You are on page 1of 4

A Study of Lead-Acid Battery Efficiency Near Top-of-Charge

and the Impact on PV System Design


John W. Stevens and Garth P. Corey

Sandia National Laboratories, Photovoltaic System Applications Department


Sandia National Laboratories, Battery Analysis and Evaluation Department
PO Box 5800, MS 0753
Albuquerque, New Mexico 87185-0753

ABSTRACT discharge and PV array size. Hence, a procedure has


been developed, and is described herein, to acquire these
Knowledge of the charge efficiency of lead-acid batteries efficiency versus SOC measurements. Preliminary
near top-of-charge is important to the design of small results agree with existing general knowledge, and
photovoltaic systems. In order to know how much energy provide the details of charge efficiency versus state of
is required from the photovoltaic array in order to charge for the specific battery under test.
accomplish the task of meeting load, including periodic Specific charge versus state of charge information is
full battery charge, a detailed knowledge of the battery particularly important for systems where a very large
charging efficiency as a function of state of charge is battery (that is, one designed to normally operate in the
required, particularly in the high state-of-charge regime, upper 10% or less of state of charge in order to achieve
as photovoltaic systems are typically designed to operate high load availability) is used. For example, a PV system
in the upper 20 to 30% of battery state-of-charge. This for an area light may be designed to allow the light to not
paper presents the results of a process for determining function for a couple of niqhts per year, but a
battery charging efficiency near top-of-charge and communication repeater may be only allowed a couple of
discusses the impact of these findings on the design of hours per year of outage time (often less). One common
small PV systems. method for increasing the availability of PV systems is to
increase the size of the battery. Increasing battery size in
a system implies that the battery will be operating at a
BACKGROUND higher average state-of-charge. If a 100 amp-hour (Ah)
battery is used in a system with a 30Ah daily load, then
Batteries are often necessary in photovoltaic (PV) one would expect the battery to be operating in the 70%
systems to store energy generated while the sun is to 100% SOC regime on the average. If this same load
shining. Therefore, it is important to understand the was operated with a 300Ah battery, then the battery
specific requirements of batteries when designing a PV would be expected to operate in the 90% to 100% SOC
system. This includes an understanding of the amount of regime on the average. Because charge efficiency
energy that will be lost in battery charging. decreases with increasing battery state-of-charge, the
Overestimating these battery charging losses results in a system with the larger battery may also need a larger PV
larger PV array than required, whereas underestimating array to account for the higher losses associated with
them results in unanticipated loss of load as well as the operating at a higher average SOC. Battery charge
possibility of damaging batteries because of lack of efficiency is also a function of charge rate, with lower
providing a periodic high state-of-charge. rates resulting in higher efficiencies. The larger battery
It is generally understood that battery charge will be operating with a lower charge rate, which will
efficiency is high (above 95%) at low states of charge and result in higher charge efficiency. A decision on
that this efficiency drops off near full charge. However, increased array size must be made with full knowledge of
actual battery charge efficiencies are often stated as charge efficiency at the actual charge rate being
though efficiency is linear across all states of charge, with employed.
general guidance that it drops off at higher states of The testing reported on here examined a single
charge. Details concerning actual charge efficiency as a sample of the Trojan 3OXHS battery. This is a 12-volt,
function of state-of-charge (SOC) would be very useful to flooded, lead-antimony battery rated 130Ah at the 20
PV system designers to allow informed trade-off hour rate by the manufacturer. Testing in PV
decisions involving battery size, battery daily depth of applications, where charging is rarely in accordance with
manufacturer’s recommendations, indicates that this
This work supported by the Photovoltaic Energy battery has a “PV capacity” of about IOOAh, and that is
Technology Division of the US Department of Energy the value that will be used as this battery’s capacity in
under contract DE-AC04-94AL85000. this paper.

