Professional Documents
Culture Documents
Protection
By
Equipotential
Bonding
Earthing
Red/Line
Yellow/Line
Voltage Switching
Detectors Rods
Phase
Comparators
Fuse
Test current
50 kARMS
IEC62305-2
IEC 62305-2
RiskAnalyses
Risk Analyses
IEC62305-3
IEC 62305-3 IEC62305-4
IEC 62305-4
Physicaldamage
Physical damage Electrical-and
Electrical- and
andlife
and lifehazard
hazard electronicsystems
electronic systems
1 2 3
I Appliances 1.5
LPS (LPS Type I to IV) – Complete system used to reduce the danger of
physical damages and injuries due to direct flashes to the structure. It consists
of both external and internal LPS and is defined as a set of construction rules,
based on corresponding protection level.
Lightning protection zone (LPZ) – With respect to the lightning threat, a zone
may be defined, inside of which is sensitive equipment. Extra protection is
applied at the zone boundary to minimize the risk of damage to equipment
inside the zone
Protection level (I to IV) – Four protection levels of lightning protection. For
each protection level, a set of maximum (sizing criteria) and minimum
(interception criteria) lightning current parameters is fixed, together with the
corresponding rolling sphere radius.
The risk R is the value of a probable average annual loss due to lightning.
For each type of loss which may appear in a structure or in a service, the
relevant risk shall be evaluated.
Separation distance
Earth-termination system
Down-conductor system
Air-termination system
r
α°
H : Height of the air-termination system above ground H Protection zone
r : Radius of the “ rolling sphere“
α : Protective angle
Sphere Dia.
according to PL
Exposed strike
points/area
Air-termination system
L1 PV modules
L2
L3
PEN
Separation distance
s Radius of the rolling Air-termination rod
sphere depending on
r the class of LPS Protective angle
α
Shadow line
15°
DC lines
Inverter
AC
DC
CPU TB
EB
© 2009 DEHN + SÖHNE / protected by ISO 16016 Surge Protection June 2008
6.1 General
IEC 62305-3
The internal LPS shall avoid the occurrence of dangerous sparking within the
structure to be protected due to lightning currents flowing in the external LPS or in
other conductive parts of the structure.
Dangerous sparking may occur between the external LPS and other components
such as;
v The metal installations
v The internal systems
v The external conductive parts and lines connected to the structure
Dangerous sparking between different parts can be avoided by means of;
v Equipotential bonding in accordance with 6.2, or
v Electrical insulation between the parts in accordance with 6.3
© 2009 DEHN + SÖHNE / protected by ISO 16016 Surge Protection June 2008
Lightning Equipotential Bonding according to LPZ
© 2009 DEHN + SÖHNE / protected by ISO 16016 Surge Protection June 2008
4. Design and installation of a LEMP protection measures system
(LPMS)
IEC 62305-4
Electrical and electronic systems are subject to damage from the lightning
electromagnetic imuplse (LEMP). Therefore LEMP protection measures need to
be provided to avoid failure of internal systems.
Protection against LEMP is based on the lightning protection zone (LPZ) concept: the
volume containing the systems to be protected shall be divided into LPZ.
Outer Zones
LPZ 0 Zone where the threat is due to the unattenuated lightning electromagnetic
field and where the internal systems may be subjected to full or partial lightning
surge currents. LPZ 0 is divided into:
LPZ 0A zone where the threat is due to the direct lightning flash and the full lightning
electromagnetic field. The internal systems may be subjected to full lightning surge
currents (Iimp 10/350 µs wave shape)
LPZ 0B zone protected against direct lightning flashes but where the threat is the full
lightning electromagnetic field. The internal systems may be subjected to partial
lightning surge currents. (In 8/20 µs wave shape)
© 2009 DEHN + SÖHNE / protected by ISO 16016 Surge Protection June 2008
4.2 Lightning protection zones (LPZ)
IEC 62305-4
Inner Zones: (protection against direct lightning flashes)
LPZ 1 Zone where the surge current is limited by current sharing and by SPDs at the
boundary. Spatial shielding may attenuate the lightning electromagnetic field.
LPZ 2....n Zone where the surge current may be further limited by current
sharing and by additional SPDs at the boundary. Additional spatial shielding may
be used to further attenuate the lightning electromagnetic field.
© 2009 DEHN + SÖHNE / protected by ISO 16016 Surge Protection June 2008
LPZ : Lightning Protection Zone Concept
IEC 62305-4
LPZ
LPZ 00AA BTS antenna
Feeder cable
PP radio
GPS
LPZ 0AA
LPZ 0AA
Boundry bonding
bar 1 between LPZ LPZ 0BB
0B and LPZ 1
- TYPE
- CLASS
- kA Rating
- Wave Shape
- Co-ordination
IEC 60364-5.53
IEC 60364-5.53
(b) SPD location - The most effective way of providing effective surge
protection for a facility is to provide SPDs at the building service point-of
– entry (known as primary protection), and then, if necessary, to provide
additional surge protection within the building closer to the equipment to be
protected (known as secondary protection)
(c) Surge ratings – (iii)...........While table 5.1 gives a surge rating for SPDs in
the case (Category C3) using the 8/20 µs wave shape, it should be
acknowledged that the IEC standards make reference to a 10/350 µs wave
shape for this use in this case, and the symbol given to the current rating
using this wave shape Iimp ..............
Given this discussion for a.c. Power system SPDs, the following surge current
ratings are recommended, where the surge rating is the Imax or single shot 8/20
µs value, and apply for each SPD from the phase to neutral conductors.
100 kA 1 2
Wave shape µs 10/350 8/20
Q As 50 0,1
20 kA
20
15
10
0
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Lightning Impulse Current (10/350µs) in kA
© 2009 DEHN + SÖHNE / protected by ISO 16016
S1150e 1150e.ppt / 10.05.2000 / KK