H. (1989). ‘‘The results of experiments on
Angles seated beam connections.’’ Engrg. J., 26(3), 90–95.