1485

0-7803-3166-4/96/$5.00 0 1996 IEEE 25th PVSC; May 13-17, 1996; Washington, D.C.
Once this testing has been completed, and the All discharges were to 10.5 volts to ensure
results have been reviewed, other batteries will be tested consistency in counting amp-hours. The battery was first
to examine the applicability of these results to other charged and discharged through 10 complete cycles in
batteries of both similar and different types. order to "form" the battery and ensure consistent results.
Full recharge (as opposed to the partial charges used to
CHARGE RATE SELECTION charge the battery with a specific number of Amp-hours)
was performed by bringing the battery voltage to 14.8
For this initial test sequence, a single charge and volts and then maintaining regulation voltage (14.8 volts)
discharge rate was selected. The rate was chosen as one by tapering the current for 10 hours.
of many that is typically seen in PV systems. For the A test procedure was developed to charge the battery
100Ah Trojan 30XHS battery, a charge and discharge in steps beginning with approximately 65% capacity, then
rate of 3.3 amps, or C130, was selected. PV system increasing the input in 8Ah increments until about 100Ah
batteries will normally have charge rates that vary from output is obtained on discharge. The Digitron tester
about l/lOth the battery capacity to about 1/50th the calculates both amp-hours and watt-hours for each data
battery capacity, or C/10 to CI50, with discharge rates point, so both Ah and energy efficiency can be easily
varying from about C/10 to C/150. A moderate rate of obtained with the same set of test data.
C/30 was selected from these ranges, resulting in 3.3 Two types of efficiency are calculated using the test
amps. It is important to select a charge and discharge data. These will be referred to as overall average
rate that is similar to that used in PV systems because efficiency (the efficiency from zero SOC to that SOC
these rates will have a significant effect on battery charge under test) and incremental efficiency (the efficiency
efficiency, between two non-zero states of charge, for example,
An example demonstrates the origin of these ranges. between 80 and 85% SOC). After the initial regime of 10
Consider a load, including losses, that requires 15Ah per full chargeldischarge cycles, the battery was charged with
day from the PV array. In an area of a good solar 68Ah which was estimated to result in about 65% SOC,
resource of 5 kWh/m2/day, also referred to as 5 sun- or that would provide about 65Ah on discharge. The
hours per day, this energy will be acquired from the array 68Ah charge actually resulted in an average discharge of
over the daylight hours, with peak current of 3 amps (15 65.9Ah. After the battery was charged with 68Ah, it was
Amp-hours/5 sun-hours) occurring in the hour around then discharged to determine the amp-hours available,
noon. A typical design might require "5 days storage" for and charge efficiency was calculated. This procedure
the batteries. That is, the batteries would be required to was repeated several times for each SOC level in the
provide 75Ah to the load with no additional solar energy testing. The amp-hours input was then increased and the
input. PV systems are typically designed with a "Iow- next level of SOC was examined in a similar manner.
voltage-disconnect'' (LVD) to keep the battery from
experiencing 100% discharges. A typical LVD might be RESULTS
designed to allow 75% discharge. This then implies that
the 75Ah energy storage is 75% of the battery capacity, The results of this testing are displayed graphically in
so we will be considering a 100Ah battery. Therefore, the Figure 1. Each data point in Figure 1 represents at least
peak charge rate will be 100/3=33, or a charge rate of four tests. Some represent more than this, as some tests
C/33 (that is, the charge rate is equal to the battery were repeated at random to verify repeatable results. The
capacity divided by 33). A 3 sun-hour per day locale greatest variance in test results for each step was 5.8%,
would require a larger array with a 5 amp peak, resulting with several of the steps resulting in variance in results of
in a peak charge rate of C/20. If the load is a light that is less than 2%. The data is represented as a minimum
on all night, the discharge rate will be 15Ahll2hours = value of amp-hours extracted for each charge level, a
1.25 amp or C/80. If the load remains 15Ah per day, but maximum value and the average. This graph shows that
is spread over 24 hours per day, the discharge rate will the scatter among data is relatively small.
be C/160. Figure 2 shows the conversion of the amp-hours out
versus amp-hours in to efficiencies. Notice that there are
TEST PROCEDURE two curves, one displaying overall efficiency from zero
state of charge to the particular state of charge under
All tests were performed on a Digitron/Firing Circuits test, and the other showing incremental efficiency
BTS 600 chargeldischarge test unit, which charges with between states of charge. Notice also that the overall
pure dc (as observed on an oscilloscope.) This test unit efficiency shows high values, with full charge represented
allows programming several test sequences, then by approximately 85% efficiency, a commonly used value
performs the tests while monitoring and logging the test for battery charge efficiency. More importantly, notice the
data. The test equipment and battery are in an air dramatically lower efficiencies for the increments above
conditioned room with the room temperature maintained about 80% state of charge, where most values are below
near 72°F. The battery temperature was monitored and 60% efficiency, and full charge is represented by less
recorded. Because of the low charge/discharge rate of than 50% efficiency. (Actually, full charge, resulting in
the testing (C/30), the battery and room temperatures 100Ah output has not been reached in the testing to date
remained essentially the same. The greatest output was 96.5Ah, which resulted from
116Ah input. An attempt to achieve 100Ah output will be
made as part of the conclusion of this testing.)

