17-May-16

Page 174 of 3011

FLUOR CONTRACT NO.: A7JJ


REV.: __0__
DATE: 5/5/2016.
.

CALCULATION SHEET BY: JMC CHK'D : _PLA_


Terminal Substation 2 Building DC NO.: P13006-00-CI-EC-0001
Foundation Calculations

persistent & transient / seismic

Mpc.bot If Kpc.bot < K', compression


Kpc.bot   0.03504
d reinforcement is not required
 fck
2
 pc.bot 
CheckK.pc.bot  "Compression reinforcement is NOT required for pile cap."

lever arm;
dpc.bot 1   1  3.53Kpc.bot 
zpc.bot  min
    767.60 mm
Note: Limiting z to 0.95*d is not a
 0.95 dpc.bot  requirement of Ref.1 but is
  considered a good practice, Ref.3
Mpc.bot Fapc.bot 2
mm
As.pc.bot    2193.39 Required area of reinforcement for the
fyd  zpc.bot 2 fyd m whole width of the pile cap
 PT  PT

accidental

Mpc.bot.Acc
Kpc.bot.Acc   0.03438 If Kpc.bot < K', compression
d 2  reinforcement is not required
 pc.bot  fck
CheckK.pc.bot.Acc  "Compression reinforcement is NOT required for pile cap."

lever arm;
dpc.bot 1   1  3.53Kpc.bot.Acc 
zpc.bot.Acc  min
    767.60 mm
Note: Limiting z to 0.95*d is not a
 0.95 d pc.bot  requirement of Ref.1 but is
  considered a good practice, Ref.3

Mpc.bot.Acc Fapc.bot.Acc 2
mm
As.pc.bot.Acc    1973.39 Required area of reinforcement for the
fyd  zpc.bot.Acc 2  fyd m whole width of the pile cap
 Acc  Acc

4 h pc 2
mm Maximum area of reinforcement
As.pc.max   40000.00 (Section 9.2.1.1 (3)), Ref.1
100 m

CheckAs.pc.bot  "Required area of reinforcement is less than the maximum. OK!"

 0.26 fctm  mm
2
As.pc.min  max 0.0013  d
pc.bot  1270.48 Minimum area of reinforcement, sec.9.2.1.1 (1),
 fyk  m Ref.1
 
2
mm

As.pc.bot.reqd  max As.pc.bot As.pc.bot.Acc As.pc.min  2193.39
m
 Required area of reinforcement

2
π ϕpc.b
2
As.ϕ.pc   615.75 mm Area of reinforcing bar provided
4
As.ϕ.pc
spc.bot.reqd   280.73 mm Required pile cap reinforcement spacing
As.pc.bot.reqd

spc.b  150.00 mm Pile cap reinforcement spacing provided


if spc.b  spc.bot.reqd "OK" "NG"  "OK" 

P13006-00-CI-EC-0001-07 Rev 0.xmcd PC3 - Pile Cap