1486
loo
90
80
i
-- r
I
i
E
I

70 -- E

60 --
z
3
0

f0 50 --

5
a
40
--

30 --

20 --
l o --
0 1 I 1 I I I I

68 76 84 92 100 108 116


Amp-hours input

Figure 1. Minimum, maximum and average values of test data, showing small scatter in test results.

0.9

0.8

h
0.7
.-
P)

E 0.6

0.5

0.4

0.3 I- 65.9
:
72.4 78.8 83.5 88.2 93.2 96.5
Ah Ouput (Also Battery SOC)

Figure 2. Incremental charge efficiency is dramatically less than overall charge efficiency at the higher states of
charge.

Clearly, the use of assumed charge efficiencies in hold up well for other deep-cycle flooded lead-antimony
the range of 80% will not result in a fully charged battery batteries as well.
when this battery is expected to operate in the upper 20%
of it's state of charge. It is expected that these results will

1487
INTERMEDIATE FULL CHARGE CYCLES

An observation early in the testing required a change


in the test procedure. The original intent had been to A test procedure has been developed to allow the
perform several partial charge/discharge cycles in examination of battery charge efficiency as a function of
sequence. For example, charge to 68Ah input, discharge, battery state of charge. Preliminary results agree well
then charge to 68Ah input and so on until the four with established general understanding that the charge
complete cycles at 68Ah input were complete. Then fully efficiency of flooded lead-antimony batteries declines with
charge and discharge the battery before proceeding with increasing state-of-charge, and that charge efficiency is a
the next level. It was seen early in the testing that this non-linear function of battery state-of-charge. These
was not going to work, as the capacity resulting from tests indicate that from zero SOC to 84% SOC the
68Ah input dropped with each succeeding cycle when no average overall battery charging efficiency is 91%, and
full charge cycles were performed between partial charge that the incremental battery charging efficiency from 79%
cycles. Therefore a full charge and discharge cycle was to 84% is only 55%. This is particularly significant in PV
added between each partial chargeldischarge cycle. systems where the designer expects the batteries to
This result has important implications to operational normally operate at SOC above 80%, with deeper
PV systems. That is, if a battery is partially charged for discharge only occurring during periods of extended bad
several consecutive cycles (for example, the array is weather. In such systems, the low charge efficiency at
marginally sized and there is a series of less than full sun high SOC may result in a substantial reduction in actual
days in the winter) the useable battery capacity decreases available stored energy because nearly half the available
each cycle, even though the same amount of energy has energy is serving losses rather than charging the battery.
been presented to the battery each day. This is the result Low charging efficiency can then result in the battery
of battery inefficiencies, electrolyte stratification, and operating at an average SOC significantly lower than the
sulfate buildup during these partial charges. An system designer would anticipate without a detailed
associated full charge, with its attendant gassing, is understanding of charge efficiency as a function of SOC.
needed to destratify the electrolyte and remove the During normal weather, capacity degradation will not be
residual sulfate. This sulfate buildup can become a evident, but it will manifest itself when the battery is
problem if this pattern continues for several months. In called on to provide the full purchased capacity, which
the short term it can be reversed by a full "equalizing" will be found to be unavailable. Extended operation in a
type charge, which, in most cases is not possible in small low SOC environment can also result in permanent loss
PV systems. Battery equalization requires a PV charge of capacity from sulfation if the battery is operated for
controller that has been specifically designed to include long periods of time without a sufficient recovery or
this function. At low charge rates (for example, less than equalizing charge.
C/40) equalization may not be possible because of The impact of low charge efficiency at high states of
charging time limitations. In any case, this reduction in charge has the greatest potential impact on systems
useable capacity will impact system availability and where high energy availability is needed Such systems
should be understood. usually utilize large batteries to ensure energy availability
during the longest stretches of bad weather. This may
FURTHER TESTING not provide the energy required if the PV array is
insufficient to provide a recovery charge for batteries at
The current set of tests will be completed by decreasing 90% SOC and above, where charge efficiency is very low.
the input to the battery progressively until a point is found Charge efficiencies at 90% SOC and greater were
at which the incremental charge efficiency stabilizes, measured at less than 50% for the battery tested here,
implying that this value will prevail throughout the lower requiring a PV array that supplies more than twice the
states of charge. During this testing, earlier tests will be energy that the load consumes for a full recovery charge
repeated as a check and to investigate the continued Many batteries in PV systems never reach a full state of
health of the battery (that is, looking for changes in charge, resulting in a slow battery capacity loss from
results that would indicate changing battery health.) stratification and sulfation over the life of the battery.
Finally, these testing procedures will be applied to other
batteries to see how common the results are and to
examine variations that may be found.

1488

You might also like